ENFORCER
User Operation for the SK-1131-SQ
SK-1131-SQ
Press u u u u # the master code.
B. Changing/Adding Users:
*
Press 1 00-99 (user ID) u u u u (user code, 4-8 digits) # (for relay output #1)
Press 2 0-9 (user ID) u u u u (user code, 4-8 digits) # (for relay output #2)
Press 3 0-9 (user ID) u u u u (user code, 4-8 digits) # (for relay output #3)
C. Deleting Individual Users:
Press 1 00-99 (user ID) # (for relay output #1)
Press 2 0-9 (user ID) # (for relay output #2)
Press 3 0-9 (user ID) # (for relay output #3)
D. Changing the Master Code:
Press 0 X X X X #
E. To exit programming mode, press the
* key.
LIFETIME LIMITED WARRANTY This SECO-LARM product is warranted against defects in material and workmanship while
used in normal service for the lifetime of the product. SECO-LARMs obligation is limited to the repair or replacement of any defective part
if the unit is returned, transportation prepaid, to SECO-LARM. Under no circumstances will SECO-LARM be responsible for any costs or
charges for removal, installation, or reinstallation. This Warranty is void if damage is caused by or attributed to acts of God, physical or
electrical misuse or abuse, neglect, repair, or alteration, improper or abnormal usage, or faulty installation, or if for any other reason Also available from SECO-LARM:
SECO-LARM determines that such equipment is not operating properly as a result of causes other than defects in material and
workmanship. The sole obligation of SECO-LARM, and the purchasers exclusive remedy, shall be limited to repair or replacement only, at
Indoor Keypad Outdoor Keypads
SECO-LARMs option. In no event shall SECO-LARM be liable for any special, collateral, incidental, or consequential personal or property
damages of any kind to the purchaser or anyone else. This lifetime limited warranty is for products sold and installed in the United States
and Canada. For all other countries the warranty is 1 (one) year.
NOTICE: The information and specifications printed in this manual are current at the time of publication. However, the SECO-LARM
policy is one of continual development and improvement. For this reason, SECO-LARM reserves the right to change specifications without
notice. SECO-LARM is also not responsible for misprints or typographical errors. Copyright 2010 SECO-LARM U.S.A., Inc. All rights
reserved. This material may not be reproduced or copied, in whole or in part, without the written permission of SECO-LARM.
SECO-LARM U.S.A., Inc. Note: Model numbers that end with "Q" or that have a round green "Q" sticker signify RoHS-compliant products.
Page 16
Digital Access Keypad Manual Digital Access Keypad Manual
DAP
Installation screws x 2 5. The keypad is now in the programming mode, ready to (-) AC/DC
4 5/8 " Mounting screws x 2 receive new programming data. ON OFF (+) AC/DC
(117mm) 6. Re-program the keypad as shown starting on page 13.
K OR A DAP
KEY AL
EG In - Egress
NOTE -- A new master code may be programmed to replace the ON OFF
Relay Relay N.O.
one that was lost or forgotten. Note that the sequence for Tamp
ENFORCER 2 1 C.
replacing the old master code is as follows:
N.C.
Option* Key in new code Confirm Exit
0 X X X X #
1 3/4 " * 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
(44mm) *Zero "0" is for new master code only; see page 13 for other options.
{
1 # Auto Entry Mode is selected. The # key that follows he user code is NOT required in
code entry. The User Codes MUST be set to he same digit length as he Master Code.
to trigger a video recorder or turn on a light, or to signal a guard that someone is
8 2
0 # Manual Entry Mode is selected. The # key that follows the user code is required in entering the protected premises.
code entry. The User Codes can be 4-8 digits, but not necessarily all of the same length.
Alarm output -- When used with an optional magnetic contact, this NPN transistor
Keypress Beeps (DEFAULT: On) open collector ground (-) output can be connected to trigger an optional alarm
Op ion Code entry Confirm Function control panel if a protected door is forced open or propped open.
8 3
{ 1
0
#
#
Keypad beeps when a key is pressed.
Silent operation -- keypad does not beep when a key is pressed. Door auto relock -- This can be programmed to relock an open door either when the
programmed relock time expires or immediately after the door is closed, depending
LED Flashes in Standby Mode (DEFAULT: On)
Code entry Confirm Function
on which occurs first. This prevents unwanted "tailgate" entries, which can happen if
8 4 { 1
0
#
#
Amber LED ON during standby mode.
Amber LED OFF during standby mode.
an unauthorized person tries to follow an authorized person through the door.
Duress output -- This NPN transistor open collector ground (-) output can be used to
Door Propped Open Alarm Timer (DEFAULT: Off) trigger a silent alarm if an authorized user is forced under duress to use the keypad.
Op ion Code entry Confirm Function The duress output is activated by adding 2 to the first digit of any user code for output
9
{ 0
1 to 999
#
#
No door propped open alarm
Allowable time from 1 to 999 seconds that the door can be left open before the alarm starts.
#1. In this case, the protected door opens as it would normally, but a signal is quietly
sent to a remote device to call for help without alerting the unauthorized person.
Exit Programming Mode
Confirm Function
Backlit keypad -- The keypad is backlit to increase nighttime visibility. For convenience,
Exits programming mode, returns keypad to normal operations the lighting intensity will increase for 10 seconds after any key is pressed.
*
SECO-LARM U.S.A., Inc.
Page 14 Page 3
Digital Access Keypad Manual Digital Access Keypad Manual
(JUHVVLQSXW &RQQHFWWRRSWLRQDO12SXVKEXWWRQRUVZLWFKLQVLGHWKHSURWHFWHGSUHPLVHV/HWVXVHUVLQVLGHWKHSURWHFWHGSUHPLVHVH[LWZLWKRXWXVLQJWKHNH\SDG
VFRGH
1. The master code -- Allows the system administrator to program or operate the keypad.
2. The user code or codes -- Allows users to use the keypad's functions.
3. Configuration of the relays and outputs -- For relay output #1, relay output #2, and output #3,
)RU9RSHUDWLRQFRQQHFWD. 2KP
determine whether the output should operate from 1 to 999 seconds and then turn OFF (momentary
mode), or turn ON/OFF via the code (shunt mode).
UHVLVWRULQVHULHVZLWKWKH/('
minute code lockout, or no reaction.
* Note: When X X X X appears in the instructions, it indicates master code entry.
:+,7(25$1*( 'XUHVVRXWSXW *URXQG ZKHQDFWLYDWHGP$#9'&
GETTING STARTED
*URXQG&RPPRQJURXQGIRUXVHZLWKPDQWUDSIXQFWLRQ
A master code is required to program the keypad. The default master code is set to "0000." To change the
&RQQHFWWRWKH1&WDPSHUFLUFXLWRIDQ
2XWSXW 7UDQVLVWRUJURXQG P$#9'&
Once the master code is set, review the programming options and decide exactly what the keypad will do,
(*,Q (JUHVV 12JURXQG &RQQHFWWRRSWLRQDO12SXVKEXWWRQRUVZLWFK
DODUPFRQWUROSDQHOLIGHVLUHG
including the format of the user access codes as well as how the keypad responds via the relay output,
``
$#9'&
2. Enter the programming codes defined in the various sections as needed, followed by the# key.
`
3. Enter the * key again to exit programming mode.
5HOD\RXWSXW &20
5HOD\RXWSXW 12
5HOD\RXWSXW 1&
Note: A rapid string of 5 beeps and/or 5 LED flashes indicates an error, while 2 beeps indicates that the
entry has been accepted.
` 1&WDPSHU
1&WDPSHU
USER PROGRAMMING
ENTER PROGRAMMING MODE
Enter Master code Confirm Func ion
&20 5HOD\RXWSXW $#9'&
X X X X
* Enter into programming mode
:+,7(%52:1
9$&'&LQSXW
25$1*(
<(//2:
/W%/8(
%52:1
*5((1
%/$&.
:+,7(
*5(<
%/8(
5('
1&
Note: For User ID, key in he number of the user. For Access Code, type in the code for that particular user.
:,5,1*%$6,&',$*5$0
.(<$/
Option User ID Confirm Function
1 00 to 99 # Deletes specific user ID from output #1
2 # Deletes specific user ID from output #2
0 to 9
3 # Deletes specific user ID from output #3
0 to 9
WIRING: WIRING:
Example Wiring, with Inhibit Control Authorized Auxiliary Accessories
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
TAMPER N.C.
OUTPUT 1 EG (+) (--) Door
N.C. C. N.O IN 12~24V AC DC Sens
WIRE HARNESS
(--) (+) ( -) (+)
(1) RED
ALARM
CONTROL
RED LED
RED LED
GREEN LED
GREEN LED
OUTPUT 3
O/P 1 Disable
(2) BLACK
(3) PANEL
(+) (4)
(5)
(6)
24-hour N.C.
(7) protection
zone
N.C. N.O.
OR
+ -- REMARKS:
Electric Output relay #1 DURESS OUTPUT
Lock 12VDC N.O. output for fail-secure lock.
+ -- power N.C. output for fail-safe lock. WIRE HARNESS
supply
LEDs: (10) ALARM
Each LED requires a 1.5K-Ohm (11) CONTROL
(for DC series resistor for 24V operation. (12) PANEL
Diode use only) (13)
1N4004 (14)
Cathode (15) LIGHT GREEN 24-hour N.O.
Egress button (inside the Additional egress buttons protection zone,
can be connected in (16) WHITE/ORANGE
N.O. N.O.
protected premises)
parallel as needed
max. 100mA
DOOR SENSING
Note:
MAGNETIC Required for:
DOOR
GND SENS
Connect a 1N4004 diode as close as possible to and in parallel with the DC- DOOR
Door Auto Relock
(--)
powered electromagnetic or electric lock. This absorbs possible electromagnetic CONTACT
(N.C.) Door Forced-open Alarm
interference to prevent operation of the lock from damaging the keypad. A 1N4004 Door Propped-up Alarm
is not required for AC-powered locks. Mantrap (Interlock) Control
Connect the ground (-) terminal of the keypad to earth to prevent electrostatic
discharge from damaging the keypad. KEY ACTIVE or ALARM OUTPUT
The connection of relay output #1 disable to output #3 as shown above is optional. 12V 12V The Key Active Output will switch to ground (-
When so wired, output #3 is the inhibit control. To use, program output #3 for shunt ) for 10 seconds whenever a key is touched.
(3) (3) Use to turn ON an LED and/or a small buzzer
on/off operation. When output #3 is ON, relay output #1 will not work. For example, (4) 1.5k
Low (4)
N.O. relay
contact to notify a guard, or to energize a relay to
power
(5) (5)
this can be used to prevent users from entering the protected premises during the (6)
piezo
(6) switch ON lights or CCTV camera.
LED buzzer
evening or weekend. See programming option 61. (7) (7)
(8) PINK (8) PINK Only one connection option is recommended.
Isolation
(9) (9) Make sure the current does not exceed the
As wired, the green LED lights while relay output #1 is activated to activate the relay
maximum rating of 100mA.
lock. OR An external power supply and isolation relay
As wired, the red LED lights to show that relay output #1 is disabled by the (See page 15 for jumper selection) are necessary to drive high power devices
such as lights or CCTV cameras.
activation of output #3.
Tape all unused wires to prevent short circuits.
WARNING: RELAY OUTPUT #2 -- Example, to shunt an alarm N.C. zone
WIRE HARNESS WIRE HARNESS Use Normally Open (N.O.) output
If the inhibit control is used, all personnel must exit the protected premises before contact to shunt a Normally Closed
output #3 is activated. Otherwise, personnel in the protected premises will not be (8)
To protection zone of an (N.C.) protection zone of an alarm
alarm control panel
able to exit until output #3 is turned OFF. (9) WHITE/BROWN system.
(10) BLUE N.C.
(11) Set relay output #2 to Start / Stop mode
The user code for output #3 in this case should be given only to personnel (12) (programming option 51)
authorized to enter the premises any time. It should not be given to other users.
N.C. magnetic contact
Wire
Harness
WIRING: WIRING:
Example Wiring, Mantrap Using Two Keypads Example Wiring, with Connection to Lock Device and Alarm Arm/Disarm
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
DOOR 1 OUTPUT 1 EG (+) (--) Door
OUTPUT 1 EG (+) (--) Door N.C. C. N.O IN 12~24V AC/DCSens
N.C. C. N.O. IN 12~24V AC/DC Sens (+)
(+)
N.C. N.O.
O/P 1 Disable
Mantrap control
Common GND
OR
N.C. N.O. N.C
+ -- REMARKS:
OR Electric Output relay #1
Lock 12VDC N.O. output for fail-secure lock.
Door 1 + -- power N.C. output for fail-safe lock.
sensor supply
Electric
To O/P 1 N.O.
To (--) GND
Lock
+ -- + --
(for DC
12VDC Diode use only)
power 1N4004
(for DC supply REMARKS: Cathode
Diode Additional egress buttons
1N4004 use only) Output relay #1 Egress button (inside the
protected premises) N.O. N.O. can be connected in
Cathode N.O. output for fail-secure lock. parallel as needed
N.C. output for fail-safe lock.
Mantrap control
Egress button (open door 1 from inside). LEDs:
Common GND
N.O.
O/P 1 Disable
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
Additional egress buttons can be Each LED requires a 1.5K-Ohm
connected in parallel as needed. series resistor for 24V operation.
O/P 1 DISABLE3
AUX LED
OUTPUT
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
DOOR 2
OUTPUT 1 EG (+) (--) Door WHITE/ORANGE N.O. Duress -- To 24-hour N.O. zone
N.C. C. N.O. IN Sens
12~24V AC/DC
LIGHT GREEN (--) Com gnd (--) of keypad & alarm system
}
(+)
PURPLE N.C. Relay output #2
GREEN LED (+)
GREEN LED (--)
}
to connect for N.C. or N.O. operation
OR
Electric
Door 2
sensor
YELLOW
LIGHT BLUE
(+)
(--) } Red LED
LEDs:
For alarm status
indication. Each LED
GREEN (+)
} requires a 1.5K-Ohm
To O/P 1 N.O.
To (--) GND
}
12VDC BLACK
power N.C. Tamper --
(for DC supply RED To a 24-hour N.C. zone
Diode REMARKS:
1N4004 use only) Output relay #1
Cathode N.O. output for fail-secure lock.
N.C. output for fail-safe lock.
Egress button (open door LEDs:
2 from inside) N.O. Note:
Each LED requires a 1.5K-Ohm
series resistor for 24V operation. PLEASE ALSO REFER TO THE NOTES ON PAGE 6 FOR MORE GENERAL INFORMATION.
The electromagnetic or electric door lock operation is the same as page 6, except the LED
Interlock -- Each keypad can be used as a stand-alone keypad. The mantrap feature is for a protected area with outputs have changed.
two doors to ensure only one door is open at a time. With the mantrap feature, when a user keys in the code to The function of the red and green LEDs depends on how they are connected to the alarm
open one door, a signal is sent to the second keypad to disable it, thereby preventing access through the second control panel.
door until the first door is closed.
Relay output #2 controls the arm/disarm of the alarm control panel. Consult the alarm
Note: PLEASE ALSO REFER TO THE NOTES ON PAGE 6 FOR MORE GENERAL INFORMATION.
control panel manual for more information.
Use an N.C. magnetic contact or some other N.C. device to detect whether a door is opened or closed. Do this
for the two entrances to the protected premises. Connect the duress output to a 24-hour N.O. zone and the tamper output to a 24-hour N.C.
The function of the red and green LEDs depends on how they are connected. zone on the alarm control panel.
Combine this wiring diagram with the diagram on page 7 if connection to an alarm control panel is required. The connection of relay output #1 disable to output #3 as shown above is optional. When so
Connect output #3 to relay output #1 disable as shown on page 6 if inhibit control is required. wired, output #3 is the inhibit control. To use, program output #3 for shunt on/off operation.
To use the mantrap feature: When output #3 is ON, relay output #1 will not work. For example, this prevents users from
o Use either the keypad from outside or the egress button from inside the protected premises to open one of entering the protected premises during the evening or weekend. See programming option
the two doors. 61. In this case, the center auxiliary LED changes from flashing green to steady red to show
o While the first door is opened, the first keypad sends a signal to the second keypad to prevent the second that relay output #1 is disabled by the activation of output #3.
keypad from being used to open the second door.
The keypad's light green wire connects to the ground (-) wire of the alarm control panel to
o After the first door is closed, both keypads are ready to use.
enable the two to work together.
Page 8
USER ID User Name Access Code USER ID User Name Access Code
00 SAMPLE - John Doe 54321 00 SAMPLE - John Doe 54321
00 50
01 51
02 52
03 53
04 54
05 55
06 56
07 57
08 58
09 59
10 60
11 61
12 62
13 63
14 64
15 65
16 66
17 67
18 68
19 69
20 70
21 71
22 72
23 73
24 74
25 75
26 76
27 77
28 78
29 79
30 80
31 81
32 82
33 83
34 84
35 85
36 86
37 87
38 88
39 89
40 90
41 91
42 92
43 93
44 94
45 95
46 96
47 97
48 98
49 99
Relay Output #2: Output: Shunt / Momentary (____secs.) Programmed For: _________________________________
0 5
1 6
2 7
3 8
4 9
Output #3: Output: Shunt / Momentary (____secs.) Programmed For: _________________________________
0 5
1 6
2 7
3 8
4 9
Note: copy this sheet to use for your installations.
Page 9