Job Number Sheet Job Number Sheet

KTP/10/13 KTP/10/13
Job Title Job Title
NEW FUTURA NEW FUTURA
Software Consultants (Pty) Ltd Client Software Consultants (Pty) Ltd Client
Internet: http://www.prokon.com M/s KTP SPORE PTE LTD Internet: http://www.prokon.com M/s KTP SPORE PTE LTD
Calcs by Checked by Date Calcs by Checked by Date
E-Mail : mail@prokon.com HT T&T MARCH 2015 E-Mail : mail@prokon.com HT T&T MARCH 2015
NC2-1300X500-(20TH-25TH STY) C13
+ 455.000 1103.750
General column design by PROKON. (GenCol Ver W2.4.01 - 01 Apr 2008) b 20.000
+ 181.667 45.000
Design code : CP65 - 1999 b 20.000
+ 181.667 1255.000
Input tables b 20.000
+ 318.333 45.000
General design parameters:
b 20.000
X/Radius or Y (mm) + 318.333 1255.000
Code Bar dia. (mm) Angle () b 20.000
+ 10.000
480.000 Design loads:
10.000 10.000 Load Ultimate limit state design loads
case Designation
1280.000 P (kN) Mx top (kNm) My top (kNm) Mx bot (kNm) My bot (kNm)
-10.000 10.000 1 Axial 7788
-480.000 2 Axial + Mxx 7788 400
-10.000 -10.000 3 Axial + Myy 7788 400
-1280.000 4 Axial + Mecc 7788 400 200
CP65 - 1999
+ 45.000 45.000 5 Axial + 34kpa 7788 450 450 Y
b 20 1500
+ 455.000 45.000
b 20
General design parameters:
Given: 1000
+ 455.000 1255.000
Lo = 4.000 m
b 20 fcu = 30 MPa X X
+ 45.000 1255.000 fy = 460 MPa 500
b 20 Ac = 646658 mm
+ 45.000 196.250
b 20.000
Assumptions: 0
(1) The general conditions of clause 3.8.1 are applicable.
+ 455.000 196.250
(2) The specified design axial loads include

500
b 20.000 the self-weight of the column. Y

0
+ 45.000 347.500 (3) The design axial loads are taken constant
b 20.000 over the height of the column.
+ 455.000 347.500
b 20.000
+ 45.000 498.750
Design approach:
The column is designed using an iterative procedure:
b 20.000
(1) An area of reinforcement is chosen.
+ 455.000 498.750 (2) The column design charts are constructed.
b 20.000 (3) The corresponding slenderness moments are calculated.
+ 45.000 650.000 (4) The design axis and design ultimate moment are determined .
b 20.000 (5) The design axial force and moment capacity is checked on
+ 455.000 650.000
the relevant design chart.
(6) The safety factor is calculated for this load case.
b 20.000
(7) The procedure is repeated for each load case.
+ 45.000 801.250 (8) The critical load case is identified as the case yielding the lowest
b 20.000 safety factor about the design axis
+ 455.000 801.250
b 20.000 Through inspection:
+ 45.000 952.500
Load case 3 (Axial + Myy) is critical.
b 20.000
+ 455.000 952.500
b 20.000
+ 45.000 1103.750
b 20.000
Job Number Sheet Job Number Sheet
KTP/10/13 KTP/10/13
Job Title Job Title
NEW FUTURA NEW FUTURA
Software Consultants (Pty) Ltd Client Software Consultants (Pty) Ltd Client
Internet: http://www.prokon.com M/s KTP SPORE PTE LTD Internet: http://www.prokon.com M/s KTP SPORE PTE LTD
Calcs by Checked by Date Calcs by Checked by Date
E-Mail : mail@prokon.com HT T&T MARCH 2015 E-Mail : mail@prokon.com HT T&T MARCH 2015
Check column slenderness: Design ultimate load and moment:
End fixity and bracing for bending about the Design axis: Design axial load:
At the top end: Condition 2 (partially fixed). Pu = 7788.0 kN
At the bottom end: Condition 2 (partially fixed).
The column is unbraced. For bending about the X-X axis, the maximum design moment is the greatest of: 3.8.3.7
= 1.30 Table 3.21 (a) M2 + Maddx = 0.0 kNm
(b) emin N = 155.8 kNm
Effective column height: Mx = 0.0 kNm
le = Lo = 5.200 m

Check if the column is slender: 3.8.1.3


le/h = 10.4 > 10 Moments about X-X axis( kNm)
Mx=0.0 kNm
The column is slender. Mxtop=0.0 kNm Mxadd=0.0 kNm Mxmin=155.8 kNm

Initial moments:
The initial end moments about the X-X axis:
M1 = Smaller initial end moment = 0.0 kNm + =
M2 = Larger initial end moment = 0.0 kNm

The initial moment near mid-height of the column : 3.8.3.2


Mi = 0.4M1 + 0.6M2 0.4M2 = 0.0 kNm Mxbot=-0.0 kNm Mxadd=0.0 kNm

The initial end moments about the Y-Y axis: Initial Additional Design
M1 = Smaller initial end moment = 0.0 kNm
M2 = Larger initial end moment = 400.0 kNm For bending about the Y-Y axis, the maximum design moment is the greatest of: 3.8.3.7
(a) M2 + Maddy = 516.2 kNm
The initial moment near mid-height of the column : 3.8.3.2 (b) emin N = 155.8 kNm
Mi = 0.4M1 + 0.6M2 0.4M2 = 240.0 kNm My = 516.2 kNm

Deflection induced moments: 3.8.3.1


Design ultimate capacity of section under axial load only: Moments about Y-Y axis( kNm)
Nuz = 0.45 fcu Ac + 0.87 fy Asc = 11495.9 kN My=516.2 kNm
Mytop=400.0 kNm Mymin=155.8 kNm
Maximum allowable stress and strain:
Allowable compression stress in steel, fsc = 0.87 fy = 400.2 MPa
Allowable tensile stress in steel, fst = 0.87 fy = 400.2 MPa
Allowable tensile strain in steel, ey = fst/Es = 0.0019 m/m
Allowable compressive strain in concrete, ec = 0.0035 m/m
+ =

For bending about the weakest axis:


Weakest axis lies at an angle of -90.00 to the X-X axis
Overall dimension perpendicular to weakest axis h-dc = 455mm Mybot=-0.0 kNm
Balanced neutral axis depth, xb = ec/(ec+es) (h-dc) =294.6 mm
Initial Additional Design
Nbal = 0.44 b fcu xbal + (Ast fs + Asc fsd) = 4736.1 kN
K = (Nuz - N) / (Nuz - Nbal) = 0.549 < 1.0
a = (1/2000) (le/h) = 0.054 Check for miminum eccentricity: 3.8.2.4
Madd = N a K h = 116.2 kNm Check that the eccentricity exceeds the minimum in the plane of bending:
Maddx = Madd*cos(-90.00) = 0.0 kNm Use emin = 20mm
Maddy = Madd*sin(-90.00) = 116.2 kNm Mmin = 155.8 kNm about the X-X axis.
Job Number Sheet Job Number Sheet
KTP/10/13 KTP/10/13
Job Title Job Title
NEW FUTURA NEW FUTURA
Software Consultants (Pty) Ltd Client Software Consultants (Pty) Ltd Client
Internet: http://www.prokon.com M/s KTP SPORE PTE LTD Internet: http://www.prokon.com M/s KTP SPORE PTE LTD
Calcs by Checked by Date Calcs by Checked by Date
E-Mail : mail@prokon.com HT T&T MARCH 2015 E-Mail : mail@prokon.com HT T&T MARCH 2015
Design of column section for ULS: Stresses at the top end of the column for the critical load case 3
The column is checked for applied moment about the design axis.
Through inspection: the critical section lies at the top end of the column.
The design axis for the critical load case 3 lies at an angle of 90.00 to the X-axis CP65 - 1999
The safety factor for the critical load case 3 is 1.10 D
Y
For bending about the design axis: 1500

Interaction Diagram
11E3

Moment max = 1019 kNm @ 4140kN


10E3 1000
9000
8000 7788 kN
90.0
7000 X X
6000
500
Axial load (kN)

5000
4000
3000
2000
0
-1100
-1000

1000
1100
-900
-800
-700
-600
-500
-400
-300
-200
-100
0.00

1000
100
200
300
400
516 kNm 500
600
700
800
900

-1000
D

500
Y

0
-2000

Bending moment (kNm)

Summary of design calculations:


Moment distribution along the height of the column for bending about the design axis:
At the top, Mx = 516.2 kNm Design table for critical load case:
Near mid-height, Mx = 240.0 kNm
At the bottom, Mx = 155.8 kNm Moments and Reinforcement for LC 3:Axial + Myy
Top Middle Bottom
Madd-x (kNm) 0.0 -0.0 -0.0
Madd-y (kNm) -116.2 0.0 116.2
Mx (kNm) 0.0 0.0 -0.0
My (kNm) 516.2 240.0 -116.2
M' (kNm) 516.2 240.0 155.8
Design axis () 90.00 90.00 90.00
Safety factor 1.10 1.28 1.30
Asc (mm) 6912 6912 6912
Percentage 1.06 % 1.06 % 1.06 %
AsNom (mm) 2587 2587 2587
Critical load case: LC 3

Design results for all load cases:

Safety
Load case Axis N (kN) M1 (kNm) M2 (kNm) Mi (kNm) Madd (kNm) Design M (kNm) M' (kNm) factor

Load case 1 X-X 0.0 0.0 0.0 0.0 0.0


Axial Y-Y 7788.0 0.0 0.0 0.0 0.0 Top 115.7 155.8 1.297
Job Number Sheet
KTP/10/13
Job Title
NEW FUTURA
Software Consultants (Pty) Ltd Client
Internet: http://www.prokon.com M/s KTP SPORE PTE LTD
Calcs by Checked by Date
E-Mail : mail@prokon.com HT T&T MARCH 2015

Safety
Load case Axis N (kN) M1 (kNm) M2 (kNm) Mi (kNm) Madd (kNm) Design M (kNm) M' (kNm) factor

Load case 2 X-X 0.0 400.0 240.0 0.0 400.0


Axial + Mxx Y-Y 7788.0 0.0 0.0 0.0 0.0 Bottom 116.2 155.8 1.303

Load case 3 X-X 0.0 0.0 0.0 0.0 0.0


Axial + Myy Y-Y 7788.0 0.0 400.0 240.0 116.2 Top 516.2 516.2 1.101

Load case 4 X-X 0.0 400.0 240.0 0.0 400.0


Axial + Mecc Y-Y 7788.0 0.0 200.0 120.0 0.0 Top 316.2 509.9 1.280

Load case 5 X-X 0.0 450.0 270.0 0.0 450.0


Axial + 34kpa Y-Y 7788.0 0.0 450.0 270.0 323.3 Top 566.2 723.2 1.167

Load case 3 (Axial + Myy) is critical.