Abstract: Boiler tube often causes abnormal boiler outage, bringing greater economic losses. This thesis mainly
comes from the dynamics of boiler water, boiler furnace accident location of wall temperature distribution to explore
the cause of the accident boiler. Calculation results show that the deformation will seriously reduce the boiler
allowable maximum temperature difference between the screens. And the boiler is not over-temperature, low
temperature difference between the screens, which have burst pipe. Analysis of the deformation of the boiler and
propose solutions.
Corresponding Author: Fu Huilin, School of Energy and Power Engineering, Chang Sha University of Science and
Technology, Changsha 410000, China
1726
Res. J. Appl. Sci. Eng. Technol., 6(10): 1726-1731, 2013
1.1
specific heat change greatly, under special
1.0
circumstances may appear film boiling and may appear
0.9
multivalent situation (the flow area slope is small and
0.8
anti-disturbance ability is weak ).
0.7 Boiler in traffic of 100% BMCR Firstly use
0.6 average flow calculation and then do the flow curve
0.5 Back calculation by the pressure drop. Obtained by
0.4 calculating the front, rear, side walls single tube flow
00
00
0
0
00
00
00
00
00
00
00
0
0
110
120
17
10
13
14
15
16
18
19
20
Temperature
420
415
Nomographic to get limit flow rate and calculation 410
coefficient, the calculation results are shown in Table 3. 405
400
395
Boiler wall temperature calculation: The highest 390
point temperature of wall is calculated by using the 385
following formula: 0 5 10 15 20 25 30
Front wall from left to right/m
q max w q max w 2
t gz + (r1 )
t= + (r1 ) Fig. 4: Boiler wall temperature calculation
(1 + )
540 Checking the water wall temperature
where, 520 Checking fin tip temperature
Temperature/ C
t : Wall positive temperature O
500
: Tube diameter ratio
480
qmax : Wall positive heat flux density
: Coefficient of heat transfer to the working fluid 460
from the inner wall 440
: Wall thickness 420
: Thermal conductivity of the tube
400
tgz : The temperature of the working fluid 0 5 10 15 20 30 35
25
u (r 1 ) : Shunt coefficient Front wall from left to right/m
The fin end temperature is calculated as follows: Fig. 5: Wall temperature in the boiler before checking
calculations
2 1
t gz + g qmax (
tg = + ) Calculation of the water wall tube temperature
1+
Calculate the fin root temperature
b 430
g =0.35 + 0.1 + ka k ks / d
d
Temperature/ C
O
420
where, 410
tg : The fins end of temperature
400
g : Shunt coefficient
: Tube diameter ratio 390
q max : Wall positive heat flux density
380
: Coefficient of heat transfer to the working 0 1 2 3 4 5 6 7 8 9 10
fluid from the inner wall Front furnace to back furnace/m
: Wall thickness
t gz : The temperature of the working fluid Fig. 6: Boiler side wall temperature calculation
b : Fin thickness
d : Tube diameter and the side wall is the single peak temperature field.
k , k , k s/d : Correction factor (Zhou, 2006) Before and after the wall about six meters away from
the side walls on both sides is the highest temperature
According to the formula to Calculate Boiler in in the boiler and the Sidewall center position has the
100% condition, the largest and most dangerous area of highest temperature. Wall temperature of the boiler is
the heat flux. The position of elevation is 40 m and the lower than the inner wall temperature about 10 to 50C.
calculation results are shown in Fig. 4 to 9. As it is calculated that the working fluid temperature is
The calculation results show that the front and back lower than tube wall temperature, pipe working fluid
walls of the boiler is the bimodal temperature field, temperature is higher than the outer wall temperature.
1728
Res. J. Appl. Sci. Eng. Technol., 6(10): 1726-1731, 2013
Checking the water wall temperature temperature. Front, rear and side walls all have the
Checking fin tip temperature smallest temperature difference between the inside and
outside wall of the corner position. The maximum wall
500 temperature of boiler is about 420C, even coupled with
the maximum temperature of 50C is only 470C, The
Temperature/ C
O
480
boiler calculation rupture strength temperature is the
460 next furnace to 511C, and the upper furnace to 492C.
Therefore boiler wall temperature does not exceed the
440 temperature. The boiler Checking Calculation
temperature is also lower than the boilers calculation
420
rupture strength temperature. Table 4 is the boiler
400 furnace water wall operating parameters, when to DC
0 1 2 3 4 5 6 7 8 9 10 process. As can be seen from the Table 4 boiler wall
Front furnace to back furnace/m running temperature much lower than the design, there
is no danger of over temperature, when boiler is
Fig. 7: Boiler side wall temperature check calculations running.
420
where obvious deformation of the section, Fig. 10
and 11 is the basis of measurement of the upper furnace
410 to the top position of 40 m in the deformation of the
400
front and rear wall. Consider the deformation of the
boiler water wall.
390 The water wall as one surrounded by a fixed sheet,
380 the bending generated by thermal stress calculated by
0 5 10 15 20 25 30 the following formula, the stress is the tangential stress:
Left furnace to right furnace/m
1 t
Fig. 8: The boiler wall temperature calculation results =
r h
t E
Checking fin tip temperature
max =
500 2 1
480
Temperature/ C
O Among,
460
r : Radius of curvature, m
t : Inner and outer wall temperature difference, C
440 max : Bending produce the greatest internal stress, pa
: Coefficient of linear expansion
420 : Elastic modulus
1729
Res. J. Appl. Sci. Eng. Technol., 6(10): 1726-1731, 2013
TO TAKE PRECAUTIONS
The front side wall of the outer wall of the boilers deformation varies. Replace the severe deformation
upper furnace should be controlled below 430C, water wall tube, to reduce operation allows the screen
under furnace is lower than 450C. The back side not higher than 70C temperature difference, prevent to
wall of the outer wall of the boilers upper furnace burst pipes happen again.
should be controlled below 410C, under furnace is
lower than 430C. REFERENCES
Replace the deformed tube: Severely deformed
under stress analysis pipe tangential stress increase, BaWei Company, 2009. Boiler Design Specification.
when it is greater than the axial stress of the boiler BaWei Co., Beijing, pp: 1-15.
will reduce the boiler allows between screen Cui, P., 2010. The study for the flow characteristics of
temperature difference cause boiler force shear, vertical tube platen water cooled wall in the ultra-
creep acceleration, tube rupture. Replacement of supercritical boiler [D]. M.A. Thesis, School of
deformed pipe to prevent pipe explosion from Energy, Power and Mechanical Engineering, North
happening again. China Electric Power University, Hebei, pp: 35-46.
Luo, K., 1981. B.A. Boiler Unit Standard Method of
CONCLUSION
Hydraulic Calculation. Power Industry Press,
Simplify the water wall to fixed flat, calculate the Beijing, pp: 17-45.
occurrence of severe deformation of boiler water wall. Song, G.L., 1995. The Boiler Calculation of Manual
The results showed that the deformation will seriously [M]. Liaoning Science and Technology Press,
reduce the boiler to allow the largest temperature Liaoning, pp: 83-200.
difference between the screen. This leads to the boiler Zhou, D., 2006. Supercritical concurrent boiler water
temperature difference between not over-temperature, cooling wall hydrodynamic force characteristic
low screen squib. Water wall deformation may be the research [D]. M.A. Thesis, School of Energy,
boiler temperature difference too large between the Power and Mechanical Engineering, North China
inside and outside wall or horizontal water wall Electric Power University, Hebei, pp: 44-49.
1731