+ + ( ............................................................... )3
+ ( .................................................... Name plate )4
+ ( ..................................... )5
( .................................................................... )6
( .................................................................................... )8-7
- ( ................................................................................................... )9
( ......................................................................................... )10
( ............................................................................... )12-11
+ ( ............................................................... )13
( .............................................................................. )15-14
+ ( ..................................................... )16
( ..................................................................................................... )17
+ ( ..................................................... )18
+ ( ...................................................... )19
( ................................................. )20
) + (Name Plate ( .................................... )21
+ ( .................................... )22
+ ( ......................................... )23
( ................................................................................ )25-24
( ..................................................................................... )26
+ ( ............................ )27
+ ( ........................ )28
( ............................................................................................ )29
+ ( ........................................ )30
(SF6) )( .................................... (Vaccum )31
+ + ( ............................................................... )32
+ ( .................................................................. )34-33
( ) ( .................................................. )36-35
+ SF6 ( ..................................................... )37
( .......................................................................................... )38
)( ........................................................................................................... (Tunger )39
+ ( ................................................. )40
( .......................................................................................... (EFI) )41
( ..................................................................................... )42
( .......................................................... )43
+ ( ........................ )44
)(2
:
14
) (Spare ,
14
)1 : 14 14 1( )
)2 : 15 :
0 ( 14 ) 1 ( 15 )
( : )14 0 ( )0 Spare
( : )15 1 ( )15 Spare
)10,9 & 6,5(
)14,13,12,11 & 4,3,2,1(
Bus Riser Bus Coupler)8 & 7(
4 :
) (Reliability 4
, (Closed Loop) :
( Phase Sequence ) : R-S-T -1
( Voltage Magnitude ) : -2
( Frequency) : -3
( Phase Angle ) : = Zero -4
R )5,6( R Zero = )9,10(
: ) 0 = (R , ) 120 = (S , ) 240 = (T
4 :
)5,6( )9,10( )(Closed Loop
)(Open Loop
( )14 1
) (Load Breaker Switch RMU
:
( )
( )
,
)(3
:
)1
)2
)3
)4
)5
)6
)7
: GIS
( SF6 )
): (Name Plate
: (Normal Voltage) U 22KV
: (Frequency) fr 50Hz
: (Rated Voltage) Ur
= 24KV
: (Break Down Voltage) Ud
50KV =
: (Peak Voltage) Up = 125KV
1.2 " 50 "
: (Rated Current) Ir
/ = 1250A
: (Short time withstand Current) Ik/tk
25KA = Short
1
:
: (Pressure Relief)
Lock
:
:
)(4
:
:
)(Skin Effect
:
:
-1 ( )
-2 ( )
:
-1 ( )Blower
-2 ( )
: Bus Coupler
:
:
: DC Loss 110VDC ( 3 )
: 110VDC ( )
: 110VDC
: 110VDC Reset
110VDC
: AC Loss 22KV
: 22KV
: 22KV
: 22KV
:
) : Ammeter (A
) : Voltmeter (V
3( 1 +) ( 3 )
Trip Reset
)(5
( ) :
/
:
: )1
( : )
( )C.B ) (MDB
RMU /
(
)
:
-1
( ) -2
(Short)
)2 ) (Megger :
:
RMU RMU MDB MDB
RMU
:
:
:
) (UPS
:
:
)1 : 2 240 2 120 2 240
)2 ) : (Voltage Drop
)3 :
:
) (Over Load ) (Starting Current
( : )220V
)1 : Shutter
)2 : Shutter
:
)(6
) (Inter Lock : 3 3
: ): (Inter Lock
( )3 2
( ) 3/2
4 ( )1
( )Closed Loop
( )( ) 4
: 3 2( : )3/2
3/2( : )2 (, )3 ( )
)2 ( 10 9 )1 ( 6 5
3/2
3/2
3/2
( 3/3 )
: InterLock : 3/2
) (Sepam ( )
( ) : 3/2
)1
)2
( + )
3/2 ( 3/3 )
:
3/2 ( )2 1
2
( )
: ) (InterLock :
) : (InterLock
: (Blocking Coil) :
3/3 )1
/ )2
Blocking Coil ( )
)3
( " ")
)(7
: (Mechanical InterLock)
) : (Positive Interlock )1
Closed ( Connected 1 )
) : (Negative Interlock Connected )2
( Test 2 )
) : (Maintenance Interlock )3
Test
( Out Of Service 3 )
: (Position Closing Interlock) )4
Test ( Connected 4 )
) : (Position Withdrawal Interlock Out of Service )5
( Test 5 )
/ : (Extension Rail Interlock) Out of Service )6
/ Pins ( 6 )
/ : (Levering Interlock) )7
In Service Test Connected Open
( Closed 7 )
) : (Gag Spring Interlock In Service )8
Closed / ( 8 )
) : (Key Interlocking )9
( Test ) ( 9 )
:
:(Rating Interferance InterLock)
( )
)(8
) - Phase Sequence - - ) :
3 :
/ ) : (ON ) (R S (R T) (T S) )1
/ : (Vibrate) ) (R R (S S) (T T) )2
/ ) : (OFF )3
:
)1 : Phasing
)2
)3 ( )RMU
)4 ( )
)5
: Phasing
)1 :
RMU MDB
( )
:
.i 3
.ii
.iii
: ( Phasing )ON
) )1
: )2
( )2
:
4 .i
.ii
)3 ( : (S-R) (R-S)
(T-T) ( ) :
)(9
:
(: )Creepage Distance/Bushing )1
) (Bushing
) (Leakage Current
( )
1 1KV
Bushing) : (
.1
)(Bushing .2
.3
(22KV) .4
Bushing) : (
(400V)
)2 : )Arc Distance(
:
()
1 1KV
( )
:
( )
( ) ()
/ () Short
:
/ : )Buchholz Relay( )3
:
:
(( )1 ) : )1
()1
(( )2 ) : Short )2
( )2
: N
)(10
:
)1 (Turns Ratio Test)
)2 )(Insulation Test
)3 )(No Load Test
: :
: 3 380V
( )
:
= 55=400/22000
380V
= 7 V = 55/380
: :
: )1
Short L
Short
E G
5KV
/
)2 :
Short L
Short
G
E 5KV
/
)3 :
Short L
Short
G
E 1KV
/
)(11
: :
2%
( ) 2%
:
S =3 x V x I
( ) S : 1 0.5 VA
) ( V : 400V =
) ) I :
:
() : 1000KVA
1000x1000 =3 x 400 x I ( ) I=1443 A
( ) Power Loss= 2% x 1443 = 28.9A 2%
: 3 380V %3
( ) %2
: 28.9A 1000KVA
:
)1
:
)2
:
)3
:
)4
:
)(12
:
) (Single Phase 300x1x3
) (Single Phase )300x3 (Three Phase
:
( )
:
(Single core)
) (Shield
:
Sepam
) (Earth Leakage
:
) : (1 3
) (Earth Leakage
) : (2
) (Twisting 500
: :
:
:
)1 :
)2 :
)3 :
)(13
:
: )1
110
( )3 2 (( )2 1 " "7 InterLock )3/2
: )2
110
: )3
: )4
: )5
Fixed Contact ()Flower Box Bushing
)(14
: )6
Short
: )7
: )8
: )9
110
110
( - - )
Spark Fixed Contact Bushing
Fixed Contact
Fixed Contact Bad Contact
)(15
( ) :
:
)1
)2 WD40
)3 WD40
)4
)5
)6
)7
)8
)9
)10
:
8A Starting
30A 3
: RMU
)1 )( (AVO : )
Bother
Bother
: Bother
: Bother
)2 )( (Megger : )
: / ( )
: / ( )
)3 ( (Phase Sequence) : )
: ( )ON/OFF
: (OFF)
:
1500KVA
1500KVA Sepam
)(16
:
:
)1
)2
)3
:
:
:
( )
%125
%10 5/100
10A
3 :
: 5A )1
: 2A )2
: 1A )3 ()
: 30
1A (Power Loss = I^2 x R)
( : )
( ( (5A (110VAC :
)(17
:
)1 :
)2 /
)3
:
: 5A
)1
)2
)3
3 (R=L/A) :
Burden :
/ )1
( / 15VA )20VA
)2
: )3
.A
( P =I^2 x R) .B
:
= ()^( x 2)
( x 2^ (5A) = 15VA + + + ..... + )
:
= ()^( x 2)
( x 2^ (5A) = 20VA + + ..... + )
)(18
): (Saturation Curve - Magnetic Curve
( ) %10
%50
: 5/100
( 100A ) ( 5A )
: 5/5/200
( +) 5A 200A
: 5/5/200/400
400 ( 200 )
( ) :
5/5/400/800
8 ( )
)(19
: 5/5/300/600
: 5/5/300
300A
) (Bridge - Plate
4
( )
300A
( )
: 5/5/600
300A 600A
(Bridge - Plate) 4
( )
600A
( )
:
: 5/5/5/200 3
)1
)2
)3
:
) (Fuses
)(20
): (Name Plate
24/50/125 KV P1-P2 = 200A
5A 15VA CL 0.5M 1S1-1S2
5A 30VA CL 5P10 2S1-2S2
I th 25/1S KA
I dyn 100 KA 50HZ
:
)1 ( : )
22KV
110VAC ( )
)2 :
110VAC Coil
(( )Resonance )
:
)(21
) (Fuses ) (6A0.5A
-1
0.5A
-2
) (Distortion -3
Short
:
Section : )1
110V Section Relay
Section
110V Section
)6,5( )2
( )4,3,2,1 5
6 6
)6,5( Section
)3
110V
Sepam
:
)1
)2
Sepam
): (Name Plate
: Un = 10/24KV
: In = 6.3A
: I3 = 36 A
3 ( I3 5 ) In
: I1 = 40KA Short
)(22
DC
AC DC
( )
( )
() :
)1
)2
)3
)4
)5
:
-1
-2
()
-3
-4
( )13
:
)1 (Turns Ratio Test)
)2 )(Saturation Test
)3 )(Polarity Test
)4 )(Insulation Test
:
)1 (Turns Ratio Test)
)2 )(Polarity Test
)3 )(Insulation Test
:
( ) ( )27
)(23
: :
: (Turns Ratio Test) (Primary Injection Test) )1
( : )
)1
Short )2
: 4
50A 0.5A 50A 0.6A
100A 1.6A 100A 1.2A
200A 2.1A 200A 2.4A
400A 4.1A 400A 4.8A
:
( ) : Test )1
( : )
220V )(0300A )2
125V )(0600A
: 200A )3
2.4A ( 3.1A )
Short )4
)(24
): (Polarity Test )3
( : )
6V )1
S11 )2
:
( )
:
-1
-2
-3
180 =
)4 ) : (Insulation Test
-1 ( ) :
Short L
Short E
G 5KV
( )
-2 :
Short L
Short E
( 5KV )
-3 :
Short L
Short E
( 1KV )
11KV : 22KV
22KV 11KV )1
22KV 11KV
22( 22KV ) ) 11( 11KV )2
)3
22KV 11KV : )4
22KV : 11KV 22KV 11KV
11KV : 22KV 22KV
)(25
: :
)1 : (Turns Ratio Test)
3 380V
) = ( / (22KV (110V
= 200 = 110/22000 380V
1.9V = =
200 = 1.9/380 22KV
)2 ): (Polarity Test
Digital DC )(+
) (-
Analog
)3 ) : (Insulation Test
-1 ( ) :
L Short
E G
( 5KV )
-2 :
L Short
E 5KV
( )
-3 :
Short L
E
( 1KV )
)(26
:
: ( ) : ( )
+Meter : + O.V+U.V+Sepam+Selector+Meter :
: ( ) : ( )
: Sepam : Sepam( )
: : ( )
C.T V.T ) + + + ):
)(27
:
() :
: ( 0.1 ) )1
: 0.3( ) )2
: ( ) )3
: )4
() :
: : .A
)1
)2
: : .B
)1
)2
: Sepam S40
Sepam S20
/ :
: :
Ii Ir
) (OverLoad ,Long Time ,Thermal Curve
Ir
: (Rated Current) Ir
) (1 100A) (
( 2 ) ) (2
) 150A ) 1( )
: / :
Short
3 (Three Phase To Ground Fault) Earth
(Phase To Ground Fault) Earth
Icu Ii (Instantaneous ,Short Time ,Magnetic Curve)
:(Instantaneous Current ) Ii
Ii
:
.. Sepam 20
Sepam
+ Sepam
Sepam
)(28
:
: )1
) : (Residual Current
3 IR+IS+IT = I0
Short IR+IS+IT I0
3
))I0 =| I | I
) : (Residual Voltage
3 VR+VS+VT = V0
Short VR+VS+VT V0
3
))V0 =| V | V
:
()Isc > Iset )1
))|V - I|set |V - I|sc )2
Sepam ( | ) | I
( | ) |V-I | I |+|V-I| :
: )2
( | ) | I | I | :
:
( ) : 12
1
1 2
( 51 )C.B1 2
( 51 )C.B2
+ C.B1
C.B2 C.B1 OverLoad
( ) : 67( )C.B1
C.B1
2
:
51 )1
67 )2
)3
)4
Blocking Coil )5
)(29
( Relays ) :
)1 : Reliability ()
( )
)2 : Sensitivity
)3 : Selectivity
)4 : Speed
) (Synchronism :
MDB
MDB ...
MDB
:
5/400
400A 5A
600A OverLoad 7.5A
5A = 2.5A = 5A 7.5A
: MDB
( : Ir )1 )(Over Load Relay
( : tr )2
( : Isd )3 (Short Current Relay)
( : tsd )4
( : Ii )5 (Instantaneous Relay)
( : Ig )6 (Earth Fault Relay)
( : tg )7
( : Alarm )8
( : Reset/Test )9
: Ii (Isd Ii) Isd
Ii
:
( : )In=2000A
1000A = 0.5x2000 = 0.5xIn = Ir 1 = tr
2000A = 2x1000 = 2xIr = Isd 0.2 = tsd
6000A = 3x2000 = 3xIn = Ii
( 640A = Ig A )J 0.2 = tg
: ( (ON Off (tg tsd) Off
)(30
(SF6) ): (Vaccum
)(Vaccum (SF6)
Vaccum SF6
SF6 Vaccum
SF6 SF6 Vaccum
%100
%99.8 %0.2
Vaccum
Short Short Short
Vaccum Short
SF6 Vaccum
( )
10,00020,000 5,00010,000
Short
10,00030,000 5,00020,000
O-0.3S-CO-3min-CO O-0.3S-CO-15S-CO
:(Open) O :(Open) O
: 0.3S : 0.3S
Short Short
0.3 = Open 0.3 = Open
:(Closing Operation) CO :(Closing Operation) CO
Short Short
Operating
: 3min : 15S
Sequence
Short
= 3 Short = 15
: = 3 : = 15
((SF6
( (Vaccum Short Short
:
: RTK SF6
: Vaccum Vaccum
)(31
+ + :
:(KN) Anti Pumping Relay )1
Shunt Closing
: Short
Anti Pumping Relay
Short ( Block )
Reset
:
: Name Plate RMU
))YO1 Shunt Opening + Shunt Close
()Under Voltage + YO2 Shunt Opening + MiTop
: 110VDC
)(32
+ :
)1 :
:
:
)2 :
)3 :
Fixed Contact
( 4)
:
ON
OFF
)4 :
/
Fixed Contact
Bushing
)5 : Dumper
)(33
)6 ) : (Closing Spring
( )
)7 : (Opening Spring)
)8 : Closing Spring
: )9
( )
3
:
:
( ) )1
)2
( ) )3
:
( ) )1
( )
)2
( ) )3
( )
)10 :
)(34
( ) :
: )2( ( )4 ()5
)6( )1( )2(
( )4 )7(
( )4 )8( )9( )10(
Charged ( )11
)6( Lock )32( )12(
( )5
)(35
:
: ABB
)35( )34(
)(36
SF6 :
SF6 6 )1
)2
5 )3
SF6 )4
)5
99.8% 0.2% + )6
H2) = H2O O( + ) ) ) (Arc :
) H2 ) ( F ) ( )
) O ) ( F S+) ( )
:
SF6
4 :
( : )1 )a( )1
( : )2 )a( )2
( )b ( )c
(d)
( : )3 ( )b ) (c )3
) (e
( )b SF6
( : )4 SF6 )4
:
)(37
:
: )1
T
T
5KV DC :
)1
)2
: )2
T
S
5KV DC :
)1
)2
: )3
20-15( )
)4 :
( )
50 3
:
)1 ( SF6 )
)2 Short SF6
)3 SF6 99.8%
)(38
): (Tunger
3 380V
( Rectifier AC )DC
110VDC
( D.C )1
( D.C )2
:
)1 DC
( )
( ) :
)2 3 ( 30-15)
-1 :
-2
)3 ) :(A.H
.
)4 3 380V
( )
)5 3 380V Sellector
)6
Open Circuit DC
)7
110VDC
)8 Short
Open
)9
)10 " "
Tunger :
AC DC )1
)2
Sepam )3
)4
( = : )86 = 110VDC
( Float Voltage )1 ) : 90V140V
( = 120.4 V DC ) ( x 1.4) 86
( Hi-Rate Voltage )2 : ) 130V160V
( = 133.3 V DC ) ( x 1.55) 86
( Boost Voltage )3 ) : 170V
( = 141.9 V DC ) ( x 1.65) 86
)(39
:
+
: + + :
:
:
:
:
DC DC
( )
:
:
=
:
:
) 1 :
)2
)3 )%15 - %10(
)4
)5
)1 :
)2
)3
) 4
)(40
: (EFI)
(Earth Fault) (Earth Leakage)
: Earth Leakage Shield
1mA 3mA
Fault
: Earth Fault :
: Line To Earth Fault )1
: Line To Line Earth Fault )2
: Three Phase Earth Fault 3 ( ) )3
: EFI Shield
Shield
Short Earth Fault Shield
EFI
:
Shield Ferranti Coil )1
)2
)3
:
)1
Short
R.M.U )2
Fuses
EFI )3
Reset EFI : )4
) : (Manually Reset EFI
) : (Automatically 220VAC
EFI Reset
:
(RMU 3 RMU 2)
RMU
: ) )RMU 2 RMU 1
EFI RMU
Open Loop
:
)(41
:
: ) (Megaohm Tester ) (MEGER
, ( - - -)
) 250V (DC10,000V
:
)1 : DC
)2 : ( ) ()
( )0 Short
: ) - + ( )E L( ) (L = Line )(+
) (E = Earth ) (-
3 ( ) E G L ) (G = Guard
Guard
:
) (Bushing L
E Guard Bushing
G( )
:
)1 ): (Phase Phase
L R Short
S & T Earth Short
( E )1
:
-1 ) (Terminals
-2
-3 Short ()1
-4 )5-1( / 1 /
-5 1KV / 5KV /
)(42
:
:
Short
( : )
: ( )
: ( )
:
)1
2 )2
)3
:
( + + + ) ( )
:
)1 :
(
)
)2 :
( + + )
( )
:
( 5 1)
( )
) (Test Link
:
E( (Electrode) ) -1
P( (Potential - Voltage) ) -2
C( (Current) ) -3
( : )
C P
E
) 30-15(
P C E
P C E ( 10-5)
)(43
: (IEC 62271-200)
English
KPS SF6 Leakage SF6
KL1 Local
KR1 Remote
KLT1 Lamp Test
KSU1 )Total Control System (TCS
KF1 C.B Trip
KU1 Under & Over Voltage Trip
K1 AC Voltage OK
KAM1 Any MCB Tripped
KDC1 DC Loss Ok 110V DC
Test
KQ1 C.B ON , C.B Off
( )
KWD1 Sepam WatchDog ( :
" )"
/ /
Q2 3 Q7 3
Q3 3 Q8 110V DC
Q4 3 PM710 Q9 110V DC
Q5 3 Q10 110V DC
Q6 3 Selector Q11 220V AC
:
: C.T : (C.T )
)(44
Reference / Subject /
1 http://3marh.mam9.com/t4401-topic
2 https://www.youtube.com/watch?v=s06q9hQytcc
3 Current transformers ) / (
4 MCT1600_UG
5 Current transformers Principle of operation of CT EEE
6 Testing and Commissioning of Current Transformer by Edvard
7 Bushing (electrical) Wikipedia Bushing
8 Buchholz Relay operation and principle www.electrical4u.com
9 Buchholz Relay - Construction, Working by Kiran Daware
10 Preparing to synchronize a generator to the grid by Edvard
11 ) (
12 Instructions for Installation, Operation and Maintenance of 24kV
13 Power/Vac Metal-Clad Switchgear and Vacuum Circuit Breakers
14 05-136-48049 Schneider Electric
15 ABB-fuses_ATO katalog_ENG_W7_8-05-15
16 AC0479EN_print
17 medium-voltage-switchgears 24kV automatica
18 AE_Understnd_Insulation_Res_Testing
19 ELECTRICAL INSULATION TESTING SUB-02-613
20
21 Measurement of insulation resistance (IR) Part 2 by jiguparmar
22 relaytraining.com.com-PTs-Back_to_the_Basics P.T
23 ) (
24 Anti Pumping Relay and its Operating Principle by Janshair K.
25 AMTED304010EN.indd Relays
26 Difference between Shunt Trip and Undervoltage Trip by gohz
27 AMTED304010EN_print
28 https://www.youtube.com/watch?v=gFoBt_wYe14
29 Circuit breakers SF 1 to 40.5 kV SF6 switchgear by Merlin Gerin
30 Evolis circuit breakers 17.5 kV schneider
31 hvx_selection_en.pdf
32 Catalogo-2011.pdf SM6 Modular units
33 AMTED397052EN.indd
34 F10 Earth Fault Indicator USER MANUAL
35 EFI.02 EARTH FAULT INDICATOR INSTALLATION
EFI
36 Nortroll_CableTroll_ENG.pdf
37 Earth Fault Indicator(HORSTMANN GMBH).pdf
38
39 https://www.youtube.com/watch?v=S3bV9ZWD1L4
40 /
41 Digital Earth Resistance Tester MODEL 4105A
42 / -2013-
(45)