CALCULATION SHEET

FIRE WATER DEMAND

JOB NO. : INL/SPJ/02/2016


FIRE ZONE : Fire Zone 10 (FZ-10)
PREP'D : ADT
PROJECT : PROYEK PEMBANGUNAN PABRIK MINYAK GORENG KAPASITAS 600.000 Ton CPO/Tahun CHK'D : ABI
APP'D : IS
CLIENT : PT. INDUSTRI NABATI LESTARI REV : 1
DATE : 22-Feb-17

1. WEIGHT BRIDGE BUILDING 2ND FLOOR (SAMPLE LAB)


Sprinkler Quantity per Area
A. Part A (Ruang Analisa Khusus)
Floor Area : 25 m2
Sprinkler spacing (maximum) : 4.6 m
Sprinkler spacing (minimum) : 1.83 m
Protection Area : 20.9 m2
Sprinkler quantity (minimum) : 2
Sprinkler quantity / branch line : 2
Distance from Sprinkler to wall (Maximum) : 2.7 meter NFPA 13 (2007) 8.6.3.2.4
Distance from Sprinkler to wall (Minimum) : 0.1 meter

1.67 m
1.67 m

2.5 m

Minimum Flow & Pressure per Sprinkler


Sprinkler distance along the wall (maximum) (S) : 2.5 m
Sprinkler distance across the room (maximum) (L) : 1.67 m
2
Protection area of coverage per sprinkler (As) : 16.7 m
Density / Application Rate : 4.10 L/min/m2
Minimum Flow per Sprinkler (Q) : 68.47 L/min
1/2
K-Factor : 80.6 L/min/bar
Minimum sprinkler pressure : 0.5 bar
Minimum pressure required (P) : 0.7 bar
Sprinkler Quantity : 2
Total Flow : 137 L/min

3. HYDRANT / MONITOR / HYDRANT BOX


Available hydrant, hydrant box or monitor:
Tag Equipment
WH-12 Pillar Hydrant (Outside of the building) : 946.4 L/min/hose NFPA 14 Section 7.10.1.1.1

4. SUMMARY
Scenario 1: Sample Lab on fire
Sprinkler system Sample Lab : 137 L/min
Pillar Hydrant WH-12 : 946 L/min
Total Fire Water Requirement 1083 L/min

Sprinkler Nozzle Head Quantity


Sample Lab : 2