Index of Revisions
Owner
JINDAL INDIA THERMAL POWER LIMITED
Project
2 x 600 MW THERMAL POWER PROJECT
Consultant
TATA CONSULTING ENGINEERS
Coord. by 07.12.2010 KSH Document Number
Checked by 07.12.2010 KSH SIEM-JITPL.5404A-EL-4-2051 Siemens Limited,
Aurangabad.
Dept. Revision Version
Approved by 07.12.2010 KSH
EFIF 0 0
Clause Title
1.0 Datasheet
breaking current
37 a Rated back to back capacitor bank Not applicable
breaking current
b Rated capacitor bank inrush making Not applicable
current
38 Maximum breaking capacity under L75 = 37.5kA, L90 = 45kA
Kilometric faults & rated TRV Rated TRV - 480kVp
Characteristic
39 Dry one minute power frequency
withstand test voltage for complete circuit
breaker :
a Between terminals with circuit breaker 610
contacts open (kVrms) (0.55 X 610kV across each
break)
b Phase to earth & between phases (kVrms) 520
40 1.2/50 full wave impulse withstand
voltage for complete circuit breaker
a Between terminals with circuit breaker 1425 (+240)
contacts open.(kVp)
b Phase to earth & between phases (kVp) 1425
41 250/2500 micro second switching surge
withstand test voltage
a Between phase to earth (KVp) 1050
b Between phases (KVp) 1050
c Across isolating distance (kVp) Not applicable
42 a Radio Interference Voltage (Micro-Volts) < 1000
b Corona Extinction voltage (kV) > 320 kVrms
43 a Total length of break per phase / arc 140.5 mm
length (Distance between pin and tube
contact)
b Total length of contact travel 150 mm
General
53 Minimum clearances in air
a Between phases 6525 mm
b Live part and earth 3400 mm
c Lowest line terminal to ground 8000 mm
54 Normal pressure of SF6 gas inside circuit 6.0 bar at 20 deg c
breaker
55 Minimum operating pressure of SF6 gas above 5.0 bar at 20 degc
56 a Density monitor Settings (Adjustable / Non adjustable
Non adjustable)
b Voltage and power supply system for As per control supply voltage
which the temp. compensating gas
pressure switch (density monitor) and
other pressure switches are suitable
57 Pressure at which gas pressure will give :
a Alarm 5.2 bar at 20 deg C
b Tripping impulse At 5.0 bar at 20 degC if
specified by the client
c Lockout 5.0 bar at 20 deg C
58 Minimum time interval between each As per operating sequence O-
make/break operation (ms) 0.3 Sec.-CO-3 min.-CO
59 Maximum pressure of SF6 gas developed Within safe limits
in the arcing chamber at rated breaking
capacity (kg/sq.cm)
60 Chemical composition of the absorbent MOS 13X
61 Recommended interval for renewal of 6000 Nos. operations
absorbent for circuit breakers operating in
tropical condition.
62 No. of operations breaker is capable of 6000 Nos. operations
performing without inspection,
replacement of contacts and other main
parts with normal current breaking
63 No. of operations breaker is capable of 18 operations
performing without inspection,
replacement of fault current breaking
capacity
64 No. of operation at rated current after 50 kA
which routine inspection of breaker is
necessary contacts and other main parts
at 100% rated Guaranteed no. of opening
SIEMENS Energy
Power Transmission High Voltage Circuit Breakers
Breaker Contacts :
68 Type of main contacts Contact Multilam, Multilam,
Heat Cylinder
69 Type of arcing contacts Pin, Finger contact
70 Whether main contacts silver plated Yes
71 Thickness of silver plating Adequate
72 Material of contact Main contact Copper
Chromium Alloy.
Arcing contact Copper
tungsten alloy.
73 Contact pressure As per Design requirement
74 Auxiliary contact :
a Type of auxiliary contact Rotary
b Material of auxiliary contact Silver Plated Brass
c Contact silver plated or not Yes
d Thickness of silver plating Sufficient
75 No. of auxiliary switch / multiplied
contacts, operating with all individual
poles of a breaker
a which are closed when breaker is closed 20
b which are open when breaker is closed 19
76 No. of spare auxiliary contacts wired up to
the terminals
a Opening 6
b Closing 6
c Those adjustable with respect to position Auxiliary switch is rotary type
of main contact and all above contacts are pre-
SIEMENS Energy
Power Transmission High Voltage Circuit Breakers
80 Bushing or insulator :
a Make of insulator Aditya Birla / Modern /
SIEMENS Energy
Power Transmission High Voltage Circuit Breakers