METALWRAP-H w/MR-100

JOINT BACK-UP FLASH APPLY BUTYL TO


12
1 " SUBFRAMING
FILL SHOULDER
AND AIR CAVITY
CONT. METALWRAP 100 BETWEEN MARRIAGE
METALWRAP INSULATED RAIL BEADS
BACK-UP PANEL

CONTINUOUS MR-100
ATTACHMENT SYSTEM AT EACH

PANEL SIDE JOINT (36" O.C.)


VERTICALLY AND FASTENED
INTO EACH FRAMING MEMBER
(16" TO 24" O.C.)
HORIZONTALLY

SUBFRAMING FASTENER
ANCHORED INTO CENTER
OF METALWRAP CLIP
6" WIDE SELF-ADHERING
FLEXIBLE MEMBRANE OR METAL
CONCEPT SERIES
FLASHING- CONTINUOUS AT ALL
CS-260 PANEL
BASE PANEL VERTICAL JOINTS.
PUNCTURE AT PANEL CLIP THEN
CSC-3 FLUSH
SEAL.
PANEL CLIP
INTERIOR GYPSUM
BASE PANEL

BOARD
METALWRAP BASE PANEL-
MODULE

FIELD RIP TO REMOVE


STEEL STUD
BOTTOM JOINERY
18 GA. MIN.

6" WIDE SELF-ADHERING


PRIMARY MEMBRANE
FLEXIBLE MEMBRANE OVER
FLASHING - EXTEND
TOP OF METAL FLASH
AND SEAL FROM
FOUNDATION
PANEL THRU-FASTENER DAMPROOFING TO
LINER SIDE OF
CONTINUOUS PANEL
STARTER FLASH

CONCRETE
CLADDING BASE
FLOOR
DRIP FLASH

NON-CURING BUTYL
SHEATHING BASE SEALANT BETWEEN
DRIP FLASH PRIMARY MEMBRANE
FLASH AND PANEL
CEMENTITIOUS INSULATION
LINER
PROTECTION BOARD
FILL ANY VOIDS
GRADE
OVER 1/4" WITH
LOW-EXPANSION
FOAM

2" RIGID
INSULATION
NOTE:
THESE DETAILS ARE FOR INSTALLATION
DAMPPROOFING OR
AND SEALING OF METALWRAP PANELS
WATERPROOFING
ONLY. FOR INSTALLATION AND SEALING
REQUIRED FOR FACE PANELS SEE CENTRIA FOUNDATION WALL
STANDARD DETAILS FOR THE SPECIFIC
FACE PANEL.

Foundation Detail w/Concept Series


MR100-01 Dec. 2012
METALWRAP-H w/MR-100
APPLY BUTYL TO
12
1 " SUBFRAMING JOINT BACK-UP FLASH
FILL SHOULDER
AND AIR CAVITY CONT. METALWRAP 100
BETWEEN MARRIAGE
RAIL
BEADS
SHOP APPLIED

AIR/VAPOR BARRIER
SEALANT

CSC-3 FLUSH
PANEL CLIP

SUBFRAMING FASTENER
ANCHORED INTO CENTER
OF METALWRAP MR-100 RAIL

CONTINUOUS MR-100
ATTACHMENT SYSTEM AT EACH

PANEL SIDE JOINT (36" O.C.) 6" WIDE SELF-ADHERING


VERTICALLY AND FASTENED FLEXIBLE MEMBRANE OR METAL
INTO EACH FRAMING MEMBER FLASHING- CONTINUOUS AT ALL

(16" TO 24" O.C.) PANEL VERTICAL JOINTS ABOVE


HORIZONTALLY SLAB. PUNCTURE AT PANEL CLIP
THEN SEAL.
PANEL THRU FASTENER
INTERIOR
AND SUBFRAMING
GYPSUM
FASTENER WITH FLEXIBLE
BOARD
MEMBRANE SEAL

SEALANT BETWEEN
CONCRETE
PANEL LINER AND
FLOOR
MEMBRANE FLASH
SLAB

CONCEPT SERIES
CS-260 PANEL

TWO-PIECE DEFLECTION
FLASHING UTILIZING
DEFLECTION
EXPOSED FASTENERS TO
EITHER SIDE OF JOINT
TRACK

(MAXIMUM 12 " DEFLECTION


DEFLECTION

STEEL STUD
SPACE

PANEL THRU FASTENER 18 GA. MIN.


WITH 3"x3" FLEXIBLE
MEMBRANE SEAL
SEMI-RIGID (4# DENSITY)
POSITIONED TO NOT MINERAL FIBER
INTERFERE WITH INSULATION INFILL
DEFLECTION TRACK. BETWEEN SHELF ANGLE
AND SLAB EDGE
METALWRAP INSULATED
BACK-UP PANEL-
PRIMARY MEMBRANE FLASHING
FIELD RIPPED TO SUIT.
(BY PANEL
NOTE: CONTRACTOR)
THESE DETAILS ARE FOR INSTALLATION
SEALANT BETWEEN
AND SEALING OF METALWRAP PANELS
PANEL LINER AND
ONLY. FOR INSTALLATION AND SEALING
PRIMARY FLASH
REQUIRED FOR FACE PANELS SEE CENTRIA
STANDARD DETAILS FOR THE SPECIFIC
FACE PANEL.

Detail at Deflecting Floor Slab w/Concept Series


MR100-02 Dec. 2012
METALWRAP-H w/MR-100
METAL COPING- LINER EXTENSION FLASH- FULLY-ADHERED
WOOD BLOCKING AND PROVIDES A SURFACE TRANSITION MEMBRANE
OTHER COPING SUPPORT TO ATTACH THE AIR CONNECTING THE ROOF
MEMBERS TYPICALLY BY BARRIER. MEMBRANE TO THE WALL
OTHERS AIR BARRIER

112 " SUBFRAMING


AND AIR CAVITY

EXTEND AIR
BARRIER TO PROVIDE
SHEATHING WATER
PROTECTION

PANEL THRU-FASTENER

BUTYL SEALANT BETWEEN


PANEL LINER AND
FLASHING AND BETWEEN
VAPOR RETARDER AND
FLASHING

PANEL THRU-FASTENER

CONCEPT SERIES
CS-260 PANEL

CSC-3 FLUSH
PANEL CLIP

VAPOR RETARDER
(BY OTHERS AS REQ'D)

METALWRAP INSULATED
BACK-UP PANEL

SHOP APPLIED AIR/VAPOR


BARRIER SEALANT

SUBFRAMING FASTENER
ANCHORED INTO CENTER
OF METALWRAP MR-100 RAIL

CONTINUOUS MR-100
ATTACHMENT SYSTEM AT EACH

PANEL SIDE JOINT (36" O.C.)


VERTICALLY AND FASTENED INTO ROOF/PARAPET MATERIALS:
EACH FRAMING MEMBER (16" TO 18GA STUD FRAMING
BACKER BOARD
24" O.C.) HORIZONTALLY VAPOR RETARDER (AS REQ'D)
NOTE: RIGID BOARD INSULATION
THESE DETAILS ARE FOR INSTALLATION PLYWOOD
AND SEALING OF METALWRAP PANELS ROOF CANT
ONLY. FOR INSTALLATION AND SEALING ROOF MEMBRANE
REQUIRED FOR FACE PANELS SEE CENTRIA
STANDARD DETAILS FOR THE SPECIFIC (ALL BY OTHERS)
FACE PANEL.

Roof at Low Parapet


MR100-03 Dec. 2012
METALWRAP-H w/MR-100

WINDOW AND WINDOW WINDOW PRIMARY

SUBSILL (BY OTHERS) SEAL (BY WINDOW


CONTRACTOR)
SEALANT
WINDOW SECONDARY
(BY OTHERS)
SEAL (BY OTHERS)
SILL FLASH
SILL EXTENSION
AND SUPPORT
FLASHING-
FLASH;SHIM TO ADHERE TO PRIMARY
ALLOW VENTING.
SILL FLASHING; FOLD
TO FORM AN END DAM
PANEL THRU FASTENER AT JAMBS.
TO SUPPORT
SUBFRAMING

WOOD
SUBFRAMING FASTENER SUBSILL
ANCHORED INTO CENTER
OF METALWRAP MR-100 RAIL

PRIMARY MEMBRANE FLASHING


CONTINUOUS MR-100
(BY PANEL
ATTACHMENT SYSTEM AT EACH
CONTRACTOR)
PANEL SIDE JOINT (36" O.C.)
VERTICALLY AND FASTENED SEALANT BETWEEN

INTO EACH FRAMING MEMBER PANEL LINER AND


PRIMARY FLASH
(16" TO 24" O.C.)
HORIZONTALLY
SHOP APPLIED

AIR/VAPOR BARRIER
SEALANT
CSC-3 FLUSH
PANEL CLIP

CONCEPT SERIES
CS-260 PANEL

STEEL STUD
METALWRAP INSULATED 18 GA. MIN.
BACK-UP PANEL

INTERIOR
112 " SUBFRAMING GYPSUM
AND AIR CAVITY BOARD

NOTE:
THESE DETAILS ARE FOR INSTALLATION AND
SEALING OF METALWRAP PANELS ONLY.
FOR INSTALLATION AND SEALING REQUIRED
FOR FACE PANELS SEE CENTRIA STANDARD
DETAILS FOR THE SPECIFIC FACE PANEL.

Window Sill w/Concept Series


MR100-04 Dec. 2012
METALWRAP-H w/MR-100
JOINT BACK-UP FLASH APPLY BUTYL TO
12
1 " SUBFRAMING FILL SHOULDER
CONT. METALWRAP 100
AND AIR CAVITY BETWEEN MARRIAGE
RAIL
BEADS
SHOP APPLIED

AIR/VAPOR BARRIER
SEALANT

CONTINUOUS MR-100
ATTACHMENT SYSTEM AT EACH

PANEL SIDE JOINT (36" O.C.)


VERTICALLY AND FASTENED
INTO EACH FRAMING MEMBER
(16" TO 24" O.C.)
HORIZONTALLY

SUBFRAMING FASTENER
ANCHORED INTO CENTER
6" WIDE SELF-ADHERING
OF METALWRAP MR-100 RAIL
FLEXIBLE MEMBRANE OR METAL
FLASHING- CONTINUOUS AT ALL
METALWRAP PANEL; PANEL VERTICAL JOINTS ABOVE
FIELD CUT AS REQ'D WINDOW. PUNCTURE AT PANEL CLIP
THEN SEAL.
PRIMARY
CONCEPT SERIES CS-260
MEMBRANE
PANEL AND CSC-3 CLIP
FLASHING FROM
WINDOW
STEEL STUD PERIMETER
18 GA. MIN. TO PANEL LINER

6" WIDE SELF-ADHERING SEALANT


FLEXIBLE MEMBRANE OVER BETWEEN
TOP OF METAL FLASH MEMBRANE
FLASH AND
PANEL LINER

PANEL THRU FASTENER


WINDOW HEADER
TO SUPPORT
PER STEEL
SUBFRAMING
DESIGN

PANEL THRU-FASTENER
WOOD BLOCKING

THREE-PIECE HEAD INTERIOR GYPSUM


FLASH; SHIM AND BOARD
PROVIDE CLEARANCE
BELOW FACE TRIM
WINDOW
FOR DRAINAGE.
PRIMARY SEAL

(BY WINDOW
SEALANT
CONTRACTOR)
(BY OTHERS)
WINDOW
NOTE: SECONDARY
THESE DETAILS ARE FOR SEAL (BY
INSTALLATION AND SEALING OF OTHERS)
METALWRAP PANELS ONLY. FOR
INSTALLATION AND SEALING WINDOW AND
REQUIRED FOR FACE PANELS PANNING (BY
SEE CENTRIA STANDARD DETAILS FOR OTHERS)
THE SPECIFIC FACE PANEL.

Window Head w/Concept Series


MR100-05 Dec. 2012
METALWRAP-H w/MR-100
PRIMARY MEMBRANE
WOOD BLOCKING FLASHING FROM STEEL STUD
WINDOW PERIMETER 18 GA. MIN.
TO PANEL LINER
WINDOW
PRIMARY SEAL SEALANT BETWEEN INTERIOR
(BY WINDOW PANEL LINER AND GYPSUM
PRIMARY MEMBRANE BOARD
CONTRACTOR)
FLASH

WINDOW
SECONDARY

SEAL (BY
OTHERS)

WINDOW AND
PANNING (BY
OTHERS)

SEALANT CONCEPT SERIES


2 12 "

CS-260 PANEL
(BY OTHERS)

JAMB FLASH METALWRAP PANEL;


AND SUPPORT FIELD CUT AS REQ'D
FLASH

112 " SUBFRAMING


AND AIR CAVITY
METAL CLOSURES
CSC-3 FLUSH
PANEL CLIP

NOTE:
THESE DETAILS ARE FOR INSTALLATION AND
SEALING OF METALWRAP PANELS ONLY.
FOR INSTALLATION AND SEALING REQUIRED FOR
FACE PANELS SEE CENTRIA STANDARD DETAILS FOR
THE SPECIFIC FACE PANEL

Window Jamb w/Concept Series


MR100-06 Dec. 2012
METALWRAP-H w/MR-100
INTERIOR SIDE METAL CLOSURE

MEMBRANE FLASHING;
CONTINUOUS TO BASE.
3 1/2"
MIN. APPLY A CURING BUTYL
NOTCH PANEL LINER AT SEALANT PLUG NEAR EACH
CORNERS AS SHOWN PANEL END DURING PANEL

(PROVIDES A THERMAL ERECTION.

BREAK) (SEE DETAIL BELOW)

SEALANT BETWEEN
PANEL LINER AND
INTERIOR MEMBRANE

9" WIDE EXTERIOR SIDE


MEMBRANE OR METAL
FLASHING; CONTINUOUS
ONTO BASE FLASHING
BELOW.

CSC-3 FLUSH
PANEL CLIP
STEEL STUD
18 GA. MIN.

12
1 " SUBFRAMING
AND AIR CAVITY

CONCEPT SERIES
CS-260 PANEL
INTERIOR
GYPSUM
BOARD
METALWRAP PANEL;
FIELD CUT AS REQ'D
MINIMUM SEALANT
CONTACT SHOWN

CONTINUOUS MR-100
ATTACHMENT SYSTEM AT EACH

PANEL SIDE JOINT (36" O.C.)


VERTICALLY AND FASTENED
" MIN.

INTO EACH FRAMING MEMBER


(16" TO 24" O.C.)
HORIZONTALLY 8
3

FLASHING TAPE
NOTE: @ VERT. JOINTS
THESE DETAILS ARE FOR INSTALLATION
AND SEALING OF METALWRAP PANELS SEALANT PLUG DETAIL
ONLY. FOR INSTALLATION AND SEALING APPLY SEALANT AS
REQUIRED FOR FACE PANELS SEE CENTRIA PANELS ARE ERECTED.
STANDARD DETAILS FOR THE SPECIFIC
FACE PANEL.

Outside 90 Corner
MR100-07 Dec. 2012
METALWRAP-H w/MR-100
INTERIOR SIDE APPLY A CURING BUTYL
MEMBRANE FLASHING; SEALANT PLUG NEAR EACH
CONTINUOUS TO BASE. PANEL END DURING PANEL
ERECTION.

NOTCH PANEL LINER AT


(SEE DETAIL BELOW)
CORNERS AS SHOWN

(PROVIDES A THERMAL
BREAK)

SEALANT BETWEEN
PANEL LINER AND
INTERIOR MEMBRANE

9" WIDE EXTERIOR SIDE


MEMBRANE OR METAL
FLASHING; CONTINUOUS
ONTO BASE FLASHING
BELOW.

CSC-3 FLUSH
PANEL CLIP
STEEL STUD
18 GA. MIN.

12
1 " SUBFRAMING
AND AIR CAVITY

CONCEPT SERIES
CS-260 PANEL
INTERIOR
(MITERED CORNER) GYPSUM
BOARD
METALWRAP PANEL;
FIELD CUT AS REQ'D
MINIMUM SEALANT
CONTACT SHOWN
CONTINUOUS MR-100
ATTACHMENT SYSTEM AT EACH

PANEL SIDE JOINT (36" O.C.)


VERTICALLY AND FASTENED
INTO EACH FRAMING MEMBER
" MIN.

(16" TO 24" O.C.)


HORIZONTALLY
8
3

NOTE: FLASHING TAPE

THESE DETAILS ARE FOR INSTALLATION @ VERT. JOINTS

AND SEALING OF METALWRAP PANELS SEALANT PLUG DETAIL


ONLY. FOR INSTALLATION AND SEALING APPLY SEALANT AS
REQUIRED FOR FACE PANELS SEE CENTRIA PANELS ARE ERECTED.
STANDARD DETAILS FOR THE SPECIFIC
FACE PANEL. PANELS ARE ERECTED.
Outside 90 Concept Series Mitered Corner
MR100-07a Dec. 2012
METALWRAP-H w/MR-100
NOTCH PANEL FACE AT APPLY A CURING BUTYL SEALANT SEALANT BETWEEN
CORNERS AS SHOWN PLUG NEAR EACH PANEL END PANEL LINER AND

(PROVIDES A THERMAL DURING PANEL ERECTION. CORNER FLASH

BREAK) (SEE DETAIL BELOW)

CONTINUOUS
INTERIOR SIDE
CORNER
FLASHING

6" WIDE
EXTERIOR SIDE
STEEL STUD
MEMBRANE OR
18 GA. MIN.
METAL FLASHING;
CSC-3 FLUSH CONTINUOUS
PANEL CLIP ONTO BASE
FLASHING BELOW.
" MIN.

3/4" SUBFRAMING
AND AIR CAVITY
INTERIOR
2
METAL CLOSURES 1 GYPSUM
2
BOARD

CONTINUOUS MR-100
ATTACHMENT SYSTEM AT EACH

PANEL SIDE JOINT (36" O.C.) MINIMUM SEALANT


VERTICALLY AND FASTENED CONTACT SHOWN
INTO EACH FRAMING MEMBER
(16" TO 24" O.C.)
HORIZONTALLY

CONCEPT SERIES 3
8
CS-260 PANEL
" MIN.

METALWRAP PANEL;
FIELD CUT AS REQ'D

NOTE:
THESE DETAILS ARE FOR INSTALLATION FLASHING TAPE
AND SEALING OF METALWRAP PANELS @ VERT. JOINTS.
ONLY. FOR INSTALLATION AND SEALING
REQUIRED FOR FACE PANELS SEE CENTRIA SEALANT PLUG DETAIL
STANDARD DETAILS FOR THE SPECIFIC APPLY SEALANT AS

FACE PANEL. PANELS ARE ERECTED.

Inside 90 Corner
MR100-08 Dec. 2012
METALWRAP-H w/MR-100
NOTCH PANEL FACE AT APPLY A CURING BUTYL SEALANT SEALANT BETWEEN
CORNERS AS SHOWN PLUG NEAR EACH PANEL END PANEL LINER AND

(PROVIDES A THERMAL DURING PANEL ERECTION. CORNER FLASH

BREAK) (SEE DETAIL BELOW)

CONTINUOUS
INTERIOR SIDE
CORNER
FLASHING

6" WIDE
EXTERIOR SIDE
STEEL STUD
MEMBRANE OR
18 GA. MIN.
METAL FLASHING;
CONTINUOUS
ONTO BASE
CSC-3 FLUSH FLASHING BELOW.
PANEL CLIP

INTERIOR
3/4" SUBFRAMING
AND AIR CAVITY GYPSUM
BOARD
CONTINUOUS MR-100
ATTACHMENT SYSTEM AT EACH

PANEL SIDE JOINT (36" O.C.)


VERTICALLY AND FASTENED MINIMUM SEALANT
INTO EACH FRAMING MEMBER CONTACT SHOWN
(16" TO 24" O.C.)
HORIZONTALLY

CONCEPT SERIES
CS-260 PANEL
3
8
" MIN.

METALWRAP PANEL;
FIELD CUT AS REQ'D

NOTE:
THESE DETAILS ARE FOR INSTALLATION FLASHING TAPE
AND SEALING OF METALWRAP PANELS @ VERT. JOINTS.
ONLY. FOR INSTALLATION AND SEALING
REQUIRED FOR FACE PANELS SEE CENTRIA SEALANT PLUG DETAIL
STANDARD DETAILS FOR THE SPECIFIC APPLY SEALANT AS

FACE PANEL. PANELS ARE ERECTED.

Inside 90 Concept Series Mitered Corner


MR100-08a Dec. 2012
METALWRAP-H w/MR-100
STEEL STUD
18 GA. MIN.
INTERIOR SEALANT BETWEEN
GYPSUM PANEL LINER AND
BOARD PRIMARY END WALL
FLASH

END WALL
FLASH

APPLY A CURING BUTYL SEALANT


PLUG NEAR EACH PANEL END
DURING PANEL ERECTION.

APPLY BED SEAL OF


(SEE DETAIL BELOW)
CURING BUTYL BETWEEN
SUBSTRATE AND END
WALL FLASH. SECURE
WITH MASONRY
FASTENERS.

CONCEPT SERIES
CS-260 PANEL
SEALANT
2 12 "

(BY OTHERS)
METALWRAP PANEL;
FIELD CUT AS REQ'D
JAMB FLASH
CSC-3 FLUSH
PANEL CLIP
MINIMUM SEALANT
METAL CLOSURES CONTACT SHOWN
12
1 " SUBFRAMING
AND AIR CAVITY

3
8
" MIN.

FACE OF ADJACENT
STRUCTURE

NOTE:
FLASHING TAPE
THESE DETAILS ARE FOR INSTALLATION AND
@ VERT. JOINTS
SEALING OF METALWRAP PANELS ONLY.
FOR INSTALLATION AND SEALING REQUIRED FOR
FACE PANELS SEE CENTRIA STANDARD DETAILS FOR SEALANT PLUG DETAIL
THE SPECIFIC FACE PANEL APPLY SEALANT AS
PANELS ARE ERECTED.

End Wall
MR100-09 Dec. 2012
METALWRAP 100 SERIES
STEEL STUD
18 GA. MIN.
INTERIOR SEALANT BETWEEN
GYPSUM PANEL LINER AND
BOARD PRIMARY END WALL
FLASH

END WALL
FLASH

APPLY A CURING BUTYL SEALANT


PLUG NEAR EACH PANEL END
DURING PANEL ERECTION.

APPLY BED SEAL OF (SEE DETAIL BELOW)


CURING BUTYL BETWEEN
SUBSTRATE AND END
WALL FLASH. SECURE
WITH MASONRY
FASTENERS.

[13]
CONCEPT SERIES
"

CS-260 PANEL
SEALANT 14 "
1
2

(BY OTHERS) [6]


METALWRAP PANEL;
FIELD CUT AS REQ'D
FIN FLASH

CSC-3 FLUSH
PANEL CLIP MINIMUM SEALANT
CONTACT SHOWN

1 1/2" DEEP HATSHAPED


SUBGIRT (SG-150-16)

3
FACE OF ADJACENT 8
" MIN.

STRUCTURE

NOTE:
FLASHING TAPE @
THESE DETAILS ARE FOR INSTALLATION AND
VERT. JOINTS
SEALING OF METALWRAP PANELS ONLY.
FOR INSTALLATION AND SEALING REQUIRED FOR
FACE PANELS SEE CENTRIA STANDARD DETAILS FOR SEALANT PLUG DETAIL
THE SPECIFIC FACE PANEL APPLY SEALANT AS
PANELS ARE ERECTED.

End Wall w/Concept Series/Fin Flash


MW100-09a Dec. 2012
METALWRAP-H w/MR-100
1 5/8"
MIN.

Seal MR-100 ATTACHMENT


Plate SYSTEM and Fastener

3/8" 3/8"

6" MIN.
Butyl Butyl
Sealant Sealant
Continuous Continuous

14 " MAX.* 14 " MAX.*


TYP. TYP.

VERTICAL JOINT VERTICAL JOINT


@ SINGLE STUD NOT @ STUD**

* Without the Need to ** Limited to standard


Add Additional 16" or 24" stud spacing
Low-Expansion Foam

Horizontal Section Describing Two


Approved Methods of Panel End Support
Two 3/8" beads of high Place 3/8" bead of high grade
grade butyl sealant are field butyl sealant over the panel liner
applied to the seal plate at male leg as shown. This "marriage
panel ends, joints, perimeters bead" will connect the shop installed
and cut edges. butyl sealant in the side joint of the
panel above to the field applied
butyl of the seal plate at the panel
ends.

The Vertical
Joint Sealant
and the Marriage Bead

Vertical Joint
MR100-10 Dec. 2012
METALWRAP-H w/MR-100
A
SIZE OF FLASH VARIES
BY LOCATION & PITCH
OF CLADDING

Seal perimeter
W/Polyurethane Sealant

112 " Subgirt


(Beyond)

Electrical Box
Surface-mount on panel
exterior. Shim to adjust
for cladding depth.
(BY ELECTRICAL CONTRACOR)
Interior opening around
conduit penetration to be
NEATLY DRILLED & SEALED

by Electrical installer.

Conduit Stub

(NBC)

Metal and Composition


Closures set in sealant

Flat Flash with


Hemmed Edge on Conduit
all sides (NBC)
STYLE-RIB
Panel
NOTE:SMALL PENETRATIONS
Dome Head ARE SIMILAR IN CONSTRUCTION
Rivet
AS SHOWN ABOVE AND SHOULD
NOT REQUIRE REMOVAL OF
Butyl Tape Flashing PANEL CORE OR METAL SKINS.
around perimeter of
electrical box.
(BY OTHER TRADES)

NOTE:
THESE DETAILS ARE FOR INSTALLATION Section A-A
AND SEALING OF METALWRAP PANELS
ONLY. FOR INSTALLATION AND SEALING
REQUIRED FOR FACE PANELS SEE CENTRIA
STANDARD DETAILS FOR THE SPECIFIC
FACE PANEL.

Electrical Box Penetration Detail


MR100-11 Dec. 2012
METALWRAP-H w/MR-100

1'-4" [406] STUD SPACING

STUDS (NBC)

METALWRAP
12
1 " DEEP HATSHAPED

SUBGIRT (SG-150-16)

14
1 " DEEP HATSHAPED

SUBGIRT (SG-125-16)

[13]
"

1 2
HORIZONTAL
1 " 2 PIECE VERTICAL REVEAL
IW-20A 4
FLASHING WITH HEM

[6]

NOTE:
THESE DETAILS ARE FOR INSTALLATION AND
SEALING OF METALWRAP PANELS ONLY.
FOR INSTALLATION AND SEALING REQUIRED FOR
FACE PANELS SEE CENTRIA STANDARD DETAILS FOR
THE SPECIFIC FACE PANEL

IW20A Vertical Joint Fin Flash


MR100-12 Dec. 2012
METALWRAP-H w/MR-100

1'-4" [406] STUD SPACING

STUDS (NBC)

METALWRAP
12
1 " DEEP SUBGIRT

(SG-150-16)

14
1 " DEEP SUBGIRT

(SG-125-16)

" [38]
" [13]
1 "
1 2
4 1

1 2

[6]
2 PIECE VERTICAL REVEAL
EXPOSED FASTENER FLASHING WITH HEM
PANEL PROFILES

NOTE:
THESE DETAILS ARE FOR INSTALLATION AND
SEALING OF METALWRAP PANELS ONLY.
FOR INSTALLATION AND SEALING REQUIRED FOR
FACE PANELS SEE CENTRIA STANDARD DETAILS FOR
THE SPECIFIC FACE PANEL

EFHZ Vertical Joint Fin Flash


MR100-13 Dec. 2012
METALWRAP-H w/MR-100

1'-4" [406] STUD SPACING

STUDS (NBC)

METALWRAP
1 1/2" DEEP SUBGIRT
(SG-150-16)

1 1/4" DEEP SUBGIRT


(SG-125-16)

[13]
"

1 2
CONCEPT SERIES
HORIZONTAL PANEL
1 "

[6]

NOTE:
THESE DETAILS ARE FOR INSTALLATION AND
SEALING OF METALWRAP PANELS ONLY.
FOR INSTALLATION AND SEALING REQUIRED FOR
FACE PANELS SEE CENTRIA STANDARD DETAILS FOR
THE SPECIFIC FACE PANEL

Concept Series Vertical Joint Fin Flash


MR100-14 Dec. 2012
METALWRAP-H w/MR-100

NOTE: (NBC) = NOT BY CENTRIA

STUDS (NBC)

ERECTOR NOTE:
AFSEALTIEHELDAASPDRCONDIREQUIOVIDETREIOED.NN.D DAM
BACK-UP ANEL
METALWRAP

FLSAESLHFINAGDHTEARPIENGBUTYL
PANELFLPROIINMAERWRIYNMDOEMWBPREANREIMFELTAESRHINTOG
FIELD TAB JAMB

SILL FLASH DRIP FLASHHEAD


NON-CURING BUTYL
SILL 50-16 SUBGIRT
SG-
1

JAMB FLASH

PERMANUFACTURE COM ENDATIONS


PRIMARYAIRSEAL(NBC)(TYP.)
CURING BUTYL

WEATHERSEAL(NBC)(TYP.)
NOTE:
THESE DETAILS ARE FOR INSTALLATION
AND SEALING OF METALWRAP PANELS
ONLY. FOR INSTALLATION AND SEALING
REQUIRED FOR FACE PANELS SEE CENTRIA
STANDARD DETAILS FOR THE SPECIFIC
FACE PANEL.

INTERSECTION OF
HEAD, JAMB AND SILL FLASH (ISO) Dec. 2012