New Site External alarm implementation guide


For new site External we have two scenario:
1. ZTE ODU External Alarm Configuration (With Sceco)
2. ZTE ODU EXTERNAL ALARM CONFIGURATION TEST (With Genset)

ZTE ODU External Alarm Configuration (With Sceco)

Alarm DDF
Designation Remarks Connection
No. SLOT
1 Door Cabinet Open(WHITE / 1 Connected directly to Sensor - DDF 1 - BBU SA
BLUE) BBU SA Card
2 High Temperature(WHITE / 2 Connected directly to Sensor - DDF 2 - BBU SA
ORANGE) BBU SA Card
3 Tower Light Failure 3 Connected directly to Sensor - DDF 3 - BBU SA
Alarm(WHITE / GREEN) BBU SA Card
4 Rectifier Alarm (WHITE / 4 From B201 SIB Board X15 - DDF 4 - BBU SA
BROWN) (Power Unit) - X15 port
5 AC Power Fail(WHITE / GRAY) 5 From B201 SIB Board X16 - DDF 5 - BBU SA
(Power Unit) - X16 port
6 Environmental Over 6 From B201 SIB Board X16 - DDF 6 - BBU SA
Humidity(RED / BLUE) (Power Unit) - X16 port
7 DC Low Voltage alarm(RED / 7 From B201 SIB Board X17 - DDF 7 - BBU SA
ORANGE) (Power Unit) - X17 port
8 SMOKE Alarm(RED / Green) 8 From B201 SIB Board X17 - DDF 8 - BBU SA
(Power Unit) - X17 port

<> 1
All Rights reserved, No Spreading abroad without Permission of ZTE
Internal Use Only

ZTE ODU External Alarm Drawing (With Sceco)

Door 1 sensor
ODU Cabinet Door open alarm
DDF Port 1 Door 2 sensor

High tep. Alarm AC1(1500W) alarm cable


DDF Port 2
AC2(1500W) alarm cable

AC3(500W) alarm cable


Smoke alarm B201 X17 B201 X24
DDF Port 8 Port(NC/COM) Port Smoke sensor

SA card D B201 Module


Rectifier alarm
(BS8800) D B201 X15 Port(NC/COM)
DDF Port 4
F

AC power fail alarm B201 X16 Port(NC/COM)


DDF Port 5

Environmental over humidity alarm


DDF Port 6 B201 X16 Port(NC/COM)

DC Low voltage alarm


B201 X17 Port(NC/COM)
DDF Port 7
virtual

Actual Tower
Medium light alarm cable
Tower Light Failre Alarm Control Junction
Low light alarm cable
DDF Port 3 box box
Low light alarm cable

NodeB(BS8800) part:

SA card D
(BS8800) D
F

For New site External alarm we through BS8800 SA card report to EMS/OMC.all external alarm sensor
should be connect to SA card through DDF terminal.before connect sensor,please make loop back test
from DDF to OMC,make sure 8channel no any cross.it very important for test external alarm.
External alarm connection :
SA card-------SA cable(B3 connector)---------SA E1 Cable----------DDF-------each sensor
1. SA cable :material code: 052740402435 DS-91228-001|Digital Signal Cable

<> 2
All Rights reserved, No Spreading abroad without Permission of ZTE
Internal Use Only

2.SA E1 Cable: material code: 052740402185 DS-91223-002|Digital Signal Cable

We used core color(new)

<> 3
All Rights reserved, No Spreading abroad without Permission of ZTE
Internal Use Only

3.connection picture:

<> 4
All Rights reserved, No Spreading abroad without Permission of ZTE
Internal Use Only

No1. Door Cabinet Open(WHITE / BLUE)(in DOU cabinet)

Door 1 sensor
ODU Cabinet Door open alarm
DDF Port 1 Door 2 sensor

SA card D
(BS8800) D
F

Door1 and Door2 Sensor cable need parallel connect to DDF port1
Door 1 Sensor :

Door2 Sensor

Door 1&Door 2 Sensor cable :

<> 5
All Rights reserved, No Spreading abroad without Permission of ZTE
Internal Use Only

No 2.High Temperature(WHITE / ORANGE) (in DOU cabinet)

ODU Cabinet

High tep. Alarm AC1(1500W) alarm cable


DDF Port 2
AC2(1500W) alarm cable

AC3(500W) alarm cable

SA card D
(BS8800) D
F

AC1&AC2&AC3 Alarm cable need parallel connect to DDF port2


1.AC1(1500W)alarm cable:(Location:in Door1 up area Port:NC/COM)

<> 6
All Rights reserved, No Spreading abroad without Permission of ZTE
Internal Use Only

2.AC2(1500W)alarm cable:(Location:in Door2 up area Port:NC/COM)

3.AC3(500W)alarm cable:(Location:in Door2 down area Port:NC/COM)

4.alarm cable in ODU location

<> 7
All Rights reserved, No Spreading abroad without Permission of ZTE
Internal Use Only

No 3.Tower Light Failure Alarm(WHITE / GREEN)-on tower

SA card D
(BS8800) D
F

Tower
Medium light alarm cable
Tower Light Failre Alarm Control Junction
Low light alarm cable
DDF Port 3 box box
Low light alarm cable

Tower lignht Alarm cable(alarm output in control box) need connect to DDF port3
Medium light(1pcs) /low light(2pcs) cable (Brow/blue) connect to Junction box alarm input terminal,
From Junction box connect to Control box alarm input terminal, From Control box alarm output
connect to DDF port3 terminal. For detail connection please reference installation and operation
manual in the box.

<> 8
All Rights reserved, No Spreading abroad without Permission of ZTE
Internal Use Only

No 4. Rectifier Alarm (WHITE / BROWN)


No 5. AC Power Fail(WHITE / GRAY)
No 6.Environmental Over Humidity(RED / BLUE)
No 7.DC Low Voltage alarm(RED / ORANGE)

SA card D
Rectifier alarm
(BS8800) D B201 X15 Port(NC/COM)
DDF Port 4
F

AC power fail alarm B201 X16 Port(NC/COM)


DDF Port 5

Environmental over humidity alarm


DDF Port 6 B201 X16 Port(NC/COM)

DC Low voltage alarm


B201 X17 Port(NC/COM)
DDF Port 7

Rectifier Alarm From X15 NC/COM connect to DDF port4


AC Power Fail From X16 NC/COM connect to DDF port5
Environmental Over Humidity From X16 NC/COM connect to DDF port6
DC Low Voltage alarm From X17 NC/COM connect to DDF port7

Below description detail how to setting external alarm in ZXDU68 B201 system.

About the relay alarm of the ZXDU68B201 power supply system

The boards of the zxdu68 B201system is integrated in the signal transfer box. Figure as below:
shown the board layout.

<> 9
All Rights reserved, No Spreading abroad without Permission of ZTE
Internal Use Only

1. Network interface board(IP/SNMP);


2. Modem power board(MPB);
3. Signal interface board(SIB)
And the signal interface board provides external communication interfaces and monitoring
unit signal interfaces. The signal board is shown in figure as below. Refer to table for the
signal board interfaces description.
Figure signal board:

Table signal interface name


Interface Interface name Interface Interface name
X4 Battery 1 temperature X21 RS485 interface
X5 Battery 2 temperature X22 Rs232 interface
X12 Temperature control X23 Flood alarm
X14 Input relays 1,2,3,4 X24 Smoke alarm
X15 Out relays 1,2 X25 Ambient temperature
X16 Out relays 3,4 X26 Intrusion alarm
X17 Out relays 5,6

Then the relays alarm function need to three interface: X15X16X17.


So the relays alarm function of the signal interface definition as belowTable-1:
Interface Pin Signal Signal description Relay alarm definition
definition (monitor parameters)
X15 1 2NO Relay output 2-NO(normally open) A3
Output relays 2 2COM Relay output 2-Common end A3
1,2 3 2NC Relay output 2-NC(normally closed) A3
<> 10
All Rights reserved, No Spreading abroad without Permission of ZTE
Internal Use Only
4 1NO Relay output 1-NO --
5 1COM Relay output 1-Common end --
6 1NC Relay output 1-NC --
X16 1 4NO Relay output 4-NO A5
Output 2 4COM Relay output 4-Common end A5
relays3,4 3 4NC Relay output 4-NC A5
4 3NO Relay output 3-NO A2
5 3COM Relay output 3-Common end A2
6 3NC Relay output 3-NC A2
X17 1 6NO Relay output 6-NO A4
Output relays 2 6COM Relay output 6-Common end A4
5,6 3 6NC Relay output 6-NC A4
4 5NO Relay output 5-NO A5
5 5COM Relay output 5-Common end A5
6 5NC Relay output 5-NC A5

The relays alarm function has two options on the signal board, one relay output-NO(normal open)
and one relay output-NC(normal close). So need to know the BTS interface alarm definition
which it is NO or NC.
If it is NO, and connect relay alarm cables step:
1 One group relay out need two signal cables , and one terminal connect with relay out ON and
relay output common end on the signal board interface, another terminal connect with the
BTS interface.

NO
COMMON

DDF

2 Other relays alarm as above the connection step, until it finished.


After finished to connect the signal cables , and set parameters in the monitor.
Step:
1check the monitor screen, find the CTRL menu.

<> 11
All Rights reserved, No Spreading abroad without Permission of ZTE
Internal Use Only
2press the button ENTER of the monitor.

3 Entering the password: 0000.

4 Enter the setup parameter system: 1. Setup Para, press the Enter button.

5 Find the Alarm Para in the Setup Para.

6 Enter the Alarm Para menu, find the 1.Set Relay to Enter

7 And find the relays alarm parameter. According to the relays alarm requirements, set the relay

<> 12
All Rights reserved, No Spreading abroad without Permission of ZTE
Internal Use Only
alarm.

Setup procedures
If the relay alarm connected the X15(1,2) of the signal board, it mean what it is SMR Alarm.
So the relay alarm parameter set A2.
Refer to above the Table-1.

Figure (set parameter:

No 8. SMOKE Alarm(RED / Green)

ODU Cabinet

Smoke alarm B201 X17 B201 X24


DDF Port 8 Port(NC/COM) Port Smoke sensor

SA card D
(BS8800) D
F

Smoke alarm From Smoke sensor first connect to X24then X17 NC/COM connect to DDF port8

<> 13
All Rights reserved, No Spreading abroad without Permission of ZTE
Internal Use Only
ZTE ODU EXTERNAL ALARM CONFIGURATION TEST (With Genset)

Alarm DDF DRY Contact Alarm


Designation Connection
No. SLOT Connection

Connected directly to BBU SA


1 Door Cabinet Open(WHITE / BLUE) 1 Sensor - DDF 1 - BBU SA
Card

Connected directly to BBU SA


2 High Temperature(WHITE / ORANGE) 2 Sensor - DDF 2 - BBU SA
Card

From B201 SIB Board


3 Rectifier Alarm (WHITE / GREEN) 3 X15 - DDF 3 - BBU SA
(Power Unit) - X15 port

From B201 SIB Board


4 AC Power Fail(WHITE / BROWN) 4 X16 - DDF 4 - BBU SA
(Power Unit) - X16 port

Environmental Over Humidity(WHITE / From B201 SIB Board


5 5 X16 - DDF 5 - BBU SA
GRAY) (Power Unit) - X16 port
From B201 SIB Board
6 DC Low Voltage alarm(RED / BLUE) 6 X17 - DDF 6 - BBU SA
(Power Unit) - X17 port
From Generator Control Port
7 Generator Fault(RED / ORANGE) 7 Generator Control - DDF 7 - BBU SA
connected directly to SA Card
From the Storage Tank
8 Generator Low Fuel(RED / GREEN) 8 Storage Tank Sensor - DDF 8 - BBU SA
Connected directly to SA Card

ZTE ODU External Alarm Drawing (With Genset)

Door 1 sensor
ODU Cabinet Door open alarm
DDF Port 1 Door 2 sensor

High tep. Alarm AC1(1500W) alarm cable


DDF Port 2
AC2(1500W) alarm cable

AC3(500W) alarm cable

B201 Module
Rectifier alarm
B201 X15 Port(NC/COM)
DDF Port 3
SA card D
(BS8800) D
AC power fail alarm B201 X16 Port(NC/COM)
F
DDF Port 4

Environmental over humidity alarm


DDF Port 5 B201 X16 Port(NC/COM)

DC Low voltage alarm


B201 X17 Port(NC/COM)
DDF Port 6

virtual
Generator
Generator Fault
Actual Generator
DDF Port 7

Generator Low Fuel


DDF Port 8 Genterator tank

<> 14
All Rights reserved, No Spreading abroad without Permission of ZTE
Internal Use Only
For alarm No.1No.6,please refer ZTE ODU EXTERNAL ALARM CONFIGURATION TEST
(With Sceco) installation.
No7. Generator Fault(RED / ORANGE)
No8 Generator Low Fuel(RED / GREEN)

SA card D
(BS8800) D
F

Generator
Generator Fault
Generator
DDF Port 7

Generator Low Fuel


DDF Port 8 Genterator tank

<> 15