CALCULATION SHEET

FIRE WATER DEMAND

JOB NO. : INL/SPJ/02/2016


FIRE ZONE : Fire Zone 06 (FZ-06)
PREP'D : ADT
PROJECT : PROYEK PEMBANGUNAN PABRIK MINYAK GORENG KAPASITAS 600.000 Ton CPO/Tahun CHK'D : ABI
APP'D : IS
CLIENT : PT. INDUSTRI NABATI LESTARI REV : 1
DATE : 22-Feb-17

1. WAREHOUSE
Sprinkler Quantity per Area
A. Warehouse
A1
2
Floor Area : 72 m
Sprinkler spacing (maximum) : 4.6 m
Sprinkler spacing (minimum) : 1.83 m
2
Protection Area : 20.9 m
Sprinkler quantity (minimum) : 4
Sprinkler quantity / branch line : 3
Distance from Sprinkler to wall (Maximum) : 2.3 meter
Distance from Sprinkler to wall (Minimum) : 0.1 meter

A2
Floor Area : 36 m2
Sprinkler spacing (maximum) : 4.6 m
Sprinkler spacing (minimum) : 1.83 m
2
Protection Area : 20.9 m
Sprinkler quantity (minimum) : 2
Sprinkler quantity / branch line : 2
Distance from Sprinkler to wall (Maximum) : 2.7 meter NFPA 13 (2007) 8.6.3.2.4
Distance from Sprinkler to wall (Minimum) : 0.1 meter

2m
3.3 m 3.3 m
2.7 m

1
2m

2m

2m
2

2m
2m

Minimum Flow & Pressure per Sprinkler


A. Warehouse
A1
Sprinkler distance along the wall (maximum) (S) : 3.3 m
Sprinkler distance across the room (maximum) (L) : 2 m
Protection area of coverage per sprinkler (As) : 26.4 m2
Density / Application Rate : 3.67 L/min/m2
Minimum Flow per Sprinkler (Q) : 96.888 L/min
1/2
K-Factor : 80.6 L/min/bar
Minimum sprinkler pressure : 0.5 bar
Minimum pressure required (P) : 1.4 bar
Sprinkler Quantity : 6
Total Flow : 581 L/min

A2
Sprinkler distance along the wall (maximum) (S) : 2m
Sprinkler distance across the room (maximum) (L) : 2m
2
Protection area of coverage per sprinkler (As) : 16 m
Density / Application Rate : 3.67 L/min/m2
Minimum Flow per Sprinkler (Q) : 58.72 L/min
1/2
K-Factor : 80.6 L/min/bar
Minimum sprinkler pressure : 0.5 bar
Minimum pressure required (P) : 0.5 bar
Sprinkler Quantity : 4
Total Flow : 235 L/min

3. HYDRANT / MONITOR / HYDRANT BOX


Available hydrant, hydrant box or monitor:
Tag Equipment
HB-07 Hydrant Box : 378.5 L/min/hose NFPA 14 Section 7.10.1.1.1
WH-09 Pillar Hydrant (Outside of the building) : 946.4 L/min/hose NFPA 14 Section 7.10.1.1.1

4. SUMMARY
Scenario 1: Warehouse on fire
Sprinkler system Warehouse : #REF! L/min

Total Fire Water Requirement #REF! L/min

Scenario 2: Warehouse fire escalate


Pillar Hydrant WH-09 : 946 L/min

Total Fire Water Requirement 946 L/min

Sprinkler Nozzle Head Quantity


Warehouse : 10