Short-Circuit Analysis
Number of Buses: 1 3 7 11
Number of Machines: 3 1 0 0 0 4
System Frequency: 50 Hz
Apply Individual
Tolerance Adjustments /Global Percent
Transformer Impedance: Yes Individual
Cable Length: No
Apply Individual
Temperature Correction Adjustments /Global Degree C
Transmission Line Resistance: Yes Individual
11 Buses Total
Ohms or Siemens per 1000 m per Conductor (Cable) or per Phase (Line)
Line/Cable Length
Grounding
T3
0.300 11.000 0.400 D/Y Solid
T4
17.250 11.000 135.300 D/Y Solid
T7
17.250 11.000 135.300 D/Y Solid
T8
0.300 11.000 0.400 D/Y Solid
T9
17.250 11.000 135.300 D/Y Solid
T10
0.300 11.000 0.400 D/Y Solid
Branch Connections
% Impedance
Power Grid Connected Bus Rating 100 MVA Base Groundin
g
ID ID MVASC kV R X" R/X" Type
Gen2 Hydro w/o Damping 16.847 11.000 600 85.00 1.000 19.00 0.0 0.05 155.00
Gen4 Hydro w/o Damping 16.847 11.000 600 85.00 1.000 19.00 0.0 0.05 155.00
Gen5 Hydro w/o Damping 16.847 11.000 600 85.00 1.000 19.00 0.0 0.05 155.00
Line-To-Ground Fault
Contribution % Voltage at From Bus Current at From Bus (kA)
Bus7 Total 0.00 0.0 99.34 -116.3 94.47 117.6 5.584 -74.2 0.000 0.0
Bus17 Bus7 20.49 -28.7 95.87 -114.7 94.49 114.8 4.231 -70.6 0.513 99.5
Bus6 Bus7 61.70 -48.2 64.10 -130.5 94.72 89.7 0.462 -85.0 0.171 -80.5
Bus13 Bus7 61.70 -48.2 64.10 -130.5 94.72 89.7 0.462 -85.0 0.171 -80.5
Bus16 Bus7 61.70 -48.2 64.10 -130.5 94.72 89.7 0.462 -85.0 0.171 -80.5
U1 Bus17 100.00 0.0 100.00 -120.0 100.00 120.0 4.231 -70.6 0.513 99.5
Gen2 Bus6 95.24 -30.0 95.24 -150.0 95.24 90.0 2.132 -86.8 2.177 92.3
Bus5 Bus4 84.56 -73.9 47.81 -178.1 86.33 73.6 0.000 0.0 0.000 0.0
Gen4 Bus13 95.24 -30.0 95.24 -150.0 95.24 90.0 2.132 -86.8 2.177 92.3
Bus11 Bus12 84.56 -73.9 47.81 -178.1 86.33 73.6 0.000 0.0 0.000 0.0
Gen5 Bus16 95.24 -30.0 95.24 -150.0 95.24 90.0 2.132 -86.8 2.177 92.3
Bus14 Bus15 84.56 -73.9 47.81 -178.1 86.33 73.6 0.000 0.0 0.000 0.0
Bus6 Bus4 61.70 -48.2 64.10 -130.5 94.72 89.7 0.000 0.0 0.000 0.0
Bus13 Bus12 61.70 -48.2 64.10 -130.5 94.72 89.7 0.000 0.0 0.000 0.0
Bus16 Bus15 61.70 -48.2 64.10 -130.5 94.72 89.7 0.000 0.0 0.000 0.0
Bus7
135.300 5.243 10.642 4.901 5.584 11.335 5.584
All fault currents are in rms kA. Current ip is calculated using Method C.
* LLG fault current is the larger of the two faulted line currents.
Sequence Impedance Summary Report
Bus Positive Seq. Imp. (ohm) Negative Seq. Imp. (ohm) Zero Seq. Imp. (ohm) Fault Zf (ohm)
ID kV Resistance Reactance Impedance Resistance Reactance Impedance Resistance Reactance Impedance Resistance
mal
Total
3 10
4
Y0
Type Angle
Secondary
kV Amp Ohm
nce, Pos. Seq., 100 MVAb
Z Y
1433.59
50.99
50.99
1433.59
50.99
1433.59
1.81 0.2029036
Excitation
Conn. Type Amp Type