Earth conduction effects in systems of overhead and

underground conductors in multilayered soils


D.A. Tsiamitros, G.C. Christoforidis, G.K. Papagiannis, D.P. Labridis and P.S. Dokopoulos

Abstract: Electromagnetic interference calculations in the case of overhead lines and underground
insulated conductors require the determination of the self and mutual impedances of all conductors
in the arrangement. For the calculation of these impedances in nonhomogeneous soils, the use of
the nite-element method is suggested. However, this is generally a complicated and time-
consuming task. Analytic expressions for these impedances are derived by a solution of the
electromagnetic eld equations for the case of n-layer soil. The innite integrals involved are
evaluated using a numerically stable and efcient integration scheme. A typical transmission line/
underground insulated pipeline arrangement is examined for various two-layer earth models and
over a wide frequency range. The validity of the proposed methodology is justied by a proper
nite-element method formulation. The inclusion of earth stratication leads to substantially
different results for the calculated impedances. These differences affect signicantly the levels of
voltages and currents induced on the pipeline, even for power frequencies, justifying the need for a
more detailed earth model representation.

1 Introduction of approximate formulas [8], or in the form of algorithmic


approximations [9].
A research topic that has received signicant attention from A further complication is due to the fact that the earth is
researchers during recent decades is the electromagnetic composed of several layers of different electromagnetic
interference between overhead power transmission lines and properties. Solutions for overhead conductors above multi-
electric traction lines or underground insulated conductors. layer earth have been proposed early enough [10, 11], but
The result of this interference is the induction of voltages these solutions do not apply to the case of underground
and currents on the underground insulated conductors, insulated conductors. The research in this area did not
which may cause electric shocks, deterioration of coating, proceed, possibly due to the lack of accurate data for proper
damage of equipment connected to the underground earth modelling. In some recent publications however
insulated conductor and corrosion. The various approaches [1215], several numerical techniques are proposed, offering
used to calculate the levels of the induced voltages and reliable estimations of the multilayered earth parameters,
currents are described in [15]. All these approaches are based on actual earth surface resistivity measurements.
based on the solution of equivalent circuits describing the A very efcient approach in nonhomogeneous earth
system of the transmission line and the underground treatment is the use of the nite-element method (FEM) for
conductor and require the calculation of the per-unit-length the calculation of the impedances of various conductor
self and mutual impedances between all conductors of the arrangements. The FEM is a numerical method used for
arrangement. the solution of electromagnetic eld equations in a region,
The impedances of the system are strongly inuenced by regardless of its geometric complexity. In a recent extension
the presence of the lossy earth. For the case of overhead [16] the FEM is applied for the calculation of the
lines, the earth return impedances are calculated using the impedances of transmission lines over nonhomogeneous
widely accepted Carsons formulas [6]. Pollaczek [7] has earth structures. A similar methodology is used in [17, 18]
proposed similar formulas applicable to cases of under- for the calculation of the impedances between overhead
ground conductors and to combinations of underground transmission lines and underground insulated metal pipe-
and overhead conductors. In both approaches the earth lines, as the rst step of a hybrid method for the calculation
is assumed to be homogeneous and semi-innite. These of the induced voltages and currents on pipelines. A major
expressions contain complex, highly oscillatory, semi- drawback is the complexity in the application of the FEM,
innite integrals, which are difcult to evaluate numerically. which is usually a time-consuming task, requiring access to
Several approaches have been proposed for the practical proper software.
calculation of the earth correction terms, either in the form The scope of this paper is to present analytic expressions
for the calculation of the per-unit-length self and mutual
earth return impedances of an overheadunderground
conductor system for the generalised case of a n-layer
r The Institution of Engineering and Technology 2006
earth. These expressions are derived by a general solution of
IEE Proceedings online no. 20050195
the electromagnetic eld equations, using a methodology
doi:10.1049/ip-gtd:20050195
based on the hertzian vector approach. This methodology,
Paper rst received 24th May and in nal revised form 8th December 2005
initially presented in [19] for underground cables in a two-
The authors are with Power Systems Laboratory, Dept. of Electrical &
Computer Engineering, Aristotle University of Thessaloniki, P.O. Box 486, layer earth, is extended for the combination of overhead
GR-54124 Thessaloniki, Greece and underground conductors and is generalised for a
E-mail: grigoris@eng.auth.gr n-layer earth case.

IEE Proc.-Gener. Transm. Distrib., Vol. 153, No. 3, May 2006 291
The resulting expressions are similar in form to the the two conductors is yik. The ith layer has permeability
corresponding proposed by Pollaczek [7] and Sunde [10], mi, permittivity ei and conductivity si. The air has a con-
containing complex semi-innite integral terms. These terms ductivity s0 equal to zero, permeability m0 and permittivity
are evaluated using a new numerical integration scheme e0 equal to those of the free space. The nth layer is con-
[20]. This scheme is based on proper combinations of sidered to be of innite depth.
numerical integration methods, to overcome efciently the The mutual impedances between the two conductors may
problems due to the highly oscillatory form of the innite be derived by integrating the eld due to the conductor
integrals. The scheme has been applied in several cases of dipoles. The eld intensities and potentials can be expressed
cable impedance calculations in both homogeneous and in terms of a single vector function P, usually referred to as
multilayered earth structures [19, 20] and proved to be the hertzian vector [10]. The P function has been adopted
numerically stable and efcient in all examined cases. for the solution of the electromagnetic eld equations in this
The accuracy of the results obtained by the new paper. Assuming a quasi-TEM propagation mode, follow-
methodology is checked using a proper FEM formulation ing assumptions apply.
in a test system, consisting of a typical single-circuit First a lamentary current source of innite length is
overhead transmission line and an insulated pipeline buried assumed to be located at the conductor centre. In the case
in different two-layer earth structures. The earth parameters of self impedances, the unequal current density on the
for each structure have been estimated from actual ground conductor surface due to the skin effect is taken into
resistivity measurements [12]. The comparison with the account by means of proper internal impedance terms.
results obtained by the FEM veries the validity of the These terms are calculated by the well-known skin effect
proposed expressions and the accuracy of the numerical formulas [21, 22] using modied Bessel functions [23] and
integration scheme. can be added to the self-impedance terms.
The impedances calculated for the two-layer earth model The second assumption is that the thickness of the
differ greatly from those calculated considering a homo- insulation of the underground insulated conductor is
geneous earth. These differences lead to signicant diver- negligible compared to its diameter. The impedance of the
gence in the level of the induced voltages and currents on insulation can be calculated using a simple formula [21] and
the pipeline, showing that a more accurate model than the can be also added to the corresponding impedances.
simple homogeneous earth model should be used in the Finally the conductors are assumed to be uniform and of
electromagnetic interference calculations. innite length, thus the end effects can be neglected and
therefore only the x-components of the hertzian vector P
2 Problem formulation and solution are used in the analysis.
Assuming a horizontal dipole with a moment Ids in the
2.1 Electromagnetic field equations place of the overhead conductor in Fig. 1, the x-compo-
The general layout of a system consisting of an overhead nents of the P function in the air and in the several earth
and an underground insulated conductor in a n-layer earth 0 0 0 0 0
layers are dened as P0x , P1x , P2x , y, Pmx , y, Pnx . The
structure is shown in Fig. 1. The underground insulated 0
equation that describes P0x at any point in the air with
conductor is buried in the mth layer of the n-layer earth.
The vertical distance of the underground insulated con- co-ordinates x; y; z is [11]
Z 1 
ductor from the upper boundary of the layer is h1. The 0 u a0 jzd1 d2 dm h2 j 0 a0 z
vertical distance of the overhead conductor from the earth P0x C e g0 ue
0 a0
surface is h2. The horizontal separation distance between
 J0 rudu; z  d1 d2    dm
1
air
and
o o Z
ox 1 h 0
i
conductor k h2 0
o = 0 P1x f 1 uea1 z g01 uea1 z J0 rudu;
0 2
first earth layer
1x d1 d2    dm  z  d1 d2    dm
1 1 1
Z 1 h i
second earth layer 0 0
2x d2 Pmx f m ueam z g0m ueam z J0 rudu; 0  z  dm
2 2 2 0
3
yik
and
h1 Z 1
mth earth layer 0 0
mx z
conductor i dm Pnx f n uean z J0 rudu; z  dm1    dn1
m m m 0

y
4
x
where C jom0 Ids=4pg20 . In these relations, J0( ) is
(n -1)th earth layer the Bessel function of the rst
q
kind of zero order,
(n -1)x n -1 n -1 n -1
dn-1 p
r x y , ai u gi , g2i jomi si joei ,
2 2 2 2

nx n -th earth layer where i 0; 1; 2; . . . ; n, j is the imaginary unit and o


n n n 2pf is the angular velocity. Equations (1)(4) are used in
[11] to derive the per-unit-length impedance expressions of
Fig. 1 Geometric configuration of system comprising of overhead the overhead conductors only. Thus the aim in this paper
and underground insulated conductor in n-layered earth is to derive the mutual impedance expression between the
292 IEE Proc.-Gener. Transm. Distrib., Vol. 153, No. 3, May 2006
overhead and the underground insulated conductor and the magnetic permeability of all earth layers can be considered
self impedance of the underground insulated conductor. to be equal to unity. Furthermore, for frequencies less than
1 MHz, the propagation constants g2i jomi si joei
2.2 Determination of per-unit-length  jomi si , where i 0; 1; 2; . . . ;p Therefore the
mutual impedance ai terms in
n.
2
(10b) can be expressed as ai u jomi si .
The boundary conditions are [11]
0 0
g2k1 Pk1x g2k Pkx 5
0 0
2.3 Determination of per-unit-length self
1 @Pk1x 1 @Pkx impedance of underground insulated
g2k1 g2k 6 conductor
mk1 @z mk @z
To determine the per-unit-length self impedance of the
where k 1; 2; . . . ; n. Substituting (1) and (2) in (5) and (6), underground insulated conductor, the electromagnetic eld
(7) and (8) are produced. Substituting the remaining P derived by the underground insulated conductor must be
functions in (5) and (6), 2n  2 similar equations are derived obtained. Thus, assuming a horizontal dipole with moment
 
u equal to IdS in the place of the underground insulated
g20 C ea0 h2 g0o ea0 d1 d2 dm conductor i, (11)(14) become the equations which describe
a0
 0  the problem [19]. Considering the origin of the co-ordinate
g21 f 1 ea1 d1 d2 dm g01 ea1 d1 d2 dm 7 system to be located directly under the insulated conductor
i, along the boundary of the regions m and m+1, the
 
a0 2 u a0 h2 0 a0 d1 d2 dm following relation is derived. For P0x :
g C e  go e
m0 0 a0 Z 1
a1  0 
P0x f 0 uea0 z J0 rudu; z  d1 d2    dm
g21 f 1 ea1 d1 d2 dm  g01 ea1 d1 d2 dm 8 0
m1
0 11
Solving the system of the 2n equations, f m and g0m are
obtained. The general form of the 2n  2 equations and the
0 For d2    dm  z  d1 d2    dm , P1x is de-
exact form of the f m and g0m functions are shown in the scribed by the following equation:
Appendix (Section 8.1). Thus the P function in the mth Z 1
0
layer Pmx is completely dened. The per-unit-length mutual

P1x f 1 uea1 z g1 uea1 z J0 rudu 12
impedance between the overhead conductor k and the 0
underground insulated conductor i can then be derived by
0
integrating Pmx along the innite conductor k, i.e. along the In the mth layer
x-axis [10] Z 1


Z 1" 0 #
Pmx f m1 ueam z gm1 ueam z J0 rudu;
0 2
Pmxzdm h1 ;yyik
Z ik gm dx 9 0
1 IdS z  dm  h1 13a
0 0
By replacing Pmxqfrom (3), Zik
takes the form of (10a). The
R1 and
2 2
term 1 J0 u x yik dx can be substituted by Z 1

2 cosuyik =u, as in [23], resulting in (10b) Pmx f m2 ueam z gm2 ueam z J0 rudu;
h i 0
Z 1 f 0 ueam dm h1 g0 ueam dm h1
0 m m z  dm  h1 13b
Z ik g2m
IdS 10a
0Z 1 q 
2 2 Finally Pnx is given by
 J0 u x yik dx du
1 Z 1

Q
m Pnx f n uean z J0 rudu 14
m1 0
jo2 mi
0 0
Z ik The P functions in (11)(14) can be determined using the
p8 9
> Q Q
m1 m  > reciprocity theorem [24]. According to this, an equation
>
Z 1> a h
ai e a d
DT rec >
>
<e similar to (10b) can be also obtained if the excitation current
0 2 i i
=
1 1 is imposed on the underground insulated conductor i,
 cosuyik du
0 >
> DTD0 >
> instead of the overhead conductor k. Therefore the per-unit-
>
: >
; 0
length mutual impedance Z ik is also given by
10b " #
Z 1
am dm h1 am dm h1 0 P0xzdm dm1 d2 d1 h2 ;yyik
where DT rec DTDm e DTN mQ e and Z ik g20 dx 15
the term products are dened as m ai di
e e a1 d1 1 IdS
Q 1Q
ea2 d2    eam dm , m1
1 ai a1    am1 and m 0 mi m0 m1
m2    mm . The terms DTDm , DTN m and DTD0 are calcula- Replacing the expression of P0x from (11) in (15) and
ted recursively by the formulas given in the Appendix equalising (15) with (10b), P0x can be fully determined.
(Section 8.1). Finally, applying the boundary conditions given in [11] at
The general form of (10b) can be simplied considering the boundaries of the earth layers, Pmx can be completely
that, since most soil types are nonmagnetic, the relative dened. The exact procedure for the determination of the

IEE Proc.-Gener. Transm. Distrib., Vol. 153, No. 3, May 2006 293
underground dipole P functions is shown in the Appendix overhead line k
(Section 8.2). air
The per-unit-length self impedance of the underground h2
o o o = 0
0
insulated conductor i Z ii is then found by integrating Pmx
along the x-axis first earth layer
Z 1" # insulated
h1
2 Pmxzdm h1 ;yrii
0 conductor i
Z ii gm dx 16 d
1 1 1
1 IdS
0 yik
In (16) rii is the insulation outer radius. The nal form of Z ii
z
results as (17)
Z
0 jomm 1 cosurii x y second earth
Z ii layer
2p 0 am 2 2 2
8
am dm h1
9
>
> DTD me DTN m eam dm h1 >
>
>
<
am h1 am h1
> >
>
=
Fig. 2 Geometric configuration of overhead and underground
am dm  TDD m1 e TDN m1 e insulated conductor in two-layer earth
 e du
>
> DTD0 >
>
>
> >
>
: ;
to (18) and (19), respectively,
17
0 jom1 m0
Z ik
The terms TDDm1 , TDN m1 are calculated by the recursive p
formulas given in the Appendix (Section 8.2). In (17) the 2 3
m2 a1 m1 a2 ea1 h1 euh2
geometrical conguration and the inuence of the earth Z 1 6 m a  m a ea1 2dh1 euh2 7
have been taken into account. Proper internal impedance 6 2 1 1 2 7
 6 7cosuyik du
4 m0 a1 m1 um2 a1 m1 a2 5
terms [21, 22] must be added in (17) to account for the skin 0

effect. m2 a1  m1 a2 m1 u  m0 a1 e2a1 d
18
3 Remarks on new expressions Z
0 jom1 1 cosurii
A closer examination of the expressions for the per-unit- Z ii
2p 0 a1
length mutual and self impedance, as given by (10b) and 2 3
(17), respectively, reveals the following. s10 s21 s10 d 21 e2a1 dh1

6 d 10 s21 e2a1 h1 d 10 d 21 e2a1 d 7
Beginning with (10b), the DTDm eam dm h1 DTN m 6 7du 19
4 s10 s21  d 10 d 21 e2a1 d 5
eam dm h1  term contains the electromagnetic and geome-
trical characteristics of the earth layers between the nth and
the mth layer, where the insulated conductor i is buried. where
This term also contains the vertical co-ordinate of the
insulated conductor i. The rest of the terms in the s10 m0 a1 m1 u; s21 m2 a1 m1 a2 and
numerator of the integral represent the geometrical and
electromagnetic characteristics of the air and the earth d 21 m2 a1  m1 a2 ; d 10 m0 a1  m1 u
layers between the rst and the mth layer. Finally, the Further observation of (18) reveals that it essentially
denominator term DTD0 includes the electromagnetic and consists of two terms. The rst and dominant one contains
geometrical properties of all the areas between the air and two exponential functions that represent the inuence of the
the nth layer. vertical distance between the underground and the overhead
Assuming that the electromagnetic properties of all earth conductor. These exponential functions have as a factor the
layers are equal, the existing formula [7] for the calculation sum of the electromagnetic properties of the two earth
of the mutual impedance between overhead and under- layers. The second term depends on the vertical distance
ground insulated conductors for the homogeneous earth between the overhead conductor and the image of the
case is derived from (10b). Furthermore, (10b) is also underground insulated conductor with respect to the two
transformed into the well-known Carson formula for the earth layers limit. This term is multiplied with a term
impedances of overhead lines above homogeneous earth. corresponding to the difference between the electromagnetic
The expression for the per-unit-length self impedance properties of the two earth layers. Thus when the resistivity,
essentially consists of the following terms. permeability and permittivity values of the two earth layers
The rst term in the square brackets contains the are equal, this term vanishes together with the boundary of
electromagnetic and geometrical characteristics of the earth the two layers.
layers between the nth and the mth layers. The second term On the other hand, observation of (19) shows that it
in the square brackets contains the electromagnetic and essentially consists of four terms. The rst and dominant
geometrical characteristics of the areas between the air and one contains two terms denoted with the symbol s to
the mth layer. The denominator term DTD0 includes all the indicate the sum of the electromagnetic properties of the
electromagnetic and geometrical properties of the areas three different areas: the air, and the rst and second earth
between the air and the nth layer. A simplication of (10b) layers.
and (17) for a two-layer earth case allows a better analysis The second term depends on the vertical distance between
of the contribution of each individual term involved in the the underground insulated conductor and its image with
expressions. Assuming the conguration of Fig. 2 and after respect to the limiting surface between the two earth layers.
setting a0 equal to u, as in [10], (10b) and (17) are simplied One factor of this term is represented by the symbol d 21 to
294 IEE Proc.-Gener. Transm. Distrib., Vol. 153, No. 3, May 2006
indicate the difference between the electromagnetic proper- 3m
ties of the two earth layers. Thus when the resistivity,
permeability and permittivity values of the two earth layers 6m
are equal, this term is set to zero.
The third term refers to the vertical distance between the 6m 6m
insulated conductor and its image with respect to the air 14 m
earth boundary. One of the factors of the last-mentioned 11 m
air
term is d 10 , indicating the difference between the electro- 0 0 0 = 0
magnetic properties of the air and the rst earth layer.
Finally the fourth term contains an exponential function first earth layer
which depends on the distance between the two images of insulated
1.2 m 1 1 1
conductor i
the insulated conductor with respect to the two boundaries
of Fig. 2. As expected, this term has as factors only d
variables representing differences in the electromagnetic 25 m
properties of the regions and it vanishes whenever one of
the two boundaries diminishes.
second earth
layer
4 Numerical integration of impedance formulas  2  2 2

Direct numerical integration is used for the calculation of Fig. 3 Geometric configuration of single-circuit overhead line with
two ground wires and underground insulated conductor in two-layer
the semi-innite integrals in (10b) and in (17)(19). The earth
implementation of a single numerical integration method
proved to be inadequate, due to the specic characteristics
Table 1: Two-layer earth models
of the integrals. The presence of the function cos( ) requires
the use of a proper numerical method, best suited to follow Case r1 (O  m) r2 (O  m) d (m)
the oscillations of the integrands. On the other hand, the
initial steep descent of the integrands suggests the use of a I 372.729 145.259 2.690
different numerical integration method in the interval II 246.841 1058.79 2.139
between zero and the rst root of the function cos( ).
III 57.344 96.714 1.651
Finally, the exponential functions, which appear in the
integrands, lead to the adoption of a method capable of IV 494.883 93.663 4.370
dealing with the effects of such terms. V 160.776 34.074 1.848
Following this reasoning, a complex integration scheme VI 125.526 1093.08 2.713
is implemented. The 20-point Lobatto rule [25] is applied to
the intervals between the subsequent roots of the function Six different two-layered earth models, based on actual
cos( ), while the 16-point shifted GaussLegendre method ground resistivity measurements [12] are investigated. The
[26] is used to calculate the integral between zero and the corresponding data for the resistivities r1 of the rst and r2
rst root of cos( ). Finally the 35-point shifted Gauss of the second layer and for the depth d of the rst layer are
Laguerre method [26] is also applied, since it is properly shown in Table 1. The second layer is considered to be of
tted for the calculation of semi-innite integrals with innite depth.
exponential weight functions. A more extensive presentation
of the proposed numerical integration scheme can be found 5.1 Verification of accuracy of new
in the Appendix (Section 8.3). expressions
This novel integration scheme has been applied success- The complex impedances for the conguration of Fig. 3 are
fully to the calculation of the earth return impedances of calculated for the six earth models of Table 1 using the
cables in cases of two-layer and homogeneous earth [19, 20]. proposed formulas of (18) and (19) for the frequency
In all cases examined the new method proved to be range of 50 Hz to 1 MHz. The novel numerical integration
remarkably efcient and numerically stable. scheme proved to be numerically stable in all cases. The
computation time for the numerical integration, with a
5 Numerical results dened tolerance of 108, is less than 15 min for the
calculation of a set of 60 impedance matrices using an
The new expressions for the n-layered earth model are used Intel Pentium IV PC at 2.66 GHz. When the tolerance is
to calculate the per-unit-length impedances of the system in dened at 107, the computational time is less than 8 min
Fig. 3. The system consists of a typical single-circuit for the same set of the 60 cases.
overhead transmission line with two ground wires. The To check the accuracy of the derived results they are
ground and phase wires are considered to be solid compared with those obtained by a FEM formulation for
cylindrical conductors with radius 0.004 and 0.0109 m, the same test cases. The FEM package developed at the
respectively. The ground wires have a conductivity equal to Power Systems Laboratory of the Aristotle University of
3.522  106 S/m and a relative permeability equal to 250. Thessaloniki has been used. Introducing a newly developed
The corresponding values for the phase conductors are iteratively adaptive mesh generation technique [27], this
3.652  107 S/m and 1. The underground insulated metal package can be applied for the computation of the self and
pipeline has an inner radius equal to 0.195 m and an outer mutual impedances of the conductors of the problem, in
radius of 0.2 m, whereas the insulation thickness is 0.1 m. unbounded discretisation areas [16].
The conductivity and the relative permeability of the pipe The relative percent differences between the results by the
are the same as those of the ground wires. The relative FEM and the new expressions are calculated using (20),
permeability of the insulation, of the air and the relative with the results obtained by the FEM used as the reference.
permittivity of the air are all equal to unity. These differences for the magnitude of the mutual

IEE Proc.-Gener. Transm. Distrib., Vol. 153, No. 3, May 2006 295
impedance between the insulated pipeline and the closest earth case as reference are presented in Fig. 6 for the
phase wire of the overhead line are shown in Fig. 4. In magnitude of the mutual impedance between the pipeline
Fig. 5 the differences between the new expressions and the and the closest phase. They reach up to 80% for high
FEM are presented for the magnitude of the self impedance frequencies and for cases of signicant divergence between
of the underground insulated conductor. the earth-layer resistivities. Differences up to 30% appear
From these diagrams it is shown that the impedance even at power frequency, indicating that earth stratication
values calculated using the new expressions show differences can affect signicantly the system impedances over the
less than 0.4% to those by FEM for the frequency whole frequency range.
range under consideration. The recorded differences for
the magnitude and the phase of all impedances of the 120
arrangement are less than 1% justifying the accuracy of the I II
III IV
proposed methodology. 90
V VI

Z approach  Z reference 60

difference, %
Relative difference %
Z reference
30

 100 20
0

1.0 30

I II
0.8 60
III IV
100 101 102 103 104 105 106
V VI
frequency, Hz
difference, %

0.6
Fig. 6 Differences in mutual impedance between underground
insulated pipeline and overhead line between two-layered and
0.4 homogeneous earth case

0.2
5.3 Influence of earth stratification on
inductive interference between pipeline
0
101 102 103 104 105 106
and overhead line
frequency, Hz To investigate the inuence of earth stratication on the
actual voltages induced on a pipeline, the calculated
Fig. 4 Differences in magnitude of mutual impedance between impedances were implemented in a practical case of
expressions and FEM inductive interference calculation in the test case of Fig. 3.
More specically, it is assumed that the power line and
1.0 the pipeline share a common right of way for 25 km, as in
[18]. A single-phase to ground fault at phase A is assumed
0.8 I II at the end of the right of way, while the other phases remain
III IV unloaded. The line supporting towers are located at
V VI distances of 250 m and are grounded with 20 O resistances.
difference, %

0.6 The pipeline has a coating resistance of 20 kO m2 and is


insulated at both ends via insulating junctions.
0.4 The pipeline is assumed to be buried in each one of the
six earth stratication cases of Table 1, while the power line
operates at power frequency. Figure 7 shows a typical
0.2
induced voltage prole along the pipeline, over the value of
the fault current, for the case V of Table 1. The dotted line
0 represents the voltage prole for the stratied earth case,
101 102 103 104 105 106 while the continuous line corresponds to a homogeneous
frequency, Hz

Fig. 5 Differences in magnitude of self impedance between 1200


expressions and FEM
induced voltage on pipeline over kA

case V two layers


1000
case V homogeneous
of fault current, V/kA

800
5.2 Comparison with homogeneous earth
case 600
The scope of the next test is to check the inuence of earth
stratication on the impedances of the conguration. The 400
complex impedances of the conductors are calculated for
the conguration of Fig. 3 and the six earth models of 200

Table 1 using the proposed formulas. The results are


0
compared with the corresponding under the assumption
0 5,000 10,000 15,000 20,000 25,000
that the earth is homogeneous with a resistivity equal to the distance from faulted tower, m
resistivity of the rst earth layer. The percentage differences
calculated using (20) and considering the homogeneous Fig. 7 Induced voltage along pipeline for case V of Table 1

296 IEE Proc.-Gener. Transm. Distrib., Vol. 153, No. 3, May 2006
earth with a resistivity equal to that of the rst layer. It can insulated conductors in a multilayered earth has been
be seen that earth stratication affects the induced voltage addressed. Analytic expressions for the self impedance of
signicantly. Table 2 summarises the percent differences the underground insulated conductor and the mutual
between the homogeneous and the two-earth layer case, impedances between the underground and the overhead
calculated using (20) with the homogeneous earth results as conductors are derived by a solution of the electromagnetic
the reference, for all earth stratication cases of Table 1. eld equations. For the numerical evaluation of the semi-
The rst two columns record the differences at both ends of innite integrals involved in the derived expressions, a new
the pipeline, where the highest induced voltages occur. numerical integration scheme, based on proper combina-
In the third column the maximum differences, which occur tions of three integration methods, is used. The proposed
along the pipeline for the length of the common right formulation is applied for the computation of the electrical
of way, are presented. The differences are greater than parameters needed for an interference computation between
20% for the higher induced voltages, reaching more than a typical single circuit overhead transmission line and an
100% at certain points of the pipeline along the common underground insulated metal pipeline, buried in the rst
track. layer of a variable two-layer earth structure.
Finally the inuence of earth stratication on the induced To check the accuracy of the results obtained by the new
voltages is also checked for higher frequencies that may analytic expressions, they are compared with the corre-
occur during transient conditions. The voltages on the sponding obtained by a suitable FEM formulation. The
pipeline at the point nearest to the faulted tower are recorded differences in the self and mutual impedance
calculated for frequencies from 50 Hz up to 1 MHz and for magnitudes and arguments are less than 1% over a wide
all cases of Table 1. The absolute percentage differences frequency range from power frequency up to 1 MHz,
between the voltages for homogeneous and the two-earth covering all possible transmission line operational states.
layer case are summarised in Fig. 8. It can be seen that the The integration scheme proved to be numerically stable and
recorded differences more or less follow the corresponding efcient in all examined cases.
of the mutual impedances in Fig. 6, as the induced voltages The impedances calculated by the expressions for a
depend mainly on the mutual coupling, which is in turn two-layer earth, show signicant differences compared
most signicantly affected by the earth return path. to those for the homogeneous earth, even at power
All these results show that it is important to include earth frequency, reaching up to 80% for the cases of great
stratication in the electromagnetic interference calculations divergence between the layer resistivities and for high
and this can be efciently accomplished using the proposed frequencies.
formulation. The calculated impedances are used in a practical
electromagnetic interference calculation. Results for the
Table 2: Percentage differences between induced voltages induced voltage along a pipeline, sharing a common right of
for homogeneous and two-layer earth cases at 50 Hz way of 25 km with an overhead power line, showed that it
may differ up to 25% in its maximum value, due to the
Case Pipeline end Pipeline end near Maximum earth stratication, even at power frequency. This difference
near fault, % source, % difference, % is further amplied for higher frequencies, showing that
earth stratication cannot be disregarded. The proposed
I 14.32 14.09 94.45
formulation, together with the new numerical integration
II 7.13 7.71 71.05 method, offers an efcient tool for the electromagnetic
III 0.24 0.74 71.48 interference computations. The use of the proposed
IV 22.28 22.21 103.77 methodology eliminates the need for complex modelling
V 24.24 24.14 102.41 in the estimation of the system parameters and avoids
VI 12.90 13.56 62.07
approximations, which may lead to inaccurate results.

7 References
100 1 Dabkowski, J., and Taove, A.: A mutual design consideration for
overhead AC transmission lines and gas pipelines (EPRI Report
I II EL-904, 1978, Vol. 1)
80 III
2 Frazier, M.J.: Power-line induced AC potential on natural gas
IV
pipelines for complex rights-of-way congurations (EPRI Report
V VI EL-3106, AGA L51418, 1984)
difference, %

60 3 Dawalibi, F.P., Southey, R.D., Malric, Y., and Tavcar, W.: Power-
line fault current coupling to nearby natural gas pipelines (EPRI
Report EL 5472, AGA, L51537, 1987, s1 & 2)
40 4 CIGRE Guide: Concerning inuence of high voltage AC power
systems on metallic pipelines. CIGRE Working group 36.02, 1995
5 Haubrich, H.J., Flechner, B.A., and Machczy*nski, W.: A universal
20 model for the computation of the electromagnetic interference on
earth return circuits, IEEE Trans. Power Deliv., 1994, PWRD-9, (3),
pp. 15931599
0 6 Carson, J.R.: Wave propagation in overhead wires with ground
return, Bell Syst. Tech. J., 1926, 5, pp. 539554
101 102 103 104 105 106 7 Pollaczek, F.: Ueber das Feld einer unendlich langen wechsel-
frequency, Hz stromdurchossenen Einfachleitung, Elektr. Nachr., 1926, 3, (4),
pp. 339359
Fig. 8 Absolute percent differences in induced voltage on pipeline 8 CCITT: Directives concerning the protection of telecommunication
between homogeneous and two-earth layer case lines against harmful effects from electric power and electried railway
lines, Vol. 3, Capacitive, inductive and conductive coupling: Physical
theory and calculation methods (ITU, Geneva, 1989)
9 Uribe, F.A.: Mutual ground impedance between overhead and
6 Conclusions underground transmission cables Paper IPST05-151, presented at the
Int. Conf. on Power System Transients, 2005, available through
www.ipst.org
The problem of the calculation of the complex impedances 10 Sunde, E.D.: Earth conduction effects in transmission systems
of a system comprising of overhead and underground (Dover Publications, 1968, 2nd edn), pp. 99139

IEE Proc.-Gener. Transm. Distrib., Vol. 153, No. 3, May 2006 297
11 Nakagawa, M., Ametani, A., and Iwamoto, K.: Further studies an1 2  0
on wave propagation in overhead transmission lines with earth g f ean1 dn1 dn2 dm1 
return: impedance of stratied earth, Proc. IEE, 1973, 120, (12), mn1 n1 n1
pp. 15211528 
12 Alamo, J.L.: A comparison among different techniques to achieve g0n1 ean1 dn1 dn2 dm1  24
an optimum estimation of electrical grounding parameters in two-
layered earth, IEEE Trans. Power Deliv., 1993, PWRD-8, (4), an  0 
pp. 18901899 g2n f n ean dn1 dn2 dm1 
13 Gonos, I.F., and Stathopoulos, I.A.: Estimation of multilayer soil mn
parameters using genetic algorithms, IEEE Trans. Power Deliv., 2005,
PWRD-20, (1), pp. 100106
14 Zhang, B., Cui, X., Li, L., and He, J.: Parameter estimation of After multiplying (23) with the factor an =mn , the right-hand
horizontal multilayer earth by complex image method, IEEE Trans. parts of (23) and (24) become equal. Equalising the left-
Power Deliv., 2005, PWRD-20, (2), pp. 13941401
15 Lagace, P.J., Fortin, J., and Crainic, E.D.: Interpretation of hand parts of the two equations the following relation
0
resistivity sounding measurements in N-layer soil using electro- between f n1 and g0n1 is obtained:
static image, IEEE Trans. Power Deliv., 1996, PWRD-11, (3),
pp. 13491354
16 Papagiannis, G.K., Triantafyllidis, D.G., and Labridis, D.P.: A one- 0 mn an1  mn1 an 2an1 dn1 dn2 dm1 
step nite-element formulation for the modelling of single and g0n1 u f n1 u e
double-circuit transmission lines, IEEE Trans. Power Syst., 2000,
mn an1 mn1 an
15, (1), pp. 3338 25
17 Christoforidis, G.C., Labridis, D.P., and Dokopoulos, P.S.: A hybrid
method for calculating the inductive interference caused by faulted
power lines to nearby pipelines, IEEE Trans. Power Deliv., 2005, For k n  1, (21) and (22) are transformed into
PWRD-20, (2), pp. 14651473  0
18 Christoforidis, G.C., Labridis, D.P., and Dokopoulos, P.S.: Inductive
interference on pipelines buried in multilayer soil, due to magnetic g2n2 f n2 ean2 dn2 dn3 dm1 
elds from nearby faulted power lines, IEEE Trans. Electromagn. 
Compat., 2005, 47, (2), pp. 254262 g0n2 ean2 dn2 dn3 dm1 
19 Tsiamitros, D.A., Papagiannis, G.K., Labridis, D.P., and Dokopou-
los, P.S.: Earth return path impedances of underground cables for the  0  26
two-layer earth case, IEEE Trans. Power Deliv., 2005, PWRD-20, (3), g2n1 f n1 ean1 dn1 dn2 dm1 
pp. 21742181
20 Papagiannis, G.K., Tsiamitros, D.A., Labridis, D.P., and Dokopou- 
los, P.S.: Direct numerical evaluation of the earth return path g0n1 ean1 dn2 dn3 dm1 
impedances of underground cables, IEE Proc., Gener., Transm.
Distrib., 2005, 152, (3), pp. 321328
21 Dommel, H.W.: Electromagnetic transients program reference
manual (Bonneville Power Administration, OR, Portland, 1986), an2 2  0
pp. 5-155-22 g f ean2 dn2 dn3 dm1 
22 Ametani, A.: A general formulation of impedance and admittance mn2 n2 n2
of cables, IEEE Trans. Power Appar. Syst., 1980, PAS-99, (3),

pp. 902910  g0n2 ean2 dn2 dn3 dm1 
23 Abramowitz, M., and Stegun, I.: Handbook of mathematical 27
functions (Dover Publications, 1972), pp. 479494 an1 2  0
24 Dorf, R.C.: The electrical engineering handbook (CRC Press, 1993), g f ean1 dn2 dn3 dm1 
pp. 7779 mn1 n1 n1
25 Davies, P., and Rabinowitch, P.: Methods of numerical integration 
(Academic Press, 2nd Edn. 1984), pp. 104, 223  g0n1 ean1 dn2 dn3 dm1 
26 Ralston, A., and Rabinowitch, P.: A rst course in numerical
analysis (McGraw-Hill, 2nd edn., 1988), pp. 100, 106
27 Labridis, D.P.: Comparative presentation of criteria used for adaptive Substituting g0n1 from (25), in (26) and (27) and eliminating
nite-element mesh generation in multiconductor eddy current 0
problems, IEEE Trans. Magn., 2000, 36, (1), pp. 267280 f n1 from the latter equations, a new equation is derived,
0
containing only the functions g0n2 and f n2 .
8 Appendix In a similar way the following general equation results:

8.1 Field derived by overhead dipole 0 DTN i 2ai ZLi


0
Substituting the exact expressions of Pk1x and Pkx in (5)
0 g0i u f i u e 28
DTDi
and (6), the following general equations are derived:
 0  where i 1; 2; . . . ; n, ZLi is the z-co-ordinate of the ith
g2k1 f k1 eak1 dk dk1 dm g0k1 eak1 dk dk1 dm layer lower boundary and
 0  
g2k f k eak dk dk1 dm g0k eak dk dk1 dm DTN i mi1 ai  mi ai1 DTDi1

21 mi1 ai mi ai1 DTN i1 e2ai1 di1 29
ak1 2  
0
gk1 f k1 eak1 dk dk1 dm  g0k1 eak1 dk dk1 dm 
mk1 DTDi mi1 ai mi ai1 DTDi1
ak  0  
g2k f k eak dk dk1 dm  g0k eak dk dk1 dm mi1 ai  mi ai1 DTN i1 e2ai1 di1 30
mk
22 DTN n 0 31
Starting from the last two earth layers, for kn, (21) and
(22) are transformed into
DTDn 1 32
 0
0
g2n1 f n1 ean1 dn1 dn2 dm1  Substituting (28) in (7) and (8) and eliminating f 1 u from
 (7) and (8), g00 u is obtained
g0n1 ean1 dn1 dn2 dm1  23
 0  u a0 h2 a0 d1 d2 dm DTN 0
g2n f n ean dn1 dn2 dm1  g00 u C e e 33
a0 DTD0

298 IEE Proc.-Gener. Transm. Distrib., Vol. 153, No. 3, May 2006
0
Replacing g00 u from (33) and g01 u from (28) in (7), f 1 u From the system of 2m equations, applying a similar
is obtained procedure as in Section 8.1, f l u, gl u are derived, where
l 0; 1; 2; . . . ; m
0 u a0 h2 g20 2m1 a0 DTD1 a1 d1 d2 dm
f 1 u C e e 34
a0 g21 DTD0 TDN l1 2al dm dm1 dl
gl u f l u e 42
0 TDDl1
Finally the following general equation is derived for f 1 u:
0 u a0 h2 g20 l1 
f i u C e ml
Q ai d i
a0 g2i 2 C m um0 e
 i i1 i1  1 g2m
Q Q Q aj dj f l u l1  l 
2 i
mj aj e DTDi Q Q g2l 43
1 0 1
mi ai
 eai ZHi 0 1
DTD0
 K 1 uTDDl1 eal dm dm1 dl
35
where ZHi is the z-co-ordinate of the ith layer upper In (42) and (43)
boundary.
TDD1 1 44
8.2 Field derived by underground dipole
Replacing the expression of P0x from (11) in (15), the per- TDN 1 0 45
0
unit-length mutual impedance Z ik between the insulated
conductor i and the overhead conductor k is
Z 1 TDDl1 ml1 al ml al1 TDDl2
0 2 2f 0 uea0 dm d2 d1 h2 cosuyik
Z ik g0 du 36 ml1 al  ml al1 TDN l2 e2al1 dl1 46
0 IdS u
Equalising (36) with (10b), the resulting expression for
f 0 u is derived and shown in (37), where C m jom m IdS TDN l1 ml1 al  ml al1 TDDl2
4pg2m
m1 m1 m1  ml1 al ml al1 TDN l2 e2al1 dl1 47
Q Q Q ai di
m a i e
u g2m 0 i 0 0 When lm the functions f l u and gl u are transformed
f 0 u 2m C m
a0 g20 DTD0 into f m1 u and gm1 u. Thus Pmx in (13a) is completely
h i dened.
 DTDm eam dm h1 DTN m eam dm h1 ea0 d1 d2 dm
g2m 8.3 Numerical integration technique
2m C m u m0 K 1 uea0 d1 d2 dm For the calculation of (10b) and (17)(19), three numerical
g20
integration methods are implemented as follows.
37 When the cos terms are not equal to one, the interval
Applying the boundary conditions (5) and (6) for the system between zero and the rst root of cosuyik or cosurii is
of (11)(13a), 2m equations like the following are derived: divided into the following subintervals:
         
g2 p106 p106 p105 p105 p104 0:1p p
g20 2m C m u m2 m0 K1 u 0; ; ; ; ; ...; ;
g 2y 2y 2y 2y 2y 2y 2y
 0 
g21 f 1 uea1 dm d2 d1 g1 uea1 dm d2 d1 where y is yik or rii. In each of these subintervals the
complex integrals are calculated using the shifted 16-point
38 GaussLegendre method [26]. Then, in the intervals
  between the subsequent roots of cosuy, the 20-point
a0 2 m g2
 g0 2 C m u m2 m0 K1 u Lobatto rule [25] is used. The procedure stops when the
m0 g0 absolute value of the calculated integral between two
a1 2   subsequent roots is less than a user predened tolerance for
g1 f 1 uea1 dm d2 d1 g1 uea1 dm d2 d1 both the real and the imaginary part of the integral.
m1
If the horizontal distance yik is zero, the integration
39 procedure is different. The shifted 16-point GaussLegendre
  method is again applied in the same way between zero and
g21 f 1 uea1 dm d3 d2 g1 uea1 dm d3 d2 uo 2p. Then the shifted 35-point GaussLaguerre method
  [25] is used for the evaluation of the rest of the integral, after
g22 f 2 uea2 dm d3 d2 g2 uea2 dm d3 d2
the integrand is scaled by the term ejh1 h2 ju . The procedure
 40 is repeated iteratively. In each iteration the use of the
a1 2  GaussLegendre method is extended by 2uo intervals to
g1 f 1 uea1 dm d3 d2 g1 uea1 dm d3 d2
m1 the right of uo, while the GaussLaguerre method is
a2   implemented for the calculation of the rest integral until
g22 f 2 uea2 dm d3 d2 g2 uea2 dm d3 d2 innity. Convergence is achieved when the absolute
m2
difference between two succedent values of the calculated
41 integral is less than a user predened tolerance.

IEE Proc.-Gener. Transm. Distrib., Vol. 153, No. 3, May 2006 299