Project Name: DANANG CITY ADMINISTRATION CENTER

Cable Calculation
Subject : MCC-E1

FROM S/S

received received Breaker


ratio load Current CABLE
FROM TO M Total
SIZE
(%) (VA) (A) Cable P AF AT
Type MM2 Structure GIV

MCC-E1 FP-01 ### 100 231250 351.76 PVC/XLPE 150.00 4x1C 50.00 3 400 400

Subject : MCC-E2

FROM S/S

received received Breaker


ratio load Current CABLE
FROM TO M Total
SIZE
(%) (VA) (A) Cable P AF AT
Type MM2 Structure GIV

MCC-E2 FP-01 ### 100 231250 351.76 PVC/XLPE 150.00 4x1C 50.00 3 400 400

Subject : MCC-E3

FROM S/S

received received Breaker


ratio load Current CABLE
FROM TO M Total
FROM TO M Total
SIZE
(%) (VA) (A) Cable P AF AT
Type MM2 Structure GIV

MCC-E3 FP-01 ### 100 206250 313.74 PVC/XLPE 240.00 8x1C 70.00 3 400 400

Subject : MCC-E4

FROM S/S

received received Breaker


ratio load Current CABLE
FROM TO M Total
SIZE
(%) (VA) (A) Cable P AF AT
Type MM2 Structure GIV

MCC-E4 FP-01 ### 100 206250 313.74 PVC/XLPE 240.00 4x1C 50.00 3 400 400

Subject : MCC-E5

FROM S/S

received received Breaker


ratio load Current CABLE
FROM TO M Total
SIZE
(%) (VA) (A) Cable P AF AT
Type MM2 Structure GIV

MCC-E5 FP-03 ### 100 112500 171.13 PVC/XLPE 120.00 4x1C 50.00 3 250 250
MCC-E5 FP-03 ### 100 112500 171.13 PVC/XLPE 120.00 4x1C 50.00 3 250 250

Subject : MCC-E6
FROM S/S

received received Breaker


ratio load Current CABLE
FROM TO M Total
SIZE
(%) (VA) (A) Cable
P AF AT
Type MM2 Structure GIV

MCC-E6 FP-04 13.750 100 13750 20.92 PVC/XLPE 10.00 4x1C 50.00 3 50 50
MCC-E6 FP-05 9.375 100 9375 14.26 PVC/XLPE 10.00 4x1C 50.00 3 50 40

Subject : MCC-E7

FROM S/S

received received Breaker


ratio load Current CABLE
FROM TO M Total
SIZE
(%) (VA) (A) Cable P AF AT
Type MM2 Structure GIV

MCC-E7 FP-06 6.875 100 6875 10.46 PVC/XLPE 10.00 4x1C 50.00 3 50 30
MCC-E7 FP-07 22.500 100 22500 34.23 PVC/XLPE 10.00 4x1C 50.00 3 100 70
MCC-E7 FP-07 22.500 100 22500 34.23 PVC/XLPE 10.00 4x1C 50.00 3 100 70
MCC-E7 FP-08 6.875 100 6875 10.46 PVC/XLPE 10.00 4x1C 50.00 3 50 30

Subject : MCC-E8

FROM S/S
received received Breaker
ratio load Current CABLE
FROM TO M Total
SIZE
(%) (VA) (A) Cable P AF AT
Type MM2 Structure GIV

MCC-E8 FP-09 128.75 100 128750 195.85 PVC/XLPE 150.0 4x1C 6 3 250 250

Subject : MCC-E9

FROM S/S

received received Breaker


ratio load Current CABLE
FROM TO M Total
SIZE
(%) (VA) (A) Cable P AF AT
Type MM2 Structure GIV

MCC-E9 FP-09 128.75 100 128750 195.85 PVC/XLPE 150.0 4x1C 50 3 250 250

Subject : MCC-E10

FROM S/S

received received Breaker


ratio load Current CABLE
FROM TO M Total
SIZE
(%) (VA) (A) Cable P AF AT
Type MM2 Structure GIV

MCC-E10 SEF-01 9.30 100 9300 14.15 PVC/XLPE 10.0 4x1C 16 3 50 50


MCC-E10 SEF-02 6.80 100 6800 10.34 PVC/XLPE 10.0 4x1C 16 3 50 50
MCC-E10 SEF-03 4.60 100 4600 7.00 PVC/XLPE 6.0 4x1C 16 3 50 32
MCC-E10 SEF-04 4.60 100 4600 7.00 PVC/XLPE 6.0 4x1C 16 3 50 32
MCC-E10 EEF-01 4.60 100 4600 7.00 PVC/XLPE 6.0 4x1C 16 3 50 32
MCC-E10 EEF-02 4.60 100 4600 7.00 PVC/XLPE 6.0 4x1C 16 3 50 32
MCC-E10 EEF-03 1.80 100 1800 2.74 PVC/XLPE 6.0 4x1C 16 3 50 20
MCC-E10 EEF-04 1.80 100 1800 2.74 PVC/XLPE 6.0 4x1C 16 3 50 20

Subject : MCC-N1

FROM S/S

received received Breaker


ratio load Current CABLE
FROM TO M Total
SIZE
(%) (VA) (A) Cable P AF AT
Type MM2 Structure GIV

MCC-N1 P-1 43.50 100.00 43.50 66.17 PVC/XLPE 35.0 4x1C 16 3 100 100
MCC-N1 P-1 43.50 100.00 43.50 66.17 PVC/XLPE 35.0 4x1C 16 3 100 100
MCC-N1 P-1 43.50 100.00 43.50 66.17 PVC/XLPE 35.0 4x1C 16 3 100 100
MCC-N1 P-1 43.50 100.00 43.50 66.17 PVC/XLPE 35.0 4x1C 16 3 100 100
MCC-N1 P-3 3.50 100.00 3.50 5.32 PVC/XLPE 10.0 1x4C 6 3 50 20
MCC-N1 P-4 13.00 100.00 13.00 19.77 PVC/XLPE 10.0 1x4C 6 3 50 50

Subject : MCC-N2

FROM S/S
received received Breaker
ratio load Current CABLE
FROM TO M Total
SIZE
(%) (VA) (A) Cable P AF AT
Type MM2 Structure GIV

MCC-N2 P-2 25.88 100.00 25.88 39.37 PVC/XLPE 10.0 4x1C 16 3 100 50
MCC-N2 P-2 25.88 100.00 25.88 39.37 PVC/XLPE 10.0 4x1C 16 3 100 50
MCC-N2 P-2 25.88 100.00 25.88 39.37 PVC/XLPE 10.0 4x1C 16 3 100 50
MCC-N2 P-2 25.88 100.00 25.88 39.37 PVC/XLPE 10.0 4x1C 16 3 100 50
MCC-N2 P-5 52.90 100.00 52.90 80.47 PVC/XLPE 35.0 4x1C 16 3 100 100

Subject : MCC-N3

FROM S/S

received received Breaker


ratio load Current CABLE
FROM TO M Total
SIZE
(%) (VA) (A) Cable P AF AT
Type MM2 Structure GIV

MCC-N3 P-6 5.20 100 5200 7.91 PVC/XLPE 10.0 1x4C 6.00 3 50 40
MCC-N3 P-7 52.90 100 52900 80.47 PVC/XLPE 150.00 4x1C 50.00 3 160 125
MCC-N3 P-7 52.90 100 52900 80.47 PVC/XLPE 150.00 4x1C 50.00 3 160 125
MCC-N3 P-8 2.70 100 2700 4.11 PVC/XLPE 10.0 1x4C 6.00 3 50 20
MCC-N3 P-8 2.70 100 2700 4.11 PVC/XLPE 10.0 1x4C 6.00 3 50 20
MCC-N3 P-9 2.70 100 2700 4.11 PVC/XLPE 10.0 1x4C 6.00 3 50 20
MCC-N3 P-10 1.80 100 1800 2.74 PVC/XLPE 10.0 1x4C 6.00 3 50 20
MCC-N3 P-10 1.80 100 1800 2.74 PVC/XLPE 10.0 1x4C 6.00 3 50 20
MCC-N3 P-11 2.70 100 2700 4.11 PVC/XLPE 10.0 1x4C 6.00 3 50 20
MCC-N3 P-11 2.70 100 2700 4.11 PVC/XLPE 10.0 1x4C 6.00 3 50 20
MCC-N3 P-12 1.80 100 1800 2.74 PVC/XLPE 10.0 1x4C 6.00 3 50 20
MCC-N3 P-13 1.80 100 1800 2.74 PVC/XLPE 10.0 1x4C 6.00 3 50 20

Subject : MCC-N4

FROM S/S

received received Breaker


ratio load Current CABLE
FROM TO M Total
SIZE
Cable
(%) (VA) (A) Type MM2 Structure GIV P AF AT

MCC-N4 SF-1 4.60 100 4600 7.00 PVC/XLPE 6.0 1x4C 6.00 3 50 30
MCC-N4 SF-1 4.60 100 4600 7.00 PVC/XLPE 6.0 1x4C 6.00 3 50 30
MCC-N4 SF-2 4.60 100 4600 7.00 PVC/XLPE 6.0 1x4C 6.00 3 50 30
MCC-N4 SF-2 4.60 100 4600 7.00 PVC/XLPE 6.0 1x4C 6.00 3 50 30
MCC-N4 SF-3 4.60 100 4600 7.00 PVC/XLPE 6.0 1x4C 6.00 3 50 30
MCC-N4 SF-3 4.60 100 4600 7.00 PVC/XLPE 6.0 1x4C 6.00 3 50 30
MCC-N4 SF-3 4.60 100 4600 7.00 PVC/XLPE 6.0 1x4C 6.00 3 50 30
MCC-N4 SF-3 4.60 100 4600 7.00 PVC/XLPE 6.0 1x4C 6.00 3 50 30
MCC-N4 SF-4 6.80 100 6800 10.34 PVC/XLPE 6.0 1x4C 6.00 3 50 40
MCC-N4 SF-5 4.60 100 4600 7.00 PVC/XLPE 6.0 1x4C 6.00 3 50 30
MCC-N4 SF-6 18.70 100 18700 28.45 PVC/XLPE 6.0 1x4C 6.00 3 50 50
MCC-N4 EF-12 0.50 100 500 0.76 PVC/XLPE 6.0 1x4C 6.00 3 50 20
MCC-N4 EF-1 9.30 100 9300 14.15 PVC/XLPE 6.0 1x4C 6.00 3 50 50

Subject : MCC-N5

FROM S/S

received received Breaker


ratio load Current CABLE
FROM TO M Total
SIZE
(%) (VA) (A) Cable P AF AT
Type MM2 Structure GIV

MCC-N5 SF-5 6.80 100 6800 10.34 PVC/XLPE 10.0 1x4C 6.00 3 50 40
MCC-N5 EF-7 4.60 100 4600 7.00 PVC/XLPE 10.0 1x4C 6.00 3 50 30
MCC-N5 EF-13 6.80 100 6800 10.34 PVC/XLPE 10.0 1x4C 6.00 3 50 40
MCC-N5 EF-13 6.80 100 6800 10.34 PVC/XLPE 10.0 1x4C 6.00 3 50 40
MCC-N5 EF-14 9.30 100 9300 14.15 PVC/XLPE 10.0 1x4C 6.00 3 50 50
MCC-N5 EF-14 9.30 100 9300 14.15 PVC/XLPE 10.0 1x4C 6.00 3 50 50
MCC-N5 EF-15 23.00 100 23000 34.99 PVC/XLPE 35.0 4x1C 16 3 100 50
MCC-N5 EF-15 23.00 100 23000 34.99 PVC/XLPE 35.0 4x1C 16 3 100 50
MCC-N5 EF-16 0.90 100 900 1.37 PVC/XLPE 6.0 1x4C 6.00 3 50 20

Subject : MCP-B1,B2-1

FROM S/S
received received Breaker
ratio load Current CABLE
FROM TO M Total
SIZE
(%) (VA) (A) Cable P AF AT
Type MM2 Structure GIV

MCB-B1,B2-2
MCB-B1,B2-2 7.67 100 7666.67 11.66 PVC/XLPE 6.0 1x4C 6.00 3 50 30
MCB-B1,B2-2
MCB-B1,B2-3 15.67 100 15667 23.83 PVC/XLPE 10.0 1x4C 6.00 3 50 50
MCB-B1,B2-2 SF-02 7.67 100 7666.67 11.66 PVC/XLPE 6.0 1x4C 6.00 3 50 30
MCB-B1,B2-2 AIR-02 1.67 100 1666.67 2.54 PVC/XLPE 6.0 1x4C 6.00 3 50 20
MCB-B1,B2-2 AHU-01 14.67 100 14667 22.31 PVC/XLPE 10.0 1x4C 6.00 3 50 50
MCB-B1,B2-2 OHU-01 31.25 100 31250 47.54 PVC/XLPE 10.0 1x4C 6.00 3 50 50

Subject : MCP-B1,B2-2

FROM S/S

received received Breaker


ratio load Current CABLE
FROM TO M Total
SIZE
(%) (VA) (A) Cable P AF AT
Type MM2 Structure GIV

MCP-B1,B2-2 SF-02 4.60 100 4600 7.00 PVC/XLPE 6.0 1x4C 4.00 3 100 20

Subject : MCP-B1,B2-3

FROM S/S
received received Breaker
ratio load Current CABLE
FROM TO M Total
SIZE
(%) (VA) (A) Cable P AF AT
Type MM2 Structure GIV

MCP-B1,B2-3 SF-02 4.60 100 4600 7.00 PVC/XLPE 6.0 1x4C 4.00 3 50 40

Subject : MCP-1

FROM S/S

received received Breaker


ratio load Current CABLE
FROM TO M Total
SIZE
(%) (VA) (A) Cable P AF AT
Type MM2 Structure GIV

MCP-1 AHU-02 32.50 100 32500 49.44 PVC/XLPE 35.0 4x1C 16 3 100 100
MCP-1 OHU-02 6.88 100 6880 10.47 PVC/XLPE 35.0 4x1C 16 3 100 50
MCP-1 EF9 0.08 100 80 0.36 PVC/XLPE 4.0 1x2C 2.5 1 30 10
MCP-1 EF10 0.08 100 80 0.36 PVC/XLPE 4.0 1x2C 2.5 1 30 10
MCP-1 FCU2 5.76 100 5760 26.18 PVC/XLPE 4.0 1x2C 2.5 1 30 10

Subject : MCP-2
FROM S/S

received received Breaker


ratio load Current CABLE
FROM TO M Total
FROM TO M Total
SIZE
(%) (VA) (A) Cable P AF AT
Type MM2 Structure GIV

MCP-2 AHU-03 23.13 100 23125 35.18 PVC/XLPE 10.0 1x4C 6.00 3 100 50
MCP-2 AHU-05 28.13 100 28125 42.78 PVC/XLPE 35.0 4x1C 16 3 100 100
MCP-2 EF9 0.08 100 75 0.11 Cu/PVC 4.0 1x2C 2.5 1 30 10
MCP-2 EF10 0.08 100 82.5 0.13 Cu/PVC 4.0 1x2C 2.5 1 30 10

Subject : MCP-3

FROM S/S

received received Breaker


ratio load Current CABLE
FROM TO M Total SIZE
(%) (VA) (A) Cable P AF AT
Type MM2 Structure GIV
MCP-3 AHU-04 41.25 100 41250 62.75 PVC/XLPE 35.0 1x4C 6.00 3 100 100

MCP-3 AHU-06 28.13 100 28125 42.78 PVC/XLPE 25.0 4x1C 16 3 100 80
MCP-3 OHU-03 4.63 100 4625 7.04 PVC/XLPE 6.0 4x1C 16 3 50 40
MCP-3 FCU1 11.16 100 11162.5 16.98 PVC/XLPE 6.0 4x1C 16 3 50 40

Subject : MCP-4

FROM S/S
received received Breaker
ratio load Current CABLE
FROM TO M Total
SIZE
(%) (VA) (A) Cable P AF AT
Type MM2 Structure GIV

MCP-4 OUTDOOR 28.09 100 28087.5 42.73 PVC/XLPE 25.0 1x4C 6.00 3 100 80
MCP-4 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-4 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-4 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-4 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-4 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-4 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-4 IDU-3 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-4 IDU-3 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-4 EF9 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-4 EF9 0.61 100 612.5 2.78 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-4 EF12 0.61 100 612.5 2.78 Cu/PVC 4.0 1x2C 2.50 1 30 10

Subject : MCP-5

FROM S/S

received received Breaker


ratio load Current CABLE
FROM TO M Total
SIZE

Type
FROM TO M Total

(%) (VA) (A) Cable P AF AT


Type MM2 Structure GIV

MCP-5 OUTDOOR 56.38 100 56375 85.75 PVC/XLPE 70.0 1x4C 6.00 3 160 160
MCP-5 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x4C 2.50 1 30 10
MCP-5 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x4C 2.50 1 30 10
MCP-5 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x4C 2.50 1 30 10
MCP-5 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x4C 2.50 1 30 10
MCP-5 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x4C 2.50 1 30 10
MCP-5 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x4C 2.50 1 30 10
MCP-5 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x4C 2.50 1 30 10
MCP-5 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x4C 2.50 1 30 10
MCP-5 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x4C 2.50 1 30 10
MCP-5 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x4C 2.50 1 30 10
MCP-5 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x4C 2.50 1 30 10
MCP-5 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x4C 2.50 1 30 10
MCP-5 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x4C 2.50 1 30 10
MCP-5 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x4C 2.50 1 30 10
MCP-5 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x4C 2.50 1 30 10
MCP-5 IDU-2 0.20 100 200 0.91 Cu/PVC 4.0 1x4C 2.50 1 30 10
MCP-5 HVU-3 0.61 100 612.5 2.78 Cu/PVC 4.0 1x4C 2.50 1 30 10
MCP-5 HVU-3 0.61 100 612.5 2.78 Cu/PVC 4.0 1x4C 2.50 1 30 10
MCP-5 HVU-3 0.61 100 612.5 2.78 Cu/PVC 4.0 1x4C 2.50 1 30 10
MCP-5 HVU-3 0.61 100 612.5 2.78 Cu/PVC 4.0 1x4C 2.50 1 30 10
MCP-5 HVU-2 0.28 100 281.3 1.28 Cu/PVC 4.0 1x4C 2.50 1 30 10
MCP-5 HVU-2 0.28 100 281.3 1.28 Cu/PVC 4.0 1x4C 2.50 1 30 10
MCP-5 HVU-1 0.13 100 133 0.60 Cu/PVC 4.0 1x4C 2.50 1 30 10

Subject : MCP-6

FROM S/S

received received Breaker


ratio load Current CABLE
FROM TO M Total
SIZE
(%) (VA) (A) Cable P AF AT
Type MM2 Structure GIV

MCP-6 OUTDOOR 23.44 100 23437.5 35.65 PVC/XLPE 10.0 1x4C 6.00 3 100 50
MCP-6 OUTDOOR 25.99 100 25987.5 39.53 PVC/XLPE 10.0 1x4C 6.00 3 100 50
MCP-6 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x4C 2.50 1 30 10
MCP-6 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x4C 2.50 1 30 10
MCP-6 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x4C 2.50 1 30 10
MCP-6 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x4C 2.50 1 30 10
MCP-6 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x4C 2.50 1 30 10
MCP-6 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x4C 2.50 1 30 10
MCP-6 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x4C 2.50 1 30 10
MCP-6 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x4C 2.50 1 30 10
MCP-6 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x4C 2.50 1 30 10
MCP-6 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x4C 2.50 1 30 10
MCP-6 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x4C 2.50 1 30 10
MCP-6 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x4C 2.50 1 30 10
MCP-6 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x4C 2.50 1 30 10
MCP-6 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x4C 2.50 1 30 10
MCP-6 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x4C 2.50 1 30 10
MCP-6 IDU-2 0.20 100 200 0.91 Cu/PVC 4.0 1x4C 2.50 1 30 10
MCP-6 HVU-3 0.61 100 612.5 2.78 Cu/PVC 4.0 1x4C 2.50 1 30 10
MCP-6 HVU-3 0.61 100 612.5 2.78 Cu/PVC 4.0 1x4C 2.50 1 30 10
MCP-6 HVU-3 0.61 100 612.5 2.78 Cu/PVC 4.0 1x4C 2.50 1 30 10
MCP-6 HVU-2 0.28 100 281.3 1.28 Cu/PVC 4.0 1x4C 2.50 1 30 10
MCP-6 HVU-2 0.28 100 281.3 1.28 Cu/PVC 4.0 1x4C 2.50 1 30 10
MCP-6 HVU-2 0.28 100 281.3 1.28 Cu/PVC 4.0 1x4C 2.50 1 30 10
MCP-6 HVU-1 0.13 100 133 0.60 Cu/PVC 4.0 1x4C 2.50 1 30 10

Subject : MCP-7

FROM S/S

received received Breaker


ratio load Current CABLE
FROM TO M Total
SIZE
(%) (VA) (A) Cable P AF AT
Type MM2 Structure GIV

MCP-7 OUTDOOR 36.25 100 36250 55.14 PVC/XLPE 50.0 1x4C 6.00 3 160 125
MCP-7 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-7 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-7 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-7 IDU-5 0.38 100 375 1.70 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-7 IDU-5 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-7 IDU-5 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-7 IDU-5 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-7 IDU-5 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-7 IDU-5 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-7 IDU-5 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-7 IDU-5 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-7 IDU-5 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-7 IDU-4 0.06 100 62.5 0.28 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-7 IDU-3 0.61 100 612.5 2.78 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-7 IDU-3 0.61 100 612.5 2.78 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-7 HVU-3 0.61 100 612.5 2.78 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-7 HVU-3 0.28 100 281.3 1.28 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-7 HVU-3 0.28 100 281.3 1.28 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-7 HVU-2 0.28 100 281.3 1.28 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-7 HVU-2 0.13 100 133 0.60 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-7 HVU-2 0.13 100 133 0.60 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-7 HVU-1 0.13 100 133 0.60 Cu/PVC 4.0 1x2C 2.50 1 30 10

Subject : MCP-8

FROM S/S
received received Breaker
ratio load Current CABLE
FROM TO M Total
SIZE
(%) (VA) (A) Cable P AF AT
Type MM2 Structure GIV

MCP-8 OUTDOOR 23.44 100 23437.5 35.65 PVC/XLPE 10.0 1x4C 6.00 3 100 50
MCP-8 OUTDOOR 38.35 100 38350 58.34 Cu/PVC 35.0 1x4C 2.50 3 100 100
MCP-8 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-8 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-8 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-8 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-8 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-8 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-8 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-8 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-8 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-8 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-8 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-8 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-8 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-8 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-8 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-8 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-8 HVU-3 0.61 100 612.5 2.78 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-8 HVU-3 0.61 100 612.5 2.78 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-8 HVU-3 0.61 100 612.5 2.78 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-8 HVU-2 0.28 100 281.3 1.28 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-8 HVU-2 0.28 100 281.3 1.28 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-8 HVU-2 0.28 100 281.3 1.28 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-8 HVU-1 0.13 100 133.75 0.61 Cu/PVC 4.0 1x2C 2.50 1 30 10

Subject : MCP-9

FROM S/S

received received Breaker


ratio load Current CABLE
FROM TO M Total
SIZE
(%) (VA) (A) Cable P AF AT
Type MM2 Structure GIV

MCP-9 OUTDOOR 26.21 100 26212.5 39.87 PVC/XLPE 16.0 1x4C 6.00 3 100 60
MCP-9 OUTDOOR 34.61 100 34612.5 52.65 Cu/PVC 25.0 1x2C 2.50 3 100 80
MCP-9 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-9 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-9 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-9 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-9 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-9 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-9 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-9 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-9 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-9 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-9 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-9 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-9 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-9 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-9 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-9 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-9 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-9 HVU-3 0.61 100 612.5 2.78 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-9 HVU-3 0.61 100 612.5 2.78 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-9 HVU-3 0.61 100 612.5 2.78 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-9 HVU-2 0.28 100 281.3 1.28 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-9 HVU-2 0.28 100 281.3 1.28 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-9 HVU-1 0.13 100 133 0.60 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-9 HVU-1 0.13 100 133 0.60 Cu/PVC 4.0 1x2C 2.50 1 30 10

Subject : MCP-10

FROM S/S

received received Breaker


ratio load Current CABLE
FROM TO M Total
SIZE
(%) (VA) (A) Cable P AF AT
Type MM2 Structure GIV
MCP-10 OUTDOOR 41.66 100 41662.5 63.37 PVC/XLPE 35.0 1x4C 6.00 3 100 100
MCP-10 OUTDOOR 28.09 100 28087.5 42.73 PVC/XLPE 25.0 1x4C 6.00 3 100 80
MCP-10 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-10 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-10 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-10 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-10 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-10 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-10 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-10 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-10 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-10 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-10 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-10 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-10 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-10 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-10 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-10 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-10 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-10 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-10 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-10 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-10 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-10 HVU-3 0.61 100 612.5 2.78 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-10 HVU-3 0.61 100 612.5 2.78 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-10 HVU-2 0.28 100 281.3 1.28 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-10 HVU-2 0.28 100 281.3 1.28 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-10 HVU-2 0.28 100 281.3 1.28 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-10 HVU-1 0.13 100 133 0.60 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-10 HVU-1 0.13 100 133 0.60 Cu/PVC 4.0 1x2C 2.50 1 30 10

Subject : MCP-11

FROM S/S

received received Breaker


ratio load Current CABLE
FROM TO M Total
SIZE
(%) (VA) (A) Cable P AF AT
Type MM2 Structure GIV

OUTDOOR OUTDOOR 26.21 100 26212.5 39.87 PVC/XLPE 16.0 1x4C 6.00 3 100 60
OUTDOOR OUTDOOR 34.61 100 34612.5 52.65 Cu/PVC 25.0 1x2C 2.50 3 100 80
IDU-5 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
IDU-5 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
IDU-5 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
IDU-5 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
IDU-5 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
IDU-5 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
IDU-5 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
IDU-5 IDU-4 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
IDU-4 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x2C 2.50 1 30 10
IDU-4 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x2C 2.50 1 30 10
IDU-3 IDU-4 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
IDU-3 IDU-4 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
IDU-3 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
IDU-3 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
IDU-3 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
IDU-3 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
IDU-3 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
IDU-3 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
HVU-3 IDU-3 0.61 100 612.5 2.78 Cu/PVC 4.0 1x2C 2.50 1 30 10
HVU-3 IDU-3 0.61 100 612.5 2.78 Cu/PVC 4.0 1x2C 2.50 1 30 10
HVU-3 IDU-3 0.61 100 612.5 2.78 Cu/PVC 4.0 1x2C 2.50 1 30 10
HVU-2 HVU-3 0.28 100 281.3 1.28 Cu/PVC 4.0 1x2C 2.50 1 30 10
HVU-2 HVU-3 0.28 100 281.3 1.28 Cu/PVC 4.0 1x2C 2.50 1 30 10
HVU-1 HVU-2 0.13 100 133 0.60 Cu/PVC 4.0 1x2C 2.50 1 30 10
HVU-1 HVU-2 0.13 100 133 0.60 Cu/PVC 4.0 1x2C 2.50 1 30 10

Subject : MCP-12

FROM S/S

received received Breaker


ratio load Current CABLE
FROM TO M Total
FROM TO M Total
SIZE
(%) (VA) (A) Cable P AF AT
Type MM2 Structure GIV

MCP-12 OUTDOOR 41.66 100 41662.5 63.37 PVC/XLPE 35.0 1x4C 6.00 3 100 100
MCP-12 OUTDOOR 28.09 100 28087.5 42.73 Cu/PVC 25.0 1x2C 2.50 3 100 80
MCP-12 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-12 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-12 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-12 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-12 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-12 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-12 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-12 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-12 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-12 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-12 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-12 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-12 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-12 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-12 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-12 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-12 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-12 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-12 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-12 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-12 HVU-3 0.61 100 612.5 2.78 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-12 HVU-3 0.61 100 612.5 2.78 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-12 HVU-2 0.28 100 281.3 1.28 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-12 HVU-2 0.28 100 281.3 1.28 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-12 HVU-2 0.28 100 281.3 1.28 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-12 HVU-1 0.13 100 133 0.60 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-12 HVU-1 0.13 100 133 0.60 Cu/PVC 4.0 1x2C 2.50 1 30 10

Subject : MCP-13

FROM S/S

received received Breaker


ratio load Current CABLE
FROM TO M Total
SIZE
(%) (VA) (A) Cable P AF AT
Type MM2 Structure GIV

MCP-13 OUTDOOR 37.73 100 37725 57.39 PVC/XLPE 35.0 1x4C 6.00 3 100 100
MCP-13 OUTDOOR 31.34 100 31337.5 47.67 Cu/PVC 25.0 1x2C 2.50 3 100 80
MCP-13 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-13 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-13 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-13 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-13 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-13 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-13 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-13 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-13 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-13 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-13 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-13 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-13 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-13 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-13 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-13 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-13 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-13 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-13 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-13 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-13 HVU-3 0.61 100 612.5 2.78 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-13 HVU-3 0.61 100 612.5 2.78 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-13 HVU-3 0.61 100 612.5 2.78 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-13 HVU-2 0.28 100 281.3 1.28 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-13 HVU-2 0.28 100 281.3 1.28 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-13 HVU-2 0.28 100 281.3 1.28 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-13 HVU-2 0.13 100 133 0.60 Cu/PVC 4.0 1x2C 2.50 1 30 10
Subject : MCP-14

FROM S/S

received received Breaker


ratio load Current CABLE
FROM TO M Total
SIZE
(%) (VA) (A) Cable P AF AT
Type MM2 Structure GIV

MCP-14 OUTDOOR 37.73 100 37725 57.39 PVC/XLPE 35.0 1x4C 6.00 3 100 100
MCP-14 OUTDOOR 34.61 100 34612.5 52.65 PVC/XLPE 35.0 1x4C 6.00 3 100 100
MCP-14 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-14 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-14 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-14 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-14 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-14 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-14 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-14 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-14 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-14 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-14 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-14 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-14 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-14 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-14 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-14 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-14 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-14 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-14 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-14 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-14 HVU-3 0.61 100 612.5 2.78 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-14 HVU-3 0.61 100 612.5 2.78 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-14 HVU-2 0.28 100 281.3 1.28 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-14 HVU-2 0.28 100 281.3 1.28 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-14 HVU-2 0.28 100 281.3 1.28 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-14 HVU-2 0.28 100 281.3 1.28 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-14 HVU-1 0.13 100 133 0.60 Cu/PVC 4.0 1x2C 2.50 1 30 10

Subject : MCP-15

FROM S/S
Current CABLE Breaker

received received
FROM TO M Total ratio load SIZE
(%) (VA) (A) Cable P AF AT
Type MM2 Structure GIV

MCP-15 OUTDOOR 37.73 100 37725 57.39 PVC/XLPE 35.0 1x4C 6.00 3 100 100
MCP-15 OUTDOOR 34.61 100 34612.5 52.65 Cu/PVC 35.0 1x2C 2.50 3 100 100
MCP-15 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-15 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-15 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-15 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-15 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-15 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-15 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-15 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-15 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-15 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-15 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-15 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-15 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-15 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-15 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-15 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-15 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-15 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-15 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-15 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-15 HVU-3 0.61 100 612.5 2.78 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-15 HVU-3 0.61 100 612.5 2.78 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-15 HVU-3 0.61 100 612.5 2.78 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-15 HVU-2 0.28 100 281.3 1.28 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-15 HVU-2 0.28 100 281.3 1.28 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-15 HVU-1 0.13 100 133 0.60 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-15 HVU-1 0.13 100 133 0.60 Cu/PVC 4.0 1x2C 2.50 1 30 10

Subject : MCP-16

FROM S/S

received received Breaker


ratio load Current CABLE
FROM TO M Total
SIZE
(%) (VA) (A) Cable P AF AT
Type MM2 Structure GIV

MCP-16 OUTDOOR 37.73 100 37725 57.39 PVC/XLPE 35.0 1x4C 6.00 3 100 100
MCP-16 OUTDOOR 34.61 100 34612.5 52.65 PVC/XLPE 35.0 1x4C 6.00 3 100 100
MCP-16 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-16 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-16 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-16 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-16 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-16 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-16 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-16 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-16 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-16 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-16 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-16 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-16 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-16 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-16 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-16 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-16 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-16 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-16 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-16 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-16 HVU-3 0.61 100 612.5 2.78 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-16 HVU-3 0.61 100 612.5 2.78 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-16 HVU-3 0.61 100 612.5 2.78 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-16 HVU-2 0.28 100 281.3 1.28 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-16 HVU-2 0.28 100 281.3 1.28 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-16 HVU-2 0.28 100 281.3 1.28 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-16 HVU-1 0.13 100 133 0.60 Cu/PVC 4.0 1x2C 2.50 1 30 10

Subject : MCP-17

FROM S/S

received received Breaker


ratio load Current CABLE
FROM TO M Total
SIZE
(%) (VA) (A) Cable P AF AT
Type MM2 Structure GIV

MCP-17 OUTDOOR 31.34 100 31337.5 47.67 PVC/XLPE 25.0 1x4C 6.00 3 100 80
MCP-17 OUTDOOR 34.61 100 34612.5 52.65 PVC/XLPE 35.0 1x2C 2.50 3 100 100
MCP-17 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-17 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-17 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-17 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-17 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-17 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-17 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-17 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-17 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-17 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-17 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-17 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-17 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-17 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-17 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-17 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-17 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-17 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-17 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-17 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-17 HVU-3 0.61 100 612.5 2.78 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-17 HVU-3 0.61 100 612.5 2.78 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-17 HVU-3 0.61 100 612.5 2.78 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-17 HVU-3 0.61 100 612.5 2.78 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-17 HVU-2 0.28 100 281.3 1.28 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-17 HVU-2 0.28 100 281.3 1.28 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-17 HVU-1 0.13 100 133 0.60 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-17 HVU-1 0.13 100 133 0.60 Cu/PVC 4.0 1x2C 2.50 1 30 10

Subject : MCP-18

FROM S/S

received received Breaker


ratio load Current CABLE
FROM TO M Total
SIZE
(%) (VA) (A) Cable P AF AT
Type MM2 Structure GIV

MCP-18 OUTDOOR 37.73 100 37725 57.39 PVC/XLPE 35.0 1x4C 6.00 3 100 100
MCP-18 OUTDOOR 34.61 100 34612.5 52.65 PVC/XLPE 35.0 1x4C 6.00 3 100 100
MCP-18 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-18 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-18 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-18 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-18 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-18 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-18 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-18 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-18 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-18 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-18 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-18 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-18 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-18 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-18 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-18 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-18 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-18 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-18 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-18 HVU-3 0.61 100 612.5 2.78 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-18 HVU-3 0.61 100 612.5 2.78 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-18 HVU-3 0.61 100 612.5 2.78 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-18 HVU-2 0.28 100 281.3 1.28 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-18 HVU-2 0.28 100 281.3 1.28 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-18 HVU-1 0.13 100 133 0.60 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-18 HVU-1 0.13 100 133 0.60 Cu/PVC 4.0 1x2C 2.50 1 30 10

Subject : MCP-19

FROM S/S

received received Breaker


ratio load Current CABLE
FROM TO M Total
FROM TO M Total
SIZE
(%) (VA) (A) Cable P AF AT
Type MM2 Structure GIV

MCP-19 OUTDOOR 28.09 100 28087.5 42.73 PVC/XLPE 25.0 1x4C 6.00 3 100 80
MCP-19 OUTDOOR 37.73 100 37725 57.39 Cu/PVC 35.0 1x2C 2.50 3 100 100
MCP-19 IDU-5 0.43 100 425 0.65 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-19 IDU-5 0.43 100 425 0.65 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-19 IDU-5 0.43 100 425 0.65 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-19 IDU-5 0.43 100 425 0.65 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-19 IDU-5 0.43 100 425 0.65 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-19 IDU-5 0.43 100 425 0.65 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-19 IDU-4 0.38 100 375 0.57 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-19 IDU-4 0.38 100 375 0.57 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-19 IDU-4 0.38 100 375 0.57 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-19 IDU-4 0.38 100 375 0.57 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-19 IDU-4 0.38 100 375 0.57 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-19 IDU-3 0.23 100 225 0.34 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-19 IDU-3 0.23 100 225 0.34 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-19 IDU-3 0.23 100 225 0.34 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-19 IDU-3 0.23 100 225 0.34 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-19 IDU-3 0.23 100 225 0.34 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-19 IDU-3 0.23 100 225 0.34 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-19 IDU-3 0.23 100 225 0.34 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-19 IDU-3 0.23 100 225 0.34 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-19 IDU-3 0.23 100 225 0.34 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-19 HVU-3 0.61 100 612.5 0.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-19 HVU-3 0.61 100 612.5 0.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-19 HVU-3 0.61 100 612.5 0.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-19 HVU-2 0.28 100 281.3 0.43 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-19 HVU-2 0.28 100 281.3 0.43 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-19 HVU-2 0.28 100 281.3 0.43 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-19 HVU-1 0.13 100 133 0.20 Cu/PVC 4.0 1x2C 2.50 1 30 10

Subject : MCP-20

FROM S/S

received received Breaker


ratio load Current CABLE
FROM TO M Total
SIZE
(%) (VA) (A) Cable P AF AT
Type MM2 Structure GIV

MCP-20 OUTDOOR 31.34 100 31337.5 47.67 PVC/XLPE 25.0 1x4C 6.00 3 100 80
MCP-20 OUTDOOR 37.73 100 37725 57.39 PVC/XLPE 35.0 1x4C 6.00 3 100 100
MCP-20 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-20 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-20 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-20 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-20 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-20 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-20 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-20 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-20 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-20 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-20 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-20 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-20 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-20 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-20 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-20 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-20 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-20 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-20 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-20 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-20 HVU-3 0.61 100 612.5 2.78 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-20 HVU-3 0.61 100 612.5 2.78 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-20 HVU-3 0.61 100 612.5 2.78 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-20 HVU-2 0.28 100 281.3 1.28 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-20 HVU-2 0.28 100 281.3 1.28 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-20 HVU-2 0.28 100 281.3 1.28 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-20 HVU-1 0.13 100 133 0.60 Cu/PVC 4.0 1x2C 2.50 1 30 10
Subject : MCP-21

FROM S/S

received received Breaker


ratio load Current CABLE
FROM TO M Total
SIZE
(%) (VA) (A) Cable P AF AT
Type MM2 Structure GIV

MCP-21 OUTDOOR 31.34 100 31337.5 47.67 PVC/XLPE 25.0 1x4C 6 3 100 80
MCP-21 OUTDOOR 37.73 100 37725 57.39 Cu/PVC 35.0 1x2C 2.5 3 100 100
MCP-21 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.5 1 30 10
MCP-21 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.5 1 30 10
MCP-21 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.5 1 30 10
MCP-21 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.5 1 30 10
MCP-21 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.5 1 30 10
MCP-21 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x2C 2.5 1 30 10
MCP-21 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x2C 2.5 1 30 10
MCP-21 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x2C 2.5 1 30 10
MCP-21 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x2C 2.5 1 30 10
MCP-21 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.5 1 30 10
MCP-21 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.5 1 30 10
MCP-21 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.5 1 30 10
MCP-21 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.5 1 30 10
MCP-21 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.5 1 30 10
MCP-21 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.5 1 30 10
MCP-21 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.5 1 30 10
MCP-21 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.5 1 30 10
MCP-21 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.5 1 30 10
MCP-21 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.5 1 30 10
MCP-21 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.5 1 30 10
MCP-21 HVU-3 0.61 100 612.5 2.78 Cu/PVC 4.0 1x2C 2.5 1 30 10
MCP-21 HVU-3 0.61 100 612.5 2.78 Cu/PVC 4.0 1x2C 2.5 1 30 10
MCP-21 HVU-3 0.61 100 612.5 2.78 Cu/PVC 4.0 1x2C 2.5 1 30 10
MCP-21 HVU-2 0.28 100 281.3 1.28 Cu/PVC 4.0 1x2C 2.5 1 30 10
MCP-21 HVU-2 0.28 100 281.3 1.28 Cu/PVC 4.0 1x2C 2.5 1 30 10
MCP-21 HVU-1 0.13 100 133 0.60 Cu/PVC 4.0 1x2C 2.5 1 30 10
MCP-21 HVU-1 0.13 100 133 0.60 Cu/PVC 4.0 1x2C 2.5 1 30 10

Subject : MCP-22

FROM S/S

received received Breaker


ratio load Current CABLE
FROM TO M Total
SIZE
(%) (VA) (A) Cable
P AF AT
Type MM2 Structure GIV

MCP-22 OUTDOOR 31.34 100 31337.5 47.67 PVC/XLPE 25.0 1x4C 6.00 3 100 80
MCP-22 OUTDOOR 37.73 100 37725 57.39 PVC/XLPE 35.0 1x4C 6.00 3 100 100
MCP-22 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-22 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-22 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-22 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-22 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-22 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-22 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-22 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-22 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-22 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-22 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-22 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-22 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-22 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-22 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-22 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-22 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-22 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-22 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-22 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-22 HVU-3 0.61 100 612.5 2.78 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-22 HVU-3 0.61 100 612.5 2.78 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-22 HVU-2 0.28 100 281.3 1.28 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-22 HVU-2 0.28 100 281.3 1.28 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-22 HVU-1 0.13 100 133 0.60 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-22 HVU-1 0.13 100 133 0.60 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-22 HVU-1 0.13 100 133 0.60 Cu/PVC 4.0 1x2C 2.50 1 30 10

Subject : MCP-23

FROM S/S

received received Breaker


ratio load Current CABLE
FROM TO M Total
SIZE
(%) (VA) (A) Cable P AF AT
Type MM2 Structure GIV

MCP-23 OUTDOOR 34.61 100 34612.5 52.65 PVC/XLPE 35.0 1x4C 6.00 3 100 100
MCP-23 OUTDOOR 25.99 100 25987.5 39.53 Cu/PVC 10.0 1x2C 2.50 3 100 50
MCP-23 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-23 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-23 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-23 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-23 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-23 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-23 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-23 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-23 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-23 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-23 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-23 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-23 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-23 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-23 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-23 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-23 HVU-3 0.61 100 612.5 2.78 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-23 HVU-3 0.61 100 612.5 2.78 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-23 HVU-2 0.28 100 281.3 1.28 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-23 HVU-2 0.28 100 281.3 1.28 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-23 HVU-2 0.28 100 281.3 1.28 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-23 HVU-1 0.13 100 133 0.60 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-23 HVU-1 0.13 100 133 0.60 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-23 HVU-1 0.13 100 133 0.60 Cu/PVC 4.0 1x2C 2.50 1 30 10

Subject : MCP-24

FROM S/S

received received Breaker


ratio load Current CABLE
FROM TO M Total
SIZE
(%) (VA) (A) Cable
P AF AT
Type MM2 Structure GIV

MCP-24 OUTDOOR 28.09 100 28087.5 42.73 PVC/XLPE 25.0 1x4C 6.00 3 100 80
MCP-24 OUTDOOR 31.34 100 31337.5 47.67 PVC/XLPE 25.0 1x4C 6.00 3 100 80
MCP-24 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-24 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-24 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-24 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-24 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-24 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-24 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-24 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-24 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-24 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-24 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-24 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-24 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-24 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-24 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-24 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-24 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-24 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-24 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-24 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-24 HVU-3 0.61 100 612.5 2.78 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-24 HVU-3 0.61 100 612.5 2.78 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-24 HVU-3 0.61 100 612.5 2.78 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-24 HVU-2 0.28 100 281.3 1.28 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-24 HVU-2 0.28 100 281.3 1.28 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-24 HVU-1 0.13 100 133 0.60 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-24 HVU-1 0.13 100 133 0.60 Cu/PVC 4.0 1x2C 2.50 1 30 10

Subject : MCP-25
FROM S/S

received received Breaker


ratio load Current CABLE
FROM TO M Total
SIZE
(%) (VA) (A) Cable P AF AT
Type MM2 Structure GIV

MCP-25 OUTDOOR 23.44 100 23437.5 35.65 PVC/XLPE 10.0 1x4C 6.00 3 100 50
MCP-25 OUTDOOR 31.34 100 31337.5 47.67 Cu/PVC 25.0 1x2C 2.50 3 100 80
MCP-25 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-25 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-25 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-25 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-25 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-25 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-25 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-25 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-25 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-25 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-25 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-25 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-25 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-25 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-25 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-25 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-25 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-25 HVU-3 0.61 100 612.5 2.78 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-25 HVU-3 0.61 100 612.5 2.78 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-25 HVU-3 0.61 100 612.5 2.78 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-25 HVU-2 0.28 100 281.3 1.28 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-25 HVU-2 0.28 100 281.3 1.28 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-25 HVU-2 0.28 100 281.3 1.28 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-25 HVU-1 0.13 100 133 0.60 Cu/PVC 4.0 1x2C 2.50 1 30 10

Subject : MCP-26

FROM S/S

received received Breaker


ratio load Current CABLE
FROM TO M Total
SIZE
(%) (VA) (A) Cable
P AF AT
Type MM2 Structure GIV

MCP-26 OUTDOOR 23.44 100 23437.5 35.65 PVC/XLPE 10.0 1x4C 6.00 3 100 50
MCP-26 OUTDOOR 31.34 100 31337.5 47.67 PVC/XLPE 25.0 1x4C 6.00 3 100 80
MCP-26 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-26 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-26 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-26 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-26 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-26 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-26 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-26 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-26 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-26 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-26 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-26 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-26 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-26 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-26 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-26 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-26 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-26 HVU-3 0.61 100 612.5 2.78 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-26 HVU-3 0.61 100 612.5 2.78 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-26 HVU-3 0.61 100 612.5 2.78 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-26 HVU-2 0.28 100 281.3 1.28 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-26 HVU-2 0.28 100 281.3 1.28 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-26 HVU-1 0.13 100 133 0.60 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-26 HVU-1 0.13 100 133 0.60 Cu/PVC 4.0 1x2C 2.50 1 30 10
Subject : MCP-27

FROM S/S

received received Breaker


ratio load Current CABLE
FROM TO M Total
SIZE
(%) (VA) (A) Cable P AF AT
Type MM2 Structure GIV

MCP-27 OUTDOOR 23.44 100 23437.5 35.65 PVC/XLPE 10.0 1x4C 6.00 3 100 50
MCP-27 OUTDOOR 28.09 100 28087.5 127.67 Cu/PVC 25.0 1x2C 2.50 3 100 80
MCP-27 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-27 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-27 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-27 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-27 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-27 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-27 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-27 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-27 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-27 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-27 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-27 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-27 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-27 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-27 HVU-3 0.61 100 612.5 2.78 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-27 HVU-3 0.61 100 612.5 2.78 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-27 HVU-2 0.28 100 281.3 1.28 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-27 HVU-2 0.28 100 281.3 1.28 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-27 HVU-2 0.28 100 281.3 1.28 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-27 HVU-1 0.28 100 281.3 1.28 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-27 HVU-1 0.13 100 133 0.60 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-27 HVU-1 0.13 100 133 0.60 Cu/PVC 4.0 1x2C 2.50 1 30 10

Subject : MCP-28

FROM S/S

received received Breaker


ratio load Current CABLE
FROM TO M Total
SIZE
(%) (VA) (A) Cable P AF AT
Type MM2 Structure GIV

MCP-28 OUTDOOR 23.44 100 23437.5 35.65 PVC/XLPE 10.0 1x4C 6.00 3 100 50
MCP-28 OUTDOOR 28.09 100 28087.5 42.73 PVC/XLPE 25.0 1x4C 6.00 3 100 80
MCP-28 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-28 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-28 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-28 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-28 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-28 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-28 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-28 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-28 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-28 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-28 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-28 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-28 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-28 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-28 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-28 HVU-3 0.61 100 612.5 2.78 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-28 HVU-3 0.61 100 612.5 2.78 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-28 HVU-3 0.61 100 612.5 2.78 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-28 HVU-2 0.28 100 281.3 1.28 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-28 HVU-2 0.28 100 281.3 1.28 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-28 HVU-1 0.28 100 281.3 1.28 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-28 HVU-1 0.13 100 133 0.60 Cu/PVC 4.0 1x2C 2.50 1 30 10

Subject : MCP-29

FROM S/S

received received Breaker


ratio load Current CABLE
FROM TO M Total
SIZE
(%) (VA) (A) Cable P AF AT
Type MM2 Structure GIV

MCP-29 OUTDOOR 23.44 100 23437.5 35.65 PVC/XLPE 10.0 4x1C 16 3 100 50
MCP-29 OUTDOOR 28.09 100 28087.5 127.67 Cu/PVC 25.0 1x2C 2.50 3 100 80
MCP-29 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-29 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-29 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-29 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-29 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-29 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-29 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-29 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-29 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-29 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-29 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-29 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-29 HVU-3 0.61 100 612.5 2.78 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-29 HVU-3 0.61 100 612.5 2.78 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-29 HVU-3 0.61 100 612.5 2.78 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-29 HVU-2 0.28 100 281.3 1.28 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-29 HVU-2 0.28 100 281.3 1.28 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-29 HVU-2 0.28 100 281.3 1.28 Cu/PVC 4.0 1x2C 2.50 1 30 10

Subject : MCP-30

FROM S/S
received received Breaker
ratio load Current CABLE
FROM TO M Total
SIZE
(%) (VA) (A) Cable P AF AT
Type MM2 Structure GIV

MCP-30 OUTDOOR 23.44 100 23437.5 35.65 PVC/XLPE 10.0 4x1C 16 3 100 50
MCP-30 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-30 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-30 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-30 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-30 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-30 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-30 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-30 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-30 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-30 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-30 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-30 HVU-3 0.61 100 612.5 2.78 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-30 HVU-3 0.61 100 612.5 2.78 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-30 HVU-3 0.61 100 612.5 2.78 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-30 HVU-2 0.28 100 281.3 1.28 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-30 HVU-2 0.28 100 281.3 1.28 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-30 HVU-1 0.13 100 133 0.60 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-30 HVU-1 0.13 100 133 0.60 Cu/PVC 4.0 1x2C 2.50 1 30 10
Subject : MCP-31

FROM S/S

received received Breaker


ratio load Current CABLE
FROM TO M Total
SIZE
(%) (VA) (A) Cable P AF AT
Type MM2 Structure GIV

MCP-31 OUTDOOR 23.44 100 23437.5 35.65 PVC/XLPE 10.0 4x1C 6 3 100 50
MCP-31 OUTDOOR 22.95 100 22950 104.32 Cu/PVC 10.0 1x2C 2.50 3 100 50
MCP-31 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-31 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-31 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-31 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-31 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-31 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-31 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-31 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-31 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-31 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-31 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-31 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-31 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-31 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-31 HVU-3 0.61 100 612.5 2.78 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-31 HVU-3 0.61 100 612.5 2.78 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-31 HVU-3 0.61 100 612.5 2.78 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-31 HVU-2 0.28 100 281.3 1.28 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-31 HVU-2 0.28 100 281.3 1.28 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-31 HVU-1 0.13 100 133 0.60 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-31 HVU-1 0.13 100 133 0.60 Cu/PVC 4.0 1x2C 2.50 1 30 10

Subject : MCP-32

FROM S/S

received received Breaker


ratio load Current CABLE
FROM TO M Total
SIZE
Cable
(%) (VA) (A) P AF AT
Type MM2 Structure GIV

MCP-32 OUTDOOR 31.34 100 31340 47.67 PVC/XLPE 35.0 4x1C 16.00 3 100 100
MCP-32 OUTDOOR 34.62 100 34620 52.66 PVC/XLPE 35.0 4x1C 16.00 3 100 100
MCP-32 OUTDOOR 6.87 100 6872 10.45 PVC/XLPE 10.0 1x4C 6.00 3 100 50
MCP-32 SF5 4.63 100 4625 7.04 PVC/XLPE 10.0 1x4C 6.00 3 100 50
MCP-32 EF6 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 16 16
MCP-32 EF7 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 16 16
MCP-32 EF7 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 16 16
MCP-32 EF7 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 16 16
MCP-32 EF10 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 16 16
MCP-32 EF13 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 16 16
MCP-32 EF14 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 16 16
MCP-32 EF15 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 16 16
MCP-32 EF17 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 16 16
MCP-32 RAUP/TTV-07 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 16 16
MCP-32 TTA/TWE120 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 16 16

Subject : MCP-33

FROM S/S

received received Breaker


ratio load Current CABLE
FROM TO M Total
SIZE
Cable
(%) (VA) (A) P AF AT
Type MM2 Structure GIV

MCP-33 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-33 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-33 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-33 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-33 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-33 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-33 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-33 IDU-4 0.38 100 375 1.70 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-33 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-33 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-33 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-33 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-33 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-33 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-33 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-33 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-33 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-33 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-33 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-33 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-33 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-33 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10
MCP-33 IDU-3 0.23 100 225 1.02 Cu/PVC 4.0 1x2C 2.50 1 30 10

Subject : MCP-34

FROM S/S

received received Breaker


ratio load Current CABLE
FROM TO M Total
SIZE
Cable
(%) (VA) (A) P AF AT
Type MM2 Structure GIV

IDU-5 OUTDOOR 0.43 100 425 1.93 Cu/PVC 10.0 1x4C 6.00 1 30 10
IDU-5 AHU-07 0.43 100 425 1.93 Cu/PVC 10.0 1x4C 6.00 1 30 10
IDU-5 FAN-NF7 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10
IDU-5 IDU-5 0.43 100 425 1.93 Cu/PVC 4.0 1x2C 2.50 1 30 10

Subject : PE-PH-1,2

FROM S/S

received received Breaker


ratio load Current CABLE
FROM TO M Total
SIZE
Cable
ELEV- (%) (VA) (A) P AF AT
Type MM2 Structure GIV
24PER
PE-PH-1,2 ELEV-
210MM 50.00 100 50000 76.06 FR-8 70.00 4x1C 25.00 3 160 160
24PER
PE-PH-1,2 ELEV-
210MM 50.00 100 50000 76.06 FR-8 70.00 4x1C 25.00 3 160 160
24PER
PE-PH-1,2 210MM 50.00 100 50000 76.06 FR-8 70.00 4x1C 25.00 3 160 160

Subject : PE-PH-3,4

FROM S/S

received received Breaker


ratio load Current CABLE
FROM TO M Total
SIZE
Cable
ELEV- (%) (VA) (A) P AF AT
Type MM2 Structure GIV
24PER
PE-PH-3,4 ELEV-
210MM 50.00 100 50000 76.06 FR-8 70.00 4x1C 25.00 3 160 160
24PER
PE-PH-3,4 210MM 50.00 100 50000 76.06 FR-8 70.00 4x1C 25.00 3 160 160

Subject : PE-4-1

FROM S/S
received received Breaker
ratio load Current CABLE
FROM TO M Total
SIZE
(%) (VA) (A) Cable
ELEV- P AF AT
Type MM2 Structure GIV
24PER
PE-4-1 ELEV-
90MM 15.00 100 15000 22.82 FR-8 25.0 4x1C 16 3 100 50
24PER
PE-4-1 90MM 15.00 100 15000 22.82 FR-8 25.0 4x1C 16 3 100 50

Subject : PE-4-2

FROM S/S

received received Breaker


ratio load Current CABLE
FROM TO M Total
SIZE
Cable
ELEV- (%) (VA) (A) P AF AT
Type MM2 Structure GIV
24PER
PE-4-2 90MM 11.00 100 11000 16.73 PVC/XLPE 10.0 1x4C 6.00 3 100 50

Subject : CT-M

FROM S/S

received received Breaker


ratio load Current CABLE
FROM TO M Total
SIZE
Cable
(%) (VA) (A) P AF AT
Type MM2 Structure GIV

CT-M CT-1 71.30 100 71300 108.46 PVC/XLPE 150.00 4x1C 95.00 3 225 225
CT-M CT-2 71.30 100 71300 108.46 PVC/XLPE 150.00 4x1C 95.00 3 225 225