Technical Data C264/EN TD/C80

MiCOM C264/C264C Page 21/46

4. RATINGS
4.1 Auxiliary Voltage
The C264 computer is available in four auxiliary voltage versions, as follows:

Version Nominal ranges Operative DC range Operative AC range


A01 24VDC 19.2 thru 28.8VDC -
A02 48 thru 60VDC 38.4 thru 72VDC -
A03 110 thru 125VDC 88 thru 150VDC -
A04 220VDC and 230VDC 176 thru 264VDC 176 thru 264VAC
The nominal frequency (Fn) for the AC auxiliary voltage is dual rated at 50/60Hz, the operate
range is 45Hz to 65Hz.
The BIU241 board includes these attributes:
x Inrush current 6.2 A at 125 VDC during the first 50 ms at startup
x Power supply: 40 W
x Nominal output voltage: + 5V
x Supply monitoring
x Permitted power outage: 50 ms
x Protection against polarity reversal
x Insulation resistance: >100 M: ( CM) at 500 VDC
x Dielectric strength: 2 kV (CM) 50 Hz for 1 minute

4.2 Power Supply


4.2.1 BIU241 Digital Outputs
On the BIU241 board, the attributes of the Watchdog Relay Contacts are the same as the
attributes for the NO+NC contacts installed on the DOU201 boards.
On the BIU241 board, the attributes of the two output relays used for C264 redundancy are
the same as for the single-pole output-relay installed on the DOU201 boards.
4.2.2 BIU261 Dual Sources power supply board
The BIU261 allows a dual source power supply from the same voltage range.
Voltage source switching sequence
The BIU261 has a voltage source switching mechanism.
Switch from main source to secondary Source: If the main power supply source disappears
(1), the secondary power supply source is supplied to C264.
Switch from secondary source to main Source: When the main power supply source
becomes available and stable the switch from secondary to main power supply source is
effective and C264 running without fugitive power supply fault.
Switching transition is logged.
(1) The board is equipped with a circuit to start / stop switching sequence. This circuit is
enabled to use the power supply if Voltage is above threshold. The absence of power supply
source voltage is considered when Usource < 80% Unominal. This thresthold is a factory
value.