Академический Документы
Профессиональный Документы
Культура Документы
a r t i c l e i n f o a b s t r a c t
Article history: The aim of this study is to develop a coordinated day-ahead voltage control strategy for an active dis-
Received 6 March 2015 tribution network. A framework comprising a synergy of real-time dynamic thermal rating (DTR) and
Received in revised form 21 May 2015 coordinated voltage control (CVC) is proposed for solving the voltage quality and thermal limit problems
Accepted 23 May 2015
associated with a high penetration level of distributed generation (DG) in an active distribution network.
Available online 9 June 2015
The CVC scheme involves solutions such as On-Load-Tap-Changers (OLTCs), active and reactive power
control of DG units, and switchable shunt VAR compensation devices (SVCs). Loss minimization and
Keywords:
voltage penalty objective functions in the CVC optimization problem are compared. A 147 bus test distri-
Active network management
Distributed generation (DG)
bution network planned for an actual geographical location is used to evaluate the proposed DTR-based
Dynamic thermal rating (DTR) day-ahead CVC strategy. In this study, we have showed that the reactive power absorption/injection
Onload tap changer (OLTC) potential of DG units can play an important role in CVC. Moreover, the study demonstrates that real-time
State estimation thermal rating boosts the utilization of reactive power resources in the distribution system. Finally, the
Voltage control study investigates the practicality of day-ahead active distribution network operation planning for CVC.
2015 Elsevier B.V. All rights reserved.
http://dx.doi.org/10.1016/j.epsr.2015.05.018
0378-7796/ 2015 Elsevier B.V. All rights reserved.
42 M.Z. Degefa et al. / Electric Power Systems Research 127 (2015) 4152
studies considered the coordination of only two voltage con- A centralized management of thermal constraints, while inhibi-
trol methods, while others investigated all the available methods, ting violation of voltage limits, is presented in [13] by employing
including the reactive power control of DG units. The study in [5] remotely controlled switches to reduce the DG curtailment. The
presents a coordination of OLTC and Static-var-Compensators (SVC) study claims that the additional degree of freedom provided by
in an unbalanced distribution system. The proposed approach is a remotely controlled network switches leads to less DG curtailment.
two-stage decision making procedure, where in stage one, an opti- However, as in [12], in [13] the thermal limits of all lines are set to
mization problem of loss minimization is solved and in stage two, a constant value.
the minimization of switching due to economic and technical con- In practice, both the capacity threshold and DG generation
siderations is solved. Nevertheless, in [5] the DG units have been uctuates a lot, following weather variations in real-time. Hence,
assumed to operate with unity power factor; no reactive power dynamic thermal rating is proposed in this study to manage voltage
supply is considered from the DG units. In [6], coordination among level and network losses while the real-time line thermal limit is
multiple SVCs, OLTC and DG units is presented for an online voltage being respected in the constraint. In addition, in this study OLTCs,
control in distribution systems. The synchronous machine-based DG units and SVCs are coordinated in addressing the voltage and
renewable DG units are also involved in the voltage regulation, thermal constraints in an active distribution network.
which minimized, according to [6], the total tap operation of SVRs. The purpose of this study is to provide a CVC strategy for
The method in [6] uses pseudo measurements for load and DG gen- the day-ahead operation of an active distribution network with
eration; however, it doesnt include the uncertainties involved with updated network capacity using real-time thermal rating (RTTR).
the measurements or uncertainties in the voltages from distribu- The CVC involves tap changing transformers, switchable static VAR
tion state estimation. The study in [7] proposes a hierarchical rule compensators and DG units. The day-ahead control strategies use
based coordinated voltage control strategy involving OLTCs and DG day-ahead forecasts of load, weather variables and DG generation.
units. In mitigating voltage problems, predened steps tap chang- Voltage penalty function and network loss minimization objectives
ing steps, Q regulation of DG units and PQ regulation of DG units are compared in solving the CVC problem involving DG units.
are initiated sequentially until the problem is alleviated. In the The limitations of the method proposed in this study are mostly
studies [4,8], the authors presented a method to enable distribu- associated with uncertainties in load and weather variable fore-
tion system operators to integrate the voltage level management casts. Further, the execution complexity due to inconsistencies
potential of DG units in their network operation and planning prin- between the planned day-ahead settings of voltage control devices
ciples. These studies are efforts to relate the vast optimization and and their intraday local measurement-based closed loop operation
rule-based coordinated voltage control theoretical studies to the pose a challenge. Nevertheless, with the development of network
practical conditions of the existing network. In [8], a planning pro- operation planning from day-ahead to hour- and minute-ahead
cedure is proposed so that implementation in the currently used planning, the inaccuracies are likely to become less signicant.
network planning tools is convenient. Section 2 reviews the various voltage regulating mechanisms
The coordination between substation voltage and DG reactive and discusses the reactive power potential of DG. In Section 3,
power is claimed to be the least cost method in [4], which used sta- a brief discussion of the real-time thermal rating (RTTR) method
tistical distribution planning to select voltage control strategy. In employed in this study is presented. The subsequent section, Sec-
the statistical planning, one year load and production curves were tion 4, presents the CVC formulation, which incorporates the DG
used to conduct load ows which can then be used to evaluate the Q/V droop control variables and network component ratings. In
costs of different control strategies [4]. Nevertheless, the rule-based this section, the loss minimization and voltage deviation penalty
procedures in [4,8] do not investigate the costs of the optimal coor- function based objectives are also discussed. In Section 5, the test
dination of different voltage control strategies. A comprehensive active distribution network and the load and weather variables uti-
voltage control strategy among OLTCs, substation switched capac- lized in the analysis are presented. Section 5 also discusses the main
itors and feeder-switched capacitors is presented in [9]. The study observations of the analysis while Section 6 briey discusses prac-
also investigated the impact of DG units on the control strategies, tical concerns related to communicating control set-points. The last
in which they found that a constant voltage operation of DG units section, Section 7, summarizes the main ndings of this study.
is benecial for a signicant reduction in OLTC operation. In [9],
however, the DG is set to generate constant active power, which is
not possible in the case of PVs and Wind, ruling out the possibility 2. Voltage control methods
of PQ control of DG.
The study in [10] proposes a simple DG local reactive power There are two typical voltage level problems in distribution
control with occasional communication with distribution network systems. The short-term problem, which lasts for not more than
operators (DNO). The proposed approach aims to guarantee that a minute, and the long-term problem, where the voltage level
active power generation does not cause voltage rise. With an objec- remains outside the 10% limit for more than 1 min. Over voltage
tive function that minimizes DG curtailment and voltage violations, and under voltage events require proper management that utilizes
the study in [11] proposes a comprehensive centralized voltage the dependencies of voltage and other variables, such as active and
constraint management approach. Provided that the VCM problems reactive load and generation, as shown in Fig. 1 and (1). The voltage
are formulated properly, the MINLP solvers generally provide an at busbar 2 in Fig. 1 can be approximated as
acceptably fast solution, as most distribution systems are equipped
R (PG PL ) + (QG QL QC ) X
with a relatively small number of discrete control means [11]. In V2 V1 + (1)
V2
[11], the transfer of DG between feeders using only remotely con-
trolled switches only occurs when the DG curtailment cost exceeds
the cost of switching.
There are only a few studies (such as [12,13]) which tackle the
real-time management of voltage and thermal constraints local
to DG connection. The decentralized approach in [12] aims to
avoid extensive sensing and communications, where the thermal
constraint is managed by setting a constant line capacity thresh-
old which triggers the trimming of wind generation if violated. Fig. 1. A simple illustration of voltage dependency in distribution network [14].
M.Z. Degefa et al. / Electric Power Systems Research 127 (2015) 4152 43
2.1.2. Switchable static VAR compensation devices (SVC) 2.1.3.1. Q/V droop controller. This type of control is also called volt-
An SVC is a shunt-connected static var generator or sink whose age dependent reactive power control. The DG units considered
output is adjusted to exchange capacitive or inductive current. in this study are PVs and wind turbines. The Q/V droop method
Hence, SVCs are capable of either supplying or absorbing reactive does not need a source of real power for generating the neces-
power. The response time of SVCs is also fast enough to respond to sary reactive power for compensation. Since the main objective of
transitional voltage uctuations. In this study, the SVCs comprise PV generators is to produce active power, their reactive power is
either thyristor-switched capacitors or reactors. limited to the maximum apparent capacity of the inverter.
V
Qmax , V < 0.9 or V > 1.1
2.1.3. DG reactive power control methods
V
The reactive power capability of DG units (wind turbines and
solar PVs in this study) originates from their inverter circuits con-
0, 1 D V 1 + D
necting to the grid. Except for limiting the maximum reactive power Q = Q
max (3)
(V + 1 + D) , 1 + D < V 1.1
intake or supply, the active power generated does not have an
0.1 D
impact on the reactive power capacity of DG units, as formulated in
(2). This fact enables solar PVs to be utilized in reactive power bal- Qmax V + 1 D , 0.9 V < 1 D
0.1 D
ance, even during night time when no generation is possible. The
inverter apparent power rating, however, sets the absolute possible Qmax = P tan (acos (PFlim )) (4)
reactive power capacity, as shown in (2) and Fig. 2.
where the power factor limit is PFlim and the deadband range set-
ting value is D. The graphical presentation of (3) and (4) is presented
Qmax (t) = 2
Smax Pact (t)2 (2) in Fig. 3.
where Smax (red line in Fig. 2) is the inverter apparent power rating,
Pact (t) is the actual active power generated by DG at time t (green
line in Fig. 2) and Qmax (t) is the corresponding maximum reactive
power supply or intake capability.
Standards such as IEEE 1547 do not currently allow active
voltage regulation by DG inverters at the point of common cou-
pling (PCC) to access maximum amount of real power and to
avoid unnecessary interaction among voltage controllers. Other-
wise, there is no other technical limitation inhibiting the usage
of reactive power of DG units. Many inverters have the capabil-
ity of providing reactive power to the grid. Inverters can also be
oversized just to increase the capacity of their reactive power
balance. Fig. 3. Q/V control with dead-band.
44 M.Z. Degefa et al. / Electric Power Systems Research 127 (2015) 4152
2.1.3.2. DG P/V droop controller. The P/V droop can be implemented are used in the RTTR system. The underground cable thermal model
with either soft curtailment in the case of dispatchable DG or dis- developed by the authors and the implementation procedures of
connection of the DG altogether in the case of non-dispatchable DG. the RTTR system are detailed in [16,17].
The P/V droop controllers are effective in resistive networks. Both
the P/V and Q/V -control could be a constant droop or with a dead- 4. Optimal day ahead CVC formulation
band. In this way, the DG units would only react to voltages that
exceed a certain threshold voltage. In the P/V droop control, the DG The main goal of CVC in distribution networks is to compen-
units contribute to the load sharing, depending on both their ratings sate for the load and DG generation variations so that the customer
(droops) and the line impedances. The P/V droop control strategy supply voltages are kept within certain bounds. The utilization
is based on the formulation shown in the following equation: of DG units coordinating with SVCs and OLTCs for voltage con-
trol can impose higher loading on the network. In other words,
Pmax,i ki Vi Vcrit,i Vi Vcrit,i
Pi = (5) to tap the supply and absorption capacity of reactive power in a
Pmax,i Vi < Vcrit,i distribution system the lines and cables are required to cope with
increased loading. The network loading capacity in a static rating
where Vcrit,i is the voltage above which the power injected by the DG regime, however, is heavily limited compared to real-time thermal
is decreased with the droop coefcient ki and Pmax,i is the nominal rating.
power or the maximum power available by the DG. Vi and Pi are The day-ahead CVC framework presented in Fig. 5 comprises
the voltage level and DG output at node i. The P/V droop equation weather variable and load forecasts. The DG output forecast is based
in (5), hence, executes the active power curtailment required for on the weather variables, while the component ratings depend
keeping the bus voltage within an acceptable range. In this study, on both the weather variables and forecasted loading. The errors
the Q/V droop controller method with dead-band is used to control in the forecasting will in fact be carried through to the CVC set-
the reactive power supply or intake of DG units. tings. Hence, evaluating the uncertainties in the control settings
is also equally crucial. Besides, while being the general day-ahead
3. Real-time thermal rating guideline for the voltage regulating devices, the optimal control set-
tings from the proposed framework require updates within each
Static distribution network ratings are usually calculated day. In this study we mainly focus on providing the optimal CVC
assuming conservative weather conditions. For example, the rat- set-points for day-ahead distribution network operation. Practical
ing of overhead lines is calculated under low wind speed conditions matters, such as communication, uncertainties and contingencies
and high ambient temperature. These ratings are usually provided are briey discussed in Section 6 from the multi-agent system per-
seasonally and are xed within the season. The RTTR method, how- spective.
ever, estimates the real-time thermal states and provides hour In the optimal decision of set-points for CVC, the ratings of
ahead ratings, for example, by using the previous loading condi- components such as lines and cables must be considered. How-
tions and local weather measurements or forecasts. The weather ever, these capacity limits could either be set based on static rating
variables relevant to the thermal ratings are wind speed, ambi- principles or real-time thermal rating methods. The incorporation
ent temperature, solar irradiation and ground soil temperature. of an RTTR system with CVC brings two main benets: the rst
The emerging active distribution network is facing distributed
generation and demand response induced stochastic loading char-
acteristics. Hence, to implement the real-time monitoring and
operation of an active distribution network, a real-time thermal
rating system is essential.
The RTTR system requires dynamic thermal models of the essen-
tial components such as underground cables, overhead lines and
substation transformers. Thermal models are expected to be capa-
ble of giving the maximum next hour carrying capacities by using
the current thermal state information and forecasts of weather vari-
ables. The equivalent ladder network circuit of underground cables
installed in unlled conduit is presented in Fig. 4. It shows the
thermal resistances and thermal capacitances emulating the tran-
sient thermal responses. IEEE Std. 738 and IEEE Std. C57.91 loading
guidelines for overhead conductors and oil-immersed transformers
Fig. 4. A seven loop thermal model for an underground cable inside an unlled
conduit.
Fig. 5. Three level CVC strategy procedure.
M.Z. Degefa et al. / Electric Power Systems Research 127 (2015) 4152 45
V G
emphases on power quality and distribution losses. The minimiza- N
tions of loss and penalty objective functions formulated in (6) and PDGi + PDi + Vi j ij cos ij + Bij sin ij = 0 i = 1, . . ., N (8)
(7), respectively, are compared in Section 5. j=1
Loss minimization demonstrates the economical aspect while
voltage deviation in the objective represents the technical lim-
V G
N
itations. The utilization of DG reactive power and impact of QCi QDGi + QDi + Vi j ij sin ij Bij cos ij = 0 i = 1, . . ., N
real-time thermal rating for CVC is the focal point of this study. j=1
where N is the total number of buses and gk (gi,j ) is the conductance akmini aki akmaxi i NOLTC (14)
of branch k or the line connecting node i to j. Vi and Vj are the
Sij Sij,max (15)
voltage magnitudes and i and j are voltage angles for nodes i and
j, respectively. 0 PDGi PDG gen,i , i = 1, . . ., N, (16)
where (11) limits the upper and lower voltage magnitude at bus i,
4.1.2. Voltage penalty function objective (12) sets the limits for DG reactive power at bus i, (13) limits the
In addition to the loss minimization objective dened in (6), a reactive power supply from the SVCs, (14) gives the range of OLTC
penalty function for the voltage exceeding a certain threshold can set-points and (15) gives the real-time dynamic thermal rating or
be dened as in the following equation: static rating of branch ij. Eq. (16) prevents the utilized DG generated
power PDGi at node i from exceeding the actual DG generated power
PDG gen,I , NDGq , NCq , and NOLTC are the set of all DG units, SVCs and
k(V Vi )2 ; Vi < Vimin
imin OLTCs connected at bus i, respectively.
Wi = 0; Vimin Vi Vimax (7) Sij,max is the capacity of the line or cable which is calculated
using the dynamic thermal models of the overhead lines and under-
k(Vi Vimax )2 ; Vi > Vimax ground cables. The previous hours optimal loading of the branch
is used to attain the initial conductor temperature for calculating
where k is the penalty factor. the coming hours line or cable rating. Hence, the iteration between
The objective function in (7), also drawn in Fig. 6, can be used the OPF with CVC and the DTR is established. In the optimization
when the voltage quality is more signicant than the overall distri- problem dened by (6)(16), the control variables are the reactive
bution network losses. power of the DG units (QDGi ), the reactive power of the SVCs (QCi )
46 M.Z. Degefa et al. / Electric Power Systems Research 127 (2015) 4152
Fig. 7. Greeneld network plan based on actual loading data and geographical location [21]. (For interpretation of the references to color in this gure legend, the reader is
referred to the web version of this article.)
and the tap set-point (ak ). The state variables, on the other hand, CVC scheme and the implementation of a real-time thermal rating
are the bus voltage magnitude and angle, while the line load ows system.
are output variables. In the test network, the secondary substation one day loading is
Due to the nonlinearity of power systems, linear programing selected randomly from a pool of hourly AMR meter measurements
loses accuracy due to linear assumptions [19]. Hence, the OPF is from actual households. The random selection considers the data
solved using the nonlinear IPOPT solver of the General Algebraic pool to be uniformly distributed. The respective reactive power
Modeling System (GAMS), while the DTR has been implemented loads are calculated to correspond to the residential loading power
in MATLAB [20]. For numerical efciency within the power ow factor range of 0.955 to 0.98. Although the forecasts of the day ahead
or the OPF solution all discrete variables (transformer taps and load and weather variables are used to compute the optimal CVC
shunt steps) are treated as continuous until the optimal solu- set-points for day ahead network operation, the forecasting method
tion is found. Then they are rounded off to their nearest discrete is not elaborated in this study. The day ahead dynamic thermal rat-
values. ings and weather and load forecasting methods employed in this
The day-ahead dynamic thermal ratings of the distribution net- study are presented in publications [16,17].
work components in Fig. 5 are attained from the load and weather By denition, the DG penetration level in a system is the ratio of
variable forecasts input into the dynamic thermal models of the gross annual energy generated by the DG to the total annual energy
components. The day-ahead dynamic thermal rating procedure is demand in the system. In this study DG penetration levels of 1.13%,
presented in [17]. 11.3%, 22.6% and 65% are investigated. The DG capacity presented
in Table A.1 is at 1.13% penetration level, which is also the rst case
scenario. Mainly the scenarios for ten and twenty-fold increases
5. Test case: An active distribution network with DG units in the DG penetration levels are investigated, which are 11.3% and
and voltage regulating devices 22.6%, respectively. To represent a high DG penetration we also
simulated a 65% penetration level. The installed DG units, however,
For the test case, a Greeneld distribution network plan based are not evenly distributed throughout the network; rather, only the
on actual loading data and geographical location is used, as shown installed capacities are varied at their respective xed geographical
in Fig. 7. In the single line network diagram the green lines represent locations, as shown in Fig. 7.
MV underground cables while the red lines are overhead. The test There are around 30 radial feeders connected to the primary
distribution network has 146 20/0.4 kV secondary substations and substation, of which the longest line is 60 km. Details of the test
a 110/20 kV primary substation. distribution network are provided in Tables A.1 and A.2. In Fig. 8,
The distribution network has voltage regulating devices, an the bus voltages of the feeder starting from the primary substation
OLTC at primary substation and two SVCs installed at the load are plotted for a network without DG units and a network with 65%
center of the network. Besides, wind turbines are installed at four penetration of DG units. There is no CVC applied in the case shown
locations and solar panels are installed at three locations, as shown in Fig. 8 and the voltage levels are the average of the 24 h voltage
in Table A.1. In this work, various formulations of the CVC problem levels. The test distribution network without DG integration (see
for day-ahead distribution network operation are investigated. The Fig. 8a) has 2.4% higher losses on the selected day than the DG inte-
most important alternative solutions studied are the involvement grated test network (see Fig. 8b) with a 65% DG penetration level.
of DG units in supplying or absorbing reactive power through the In Fig. 9, the substation voltage level on the 30 feeders of the test
M.Z. Degefa et al. / Electric Power Systems Research 127 (2015) 4152 47
1.001
0.998
0.997
0.996
(a) 0 10 20 30 40 50 60
Distance from primary substation (km)
1.15
1.1
Voltage level (pu)
1.05
0.95
(b) 0 10 20 30 40 50 60
Distance from primary substation (km)
Fig. 8. Daily average voltage levels of buses on the 30 feeders radiating from the primary substation for the test distribution network without DG (a) and with 65% DG
penetration (b) (in (b) the blue feeders are connected with wind turbines and the red feeders are connected with solar panels). In both (a) and (b), there is no CVC applied.
(For interpretation of the references to color in this gure legend, the reader is referred to the web version of this article.)
network is plotted before and after the CVC is applied. Fig. 9a shows the greater utilization of active power generation from the DG units
the case for a 65% DG penetration level while Fig. 9b shows the case came with a slight increment in losses. A voltage penalty function
for 1.11% DG penetration. The CVC corrects both the overvoltages can minimize the voltage burden on the customer. As shown in
caused by DG connected at the end of radial feeder and undervolt- Fig. 10, the static and DTR ratings coupled with both the voltage
ages due to long distances from the primary substation. From Fig. 9 penalty function and loss minimization gave the voltage level clos-
it is also apparent that the two-third rule for SVC placement on a est to the nominal. DTR, therefore, enables the proper utilization
radial feeder does not apply in the test network, where the DG units of resources for CVC, where a superior benet can be attained by
are scattered at the ends of the feeders. using DTR coupled with the penalty function and loss minimization
In this study, the day ahead model predictive CVC strategy is objectives.
applied on the test distribution network by varying the CVC objec- The following characteristics of the CVC objective function for-
tive functions and the network rating types. The results in Table 1 mulation methods are observed:
compare the six types of CVC formulation involving DG units at Observation no. 1: The CVC formulations experienced a higher
1.13% penetration level with DG curtailment, and at 11.3% and voltage level from the nominal without the involvement of DG reac-
22.6% penetration level, with and without DG curtailment. Table 1 tive power capacity than with (see Fig. 11). In addition, the optimal
presents the overall network losses after applying the control set- set-point is achieved at signicantly higher network loss values for
points for a period of 24 h. Besides, the number of OLTC and SVC CVC without DG reactive power involvement.
operations per day, and the cumulative reactive power supplied by Observation no. 2: With the voltage deviation penalty function
DG units and SVCs are presented. The lowest network losses are objective; there is a higher requirement for the operation of the
attained, as expected, for a CVC formulation where loss minimi- SVCs and OLTCs, as shown in Table 1. In both Static and DTR rating
zation is the objective. Apparently there is no difference between methods, the voltage penalty function objective utilizes a higher
static and dynamic rating when loss minimization is the only objec- reactive power supply from the SVCs and OLTCs while injecting
tive as DTR does not directly reduce losses. Nevertheless, the DG reactive power into the DG units. This is because the objective
soft curtailment is too high when voltage loss minimization is the places less emphasis on losses, leading to a greater tendency to
objective. DTR shows a clear advantage over static rating in terms use reactive power absorption and supply to keep the voltage level
of maximizing the utilization of the DG units, while SVCs are effec- in the entire network close to unity. With the voltage penalty func-
tive for voltage control and reducing the stress on OLTCs. However, tion objective, the voltage level stays closer to the at one per
48 M.Z. Degefa et al. / Electric Power Systems Research 127 (2015) 4152
1.16
65% DG penetration without CVC
1.14 65% DG penetration with CVC+DTR+LOSS+PENALITY
1.12
1.08
1.06
1.04
1.02
0.98
0 10 20 30 40 50 60
(a) Distance from primary substation (km)
1.0005
1.13% DG penetration without CVC
1.13% DG penetration with CVC + DTR + Loss
1
Voltage level (pu)
0.9995
0.999
0.9985
0 10 20 30 40 50 60
(b) Distance from primary substation
Fig. 9. An average day-ahead voltage level prole of the secondary substations on the 30 feeders, with and without the implementation of CVC. (a) shows the prole with
65% of DG penetration and (b) shows the result with a 1.13% DG penetration level.
unit compared to the loss minimization objective function. How- also lower the DG active power generation curtailment better than
ever, the network losses increased tremendously with the voltage static ratings, as shown in Table 1.
penalty function objective, as shown in Table 1. With the penalty Observation no. 3: DTR shows no signicant difference from
function objective, DTR can use the reactive power resources and static rating when loss minimization is an objective. In principle,
the DTR utilizes the opportunities provided by the weather for the
cooling of distribution network components. It is evident that with
1.0015
No CVC
CVC+STATIC+Loss
CVC+STATIC+Penality
1.001 CVC+DTR+Loss 1.15
CVC+DTR+Penality No CVC
Bus voltage magnitude (pu)
1.1
1.05
0.9995
1
0.999 0 10 20 30 40 50 60
0 5 10 15 20 25 30 35
Distance from primary substation (km) Distance from primary substation (km)
Fig. 10. Voltage level at hour 4:00 on feeder 10, where a wind turbine is connected Fig. 11. Voltage level on the longest feeder of the network after implementation
at the furthest node. The DG penetration level is 1.13% and the CVC involves DG of CVC with and without the involvement of DG reactive power supply. (In all the
curtailment. three scenarios, 65% DG penetration.)
M.Z. Degefa et al. / Electric Power Systems Research 127 (2015) 4152 49
Table 1
Evaluation of the CVC formulation techniques for the period of 24 h ahead implementation.
No. Specication DG penetration DG Losses Max. No. of OLTC No. of SVC DG Qgen. DG Pgen SVC Qgen.
(objective and rating) (%) curtailment (kW h) Vdev* (%) operations operations (MVARh) curtailed (%) (MVARh)
1 Obj: losses & rating: 1.13 Yes 25.6 0.14 0 0 2.439 31.63 0.856
static 1.13 No 34.5 0.14 0 0 1.016 0 0.994
11.3 Yes 23.0 0.14 0 0 1.459 90.39 0.946
11.3 No 2,610.7 0.91 0 12 36.455 0 7.521
22.6 Yes 22.8 0.14 0 0 1.457 94.97 0.946
22.6 No 10,352.5 1.83 0 27 73.620 0 15.146
2 Obj: losses & rating: 1.13 Yes 25.6 0.14 0 0 2.438 31.64 0.858
DTR 1.13 No 34.5 0.14 0 0 1.017 0 0.991
11.3 Yes 23.0 0.14 0 0 1.459 90.39 0.947
11.3 No 2,609.6 0.89 0 10 36.161 0 6.584
22.6 Yes 22.831 0.14 0 0 1.454 94.97 0.954
22.6 No 10,352.5 1.83 0 25 73.620 0.00 15.147
3 Obj: penalty & rating: 1.13 Yes 47.9 0.24 11 1 1.506 2.27 9.866
static 1.13 No 55.8 0.28 9 2 2.185 0 11.915
11.3 Yes 2,981.9 3.56 10 20 48.952 0.69 50.989
11.3 No 3,261.6 3.56 16 31 50.713 0 56.733
22.6 Yes 10,798.6 1.86 16 31 87.857 0.12 63.214
22.6 No 11,502.7 3.88 17 32 92.136 0 78.740
4 Obj: penalty & rating: 1.13 Yes 49.8 0.21 5 0 1.647 2.10 10.292
DTR 1.13 No 57.0 0.29 13 0 2.296 0 12.351
11.3 Yes 2,926.5 1.94 13 19 49.411 1.39 53.125
11.3 No 3,041.3 2.54 12 27 48.449 0 48.768
22.6 Yes 10,866.95 1.92 7 22 89.359 0.14 68.587
22.6 No 11,546.9 3.99 16 36 94.552 0 87.551
5 Obj: losses + penalty & 1.13 Yes 36.0 0.16 6 2 0.929 4.23 1.867
rating: static 1.13 No 34.5 0.14 0 0 1.021 0 0.979
11.3 Yes 2,544.5 0.89 5 0 36.076 0.97 6.775
11.3 No 2,613.9 0.91 2 3 36.641 0 8.051
22.6 Yes 10,302.71 1.83 4 4 73.316 0.31 14.752
22.6 No 10,352.5 1.83 0 3 73.619 0 15.143
6 Obj: losses + penalty & 1.13 Yes 34.6 0.14 8 0 1.026 3.77 1.454
rating: DTR 1.13 No 34.5 0.14 0 0 1.018 0 0.990
11.3 Yes 2,542.9 0.89 4 0 36.113 0.82 6.752
11.3 No 2,610.1 0.90 2 1 36.352 0 7.213
22.6 Yes 10,338.9 1.83 4 3 73.553 0.14 15.142
22.6 No 10,352.5 1.83 0 3 73.619 0 15.144
*
Vdev = max(|1 Vij |), i = 1; 24, j = 1; 147.
DTR network losses could even increase as long as they remain Observation no. 4: The combined loss minimization and voltage
within the economically acceptable level. As shown in Fig. 12 and penalty objective function with both static and DTR rating reduced
Table 1, the voltage penalty minimization objective provides bet- signicantly the operations of OLTCs and SVCs, while utilizing both
ter voltage levels with DTR than with static rating, even though the the active and reactive power resources of the installed DG units to
total losses are the same. the utmost. This has been observed in all the four cases presented
in Table 1.
The simulation results for the network loss minimization
objective and the voltage penalty function objective in the CVC
1.035
DTR voltage penalty minimization formulations are presented in Table 1. When network losses are
STATIC voltage penalty minimization insignicant, such as in the test network in Fig. 7, the voltage
1.03
penalty function objective performs better, by bringing the volt-
1.025 age to a at stable level close to one per unit. In addition, the
incorporation of static rating or DTR with a loss minimization objec-
Voltage leve (pu)
1.02
tive brought down the network losses by about 29%, compared
1.015 to the static or DTR rating with only the voltage penalty func-
tion objective. Furthermore, when the voltage penalty function and
1.01
loss minimization objectives are used together the observed overall
1.005 performance is superior.
1
6. Discussion on practical implementations
0.995
0 20 40 60 80 100 120 140 150
The 147 buses in order of their number Planning CVC for day-ahead distribution network operation
requires reliable load and environmental variable forecasting.
Fig. 12. The voltage level at hour 16:00, after the static and DTR based CVC control
settings are applied with the voltage penalty minimization objective and with 20% Nevertheless, the control setting planned a-day-before faces two
DG penetration. fundamental challenges. The rst is the question of where to
50 M.Z. Degefa et al. / Electric Power Systems Research 127 (2015) 4152
7. Conclusion
Table A.2
The 147 bus active distribution test network specications (40 MVA base 20 kV MV system).