Fault Interruption

Mediums

MV Switchgear & Apps Seminar


1
Switchgear Insulating Mediums

Insulator =S= product Type

Air Masterpact LV Air Circuit Breaker

Oil So-Hi Oil Circuit Breaker (obsolete)

Vacuum MCset Withdrawable Circuit Breaker

SF6 gas Genie & Ringmaster Switches & Circuit Breakers

MV Switchgear & Apps Seminar


2
Fault Interruption mediums for 11kV
Oil Vacuum SF6

IVI (Yorkshire Switchgear) MC set Genie

MV Switchgear & Apps Seminar


3
Oil Long & Crawford Oil Switch

Oil has high dielectric strength

Interruption effectively takes place


in a hydrogen bubble Oil

Carbon based by products which


drastically affect the dielectric Earth
strength Contact

After 3 operations on fault need to Moving


change oil due to build up of Contact
carbon deposits and inspect the
arcing contacts Fixed
contact
Oil/hydrogen very flammable and
any explosions can be
catastrophic

MV Switchgear & Apps Seminar


4
Oil test

MV Switchgear & Apps Seminar


5
Oil test

MV Switchgear & Apps Seminar


6
Oil test

MV Switchgear & Apps Seminar


7
Oil test

MV Switchgear & Apps Seminar


8
Oil test

MV Switchgear & Apps Seminar


9
Oil test

MV Switchgear & Apps Seminar


1
0
Oil test

Lid blown off

Holes burnt
Oil covering through
floor switchgear tank
(6mm thick steel)

MV Switchgear & Apps Seminar


1
1
SF6 as an interrupting medium

Sulphur hexafluoride (SF6) is used as a


switchgear interrupting medium from 1 to
800kV - a non-flammable, non-toxic, inert and
highly stable gas

Two different types of arc control device, both


relying on extending and cooling the arc.
Puffer
Rotating arc

MV Switchgear & Apps Seminar


1
2
Puffer technology

As the contacts open the piston pressurises


the SF6 gas beneath. As the arcing contacts
separate the gas is released across the arc
path to blow out the arc.

MV Switchgear & Apps Seminar


1
3
Rotating arc technology

Position 1 - CB closed
Main current flows through central
electrode and down the outgoing contact
blades.

Position 2 - CB opening
Opening movement of outgoing contact
blades draws the arc from the central
arcing electrode to the arcing blade.

Position 3 - CB open
Arc rotates under influence of Lorenze
force and finally extinguishes at current
zero

MV Switchgear & Apps Seminar


1
4
Rotating arc technology
Rotating
busbar arc coil busbar

earth earth
cable cable

MV Switchgear & Apps Seminar


1
5
Rotating arc technology

MV Switchgear & Apps Seminar


1
6
Vacuum as an interrupting medium

Rapid recovery of dielectric


guarantees interruption within
the first subsequent zero
crossing

Over 100 interruptions of the


rated short circuit current

Short arc times minimum


three milli seconds

A separate line isolator is


required as gap in vacuum
bottle is only approx. 10mm

MV Switchgear & Apps Seminar


1
7
Internal arc conformity with IEC standard 60298

busbar compartment

circuit breaker compartment

cable connection compartment

MV Switchgear & Apps Seminar


1
8
Internal arc conformity with IEC standard 60298

Cubicle design must allow the effects of


an internal arc to be contained
(internal overpressure, mechanical and
thermal strain)

Use non flammable materials

Channelling of hot gases

MV Switchgear & Apps Seminar


1
9
Internal arc conformity with IEC standard 60298
MC Set Internal Arc Witness Test 25kA for 1 sec

MV Switchgear & Apps Seminar


2
0
UK MV offer - Summary
The UK offer for MV is:-

Low level Primary,


Secondary Ringmaster range..

Primary Genie...

High level Primary,


Heavy duty industrial MCset..

MV Switchgear & Apps Seminar


2
1
Ringmaster RN2c
Compact Ringmain Units

RN2c Standard RMU with 200A CB


RE2c Extensible RMU with 200A CB
RN6c Enhanced RMU with 630A CB

TFL

MV Switchgear & Apps Seminar


2
2
Ringmaster Extensible Range
Flexibility of application
- 4 popular configurations

Joint Ownership Switchboards


REC Incomer and Bus section
Consumer feeders
Main Intake Switchboards
Metered Incomers
630A bus sections
IDMT feeders
Double Ended Substations
Ring main application
multiple transformer feeds
Network Sectionalisers
Motorised 630A ring circuit breakers

MV Switchgear & Apps Seminar


2
3
Genie
Intelligent Protection, Control and Monitoring Systems
Evolution from separate relays to
integrated protection, control,
monitoring and metering units

Protection, control and monitoring


schemes to meet the application
main incomers and feeders
UPS input and output
changeover, etc

Provides communications interface


for remote monitoring & control

MV Switchgear & Apps Seminar


2
4
The End