Академический Документы
Профессиональный Документы
Культура Документы
1 INTRODUCTION ........................................................................................... 1
2 PRODUCT DESCRIPTION............................................................................3
2.1 Controls & Indicators ..............................................................................3
2.2 Connection Overview..............................................................................4
2.3 Connection Overview..............................................................................5
2.4 Specifications .........................................................................................6
Part Number Details ..........................................................................................8
3 INSTALLATION and CONNECTIONS........................................................... 9
3.1 Mounting.................................................................................................9
3.2 Power Hookup ......................................................................................11
3.3 Temperature Probes.............................................................................12
3.3.1 TTC-PROBE-01 Installation ..........................................................12
3.3.2 TTC-PROBE-11 Installation ..........................................................13
3.3.3 Magnetic Mount Probe (TTC-PROBE-02) Installation ...................14
3.3.4 Probe Lead Connections ...............................................................15
3.4 Auxiliary CT Input for Calculated Winding Temperature.......................17
3.5 Cooling Control and Condition Alarm Connections...............................17
3.6 Unit Alarm Connections ........................................................................18
3.7 Telemetry Connections.........................................................................19
3.7.1 RS-232 Terminal Connections ......................................................19
3.7.2 Analog Outputs..............................................................................19
3.7.3 RS-485 for DNP3.0 Communications ............................................20
3.7.4 Fiber Optic Interface for DNP3.0 Communications........................21
3.8 Optically Isolated Inputs .......................................................................23
3.9 Heater Connections..............................................................................23
4 SETTINGS...................................................................................................23
4.1 Programming Settings Through Front Panel ........................................24
4.2 Programming Settings Through a PC...................................................24
4.3 Settings for Calculated Winding Temperature ......................................27
4.3.1 CT RATIO......................................................................................28
4.3.2 Rated Load....................................................................................28
All new products sold to customers are warranted against defects in design, materials, and
workmanship for the life of their use to the original end user. If it is determined that the new
product defect is covered under this warranty, Advanced Power Technologies, LLC (the
Company) will repair, replace, or substitute an identical unit at its own discretion to the customer
at no charge. The Company requires the customer to ship the unit back to the factory for
diagnosis under all circumstances. In such event, the Company may, at its own discretion, decide
to provide the customer with a substitute unit which may be sent to the customer either from the
Companys factory or from an authorized representative or distributor from their inventory. All
expenses related to the shipment of defective units back to the Company or the provision of a
substitute unit to the customer are the responsibility of the customer. This expense may include,
but is not limited to, freight, insurance, Customs clearance, and duties. All expenses related to the
shipment of repaired units back to customers (or the provision of a new unit to the customer) will
be borne by the Company.
Product Upgrade Policy
From time to time, the Company makes product upgrades to add or enhance the performance of
the products. Customers of a particular product being issued an upgrade will be notified either by
the Company directly or through its authorized representatives or distributors. Customers who
have purchased an annual upgrade policy will receive all upgrades during the calendar year free
of charge. Customers who did not purchase the annual upgrade policy may purchase each unit
upgrade individually. The annual upgrade policy can be purchased at any time. Regardless of
whether the upgrade policy is purchased, the Company will make reasonable efforts to notify all
customers of all available upgrades.
Equipment Repair and Warranty
Repair costs of products not covered under this warranty are paid for by customers. Customers
are responsible for the cost of shipping the products to the Company located at: 215 State Route
10, BLDG 2, Randolph, NJ 07869, USA. All products repaired by the Company will continue to be
warranted against defects in material and workmanship for its installed life at the original end
user.
Limitations
The Company's warranty does not extend to (A) The Company's products subject to (i) improper
installation, connection, operation, maintenance, or storage; (ii) accident, damage, abuse, or
misuse; (iii) abnormal or unusual operating conditions or applications outside the specifications
for the product; (iv) a purpose or application in any way different from that for which the products
were designed; (v) repairs conducted by persons other than the Company employees or an
authorized representative or distributor; or (vi) modifications made to the product by the customer
or end user, (B) Equipment and products not manufactured by the Company. Such equipment
and products may be covered by a warranty issued by the respective manufacturer. This warranty
is in lieu of any other warranties, express or implied, including without limitation, any warranty of
merchantability or fitness for a particular purpose, and is in lieu of any and all other obligations or
liability of the Company. Under no circumstances shall the Company be liable for any accidental
or consequential damages or for any other loss, injury, damage, or expense of any kind including
loss of profits arising hereunder. To the extent any court, arbitration panel, or other governmental
body of competent jurisdiction shall declare any provision of this warranty invalid or
unenforceable by reason of a rule of law or public policy, all the other provisions hereof shall
remain in full force and effect.
TTC-1000
9 CLEAR WINDOW NO TEXTURE
ALARM
ACTIVE
YES NO RS-232
10
1 2 3 4 5 6 7 8
1. UP arrow button for navigating forward into menu categories and increasing settings.
2. DOWN arrow button for navigating backward into menu categories and decreasing settings.
3. LEFT arrow button used for moving to the next character to the left when changing settings.
4. RIGHT arrow button used for moving to the next character to the right when changing
settings.
5. YES button is used to enter a menu category, request to change a setting, and acknowledge
a setting change.
8. ALARM indicator is a red LED that illuminates whenever an alarm condition is present.
Alarms can be caused by a failure detected in the electronics, or a broken temperature
probe. In NEMA 4 mounting models, this indicator will flash when using the light activated
Min/Max reset feature.
TB4 TB5
_ 1 1
2 Wire
A1 RS-485
+ 2 2
DNP 3.0
_ 3
A2 - or -
+ 4 Rx
_ 5
A3 Fiber connection
+ 6 Tx
(2 ST Connectors)
Analog Output DNP Output
connections connections
on daughter on daughter
card card
Main circuit TB3
1 Power In
board
2 38 to 160VDC or 120VAC
3 Aux CT Input
4 Must use EXTERNAL CT Supplied
TB2
NC
1
2 To Alarm TTC-PROBE-YY-XXX
COM
N/C 1 NO 3 RED REF RTD
Rx 2 4 BLK
Tx 3 5 WHT
Front Panel N/C 4 6 TTC-PROBE-YY-XXX
DB-9 REF 7
GROUND 5 RED REF RTD
RS-232 N/C 6 TMP 8 BLK
RTS 7 COM 9 WHT
REF 10 TTC-PROBE-YY-XXX
CTS 8
TMP 11
N/C 9 RED
REF RTD
COM 12 BLK
WHT
Shield TTC-PROBE-YY-XXX
TB3
1 Power In
2 38 to 160VDC or 120VAC
NC 3
COM
4 To Alarm
NO 5
6 Aux CT Input
7 Must use EXT ERNAL CT Su pplied
TB4
1
TB5 IN2
_ 1
2
A1 3
+
_
2
4 IN1
3
A2 + 4
_ 5 Rx Fiber connection
A3 + 6 (2 ST Connectors)
Tx
- OR -
TB2
B 1 2 Wire
A 2 RS-485 TTC-PROBE -YY-XXX
Analog Output:
Selectable, 0 to 1 mA or 4 to 20 mA current source referenced to chassis
ground
Maximum load 9,500 ohms for 0 to 1 mA and 450 ohms for 4 to 20 mA
EMI Withstand:
ANSI C37.90.2
Dielectric Withstand:
1500 VDC for 10 seconds
Electrostatic Discharge:
IEC 801-2
Timers:
Output and Load Pick Up Timer: 0 to 255 seconds (actual minimum delay 32
msec)
Optically Isolated Inputs:
External wetting required. Picks up between 38 and 160 VDC. Maximum input
160 VDC.
Fiber Optic Interface:
Transmit/Receive Wavelength 850nm. Supports 50 or 62.5 micron multi-mode
fiber. Optical budget is 9.1 dB. Modulation is Non Return to Zero (NRZ).
1 Single Probe
2 Dual Probe
3 AUX CT, Single Probe
4 AUX CT, Dual Probe
6 Three Probe (NEMA)
7 Three Probe w/AUX CT (NEMA)
6.0 in.
TTC-1 0 0 0
4.779
ALARM
ACTIVE
3.558
YES NO RS-232
Set
Screw
0.40
7.559
TB5 A1 A2 A3
+ - + - + -
3.558 3.7
Panel
Case
GROUND
TB4
IN2 IN1 TB1B N C N
C
OUT 6
O
N
C
C
OUT 5
N
O
N
C
C
OUT 4
N
O
TB1A N
C
C
OUT 3
N
O
N
C
C
OUT 2
N
O
N
C
C
OUT 1
N
O GROUND
Cutout
PROBE1 PROBE2 PROBE3
Rx
Tx
Rpt
TB2 TB 3
C T R C T R C T R B A Rx Tx
O M E O M E O M E AUX CT
DNP ALARM POWER
M P F M P F M P F
7.00
5.00
Oblong
0.312 X 0.500
Lexan Window
12.75
5.25
0.000
14.000
13.375
12.628
10.753
0.516
10 PLACES
7.000
6.000
5.000
4.250
2.375 45.0
2 PLACES
0.625
0.000
0.000 2.000
Aux CT Power
TB5 A1 A2 A3 4 3 2 1 TB3
+ - + - + - TB2
N
C
C N
O
N
C
C N
O
N
C
C N
O
TB1A TB1
GROUND
OUT 3 OUT 2 OUT1
Rx
Tx
Rpt
TB3
Figure 3.4b: NEMA Power Connections
Tx
AUX CT
ALARM POWER
Washer Probe
Snap Elbow (Included) Spring Washer Sleeve Thermometer Well
(Included) (Included) (Included)
Probe
Brass Fittings
(Included)
Flexible Conduit
Not Included
Tank Wall
C T R C T R C T R N C N
O M E O M E O M E O O C
M P F M P F M P F M TB4 TB1B N
IN2 IN1 C N N C N N C
GROUND C O C O C
12 11 10 9 8 7 6 5 4 3 2 1 OUT 6 OUT 5 OUT 4
PROBE1 PROBE 2 PROBE3
TB2
TB 2
B A Rx
C T R C T R C T R
O M E O M E O M E DNP
M P F M P F M P F
TB1
NOTE:
You must use all temperature probes for proper operation. The unit will
continuously alarm if you fail to use all probes.
If a probe is unavailable, you can use two 1,000 ohm resistors. One end of
one resistor to REF, the end of the second resistor to TMP. Tie the loose
end of both resistors to COM.
It is noted that probes can be supplied from lengths of 10 feet to 250 feet. When
using existing substation wiring with probe lengths less than 250 feet, it is
important to connect the probes shield drain wire to the shield the cable and
observe that the total wiring length does not exceed 250
feet. Also it is important to ensure that the TTC-1000s Advanced Power Technologies
TTC-1000
ALARM
terminates as Temperature
Probe
shown in Figure
3.11. Substation
Cable
12 11 10 9 8 7 6 5 4 3 2 1 TB2 4 3 2 1 TB3
TB1A 9 8 7 6 5 4 3 2 1 9 8 7 6 5 4 3 2 1 TB1
Probe Drain
TB 5 A1 A2 A3
Aux CT Power + - + - + -
4 3 2 1 TB3
TB2 N
C
C N
O
N
C
C N N
O C
C N
O GROUND
OUT 3 OUT 2 OUT 1
Rx
Tx
Rpt
TB3
Tx
TB1A TB1 AUX CT
ALARM POWER
N C N N C N N C N N C N N C N N C N
C O C O C O C O C O C O
GROUND
C T R C T R C T R Rx
O M E O N E O N E Alarm Tx
M P F M F F M F F
Rpt
12 11 10 9 8 7 6 5 4 3 2 1 TB 3
TB2 Tx
AUX CT
ALARM POWER
PIN FUNCTION
1 No connection
2 Receive Data
3 Transmit Data
4 No connection
5 Ground
6 No connection
7 Request to send
8 Clear to send
9 No connection
A3 A2 A1
- + - + - + TB1A N C N N C N N C N
C O C O C O GROUND
OUT 3 OUT 2 OUT1
TB5
NEMA Panel
DO DO
/RI /RI
TB4
A B
PT-PT
TXD
REPEAT
Tx
RXD
Rx
- + - + N C N N C N N C N N C N N C N N C N
C O C O C O C O C O C O
IN2 IN1
4 SETTINGS
Settings can be made either through the front panel or using a PC equipped with
terminal emulation software. Proper operation of the TTC-1000 has been verified
with Windows Terminal, HyperTerminal and Procomm. For settings through a PC
you will need a female to male DB-9 null modem cable. The TTC-1000 is fixed to
communicate at 9600 bits/sec with 8 bits, no parity and one stop bit.
ENTER PROGRAM
PASSWORD=0
You cannot enter PROGRAM unless you enter the correct password. The TTC-
1000 recognizes two passwords, one programmed and a super user password.
The password programmed at the factory is 0000. The super user password is
0905 and cannot be changed.
First, you must press YES to begin entering the password. The zero will flash.
Use the or buttons to scroll between the digits. Each digit moved to will
flash. Use the or arrow buttons to scroll through the digits 0 9. Press YES
after you have entered all four digits.
If the password is correct, you will see the 1 st setting, SP11PICKUP. Pressing the
NO button at any time will bounce you back to the password entry display.
If the password is incorrect the display will read:
WRONG PASSWORD
PASSWORD=0
There is no limit to the number of times you may try to enter a password.
Enter Code:
Where:
TWindingU = Ultimate calculated winding temperature
TRTO = Hot Spot Rise over Top Oil temperature at rated load
Load = Measured load current
CTRatio = Primary CT ratio
Rated Load = Rated load current
m = 1.0 for directed FOA or FOW, 0.8 for all other cooling
TTopOil = Measured Top Oil temperature
It is noted that the Hot Spot Rise over Top Oil at rated load is not always
available. In this case we recommend using a value between 18 to 22 C.
To accommodate the transient affect of changing load current, the winding
temperature can be estimated at any point in time by entering the winding time
constant. Therefore, the displayed winding temperature is calculated as follows:
1
ANSI C57.91-1995
Where:
TWinding(t) = Winding temperature at time t
TWindingU = Ultimate winding temperature using equation [1] above
TWindingI = Initial winding temperature using equation [1] above
W = Winding time constant in minutes
Because data to calculate W may not be available, the recommended setting for
the winding time constant is between 5 to 10 minutes.
4.3.1 CT RATIO
The CT RATIO is the CT ratio of the bushing CT which the split core CT is
applied to. The CT ratio must be relative to 1. Therefore, if the CT ratio is 300:5
the CT ratio to enter is 60.
Programming from the front panel, press the arrow button until the setting 025
is displayed:
Press the YES button. The first digit will flash. Use the or arrow buttons to
scroll through the digits 0 9. Use the or buttons to scroll between the
digits. Each digit moved to will flash. Press YES after you have entered all four
digits.
For programming from a PC just type the CT ratio on the Enter: line as follows:
Enter:104/60
Programming from the front panel, press the arrow button until the setting 0126
is displayed:
PRGM SETTING
28 026 V5.202, June 8, 2006
RATED LOAD=00000
Press the YES button. The first digit will flash. Use the or arrow buttons to
scroll through the digits 0 9. Use the or buttons to scroll between the
digits. Each digit moved to will flash. Press YES after you have entered all digits.
For programming from a PC just type the Rated Load on the Enter: line as
follows:
Enter:105/1473
This will program the Rated Load to 1473 Amps.
Programming from the front panel, press the arrow button until the setting 027
is displayed:
Press the YES button. The first digit will flash. Use the or arrow buttons to
scroll through the digits 0 9. Use the or buttons to scroll between the
digits. Each digit moved to will flash. Press YES after you have entered all digits.
For programming from a PC just type the Winding Rise @ Rated Load on the
Enter: line as follows:
Enter:106/20
This will program the hot spot rise to 20 degrees Celsius.
For programming from a PC just type the Winding TC on the Enter: line as
follows:
Enter:107/7
This will program the winding rise time constant to 7 minutes.
Programming from the front panel, press the arrow button until the setting 029
is displayed:
Press the YES button. The first character will flash. Use the or arrow buttons
to scroll between NO and YES. Press YES when you have made the correct
selection.
For programming from a PC just type the Cooling Type on the Enter: line as
follows:
Enter:108/1
This will program the Cooling Type to directed FOA/FOW. Enter 0 for all other
cooling types.
WNDG TEMP AT 5A
WINDINGCAL = 45c
30 V5.202, June 8, 2006
Read the number where 45 appears above, record this number. This is the
computed value of the current top oil plus the rated rise of the transformer at
5 amperes of CT current.
Press the arrow button once. The display will read:
07/21/03 13:35
P 1 T O P O I L 2 5 C
Where the number in place of 25 is the current top oil temperature
07/21/03 13:35
W I N D I N G = 4 5 C
This feature compares the computed result for 5 amperes as compared to the
actual result of 5 amperes in the CT. The above assumes the rated rise was
20C, the actual rise will be the rise entered as Rated Rise in 4.3.3 above.
NOTE: The MIN/MAX log should always be reset after changing probe
names. This is especially critical for the LTCDIFF as its range is different
from the TOP OIL, WINDING, BOTMOIL and AMBIENT temperatures.
Programming from the front panel, press the arrow button until the setting 096
is displayed:
Press the YES button. The first character will flash. Use the or arrow buttons
to scroll through the available names. Press YES after you have made your
selection.
When programming from a PC the following are the valid codes for the probe
names available are shown in the table above.
Enter:109/0
In a similar manner, the remaining probes would be on program lines 110 and
111.
SPpn Pick Up
Temperature
Time
SPpn
SPpn Pick
Up
Temperature
Time
SPpn
Press the YES button. The first digit will flash. Use the or arrow buttons to
scroll through the digits. Use the or buttons to scroll between the digits.
Each digit moved to will flash. The first digit will scroll -, 0, 1. The second digit
will scroll 0 to 9 if the first digit is 0, 0 to 6 if the first digit is 1 and last digit is 0, 0
to 5 if the first digit is 1 and the last digit is greater than 0. The last digit will scroll
0 to 9 if the first two digits are less than 16. Press YES after you have entered all
digits.
After setting the pickup temperature, press the arrow button once:
Use the procedure described above to change the drop out setting.
For programming from a PC just type the desired temperature on the Enter: line
as follows:
Enter:1/75
This will program SP11 pickup to 75
C.
Enter:2/70
This will program SP11 drop out to 70
C.
Press the YES button. The first digit will flash. Use the or arrow buttons to
scroll through the digits. Use the or buttons to scroll between the digits.
Each digit moved to will flash. The first digit will scroll -, 0, 1. The second digit
will scroll 0 to 9 if the first digit is 0, 0 to 6 if the first digit is 1 and last digit is 0, 0
to 5 if the first digit is 1 and the last digit is greater than 0. The last digit will scroll
0 to 9 if the first two digits are less than 16. Press YES after you have entered all
digits.
After setting the pickup temperature, press the arrow button once:
Use the procedure described above to change the drop out setting.
For programming from a PC just type the desired temperature on the Enter: line
as follows:
Enter:25/85
This will program WSP1 pickup to 85
C.
Enter:26/80
This will program WSP1 dropout to 80
C.
Temperature
supervise the LTC set point. The above example shows that the LTCDIFF1 & 2
set points do not pickup until after the timer is complete. If the differential
temperature drop down below the pick up temperature while the timer is in
progress, the timer will reset. This timer allows the LTCDIFF1 & 2 set points to
ride through daylight heating and hence permits a more sensitive setting. The
above example shows that the LTC set point does not drop out because the
difference between the LTC Tank temperature and the Top Oil temperature does
not drop down to the LTCDIFF1 or 2 drop out temperature set point.
NOTE: The LTCDIFF and LTCDIFF1 & 2 temperature displayed is the
calculated differential. The corresponding analog output tracks this
differential temperature.
All LTCDIFF temperature set points are designed to read negative as well as
positive because sometimes the LTC tank runs cooler than the top oil
temperature. It is recommended that you monitor the LTCDIFF temperature for a
period of time to determine the normal operating differential for the transformer. A
good rule of thumb is to set the LTCDIFF pickup temperature from 3 to 7 degrees
higher than the observed operating differential. For LTCDIFF1 & 2, the sensitivity
NOTE:
1. In single probe versions, all LTCDIFF pickup and dropout settings
display N/A.
2. Be careful to check that the LTCDIFF & LTCDIFF1 & 2 pickup and
dropout set points are never set to greater than 20 or less than 20.
Erroneous operation of the LTCDIFF pickup or dropout will result if
these set points are set beyond the stated range.
Use the procedure described above to change the drop out setting.
For programming from a PC just type the desired temperature on the Enter: line
as follows:
Enter:33/3
This will program LTCDIFF pickup to 3
C.
Enter:34/-3
This will program LTCDIFF drop out to -3
C.
For programming from a PC just type the LTC pickup timer value on the Enter:
line as follows:
Load Pick Up
Current
Load Drop Out
Current
Time
Timer Resets
Load Pickup
Timer
Load Pickup
Set Point
Programming load set points from the front panel, press the or arrow buttons
until the setting 044 is displayed:
Press the YES button. The first digit will flash. Use the or arrow buttons to
scroll through the digits. Use the or buttons to scroll between the digits.
Each digit moved to will flash. Press YES after you have entered all digits.
After setting the pickup current, press the arrow button once:
Use the procedure described above to change the drop out setting.
The second load set point, LSP2, can be changed by pressing the arrow
button and following the above procedure.
Enter:39/4.0
This will program LSP1 pickup to 4.0A.
Enter:40/3.3
This will program LSP1 drop out to 3.3A.
NOTE: Load pickup and drop out set points are the CT busing secondary
current and must always be entered with a decimal point and trailing 1/10s
digit. For 3 amps you must enter 3.0. For .5 amps you must enter 0.5.
Press the YES button. The first digit will flash. Use the or arrow buttons to
scroll through the digits 0 9. Use the or buttons to scroll between the
digits. Each digit moved to will flash. Press YES after you have entered all digits.
The LSP2 Pickup Timer, can be changed by pressing the arrow button and
following the above procedure.
For programming from a PC just type the load set point pickup timer value on the
Enter: line as follows:
Enter:43/120
This will program the Load pickup timer to 120 seconds.
Signal
Applied to
Input n
Debounce
Timer
INn
Signal
Applied to
Input n
Debounce
Timer
INn
The second input, IN2, can be changed to LEVEL or PULSE MODE by pressing
the arrow button and following the above procedure.
For programming from a PC just type the input detection, IN1 or IN2 CNTRL,
mode on the Enter: line as follows:
Enter:45/1
This will program the IN1 CNTRL to PULSE MODE. Type 0 for LEVEL MODE.
NOTE: Do not use the inversion operator on individual set points when
remote control through DNP3.0 and fail-safe cooling control is desired. The
INVERT setting must be used on each output requiring fail-safe cooling
control when remote cooling control through DNP3.0 is required. The use
of the inversion operator on a set point will not be recognized by the
remote control functions resulting in the cooling to be de-energized.
There are additional settings available that enhance the flexibility of the
programmable logic. These functions include:
Output Timers for delaying pickup of the output relays.
Output Inversion that permits overall inversion of logic equations controlling
outputs. This is particularly useful for fail safe operation.
Use the or buttons to scroll to the AND/OR logic operator. The operator will
flash. Use the or arrow buttons to scroll between the and + operators.
Selecting will AND SP11 with any other set point or operand controlling the
same output. Use to permit or block an output from operating. Selecting + will
OR SP11 with any other set point or operand controlling the same output. Use +
when you have a number of operands which can command the same output:
Use the or buttons to scroll to the output #. The output number will flash.
Use the or arrow buttons to scroll from 0 to 4. Setting the output number to
zero will have the effect of de-assigning the set point. The following illustrates the
change to output 1:
Press YES after you have set the inversion, AND/OR and output number.
The remaining set points, SP12, SP13, SP14, SP21, SP22, SP23 and SP24 can
be assigned by pressing the arrow button and following the above procedure.
For programming from a PC just type the SP11 assignment on the Enter: line
as follows:
Enter:65/0/1/1
This will assign SP11 Ored to OUT1. To assign !SP11 Anded OUT1:
Enter:55/1/0/1
Consult the setting sheets to assign the remaining temperature set points SP12
through SP24.
Use the or buttons to scroll to the AND/OR logic operator. The operator will
flash. Use the or arrow buttons to scroll between the and + operators.
Selectingwill AND WSP1 with any other set point or operand controlling the
same output. Use to permit or block an output from operating. Selecting + will
OR WSP1 with any other set point or operand controlling the same output. Use +
when you have a number of operands which can command the same output:
Use the or buttons to scroll to the output #. The output number will flash.
Use the or arrow buttons to scroll from 0 to 4. Setting the output number to
zero will have the effect of de-assigning the set point. The following illustrates the
change to output 1:
Press YES after you have set the inversion, AND/OR and output number.
The remaining set points, WSP2, WSP3 and WSP4 can be assigned by pressing
the arrow button and following the above procedure.
For programming from a PC just type the WSP1 assignment on the Enter: line
as follows:
Enter:81/0/1/1
This will assign WSP1 ORed to OUT1. To assign !WSP1 Anded OUT1:
Enter:81/1/0/1
Consult the setting sheets to assign the remaining temperature set points WSP2
through WSP4.
Use the or buttons to scroll to the AND/OR logic operator. The operator will
flash. Use the or arrow buttons to scroll between the and + operators.
Selecting will AND LTC with any other set point or operand controlling the
same output.
Use to permit or block an output from operating. Selecting + will OR LTC with
any other set point or operand controlling the same output. Use + when you have
a number of operands which can command the same output:
Use the or buttons to scroll to the output #. The output number will flash.
Use the or arrow buttons to scroll from 0 to 4. Setting the output number to
zero will have the affect of de-assigning the set point. The following illustrates the
change to output 4:
Press YES after you have set the inversion, AND/OR and output number.
Enter:77/0/1/4
This will assign LTCDIFF ORed to OUT4.
Use the or buttons to scroll to the AND/OR logic operator. The operator will
flash. Use the or arrow buttons to scroll between the and + operators.
Selecting will AND LSP1 with any other set point or operand controlling the
same output. Use to permit or block an output from operating. Selecting + will
OR LSP1 with any other set point or operand controlling the same output. Use +
when you have a number of operands which can command the same output:
Use the or buttons to scroll to the output #. The output number will flash.
Use the or arrow buttons to scroll from 0 to 4. Setting the output number to
Press YES after you have set the inversion, AND/OR and output number.
LSP2 can be assigned by pressing the arrow button and following the above
procedure.
For programming from a PC just type the LSP1 assignment on the Enter: line
as follows:
Enter:85/0/1/1
This will assign LSP1 ORed to OUT1. To assign !LSP1 Anded OUT1:
Enter:85/1/0/1
Consult the setting sheets to assign LSP2.
The first character is the inversion operator. Use the or arrow buttons to scroll
between the inversion operator, !, and a blank space. While the inversion
operator is displayed, the ! character will flash.
Use the or buttons to scroll to the AND/OR logic operator. The operator will
flash. Use the or arrow buttons to scroll between the and + operators.
Use the or buttons to scroll to the output #. The output number will flash.
Use the or arrow buttons to scroll from 0 to 4. Setting the output number to
zero will have the affect of de-assigning the set point. The following illustrates the
change to output 1:
Press YES after you have set the inversion, AND/OR and output number.
IN2 can be assigned by pressing the arrow button and following the above
procedure.
For programming from a PC just type the IN1 assignment on the Enter: line as
follows:
Enter:93/0/1/1
This will assign IN1 ORed to OUT1. To assign !IN1 Anded OUT1:
Enter:93/1/0/1
Consult the setting sheets to assign IN2.
Use the or buttons to scroll to the AND/OR logic operator. The operator will
flash. Use the or arrow buttons to scroll between the and + operators.
Selecting will AND OUT1 with any other set point or operand controlling the
same output. Use to permit or block an output from operating. Selecting + will
OR OUT1 with any other set point or operand controlling the same output. Use +
when you have a number of operands which can command the same output:
Use the or buttons to scroll to the output #. The output number will flash.
Use the or arrow buttons to scroll from 0 to 4. Setting the output number to
zero will have the affect of de-assigning the set point. The following illustrates the
change to output 2:
OUT2, OUT3, OUT4, OUT5, & OUT6 can be assigned by pressing the arrow
button and following the above procedure.
For programming from a PC just type the OUT1 assignment on the Enter: line
as follows:
Enter:87/0/1/2
This will assign OUT1 ORed to OUT2. To assign !OUT1 Anded OUT2:
Enter:87/1/0/2
Consult the setting sheets to assign OUT2, OUT3, OUT4, OUT5, or OUT6.
The first time, 00:00 is the pickup time. The second time, 00:00 is the drop out
time. OUT0 is the output the time set point is assigned to. In this case TSP1 is
not assigned.
Press the YES button. The 10s hour digit will flash. Use the or arrow buttons
to set this digit. Use the button to move to the 1s hour digit and observe that
it flashes. Again use the or arrow buttons to set this digit. Scroll to the 10s
minute digit by pressing the button and observe that it flashes. Use the or
arrow buttons to set this digit. Scroll to the 1s minute digit and observe that it
flashes. Use the or arrow buttons to set this digit. Scroll once more to the
output number by pressing the button. Use the or arrow buttons to set the
output number from 0 to 4.
The following shows TSP1 set to pickup output 1 at 14:00 and drop out output 1
after 14:15:
TSP2 and TSP3 are set using the same procedure described above.
For programming from a PC just type the TIME1 setting and assignment on the
Enter: line as follows:
Enter:95/09:00/09:15/2
This will assign TIME1 ORed to OUT2. Consult the setting sheets to assign
TIME2 and TIME3.
NOTE:
1. ALL 4 DIGITS OF THE TIME SET POINT PICKUP AND DROP OUT TIMES
MUST BE ENTERED TO SET THE CORRECT TIME.
2. IF USING ALTERNATE, THE STOP TIME OF THE FIRST SET POINT
MUST OVERLAP THE START TIME OF THE SECOND SET POINT.
3. OUT5 AND OUT6 CAN NOT BE ASSIGNGED TO ALTERNATE
4.6.2.2 Time Set Point Counter Setting
The time set point counter sets the frequency which the time set points will be
allowed to pick up. It is settable from 0 to 255. A setting of 0 or 1 will operate the
time set points on a daily basis.
Programming time set point counter from the front panel, press the or arrow
buttons until the setting 125 is displayed:
Press the YES button. The first digit will flash. Use the or arrow buttons to
scroll through the digits 0 9. Use the or buttons to scroll between the
digits. Each digit moved to will flash. Press YES after you have entered all digits.
For programming from a PC just type the time set point counter value on the
Enter: line as follows:
Enter:131/30
This will set all of the time set points programmed to pickup every 30 th day.
Press the YES button. The first digit will flash. Use the or arrow buttons to
scroll through the digits 0 9. Use the or buttons to scroll between the
digits. Each digit moved to will flash. Press YES after you have entered all digits.
For programming from a PC just type the output timer value on the Enter: line
as follows:
Enter:36/15
This will set the delay to pickup output 1 by 15 seconds. Consult the setting
sheets to program the pickup timers for OUT2, OUT3, OUT4, OUT5, & OUT6.
For programming from a PC just type the setting for output invert on the Enter:
line as follows:
Enter:98/1
This will set OUT1 to INVERT. Type 0 for OUT1 not INVERT.
Consult the setting sheets to change INVERT OUT2, INVERT OUT3, INVERT
OUT4, INVERT OUT 5, or INVERT OUT6.
Programming from the front panel, press the or arrow button until the setting
119 is displayed:
Press the YES button. The first character will flash. Use the or arrow buttons
to scroll between PCKUP, SUPVS or UNCHG.
For programming from a PC just type the setting for Output Control with Alarm on
the Enter: line as follows:
Enter:49/2
This will set OUT1 supervised with a Device or Temperature Probe Alarm. Type
1 to pickup OUT1 with a Device or Temperature Probe Alarm, or 0 to leave the
output unchanged with a Device or Temperature Probe Alarm.
Consult the setting sheets to change output control for OUT2, OUT3, OUT4,
OUT5 OR OUT6.
Programming from the front panel, press the or arrow button until the setting
095 is displayed:
Press the YES button. The first character will flash. Use the or arrow buttons
to scroll between 1 2, 1 3, 1 4, 2 3, 2 4, 3 4, or DSABL:
For programming from a PC just type the setting for ALTERNATE on the Enter:
line as follows:
Enter:112/1
Setting from the front panel, press the or arrow button until the setting 134 is
displayed:
Press the YES button. The first character will flash. Use the or arrow buttons
to scroll between MAN OFF, MAN ON or AUTO.
Setting outputs from AUTO to MANUAL from a PC will only allow the output to be
dropped out. It is not possible to pickup an output when setting from a PC. To
change from AUTO to MANUAL using a PC just type the setting for auto or
manual on the Enter: line as follows:
Enter:48/1
This will set OUT1 to MANUAL OFF. Type 0 to return OUT1 to AUTO.
Consult the setting sheets to change AUTO to MANUAL for OUT2, OUT3, and
OUT4, OUT5 AND OUT6.
Press YES when you have made the correct selection. Selecting DSABL will
block the device alarm relay and the front panel alarm LED from illuminating.
For programming from a PC just type the setting for device alarm enable on the
Enter: line as follows:
Enter 129/1
This will disable the device alarm. Type 0 to enable the device alarm.
Setting from the front panel, press the or arrow button until the setting 116is
displayed:
Press the YES button. The first character will flash. Use the or arrow buttons
to scroll between ENABL (enable) and DSABL (disable).
Press YES when you have made the correct selection. Selecting DSABL will
block the device alarm relay and the front panel alarm LED from illuminating.
However, the front panel will display the alarm if present.
Enter:130/1
This will disable the temperature probe alarm. Type 0 to enable the alarm.
Press the YES button. The first character will flash. Use the or arrow buttons
to scroll between ENABL (enable) and DSABL (disable).
Press YES when you have made the correct selection. Selecting DSABL will
block the device alarm relay and the front panel alarm LED from illuminating.
However, the front panel will display the alarm if present.
For programming from a PC just type the setting for manual mode alarm enable
on the Enter: line as follows:
Enter:131/1
This will disable the manual mode alarm. Type 0 to enable the alarm.
Press the YES button. The first character will flash. Use the or arrow buttons
to scroll between ENABL (enable) and DSABL (disable).
Press YES when you have made the correct selection. Selecting DSABL will
block the device alarm relay and the front panel alarm LED from illuminating.
However, the front panel will display the alarm if present.
For programming from a PC just type the setting for the winding circuit alarm
enable on the Enter: line as follows:
Enter:128/1
This will disable the winding circuit probe alarm. Type 0 to enable the alarm.
Press the YES button. The 10s month digit will flash. Use the or arrow
buttons to set this digit. Use the button to move to the 1s month digit and
observe that it flashes. Again use the or arrow buttons to set this digit. Press
the YES button after entering the month.
Press the YES button. The 10s day digit will flash. Use the or arrow buttons
to set this digit. Use the button to move to the 1s day digit and observe that it
flashes. Again use the or arrow buttons to set this digit. Press the YES button
after entering the day.
Press the arrow button to set the year:
Press the YES button. The 10s year digit will flash. Use the or arrow buttons
to set this digit. Use the button to move to the 1s year digit and observe that
it flashes. Again use the or arrow buttons to set this digit. Press the YES
button after entering the year.
Enter:126/8:05
This will set the time to 8:05AM. The time entered must be a 4 digit international
time.
For setting the date from a PC just type the current date on the Enter line as
follows:
Enter:127/28/03
This will set the date to July 28, 2003. The date must be entered with a total 6
digits. A date entered of 5/3/03 will not register correctly. The correct entry for
May 3, 2003 is:
Enter:127/03/03
Programming from the front panel, press the or arrow buttons until the setting
140 is displayed:
Press the YES button. The first digit will flash. Use the or arrow buttons to
scroll through the digits 0 9. Use the or buttons to scroll between the
digits. Each digit moved to will flash. Press YES after you have entered all four
digits.
For programming from a PC just type the new password on the Enter: line as
follows:
Enter:139/2767
Press the YES button. The first digit will flash. Use the or arrow buttons to
scroll through the digits 0 9. Use the or buttons to scroll between the
digits. Each digit moved to will flash. Press YES after you have entered all four
digits.
For programming from a PC just type the Unit ID on the Enter: line as follows:
Enter:133/TX2767
5 TELEMETRY OPTIONS
This section will discuss the various telemetry options available, their use and
any relevant settings. The TTC-1000 can be optionally equipped with either
current loop outputs and a RS-485 DNP3.0 communications interface. All TTC-
1000s come equipped with a 9 pin DB-9 connector for RS-232 ASCII
communications. Temperature information can be retrieved through the RS-232
interface.
Press the YES button. The first character will flash. Use the or arrow buttons
to scroll between 0to1mA and 4to20mA.
For programming from a PC, enter PROGRAM through the main menu as
discussed in Section 4.2. Once in PROGRAM, type the setting for the
ANALGOUT range on the Enter: line as follows:
Enter:113
This will change the analog output range from 0 1 mA to 4 20 mA. Type 0 to
change to 0 1 mA.
Press the YES button. The first character will flash. Use the or arrow buttons
to scroll between P1, P2 and WINDING.
Press YES when you have made the correct selection. A2 source can be
selected by pressing the arrow button and following the above procedure. The
setting for A3 source will appear if installed.
For programming from a PC, enter PROGRAM through the main menu as
discussed in Section 4.2. Once in PROGRAM, type the setting for the A1
SOURCE on the Enter: line as follows:
Enter:114
This will change the source for analog output A1 to WINDING. Type 0 to change
the source to P1 or 1 to change the source to P2.
Press the YES button. The first character will flash. Use the or arrow buttons
to scroll between YES and NO.
Enter:1341
This will change the scaling from normal to negative. Type 0 to change back to
normal scaling.
5.2 DNP3.0
Units equipped with the optional DNP3.0 communications interface contain a
plug-in Communications Processor module. The module contains a separate
microprocessor to handle all overhead functions associated with the DNP3.0
protocol without affecting operation of the transformer cooling control and
monitoring. The module contains either a half duplex, full duplex isolated RS-485,
multi-mode fiber optic asynchronous communications interface capable of
supporting multi-drop topologies. RS-485 interfaces differ from RS-232 in that
RS-485 uses a differential receiver and transmitter pair. This permits RS-485
links to send and receive data over much greater distances as long as some
simple rules are followed. See Sections 3.7.3 and 3.7.4 for connections and
jumper settings.
After making the proper connections to the TTC-1000, there are only two settings
that need to be made: Node Address and Baud Rate. Node Addresses can be
any number from 0 to 65535. Please consult the DNP3.0 reference materials as
some higher order addresses are reserved for broadcast messages.
Baud Rates can be set to either 1200, 2400, 9600 or 19200. It is recommended
that both Node Address and Baud Rate settings be made before attempting to
communicate, however these settings can be changed on-the-fly without
powering down the TTC-1000.
The TTC-1000 implements DNP3.0 Level 1 communications. This includes Class
0 polls (Object 60 Variation 1) of analog and binary output points. The TTC-1000
supports Object 1 Variation 2 binary outputs. Binary outputs include all
temperature and load set points along with the state of each output relay.
Because Variation 2 is supported, the TTC-1000 communicates whether or not
an output relay is under manual control by exerting the forced status bit for
these points only. The forced status bit is located in bit 4 of each binary output
octet transmitted to the Master. For Analog Outputs, the TTC-1000 supports
Object 30 Variation 4. These are 16 bit signed analog quantities without status.
Included in the Analog Output points are all temperatures equipped plus load
data if available. Also, the TTC-1000 uses two points to identify whether or not
the probe is measuring Top Oil, Heated Well, LTC Differential or Ambient
temperature. This is particularly useful for dual probe units. It is noted that Object
1 Variation 2 and Object 30 Variation 4 points cannot be read individually and
can only be read by a Class 0 poll.
In addition, the TTC-1000 supports the remote control of the four output relays.
The TTC-1000 supports both direct control (Object 10 Variation 0) and Select
Press the YES button. The first character will flash. Use the or arrow buttons
to scroll between 1200, 2400, 9600 and 19200.
For programming from a PC, enter PROGRAM through the main menu as
discussed in Section 4.2. Once in PROGRAM, type the setting for the BAUD
RATE on the Enter: line as follows:
Enter:117/2
This will change the BAUD RATE to 9600. Type 0 to change the BAUD RATE to
1200, 1 to change to 2400, or 3 to change to 19200.
Press the YES button. The first digit will flash. Use the or arrow buttons to
scroll through the digits 0 9. Use the or buttons to scroll between the
Enter:118/7
Press the YES button. The first character will flash. Use the or arrow buttons
Press YES when you have made the correct selection. Selecting ENABL will
block the remote control of the output relays.
For programming from a PC, enter PROGRAM through the main menu as
discussed in Section 4.2. Once in PROGRAM, type the setting for remote block
on the Enter: line as follows:
Enter:119/1
This will enable remote block. Type 0 to disable remote block.
07/29/05 13:15
P1 TOP OIL 45C
RST MIN/MAX
PUSH YES TO RST
The name set for P1 will appear on the display as shown above.
07/29/05 13:15
P1 TOP OIL 45C
07/29/05 13:15
P2 WINDING 58C
RST MIN/MAX
PUSH YES TO RST
The name set for P1 and P2 will appear on the display as shown above.
07/29/05 13:15
P1 TOP OIL
07/29/05 13:15
WINDING
07/29/05 13:15
LOAD 453 A
WINDING MIN=
43
C
WINDING MAX=
83C
RST MIN/MAX
PUSH YES TO
The name set for P1 will appear on the display as shown above.
LTCDIFF MAX= 02
C LTCDIFF MIN= -08 C
@ 17:42 07/18/05 @ 03:15 07/29/05
WINDING MIN= 43
C WINDING MAX= 83C
@ 03:15 07/29/05 @ 17:42 07/18/05
RST MIN/MAX
PUSH YES TO
R S T as shown above.
The name set for P1 and P2 will appear on the display
The name set for P1, P2 and P3 will appear on the display as shown above.
RST MIN/MAX
PUSH YES TO RST
To confirm that the min/max values are reset, the display will read:
MIN/MAX IS RST
VIEW SETTINGS
PUSH YES TO VIEW
Pressing the YES button will allow you to scroll through each parameter by using
the or arrow buttons. By pressing NO you will bounce back to the above
display.
After transmitting the data to the host computer, the TTC-1000 automatically logs
off. The user must press the Enter key to re-display the Main Menu.
NOTE: In single probe units, TEMP PROBE 2 & 3 NAMES=N/A.
VIEW STATUS
PUSH YES TO VIEW
To view the status of each operand you must first press YES. After pressing YES
you can use the or arrow buttons to scroll between the operands. Pressing
NO at any time will bounce you out of the display of status.
You must press the Enter key on your keyboard to display the Main Menu.
NOTE: Upload can be terminated by pressing the Esc key on your PC prior
to starting the file transfer.
NOTE: Upload can be terminated by pressing the Esc key on your PC prior
to starting the file transfer.
NOTE: HyperTerminal and Procomm first use CRC error checking for the
first two message packet reception tries. A good packet should be received
on the 2nd, 3rd or 4th try as both programs automatically switch to Check
Sum error checking. The TTC-1000 has a built in 60 second delay to wait for
retries. Should you wish to abort the reception, close all active terminal
emulation receive windows and press the ESC key followed by the Enter
key on your PC.
3. Select the Folder by clicking Browse to locate folder where the file is to be
stored and enter the file name. Select Xmodem protocol:
Press the YES button. The first digit will flash. Use the or arrow buttons to
scroll through the digits 0 9. Use the or buttons to scroll between the
digits. Each digit moved to will flash. Press YES after you have entered all four
digits.
For programming from a PC, enter PROGRAM through the main menu as
discussed in Section 4.2. Once in PROGRAM, type the setting for the time base
on the Enter: line as follows:
Enter:120/3600
Press the YES button. The first character will flash. Use the or arrow buttons
to scroll between YES and NO.
For programming from a PC, enter PROGRAM through the main menu as
discussed in Section 4.2. Once in PROGRAM, type the setting for P1 RECORD
on the Enter: line as follows:
Enter:121/1
This will add P1 to the log. Type 0 to remove from the log.
Press the YES button. The first character will flash. Use the or arrow buttons
to scroll between YES and NO.
For programming from a PC, enter PROGRAM through the main menu as
discussed in Section 4.2. Once in PROGRAM, type the setting for P2 RECORD
on the Enter: line as follows:
Enter:122/1
This will add P2 to the log. Type 0 to remove from the log.
Press the YES button. The first character will flash. Use the or arrow buttons
to scroll between YES and NO.
For programming from a PC, enter PROGRAM through the main menu as
discussed in Section 4.2. Once in PROGRAM, type the setting for P2 RECORD
on the Enter: line as follows:
Enter:123/1
This will add P2 to the log. Type 0 to remove from the log.
Press the YES button. The first character will flash. Use the or arrow buttons
to scroll between YES and NO.
For programming from a PC, enter PROGRAM through the main menu as
discussed in Section 4.2. Once in PROGRAM, type the setting for Calculated
Winding Record on the Enter: line as follows:
Enter:124/1
This will add Calculated Winding to the log. Type 0 to remove from the log.
Press the YES button. The first character will flash. Use the or arrow buttons
to scroll between YES and NO.
For programming from a PC, enter PROGRAM through the main menu as
discussed in Section 4.2. Once in PROGRAM, type the setting for LOAD
RECORD on the Enter: line as follows:
Enter:125/1
This will add Load to the log. Type 0 to remove from the log.
Select:
1. VIEW
2. PROGRAM (2/XXXX)
3. STATUS
4. UPLOAD SETTINGS
8. LOG OFF
Enter Code:
Press 6 followed by the Enter key. If no data is logged the data reported through
the terminal emulation program will show:
NO DATA
Should the log contain data, the terminal emulation program will show:
DATE,TIME,TOP OIL,WINDING,LOAD
4. Click Browse to find a Path to store the download and enter a file name and
click the Save button:
6. Click on Transfer, Capture Text and click Stop to halt the data capture:
5. Click the General button in the Column data format and click Finish:
Select:
1. VIEW
2. PROGRAM (2/XXXX)
3. STATUS
4. UPLOAD SETTINGS
8. LOG OFF
Enter Code:
Type 7/ followed by the password programmed or the super user password.
Press the Enter key. If the terminal emulation screen clears, you have entered an
incorrect password. Otherwise the screen will display:
FIRMWARE FILE TRANSFER IN PROGRESS. PRESS Any KEY TO ABORT.
PLEASE WAIT
LOADING FIRMWARE
3. Select Xmodem from the Protocol pull down list. Enter the Filename if in the
Folder indicated or click the Browse button to find the file:
5. The download will now begin. Clicking Cancel aborts the transfer:
7. Press the Enter key after 15 seconds to display the Main Menu:
8. If the Main Menu does not appear, check the front panel display to see if the
display is scrolling. If not de-energize the unit and re-energize. Wait 15
seconds. If the unit does not respond after 15 seconds call the factory at
(866) 563-6600 for assistance.
7. If the Main Menu does not appear, check the front panel display to see if the
display is scrolling. If not de-energize the unit and re-energize. Wait 15
seconds. If the unit does not respond after 15 seconds call the factory at
(866) 563-6600 for assistance.
! SP11 + OUT n
where n=1,2,3,4,5,6
! R-R1 + OUT n
where n=1,2,3,4,5,6
134 (!) R-R2 (*/+) TO Assigns an output to a R-R2 * OUT n R-R2 *
OUTn specific output using a OUT0
defined AND or OR logic ! R-R2 * OUT n
operator
R-R2 + OUT n
! R-R2 + OUT n
where n=1,2,3,4,5,6
135 OUT1CTRL Permits manual control AUTO, MAN OFF, MAN AUTO
of OUT1 ON
136 OUT2CTRL Permits manual control AUTO, MAN OFF, MAN AUTO
of OUT2 ON
137 OUT3CTRL Permits manual control AUTO, MAN OFF, MAN AUTO
of OUT3 ON
138 OUT4CTRL Permits manual control AUTO, MAN OFF, MAN AUTO
of OUT4 ON
139 OUT5TRL Permits manual control AUTO, MAN OFF, MAN AUTO
of OUT5 ON
140 OUT6TRL Permits manual control AUTO, MAN OFF, MAN AUTO
of OUT6 ON
141 PASSWORD Allows access to 4 digits 0000
112/2: 1 3
112/3: 1 4
112/4: 2 3
112/5: 2 4
112/6: 3 - 4
113 ANALGOUT Sets scaling of 113 0 to 1 mA
Analog output
11: 4 to 20 mA
DNP V3.00
DEVICE PROFILE DOCUMENT
Vendor Name: Advanced Power Technologies, LLC
Device Name: TTC-1000, Transformer Temperature Controller
Highest DNP Level Supported: Device Function:
IMPLEMENTATION TABLE
REQUEST RESPONSE
OBJECT (supported) (may generate)
Object Variation Function Qualifier Codes Function Qualifier Codes
Description
Number Number Codes (dec) (hex) Codes (dec) (hex)
10 0 Binary Output Status (Variation 0 is 1 (read) 06 (no range, or all)
used to request default variation)
12 1 Control Relay Output Block 3 (select) 17, 28 129 (response) echo of request
4 (operate)
5 (direct op)
6 ( dir. op, noack)
60 1 Class 0 Data 1 (read) 06
80 1 Internal Indications 2 00 (start-stop)