6000
Digital
Thermostat
Series
Installation
Instructions
Wallplate installation
Remove the wallplate from the thermostat,
then follow directions below for mounting.
1. Remove battery holder.
2. Pull here to remove wallplate from new
thermostat.
3. Pull wires through wire hole.
4. Position wallplate on wall, level and mark
hole positions with pencil.
5. Drill holes at marked positions as shown
M29433
MCR29434
Drill 3/16"
holes for
drywall.
Drill 7/32"
holes for
plaster.
M29369
Power options
TH6110D TH6110D
G W C Y R Rc G C Y R Rc
TH6220D TH6220D
Y2 W2 G W C Y R Rc L Aux G C Y R Rc
E
TH6320U TH6320U
Y2 W2 G W C Y R Rc L Y2 Aux G C Y R Rc
E MCR29438A
MCR29437A
2
Wiring conventional systems
Shaded areas below apply only to TH6320U/TH6220D or as otherwise noted.
1H/1C System Heat-only System
(1 transformer) G W C Y R Rc with Fan G W C R Rc
M29372 M29377
Rc Power [1] Rc Power [1]
R [R+Rc joined by jumper] R [R+Rc joined by jumper]
Y Compressor contactor C 24VAC common [3]
C 24VAC common [3] W Heat relay
W Heat relay G Fan relay
G Fan relay Cool-only System
Heat-only System Rc Power [1] G C Y R Rc
M29378
Rc Power [1] W C R Rc R [R+Rc joined by jumper]
M29373
R [R+Rc joined by jumper] Y Compressor contactor
C 24VAC common [3] C 24VAC common [3]
W Heat relay G Fan relay
Heat-only System 2H/2C System
(Series 20) [5] W C Y R Rc (1 transformer) [6] Y2 W2 G W C Y R Rc
M29379
M29374
Rc [R+Rc joined by jumper] Rc Power [1]
R Series 20 valve terminal R [1] R [R+Rc joined by jumper]
Y Series 20 valve terminal W Y Compressor contactor (stage 1)
C 24VAC common [3] C 24VAC common [3]
W Series 20 valve terminal B W Heat relay (stage 1)
Heat-only System G Fan relay
(normally open zone C Y R Rc
W2 Heat relay (stage 2)
valve) [5]
M29375 Y2 Compressor contactor (stage 2)
Rc [R+Rc joined by jumper] 2H/2C System
R Power [1] (2 transformers) [6] Y2 W2 G W C Y R Rc
M29380
Y Normally open zone valve Rc Power (cooling transformer) [1, 2]
C 24VAC common [3] R Power (heating transformer) [1, 2]
1H/1C System Y Compressor contactor (stage 1)
(2 transformers) G W C Y R Rc C 24VAC common [3, 4]
M29376
W Heat relay (stage 1)
Rc Power (cooling transformer) [1, 2]
G Fan relay
R Power (heating transformer) [1, 2]
W2 Heat relay (stage 2)
Y Compressor contactor
Y2 Compressor contactor (stage 2)
C 24VAC common [3, 4]
W Heat relay
G Fan relay
3
Wiring heat pump systems
Shaded areas below apply only to TH6320U/TH6220D or as otherwise noted.
Thermostat mounting
1. Push excess wire back into the
wall opening.
2. Plug wall opening with non-
flammable insulation.
3. Align the 4 tabs on the wallplate
with corresponding slots on the
back of the thermostat.
4. Push gently until the thermostat
snaps in place.
MCR29453
4
Installer setup
Follow the procedure below to configure
the thermostat to match the installed
heating/cooling system, and customize
feature operation as desired.
1
1. To begin, press and hold the s Done
MCR29454
Function Setting
number
Setup function Settings & options (factory default in bold)
Shaded areas below apply only to TH6320U/TH6220D or as otherwise noted.
5 Stage 1 heat cycle 5 For gas or oil furnaces of less than 90% efficiency
rate 1 For steam or gravity systems
(CPH: cycles/hour)* 3 For hot water systems & furnaces of over 90% efficiency
9 For electric furnaces
6 Stage 2 heat cycle 5 For gas or oil furnaces of less than 90% efficiency
rate/Auxiliary heat 1 For steam or gravity systems
cycle rate (CPH)* 3 For hot water systems & furnaces of over 90% efficiency
9 For electric furnaces
7 Auxiliary heat 5 For gas or oil furnaces of less than 90% efficiency
cycle rate (CPH)* 1 For steam or gravity systems
Only TH6320U 3 For hot water systems & furnaces of over 90% efficiency
for 3H/2C Heat 9 For electric furnaces
Pumps
5
Setup function Settings & options (factory default in bold)
Shaded areas below apply only to TH6320U/TH6220D or as otherwise noted.
9 Stage 1 compressor 3 Recommended for most compressors
cycle rate (CPH) [Other cycle rate options: 1, 2, 4, 5 or 6 CPH]
10 Stage 2 compressor 3 Recommended for most compressors
cycle rate (CPH) [Other cycle rate options: 1, 2, 4, 5 or 6 CPH]
Special function
Auto Changeover (Setup Function 12): When set to Auto, the thermostat
automatically selects heating or cooling depending on the indoor temperature.
The thermostat will automatically adjust heat and cool settings to maintain
a 3-degree separation (fixed). Note: If you select Auto Changeover Only,
the System Setting on the thermostat will stay locked in the Auto position,
preventing the user from changing it to Em Heat, Heat, Cool or Off.
6
Installer system test
1. To begin, press and hold the
s and t buttons until the
display changes.
2. Press s / t to turn system
1
on/off.
3. Press NEXT to advance to next
test
4. Press DONE to terminate
system test.
10 0
System test System
MCR29455
number status
System test System status
Shaded areas below apply only to TH6320U/TH6220D or as otherwise noted.
10 Heating system 0 Heat and fan turn off.
1 Stage 1 heat turns on. Fan turns on if Setup Function 1 is
set to 1, 5, 9 or 10 OR Setup Function 3 is set to 1
2 Stage 2 heat turns on
3 Stage 3 heat turns on - TH6320U only
Specifications
Temperature Ranges Electrical Ratings
Heat: 40 to 90F (4.5 to 32C) Terminal Voltage (50/60Hz) Running Current
Cool: 50 to 99F (10 to 37C) W Heating 20-30 Vac 0.02-1.0 A
Operating Ambient Temperature (Powerpile) 750 mV DC 100 mA DC
32 to 120F (0 to 48.9C) W2 (Aux/E) Heating 20-30 Vac 0.02-1.0 A
Shipping Temperature Y Cooling 20-30 Vac 0.02-1.0 A
-20 to 120F (-28.9 to 48.9C) Y2 Cooling 20-30 Vac 0.02-1.0 A
Operating Relative Humidity G Fan 20-30 Vac 0.02-0.5 A
5% to 90% (non-condensing) O/B Changeover 20-30 Vac 0.02-0.5 A
Physical Dimensions L Output 20-30 Vac 0.02-0.5 A
3-9/16 H x 5-13/16 W x 1-1/2 D
91 mm H x 147 mm W x 38 mm D
7
Customer assistance
Pull at bottom
For assistance with this product, please to remove
visit customer.honeywell.com. thermostat
from
Or call Honeywell Customer Care toll- wallplate.
free at 1-800-468-1502.
Turn thermostat
over to find model
number and date
code.
CAUTION:
EQUIPMENT DAMAGE HAZARD
Compressor protection is bypassed during testing. To prevent equipment damage, avoid
cycling the compressor quickly.
CAUTION:
ELECTRICAL HAZARD
Can cause electrical shock or equipment damage. Disconnect power before beginning
installation.
CAUTION:
MERCURY NOTICE
If this product is replacing a control that contains mercury in a sealed tube, do not
place the old control in the trash. Contact your local waste management authority for
instructions regarding recycling and proper disposal.
Honeywell Ltd
705 Montrichard Avenue
Saint-Jean-sur-Richelieu, Qubec
J2X 5K8
customer.honeywell.com
6000
numrique
programmable
Srie
Notice
Dinstallation
MCR29434
Utiliser une
mche de
3/16 po si le
mur est en
placopltre
M29369
Options dalimentation
Garder les fils dans Enlever le cavalier
cettezone install en usine
ombrage uniquement pour
les systmes
deux
transformateurs.
TH6110D TH6110D
G W C Y R Rc G C Y R Rc
TH6220D TH6220D
Y2 W2 G W C Y R Rc L Aux G C Y R Rc
E
TH6320U TH6320U
Y2 W2 G W C Y R Rc L Y2 Aux G C Y R Rc
E MCR29438A
MCR29437A
2
Guide de cblage systmes traditionnels
Les zones ombrages ci-dessous sappliquent seulement au TH6320U/
TH6220D ou selon les indications.
Systme 1C/1F Systme de
(1 transformateur) G W C Y R Rc
M29372
chauffage seulement G W C R Rc
M29377
Rc Alimentation [1] avec soufflante
R [R+Rc reli par le cavalier] Rc Alimentation [1]
Y Contacteur de compresseur R [R+Rc relis par le cavalier]
C Neutre 24 V CA [3] C Neutre 24 V CA [3]
W Relais de chauffage W Relais de chauffage
G Relais de la soufflante G Relais de la soufflante
Systme de chauffage Systme de
seulement W C R Rc climatisation G C Y R Rc
M29373 M29378
Rc Alimentation [1] seulement
R [R+Rc reli par le cavalier] Rc Alimentation [1]
C Neutre 24 V CA [3] R [R+Rc relis par le cavalier]
W Relais de chauffage Y Contacteur de compresseur
Systme de chauffage C Neutre 24 V CA [3]
seulement (Srie 20) [5] G Relais de la soufflante
W C Y R Rc
Rc [R+Rc relis par le cavalier] M29374 Systme 2C/2F
R Borne de soupape R de Srie 20 [1] (1 transformateur) [6] Y2 W2 G W C Y R Rc
Y Borne de soupape W de Srie 20 Rc Alimentation [1]
M29379
3
Guide de cblage systmes de thermopompes
Les zones ombrages ci-dessous sappliquent seulement au TH6320U/
TH6220D ou selon les indications.
Systme de Systme de
thermopompe 1C/1F G C Y R Rc thermopompe 2C/2F L Y2 G C Y R Rc
M29381
Rc Alimentation [1] (TH6320U seulement)
R [R+Rc relis par le cavalier] [9]
Y Contacteur de compresseur Rc Alimentation [1]
C Neutre 24 V CA [3] R [R+Rc relis par le cavalier]
O/B Robinet de substitution [7] Y Contacteur du compresseur (stade 1)
G Relais de la soufflante C Neutre 24 V CA [3]
Systme de O/B Robinet de substitution [7]
thermopompe 2C/1F G Relais de la soufflante
L Aux G C Y R Rc
Y2 Contacteur du compresseur (stade 2)
(TH6220D seulement) [8] E
L Envoie le signal de sortie lorsque rgl
Rc Alimentation [1] Em. Chauffage [11]
R [R+Rc relis par le cavalier]
Y Contacteur de compresseur Systme de
C Neutre 24 V CA [3] thermopompe 3C/2F L Y2 AuxG C Y R Rc
O/B Robinet de substitution [7] (TH6320U seulement) E
G Relais de la soufflante [8]
Aux/E Relais auxiliaire de chauffage/ Rc Alimentation [1]
de chauffage durgence
R [R+Rc relis par le cavalier]
L Envoie le signal de sortie lorsque rgl
Y Contacteur du compresseur (stade 1)
Em. Chauffage [11]
C Neutre 24 V CA [3]
2H/1C Heat Pump O/B Robinet de substitution [7]
System (TH6320U L Aux G C Y R Rc
G Relais de la soufflante
seulement) [8] E Aux/E Relais auxiliaire de chauffage/
de chauffage durgence
Rc Power [1] Y2 Contacteur du compresseur (stade 2)
R [R+Rc joined by jumper] L Envoie le signal de sortie lorsque rgl
Y Compressor contactor Em. Chauffage [11]
C 24VAC common [3]
O/B Changeover valve [7]
G Fan relay Voir Remarques la page 3.
Aux/E Auxiliary/Emergency heat relay
L Sends output when set to Em. Heat [11]
Montage du thermostat
1. Repousser le fil en excs dans
louverture dans le mur.
2. Boucher louverture dans le
mur au moyen dun isolant
ininflammable.
3. Faire correspondre les 4
languettes de la plaque murale
avec les fentes correspondantes
au dos du thermostat.
4. pousser doucement jusqu ce
que le thermostat fasse entendre
un dclic.
4
MCR29453
Mode de configuration par linstallateur
Suivre les directives ci-dessous pour
configurer le thermostat pour quil
corresponde au systme de chauffage-
refroidissement install, et pour
personnaliser son fonctionnement. 1
1. Pour commencer, appuyer sur les Done
touches s et FAN les maintenir
enfoncs jusqu ce que laffichage
change.
1
2. Appuyer sur la touche s ou t pour
modifier les rglages.
3. Appuyer sur NEXT pour passer la 0
fonction suivante.
4. Appuyer sur DONE pour quitter et Done Next
enregistrer rglages.
MCR29454
Numro de Rglage
fonction
Fonctions Rglage et options (rglages de lusine en gras)
Les zones ombrages ci-dessous sappliquent seulement au TH6320U/
TH6220D ou selon les indications.
1 Type de systme 0 Traditionnel 1 chauffage/1 climatisation (1 heat/1 cool conventional)
1 Thermopompe 1 chauffage/1 climatisation (aucun chauffage auxiliaire) (1 heat/1
cool heat pump)
2 Chauffage seulement (Heat only) systmes 2 fils, soupapes de zone 3 fils
(Srie 20) et soupapes de zone normalement ouvertes
3 Chauffage seulement avec soufflante (Heat only with fan)
4 Climatisation seulement (Cool only)
5 Thermopompe 2 chauffage/1 climatisation (avec chauffage auxiliaire) (1 heat/1
cool heat pump with aux. heat)
6 Traditionnel 2 chauffage/2 climatisation (2 heat/2 cool conventional)
7 Traditionnel 2 chauffage/1 climatisation (2 heat/1 cool conventional)
8 Traditionnel 1 chauffage/2 climatisations (1 heat/2 cool conventional)
9 Thermopompe 2 chauffage/2 climatisation (aucun chauffage auxiliaire) (2 heat/2
cool heat pump) - TH6320U seulement
10 Thermopompe 3 chauffage/2 climatisation (avec chauffage auxiliaire) (3 heat/2
cool heat pump with aux. heat) - TH6320U seulement
5
Fonctions Rglage et options (rglages de lusine en gras)
Les zones ombrages ci-dessous sappliquent seulement au TH6320U/
TH6220D ou selon les indications.
7 Rythme de cycle de 5 Pour systmes au gaz naturel ou au mazout dune efficacit infrieure 90 %
chauffage auxiliaire 1 Pour systmes la vapeur ou gravitaires
(CPH)* 3 Pour systmes leau chaude et systmes de chauffage dune efficacit suprieure
Seulement le 90 %
TH6320U pour les 9 Pour fournaises lectriques
thermopompes
3C/2F
14 Affichage de la 0 Fahrenheit
temprature 1 Celsius
15 Protection du 5 Dsactivation du compresseur de cinq minutes
compresseur [Autres options : dsactivation de 0, 1, 2, 3 ou 4 minutes]
26 Commande de 0 Confort
chauffage auxiliaire 1 conomie
Fonction spciale
Substitution automatique (Fonction de configuration 12) : Lorsque rgl Auto, le thermostat
slectionne automatiquement le chauffage ou la climatisation selon la temprature intrieure. Le
thermostat ajuste automatiquement les rglages pour maintenir un cart de 3 degrs (fixe). Remarque:
Si vous slectionnez Substitution automatique seulement, le rglage du systme dans le thermostat
demeurera verrouill la position Auto, empchant lutilisateur de le changer Em Heat, Heat, Cool ou
Off.
Adaptive Intelligent Recovery (Fonction de configuration 13) : Permet au thermostat dapprendre
combien de temps la fournaise ou le climatiseur prend pour atteindre la temprature programme afin que
la temprature atteigne la temprature voulue au moment voulu.
Protection du compresseur (Fonction de configuration 15) : Force le compresseur attendre quelques
minutes avant de redmarrer pour prvenir les dommages. Durant la priode dattente, le message Cool
On ou Heat On (thermopompes seulement) clignotera sur laffichage.
6
Test du systme par linstallateur
1. Pour commencer, enfoncer
et tenir les touches s et t
jusqu ce que laffichage
change.
2. Appuyer sur s / t pour
10
activer ou dsactiver le
systme.
3. Appuyer sur NEXT pour passer
lessai suivant.
4. Appuyer sur DONE pour
terminer lessai du systme.
10 0
MCR29455
Numro de test tat du
du systme systme
Caractristiques techniques
Gammes de temprature Caractristiques lectriques nominales
Chauffage : 4,5 32 C (40 90 F) Terminal service Tension (50/60Hz) Intensit de
Refroidissement : 10 37 C (50 99 F) W Chauffage 20-30 V CA 0,02-1,0 A
Gamme de temprature ambiante de service (Pile) 750 mVCC 100 mA CC
0 48,9 C (32 120 F) W2 (Aux/E) Chauffage 20-30 Vac 0,02-1.0 A
Temprature lexpdition Y Refroidissement 20-30 V CA 0,02-1,0 A
-28,9 48,9 C (-20 120 F) Y2 Refroidissement 20-30 V CA 0,02-1,0 A
Humidit relative de service G Soufflante 20-30 V CA 0,02-0,5 A
5 % 90 % (sans condensation) O/B Substitution 20-30 V CA 0,02-0,5 A
Encombrement L Sortie 20-30 V CA 0,02-0,5 A
3-9/16 po H x 5-13/16 po L x 1-1/2 po P
91 mm H x 147 mm L x 38 mm P
7
Services la clientle
Tirer le
Pour obtenir de laide avec ce produit, thermostat par
veuillez consulter le site customer. le bas pour le
honeywell.com. dtacher de la
plaque murale.
ou vous adresser aux Services la
clientle de Honeywell en composant le Retourner le
1-800-468-1502. thermostat pour
trouver le numro
de modle et le
code de date.
Honeywell Ltd
705 Montrichard Avenue
Saint-Jean-sur-Richelieu, Qubec
J2X 5K8
customer.honeywell.com
6000
digital
programable
Series
Instrucciones para
la instalacin
MCR29434
En
tablarroca,
realice
agujeros En yeso,
de 3/16". realice
agujeros
de 7/32".
M29369
Opciones de fuentes de energa
Designacin de terminales
Las reas sombreadas que aparecen abajo slo se utilizan para los modelos
TH6320U y TH6220D o segn se indique.
TH6110D TH6110D
G W C Y R Rc G C Y R Rc
TH6220D TH6220D
Y2 W2 G W C Y R Rc L Aux G C Y R Rc
E
TH6320U TH6320U
Y2 W2 G W C Y R Rc L Y2 Aux G C Y R Rc
E MCR29438A
MCR29437A
2
Cableado: sistemas convencionales
Las reas sombreadas que aparecen abajo slo se utilizan en el caso de los
modelos TH6320U y TH6220D o segn se indique.
Sistema de 1 Sistema de
calentador y 1 G W C Y R Rc calefaccin G W C R Rc
M29372 M29377
refrigerador nicamente con
(1 transformador) ventilador
Rc Electricidad [1] Rc Electricidad [1]
R [R+Rc unidos por un puente] R [R+Rc unidos por un puente]
Y Interruptor automtico del compresor C 24 V CA [3]
C 24 V CA [3] W Rel de calor
W Rel de calor G Rel del ventilador
G Rel del ventilador Sistema nicamente
Sistema de calefaccin de refrigeracin G C Y R Rc
nicamente W C R Rc Rc Electricidad [1]
M29378
M29373
Rc Electricidad [1] R [R+Rc unidos por un puente]
R [R+Rc unidos por un puente] Y Interruptor automtico del compresor
C 24 V CA [3] C 24 V CA [3]
W Rel de calor G Rel del ventilador
Sistema de calefaccin Sistema de 2
nicamente W C Y R Rc calentadores y dos Y2 W2 G W C Y R Rc
M29374
(Serie 20) [5] refrigeradores (1 transformador) [6] M29379
4
Configuracin de instalacin
Siga el procedimiento que aparece
a continuacin para configurar el
termostato a fin de que se corresponda
con el sistema de calefaccin y
refrigeracin instalado, y seleccione las
funciones segn lo desee.
1
Done
1. Para comenzar, pulse y mantenga
presionados los botones s y FAN
hasta que cambie la pantalla.
2. Presione s o t para cambiar la
configuracin.
3. Presione NEXT para avanzar a la
siguiente funcin.
1 0
4. Presione DONE para salir y guardar Done Next
la configuracin.
MCR29454
Nmero Configuracin
de funcin
Funciones de Configuraciones y opciones (las que vienen
la configuracin desde la fbrica aparecen en negrita)
Las reas sombreadas que aparecen abajo slo se utilizan en el caso de los
modelos TH6320U y TH6220D o segn se indique.
1 Tipo de sistema 0 1 calentador y 1 refrigerador convencional
1 1 bomba de calor con calentador y 1 refrigerador (sin calor aux.)
2 Slo calorsistemas de dos cables, vlvulas de separacin de tres cables
(serie 20) y vlvulas de separacin normalmente abiertas
3 Slo calor con ventilador
4 Slo fro
5 Bomba de calor con 2 calentadores y 1 refrigerador (con calor aux.)
6 2 calentadores y 2 refrigeradores convencionales
7 2 calentadores y 1 refrigerador convencional
8 1 calentador y 2 refrigeradores convencionales
9 Bomba de calor con 2 calentadores y 2 refrigeradores (sin calor aux.)
nicamente en TH6320U
10 Bomba de calor con 3 calentadores y 2 refrigeradores (con calor aux.)
nicamente TH6320U
2 Vlvula inversora 0 Vlvula inversora (terminal O/B con energa durante la refrigeracin)
(terminal O/B) 1 Vlvula de inversora (terminal O/B con energa durante la calefaccin)
3 Control del ventilador 0 Sistemas de calefaccin a gas o a aceite (el equipo controla al ventilador
(calefaccin) para calefaccin)
1 Sistema de calefaccin elctrico (el termostato controla el ventilador para
calefaccin)
5 Velocidad del ciclo 5 Para sistemas de calefaccin a gas o a aceite de menos de un 90% de
trmico de la primera efectividad
etapa 1 Para sistemas de vapor o de gravedad
(CPH: ciclos por hora)* 3 Para sistemas de agua caliente y sistemas de ms de un 90% de efectividad
9 Para sistemas elctricos
5
Funciones de Configuraciones y opciones (las que vienen
la configuracin desde la fbrica aparecen en negrita)
Las reas sombreadas que aparecen abajo slo se utilizan en el caso de los
modelos TH6320U y TH6220D o segn se indique.
7
Velocidad de ciclo de 5 Para sistemas de calefaccin a gas o a aceite de menos de un 90% de
calor auxiliar (CPH)* efectividad
nicamente TH6320U 1 Para sistemas de vapor o de gravedad
para sistemas de 3 Para sistemas de agua caliente y sistemas de ms de un 90% de efectividad
bombas de calor de 9 Para sistemas elctricos
3 calentadores y 2
refrigeradores
16 Formato del 0 5/2 (programable los das de semana y los fines de semana)
programa 1 5/1/1 (programable los das de semana, sbados y domingos)
Funciones especiales
Conveasor automtico (configuracin 12): Cuando el sistema est configurado en Auto,
el termostato elige automticamente cundo calentar o enfriar, dependiendo de la temperatura interior.
El termostato ajustar automticamente las configuraciones de calor y fro a fin de
mantener una separacin de 3 grados (fija). Nota: Si selecciona Auto Changeover Only (slo
conversin automtica), la configuracin del termostato permanecer bloqueada en la posicin
Auto, de modo que el usuario no pueda cambiarla a Em.Heat, Heat, Cool u Off.
Adaptive Intelligent Recovery (Setup Function 13): Allows the thermostat to learn how long
the furnace and air conditioner take to (configuracin 13): Permite al termostato saber cunto
tiempo requiere el sistema de aire acondicionado para alcanzar las configuraciones de temperatura
programadas a fin de alcanzar la temperatura deseada a la hora programada.
Proteccin del compresor (configuracin 15): Hace que el compresor espere unos minutos
antes de reiniciarse, para prevenir daos. Durante el tiempo de espera, el mensaje Cool On
o Heat On (slo para las bombas de calor) aparecer parpadeando en la pantalla del visor.
6
Prueba del sistema
1. Para comenzar, pulse y mantenga
presionados los botones s y t
hasta que cambie la pantalla
10
2. Presione s / t para encender o
apagar el sistema.
3. Presione NEXT para avanzar
hacia la prxima prueba.
4. Presione DONE para finalizar la
prueba del sistema.
10 0
MCR29455
Nmero de prueba Estado del
del sistema sistema
Especificaciones
Rangos de temperatura Rangos elctricos
Calor: De 40 F a 90 F (de 4,5 C a 32 C) Terminal Voltaje (50/60 Hz) Corriente
Fro: De 50 F a 99 F (de 10 C a 37 C) W Calefaccin 20 a 30 V CA 0,02 a 1,0 A
Temperatura ambiente de funcionamiento (Powerpile) 750 mV CC 100 mA CC
De 32 F a 120 F (de 0 C a 48,9 C) W2 (Aux/E) Calefaccin 20 a 30 V CA 0,02 a 1,0 A
Temperatura de embalaje Y Refrigeracin 20 a 30 V CA 0,02 a 1,0 A
De -20 F a 120 F (de -28,9 C a 48,9 C) Y2 Refrigeracin 20 a 30 V CA 0,02 a 1,0 A
Humedad relativa de funcionamiento G Ventilador 20 a 30 V CA 0,02 a 0,5 A
5% a 90% (no condensable) O/B Conversin 20 a 30 V CA 0,02 a 0,5 A
Dimensiones fsicas L Salida 20 a 30 V CA 0,02 a 0,5 A
3-9/16 de altura x 5-13/16 de ancho x
1-1/2 de profundidad
91 mm de altura x 147 mm de ancho x
38 mm de profundidad
7
Asistencia al cliente
Hale de la
Para obtener asistencia relacionada parte inferior
con este producto, visite para quitar el
customer.honeywell.com. termostato de la
placa para pared.
O comunquese con el nmero gratuito
del servicio de atencin al cliente,
llamando al 1-800-468-1502. Gire el termostato
para ver el nmero
de modelo y el
cdigo de fecha.
Honeywell Ltd
705 Montrichard Avenue
Saint-Jean-sur-Richelieu, Qubec
J2X 5K8
customer.honeywell.com