Академический Документы
Профессиональный Документы
Культура Документы
Service Instructions
\
Please ensure that this manual is read and uderstood before commencing installation. Failure to comply with the
issues listed below and details printed in this manual can cause product/property damage, severe personal injury,
and/or loss of life. Ensure all requirements below are understood and fulfilled (including detailed information found
in manual subsections).
Safety Terminology
The following terms are used throughout this manual to bring attention to the presence of potential hazards or important product
information. Please heed the advice given!
IMPORTANT
5581 750 v1.3
2
Downloaded from www.Manualslib.com manuals search engine
Contents
Index
Page
General information
Product information .............................................................................................................. 7
3
Downloaded from www.Manualslib.com manuals search engine
Contents
Index (cont.)
Initial start-up
Steps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Further step-by-step instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
4
Downloaded from www.Manualslib.com manuals search engine
Contents
Index (cont.)
5
Downloaded from www.Manualslib.com manuals search engine
Contents
Index (cont.)
Appendix
Specification Vitotronic 100, GC1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 174
Specification Vitotronic 300-K, MW1S . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 175
Applicability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 175
6
Downloaded from www.Manualslib.com manuals search engine
General information
Product information
These application examples are only recommendations, and must therefore be checked on site for
completeness and function.
Vitotronic 100, GC1, without LON communication module as part of the standard delivery.
LON module (PN: 7172 173) is supplied with control panel.
Vitotronic 300-K, MW1S, with integral LON communication module.
5581 750 v1.3
7
Downloaded from www.Manualslib.com manuals search engine
General information
Please note that the following examples are simplified conceptual drawings only!
Piping and necessary componentry must be field verified.
A low water cut off (LWCO) must be installed where required by local codes.
Proper installation and functionality in the field is the responsibilty of the heating contractor.
8
Downloaded from www.Manualslib.com manuals search engine
Heating system designs
System version 1
2
20 M2
52
1 2 D D
28
5 B 20 M3
21 52
143
146
LON
LON
40
2
LON
LON
LON
LON
3 3
17B T2 17B T2
17A 17A
143
41
52 A1
41
52 A1
146
143
146
40
90
29
40
90
29
T1 T1
C A A
Plug
! Outdoor temperature sensor sM2/M3Heating circuit pump mixing l Burner
? Supply temperature sensor valve circuit 2 or 3 (burner stage 2/mod.)
common heating supply sA DHW pump aVD/aVH External connections
?M2/M3 Supply temperature sensor sK DHW recirculation pump (see page 39)
mixing valve circuit 2 or 3 sL Shunt pump
Boiler temperature sensor f Power supply, 120 VAC,
% DHW tank temperature sensor 60 Hz
aJA Temperature sensor T1 fA Burner (burner stage 1)
aJB Temperature sensor T2 gSA1 Motorized isolation valve
gSM2/M3Mixing valve actuator
circuit 2 or 3
5581 750 v1.3
9
Downloaded from www.Manualslib.com manuals search engine
Heating system designs
Possible applications
Heating systems with distribution manifold installed close to the boiler. The boiler water volume flow will be reduced via the
motorized isolation valve.
Temperature sensor T2 activates the shunt pump if the required minimum return temperature is not reached. If this fails to
achieve the required minimum return temperature, the boiler water volume flow must be reduced by at least 50% via
temperature sensor T1, via the isolation valve or the heating circuit control units. Where the T1 temperature sensor cannot
affect the motorized isolation valves it must, instead, regulate the mixing valves of the heating circuits downstream.
Size the shunt pump to approx. 30% of the total throughput capacity of the boiler.
The boiler receives optimum protection when controlling the heating circuits via Vitotronic 300-K, MW1S or a
Vitotronic 200-H connected to the boiler control unit. No additional on-site protective measures are required.
IMPORTANT
5581 750 v1.3
The connection diagram is only a recommendation and needs to be verified for completeness and functionality at the
installation site. Single-phase and three-phase pumps must be connected with field supplied motor contactors and/or motor
starters.
*1 If required.
10
Downloaded from www.Manualslib.com manuals search engine
Heating system designs
System version 2
2
20 M2
52
1 2 D D
28
5 B 20 M3
21 52
2
143
146
40
29
LON
LON
20A1
20A1
LON
LON
LON
LON
3 3
17A T1 17A T1
90
52 A1
143
146
90
41
52 A1
41
143
146
40
40
C A A
Plug
! Outdoor temperature sensor sA1 Closing the mixing valves l Burner
? Supply temperature sensor with external heating circuit (burner stage 2/mod.)
common heating supply control units aVD/aVH External connections
?M2/M3Supply temperature sensor sM2/M3Heating circuit pump mixing (see page 39)
mixing valve circuit 2 or 3 valve circuit 2 or 3
Boiler temperature sensor sA DHW pump
% DHW tank temperature sensor sK DHW recirculation pump
aJA Temperature sensor T1 sL Common supply pump
f Power supply, 120 VAC
60 Hz
5581 750 v1.3
11
Downloaded from www.Manualslib.com manuals search engine
Heating system designs
*1
If required.
5581 750 v1.3
12
Downloaded from www.Manualslib.com manuals search engine
Heating system designs
IMPORTANT
The connection diagram is only a sA1 Closing mixing valves
recommendation and needs to be (Vitotronic 100, GC1)
verified for completeness and A Contactor relay
functionality at the installation site. B Downstream heating circuit
Single-phase and three-phase pumps control unit
must be connected with field supplied Switching contact closed:
motor contactors and/or motor signal for close mixing valve(s)
starters. C Power connection 120 VAC
60 Hz
D Junction box, field supplied
5581 750 v1.3
13
Downloaded from www.Manualslib.com manuals search engine
Heating system designs
System version 3
2
20 M2
52
1 2 D D
28
5 B 20 M3
21 2 52
40
29
143
146
LON
LON
LON
LON
LON
LON
3 3
17A 17A
41
41
40
90
29
40
90
29
143
146
143
146
52 A1
52 A1
T1 T1
C A A
Plug
! Outdoor temperature sensor sM2/M3Heating circuit pump mixing l Burner
? Supply temperature sensor valve circuit 2 or 3 (burner stage 2/mod.)
common heating supply sA DHW pump aVD/aVH External connections
?M2/M3Supply temperature sensor sK DHW recirculation pump (see page 39)
mixing valve circuit 2 or 3 sL Boiler circuit pump
Boiler temperature sensor f Power supply, 120 VAC
% DHW tank temperature sensor 60 Hz
aJA Temperature sensor T1 fA Burner (burner stage 1)
gSA1 Three-way mixing valve
gSM2/M3Mixing valve actuator
5581 750 v1.3
circuit 2 or 3
14
Downloaded from www.Manualslib.com manuals search engine
Heating system designs
Possible applications
For example, older heating systems or systems in nurseries and/or systems where downstream heating circuits cannot be
controlled.
Temperature sensor T1 closes the three-way mixing valve in proportion and therefore protects the boiler, if the required
minimum return temperature is not achieved.
Please note:
Size the boiler circuit pump for each boiler so that their volume flow rate is at least as large as the max. total heating circuit
volume flow rate.
Recommendation: 110%
IMPORTANT
The connection diagram is only a recommendation and needs to be verified for completeness and functionality at the
5581 750 v1.3
installation site. Single-phase and three-phase pumps must be connected with field supplied motor contactors and/or motor
starters.
*1 If required.
15
Downloaded from www.Manualslib.com manuals search engine
Heating system designs
System version 4
Controlling the return temperature with a low loss header and a three-way mixing valve
Vitorond 200
2
20 M2
52
1 2
28
5 B 20 M3
21 52
D D
2
40
29
143
146
LON
LON
E
LON
LON
LON
LON
3 3
17A 17A
41
41
40
90
29
40
90
29
143
146
143
146
52 A1
52 A1
T1 T1
C A A
Plug
! Outdoor temperature sensor sA DHW pump aVD/aVH External connections
? Supply temperature sensor sK DHW recirculation pump (see page 39)
common heating supply sL Boiler circuit pump
?M2/M3Supply temperature sensor f Power supply, 120 VAC
mixing valve circuit 2 or 3 60 Hz
Boiler temperature sensor fA Burner (burner stage 1)
% DHW tank temperature sensor gSA1 Three-way mixing valve
aJA Temperature sensor T1 gSM2/M3Mixing valve actuator
5581 750 v1.3
16
Downloaded from www.Manualslib.com manuals search engine
Heating system designs
Possible applications
For example, older systems or systems in nurseries and/or systems, where the hydraulic conditions cannot be clearly
defined and/or systems where downstream heating circuits cannot be controlled.
Temperature sensor T1 closes the three-way mixing valve in proportion and therefore protects the boiler, if the required
minimum return temperature is not achieved. The temperature sensor in the low loss header controls the supply
temperature.
Please note:
Size the boiler circuit pumps for each boiler so that their volume supply is at least as large as the max. total heating circuit
volume supply.
Recommendation: 110%
IMPORTANT
5581 750 v1.3
The connection diagram is only a recommendation and needs to be verified for completeness and functionality at the
installation site. Single-phase and three-phase pumps must be connected with field supplied motor contactors and/or
motor starters.
*1 If required.
17
Downloaded from www.Manualslib.com manuals search engine
Heating system designs
System version 5
2
20 M2
52
1 2 D D
28
5 B 20 M3
21 52
2
40
29
143
146
LON
LON
LON
LON
LON
LON
3 3
41
41
40
90
40
90
156
143
146
156
143
146
52 A1
52 A1
C E A E A
Plug
! Outdoor temperature sensor sM2/M3Heating circuit pump mixing fA Burner (burner stage 1)
? Supply temperature sensor valve circuit 2 or 3 gSA1 Motorized isolation valve
common heating supply sA DHW pump gSM2/M3Mixing valve actuator
?M2/M3Supply temperature sensor sK DHW recirculation pump circuit 2 or 3
mixing valve circuit 2 or 3 f Power supply, 120 VAC aVD/aVH External connections
Boiler temperature sensor 60 Hz (see page 39)
% DHW tank temperature sensor
l Burner
5581 750 v1.3
18
Downloaded from www.Manualslib.com manuals search engine
Heating system designs
*1
If required.
5581 750 v1.3
19
Downloaded from www.Manualslib.com manuals search engine
Heating system designs
Possible applications
Vitocrossal 300 is operated via a
Viessmann boiler control unit with
outdoor reset function, modulating
boiler water temperature, and
load-dependent sequential
control two-stage or modulating
burners are controlled.
IMPORTANT
The connection diagram is only a
recommendation and needs to be
verified for completeness and
functionality at the installation site.
Single-phase and three-phase pumps
must be connected with field supplied
motor contactors and/or motor
starters.
20
Downloaded from www.Manualslib.com manuals search engine
Heating system designs
System version 6
Heating circuit and one low temperature heating circuit plus Vitorond with shunt pump
Vitocrossal 300
Vitorond 200, 125 kW-500 kW
2
20 M2
52
1 2 D D
28
5 B 20 M3
21 52
143
146
2
LON
40
29
LON
LON
LON
LON
LON
3
3 17B T2
17A
143
90
52 A1
146
41
41
40
90
40
29
143
146
T1
C E A A
Plug
! Outdoor temperature sensor sA DHW pump aVD/aVH External connections
? Supply temperature sensor sK DHW recirculation pump (see page 39)
common heating supply sL Shunt pump
?M2/M3Supply temperature sensor f Power supply, 120 VAC,
mixing valve circuit 2 or 3 60 Hz
Boiler temperature sensor fA Burner (burner stage 1)
% DHW tank temperature sensor gSA1 Motorized isolation valve
aJA Temperature sensor T1 gSM2/M3Mixing valve actuator
aJB Temperature sensor T2 circuit 2 or 3
sM2/M3Heating circuit pump mixing l Burner
valve circuit 2 or 3 (burner stage 2/mod.)
5581 750 v1.3
21
Downloaded from www.Manualslib.com manuals search engine
Heating system designs
22
Downloaded from www.Manualslib.com manuals search engine
Heating system designs
Possible applications
The Vitocrossal 300 (lead boiler) and the Vitorond 200 (lag boiler) are operated via a Viessmann control system with outoor
reset logic, modulating boiler water temperature, and load-dependent sequential control two-stage or modulating burners
are controlled.
Vitocrossal 300 is equipped with two return connections. The heating circuits with the higher return temperature are
connected to the upper return connection, and those with lower return temperatures to the lower return connection. Please
note: Connect at least 15% of the rated output to the lower return connection. The return temperature control is available
as accessory or must be provided on site.
Return temperature control for Vitorond can be achieved using the shunt pump and by closing the isolation valve.
Temperature sensor T1 controls the isolation valve. Temperature sensor T2 switches the shunt pump.
Due to the LON-BUS communication between controls, a boiler supply temperature is automatically set.
This temperature is based on the highest required mixing valve circuit temperature plus adjustable differential.
IMPORTANT
The connection diagram is only a recommendation and needs to be verified for completeness and functionality at the
installation site. Single-phase and three-phase pumps must be connected with field supplied motor contactors and/or motor
starters.
5581 750 v1.3
23
Downloaded from www.Manualslib.com manuals search engine
Heating system designs
System version 7
Three-way mixing valve, several heating circuits and one low temperature heating circuit
Vitocrossal 300
Vitorond 200, 125KW- 500 KW
2
20 M2
52
1 2 D D
28
5 B 20 M3
21 52
143
146
LON
2
LON
40
29
LON
LON
LON
LON
3 3
17A
41
41
52 A1
40
90
40
90
29
143
146
143
146
T1
C E A A
Plug
! Outdoor temperature sensor sL Boiler circuit pump
? Supply temperature sensor f Power supply,120 VAC,
common heating supply 60 Hz
?M2/M3Supply temperature sensor fA Burner (burner stage 1)
mixing valve circuit 2 or 3 gSA1 Three-way mixing valve
Boiler temperature sensor gSM2/M3Mixing valve actuator
% DHW tank temperature sensor circuit 2 or 3
aJA Temperature sensor T1 l Burner
sM2/M3Heating circuit pump mixing (burner stage 2/mod.)
valve circuit 2 or 3 aVD/aVH External connections
5581 750 v1.3
24
Downloaded from www.Manualslib.com manuals search engine
Heating system designs
25
Downloaded from www.Manualslib.com manuals search engine
Heating system designs
Possible applications
For heating circuits with temperature differentials 20 C / 68 F
The Vitocrossal 300 (lead boiler) and the next Vitorond (lag boiler) are operated via a Viessmann control system with
outdoor reset logic, modulating boiler water temperature, and load-dependent sequential control two-stage or modulating
burners are controlled.
Vitocrossal 300 is equipped with two return connections. The heating circuits with the higher return temperature are
connected to the upper return connection, and those with lower return temperatures to the lower return connection.
Please note: Connect at least 15% of the rated output to the lower return connection.
Due to the LON-BUS communication between controls, a boiler supply temperature is automatically set.
This temperature is based on the highest required mixing valve circuit temperature plus adjustable differential.
IMPORTANT
The connection diagram is only a recommendation and needs to be verified for completeness and functionality at the
installation site. Single-phase and three-phase pumps must be connected with field supplied motor contactors and/or
motor starters.
5581 750 v1.3
26
Downloaded from www.Manualslib.com manuals search engine
Installation Vitotronic 100, GC1
145
17 B
17 A
5 151
3/2 90
15 21
143 52 A1/M1 41
146 20 A1/M1
29
50 150
40
156
156
27
Downloaded from www.Manualslib.com manuals search engine
Installation Vitotronic 100, GC1
28
Downloaded from www.Manualslib.com manuals search engine
Installation Vitotronic 100, GC1
Run the cables from the connection enclosure into the control unit.
Apply strain relief to cables (see below).
OR
29
Downloaded from www.Manualslib.com manuals search engine
Installation Vitotronic 100, GC1
Only use the boiler coding card included with the boiler.
30
Downloaded from www.Manualslib.com manuals search engine
Installation Vitotronic 100, GC1
WARNING
If adjusted to 99 C / 210 F, do not
set the adjustable high limit above
75 C / 167 F.
31
Downloaded from www.Manualslib.com manuals search engine
Installation Vitotronic 100, GC1
A B C
1. Disconnect power to control and
burner.
A 75 to 195 C
167 to 203 F
A, B 75 to 100 C
167 to 212 F
A, B, C 75 to 110 C
167 to 230 F
IMPORTANT
Note the setting of coding address
06!
WARNING
If the system is operated in conjunction
with a domestic hot water tank, ensure
1. that the maximum permissible
domestic hot water temperature is
not exceeded. If necessary, install a
suitable safety device for this purpose.
5581 750 v1.3
32
Downloaded from www.Manualslib.com manuals search engine
Installation Vitotronic 100, GC1
660
Electrical connection
640 The sensors are ready to plug in. Insert
the boiler temperature sensor in socket
3 of the boiler control.
620
600
580
Resistance in
560
5581 750 v1.3
400
540
0 20 40 60 80 100 120 140
32 68 104 141 176 212 248 284
Boiler temperature in C / F
33
Downloaded from www.Manualslib.com manuals search engine
Installation Vitotronic 100, GC1
Electrical connection
The sensor is inserted in socket 17A
17A or 17B or 17B on the control unit.
Flow/return Resistance
temperature in
in C / F
30 / 86 569
40 / 104 592
17A or 17B 60 / 140 643
640
620
Resistance in
600
580
560
5581 750 v1.3
540
20 30 40 50 60 70 80 90 100
68 86 104 122 140 158 176 194 212
34
Downloaded from www.Manualslib.com manuals search engine
Installation Vitotronic 100, GC1
Electrical connection
The sensor is inserted in socket 15
on the control unit.
660
620
Resistance in
580
540
5581 750 v1.3
500
0 40 80 120 160 200 240 280
32 104 176 248 360 392 464 536
35
Downloaded from www.Manualslib.com manuals search engine
Installation Vitotronic 100, GC1
36
Downloaded from www.Manualslib.com manuals search engine
Installation Vitotronic 100, GC1
1 120V or 24V Valve Adaptor 1 120V Valve Adaptor 1 24V Valve Adaptor
2 DIN rail in connection enclosure 2 120V Valve actuator 2 24V Valve actuator
3 aBH Terminals
37
Downloaded from www.Manualslib.com manuals search engine
Installation Vitotronic 100, GC1
A Boiler disable
A
B Activate boiler as last in the
boiler sequence
B
C External changeover between
staged/modulating burner
C
143 146
B
Activate boiler as last in the boiler
A sequence. C
Boiler disable Connect dry contact at terminals 2 External changeover between
Connect dry contact at terminals 1 and 3 of the plug aVD. staged/modulating burner
and 2 of the plug aVD. Connect dry contact to terminals 1
The boiler is activated as last in the and 2 of the plug aVH.
Contact closed: boiler sequence. The other boiler take
The boiler burner is disabled. over the supply of heat for the heating Contact open: Modulating operation
It is taken out of the boiler sequence, system. If the output of the other Contact closed: Two-stage operation
i.e. isolation valve/return valve are boilers is not sufficient, the boiler The burner type must be set to
closed. The shunt pump/boiler circuit is activated. modulating in coding 1
pump are switched off. The heat must (coding 02: 2).
be supplied by other boilers. Contact open:
The boiler is put back in the Please note:
Safety instruction! current boiler sequence. When the burner type is scanned,
If all boilers are disabled or no other modulating continues to be displayed
boilers are ready for operation, there after external changeover (the display
is no frost protection of the heating in not changed).
sysytem.
Contact open:
The boiler is put back in the current
boiler sequence.
5581 750 v1.3
38
Downloaded from www.Manualslib.com manuals search engine
Installation Vitotronic 100, GC1
39
Downloaded from www.Manualslib.com manuals search engine
Installation Vitotronic 100, GC1
IMPORTANT
Wire BK2 must be connected to
terminal 16 and BK3 to terminal 17
- DO NOT reverse.
Safety instruction!
Provide disconnect means and
overcurrent protection as required
by local codes.
40
Downloaded from www.Manualslib.com manuals search engine
Installation Vitotronic 100, GC1
E
1. Disconnect power to control and
burner.
Safety instruction!
Provide disconnect means and
overcurrent protection as required
by local codes.
Note:
Spring return air dampers do not
require field supplied relay.
5581 750 v1.3
41
Downloaded from www.Manualslib.com manuals search engine
Installation Vitotronic 100, GC1
42
Downloaded from www.Manualslib.com manuals search engine
Installation Vitotronic 100, GC1
Safety instruction!
Provide disconnect means and
overcurrent protection as required
by local codes.
43
Downloaded from www.Manualslib.com manuals search engine
Installation Vitotronic 100, GC1
Safety instruction!
E Provide disconnect means and
overcurrent protection as required
by local codes.
44
Downloaded from www.Manualslib.com manuals search engine
Installation Vitotronic 100, GC1
B
5581 750 v1.3
45
Downloaded from www.Manualslib.com manuals search engine
Installation Vitotronic 100, GC1
46
Downloaded from www.Manualslib.com manuals search engine
Installation Vitotronic 100, GC1
BK Black
BN Brown
5581 750 v1.3
BU Blue
47
Downloaded from www.Manualslib.com manuals search engine
Installation Vitotronic 100, GC1
Caution!
This is a generic connection drawing only! Follow the burner manufacturers connection drawings for Viessmann
controls.
a b
A Control unit f Power supply connection of control aB Plugs for external equipment
(Legend: see wiring diagram) unit 120 VAC a External safety devices
B 2nd stage or modulating *1 fA Burner, 1st stage (remove jumper when connecting)
C Hours counter, stage 1 *1 l Burner, 2nd stage b External controlled switch-off
D Burner fault indicator *1 (remove jumper when connecting)
E Control circuit, stage 1/ aBA Safety circuit. Emergency
basic load *1 shut-off
F Burner
5581 750 v1.3
48
Downloaded from www.Manualslib.com manuals search engine
Installation Vitotronic 100, GC1
Burner motor power supply connection See burner manual for correct
fuse and wire gauge sizing, and
For burners with 120 VAC, 1PH power specific connections for Viessmann
supply and soft cable connection. controls.
49
Downloaded from www.Manualslib.com manuals search engine
Installation Vitotronic 100, GC1
50
Downloaded from www.Manualslib.com manuals search engine
Installation Vitotronic 100, GC1
For burners with 240 VAC, 1PH power See burner manual for correct fuse
supply and connection in conduit. and wire gauge sizing, and specific
connections for Viessmann controls.
51
Downloaded from www.Manualslib.com manuals search engine
Installation Vitotronic 100, GC1
CAUTION
During commissioning check for correct
motor rotation. If motor rotates in
opposite direction than indicated on the
burner, disconnect power supply and
reverse wires BK1 and BK2 on the
burner terminals.
52
Downloaded from www.Manualslib.com manuals search engine
Installation Vitotronic 100, GC1
WARNING
The control must be grounded.
Ensure that L, N and G are
not interchanged.
L: Line
N: Neutral
G: Ground
A Power supply 120 VAC, 1 PH . Provide disconnect means and overcurrent protection as per local codes
B Terminals f
C Connection enclosure
5581 750 v1.3
53
Downloaded from www.Manualslib.com manuals search engine
Installation Vitotronic 100, GC1
54
Downloaded from www.Manualslib.com manuals search engine
Installation Vitotronic 100, GC1
55
Downloaded from www.Manualslib.com manuals search engine
Installation Vitotronic 333, MW1S
Installing modules
1. Make a cutout with the dimensions 4. Plug the connecting cable into the
305 129 mm in the front door of back of the programming unit and
the control panel. into the cascade electronic module
When installing two programming (A2).
units, maintain a distance between
both of 20 mm.
56
Downloaded from www.Manualslib.com manuals search engine
Installation Vitotronic 333, MW1S
305
1.
318
2.
129
139
4.
X10
X2
X1
5581 750 v1.3
57
Downloaded from www.Manualslib.com manuals search engine
Installation Vitotronic 300-K, MW1S
F1 4A
(slow)
5581 750 v1.3
58
Downloaded from www.Manualslib.com manuals search engine
Installation Vitotronic 333, MW1S
59
Downloaded from www.Manualslib.com manuals search engine
Installation Vitotronic 300-K, MW1S
60
Downloaded from www.Manualslib.com manuals search engine
Installation Vitotronic 300-K, MW1S
4.
WARNING
When extending wire, there is the
2. possibility of exposure to
electromagnetic interference.
Avoid running wires beside or near
high voltage 120/240 VAC
conductors. If proximity to high
voltage conductors cannot be avoided,
use stranded, twisted pair or shield
design wire. Ensure that only one end
of the shielding is grounded.
5581 750 v1.3
61
Downloaded from www.Manualslib.com manuals search engine
Installation Vitotronic 300-K, MW1S
Electrical connection
Connect in accordance with the
overview on page 58 and 59 and
2 the control panel wiring diagram.
Remove the plug from the sensor
cable.
Flow/return Resistance
temperature in
in C / F
30 / 86 569
40 / 104 592
60 / 140 643
620
Resistance in
600
580
560
5581 750 v1.3
540
20 30 40 50 60 70 80 90 100
68 86 104 122 140 158 176 194 212
62
Downloaded from www.Manualslib.com manuals search engine
Installation Vitotronic 300-K, MW1S
Electrical connection
17A or 17B Connect in accordance with the
overview on page 58 and 59 and
the control panel wiring diagram.
Remove the plug from the sensor
cable.
Flow/return Resistance
temperature in
17A or 17B in C / F
30 / 86 569
40 / 104 592
60 / 140 643
620
Resistance in
600
580
560
5581 750 v1.3
540
20 30 40 50 60 70 80 90 100
68 86 104 122 140 158 176 194 212
63
Downloaded from www.Manualslib.com manuals search engine
Installation Vitotronic 300-K, MW1S
Electrical connection
660 Connect in accordance with the
overview on page 58 and 59 and
the control panel wiring diagram.
640 Remove the plug from the sensor cable.
620
temperature sensor.
560
540
5581 750 v1.3
0 20 40 60 80 100
32 68 104 140 176 212
64
Downloaded from www.Manualslib.com manuals search engine
Installation Vitotronic 300-K, MW1S
Use as:
Actuator for mixing valve for DHW Implement the connection gS on A3 or
tank loading system on A3 A4 in accordance with the overview on
Actuator, mixing valve circuit page 58 and 59 and the control panel
M2/M3 on A4 wiring diagram.
5581 750 v1.3
65
Downloaded from www.Manualslib.com manuals search engine
Installation Vitotronic 300-K, MW1S
B External blocking/
C B A external Mixing valve close
66
Downloaded from www.Manualslib.com manuals search engine
Installation Vitotronic 300-K, MW1S
67
Downloaded from www.Manualslib.com manuals search engine
Installation Vitotronic 300-K, MW1S
The Viessmann LON system is designed for the Line BUS topology with end of line resistors on both ends.
A A A
C 7 m / 23 ft 7 m / 23 ft C
B B
Connection with
Viessmann LON cable and
Viessmann LON coupling
A A A
7 m / 23 ft 7 m / 23 ft 7 m / 23 ft 7 m / 23 ft 7 m / 23 ft 7 m / 23 ft
C C
B B B B B B
D D D D
A Control unit or Vitocom C End of line resistor (standard D LON coupling, part no. 7143 496
B LON cable, part no. 7143 495, delivery of Vitotronic 300-K,
(max. 3 cables between MW1S)
two devices)
68
Downloaded from www.Manualslib.com manuals search engine
Installation Vitotronic 300-K, MW1S
Connection with
Viessmann LON cable,
on-site cable for extensions up to 900 m / 3000 ft.
A A A
E E E E
C 7 m / 23 ft 7 m / 23 ft 7 m / 23 ft 7 m / 23 ft C
B B B B
F D
max. 900 m / 3000 ft.
69
Downloaded from www.Manualslib.com manuals search engine
Installation Vitotronic 300-K, MW1S
Power supply
70
Downloaded from www.Manualslib.com manuals search engine
Initial start-up
Steps
Page
2. Changing the display language selection (Vitotronic 300-K, MW1S, if necessary) ....................................................................................................................72
71
Downloaded from www.Manualslib.com manuals search engine
Initial start-up
72
Downloaded from www.Manualslib.com manuals search engine
Initial start-up
Please note:
Data transfer via the LON system can take several minutes.
73
Downloaded from www.Manualslib.com manuals search engine
Initial start-up
Please note:
In each heating system, only one Vitotronic may be encoded as fault manager.
2. Press D.
The participant list is updated after
approx. 2 minutes.
The participant check is completed.
74
Downloaded from www.Manualslib.com manuals search engine
Initial start-up
VitotronicLON
100 Vitotronic LON
100 Vitotronic 333
LON Vitocom
75
Downloaded from www.Manualslib.com manuals search engine
Initial start-up
76
Downloaded from www.Manualslib.com manuals search engine
Initial start-up
In coding 1, set the following coding In coding 2, set the following coding
addresses: addresses:
01 Multi-boiler system 0C Return temperature control
02 Burner type 0d Therm-Control
03 Oil or gas operation 4C Function plug s
07 Boiler number 4d Function plug sL
4E Function plug gS
77 LON participant number
98 Viessmann system number
In coding 1, set the following coding A5 Heating circuit pump logic 4d Function plug sL
addresses: function (economy circuit) 4E Function plug gS
00 System design C5 Minimum limit of the heating 55 Function DHW temperature
35 Number of boilers in the cascade circuit supply temperature control
36 Minimum supply temperature limit C6 Maximum limit of the heating 77 LON participant number
of the cascade circuit supply temperature 7A Central control
37 Maximum limit of the cascade 7F Detached house or apartment
supply temperature In coding 2, set the following coding building
3b Control type addresses: 98 Viessmann system number
3C Control strategy 39 Permanent lead boiler
40 Actuator run time 3A Permanent last boiler
A2 DHW priority 4C Function plug s
5581 750 v1.3
77
Downloaded from www.Manualslib.com manuals search engine
Initial start-up
Matching the control unit to a two stage burner (Vitotronic 100, GC1)
1. Start up the burner. 5. Press 9 and simultaneously Record the relevant value.
for approx. two seconds.
2. Set the override switch to . Relay test is activated. 8. Press .
Relay test is completed.
3. Determine the maximum burner 6. Activate the burner stage 1 ON
output through the fuel function with (display shows: 4). 9. Set the determined values in
consumption. coding 1, see the table below
Record the relevant value. 7. Determine the minimum burner and page 138.
output (basic load) through the
4. Set the override switch fuel consumption.
to a.
78
Downloaded from www.Manualslib.com manuals search engine
Initial start-up
Please note:
The burner must be fully adjusted. To achieve a wide modulating range, set the minimum output as low as possible
(observe the chimney and flue gas system).
1. Start up the burner. 5. Press 9 and simultaneously 8. Activate the mod. burner open
for approx. two seconds. function with (display
2. Set the override switch to . Relay test is activated. shows: 2), and set mod. burner
neutral function (display shows: 3)
3. Wait until the burner actuator is 6. Activate the mod. burner close using , after 1/3 of the time
set to maximum output. function with (display shows: 4), checked under item 6 (stop burner
and set the override switch to a. module controller).
4. Determine the maximum burner Check the time it takes until the
output through the fuel actuator is at minimum output. 9. Determine the partial output
consumption. Record the relevant value. through the fuel consumption.
Record the relevant value. Record the relevant value.
7. Determine the minimum burner
output (basic load) through the 10. Press .
fuel consumption. Relay test is completed.
Record the relevant value.
11. Set the determined values in
coding 1, see the table below
and on page 138.
Address Setting of
08 Units and tens of the determined maximum output;
e.g. max. output: 225 kW set here: 25
values including 199 kW can be entered directly.
09 Hundreds of the determined maximum output;
e.g. max. output: 225 kW set here: 2
15 Determined run time in seconds
0A Relationship between basic output and max. output in percent; e.g.
basic output: 72 kW
max. output: 225 kW
72 kW x100 % = 32 %
225 kW
05 Relationship between partial output and max. output in percent; e.g.
partial output: 171 kW
max. output: 225 kW
171 kW x100 % = 76 %
225 kW
5581 750 v1.3
79
Downloaded from www.Manualslib.com manuals search engine
Initial start-up
11 Burner or stage 1 ON
15 Output 20 ON
16 Output 29 ON
17 Output 52 open
18 Output 52 neutral
19 Output 52 close
Check sensors
1. Press . 3. Press .
Scanning operating conditions is Scanning is completed.
1234567
active, see page 88.
80
Downloaded from www.Manualslib.com manuals search engine
Initial start-up
Relay test
Check sensors
1
1. Press . 3. Press .
Relay test
2 Scanning operating conditions is Scanning is completed.
3 active, see page 93.
1
1. If required: 4. Press .
Relay test
2 In coding 2, set coding addresses 39 The adjustment has been
3 (permanent lead boiler) and 3A transferred.
(permanent last boiler).
5. In coding 2, set the coding
2. Press and simultaneously for addresses 38, 41, 42, 43 and 44;
approx. two seconds. see also the function description.
modifications made.
81
Downloaded from www.Manualslib.com manuals search engine
Initial start-up
Slope
3.4
3.2
3.0
2.8
2.6
2.4
110/230
2.2
100/212
2.0
90/194 1.8
Supply tempertaure in C / F
1.6
80/176
1.4
70/158
1.2
60/140 1.0
50/122 0.8
0.6
40/104
0.4
35
30/86
95 30 0.2
86 25
77 20
10 5 0 -5 -10 -15 -20
50 68 15 41 32 23 14 5 -4
10 59 Outdoor temperature in C / F
50 5
Set room temperature in C / F 41
5581 750 v1.3
82
Downloaded from www.Manualslib.com manuals search engine
Initial start-up
3.5
110
230
Supply temperature in C / F
B
1.4
0.2
+20 / 68 -20 / -4
Outdoor temperature in C / F
A Change slope
B Change shift
5581 750 v1.3
83
Downloaded from www.Manualslib.com manuals search engine
Initial start-up
Temperature conversion:
C F
-20 -4
5 41
14 57
20 68
26 79
110 230
D E D E
Example 1: Example 2:
Adjustment of the normal room Adjustment of the reduced room
temperature from 20 to 26 C / temperature from 5 to 14 C /
68 to 79 F. 41 to 57 F.
84
Downloaded from www.Manualslib.com manuals search engine
Service scanning Vitotronic 100, GC1
85
Downloaded from www.Manualslib.com manuals search engine
Service scanning Vitotronic 100, GC1
Subject to the system equipment level, the following values can be scanned:
(for scans, see table below):
08888 Scan 0
18888 Scan 1
28888 Scan 2
3__65 C Set boiler water temperature Effective set value including boiler protection
4_888 Scan 4
8_230 C Maximum flue gas temperature See coding address 1F; can be reset to the actual
value with D
l_888 Scan L
Co8888 Scan o
86
Downloaded from www.Manualslib.com manuals search engine
Service scanning Vitotronic 100, GC1
Scans
F8 8 8 8 8
0 LON participant number Software version SNVT configuration
communication 0 = Auto
co-processor 1 = Tool
87
Downloaded from www.Manualslib.com manuals search engine
Service scanning Vitotronic 100, GC1
1. Press . 3. Press .
1234567
The following values can be scanned subject to the actual system layout:
8_190 C Flue gas temperature Only with flue gas temperature sensor
| Burner run hours The run hours can be reset to 0 with D. The run
63572 h Stage 1 hours displayed are only approximate values
88
Downloaded from www.Manualslib.com manuals search engine
Service scanning Vitotronic 100, GC1
After limits have been reached, which were set up via coding addresses 1F, 21 and 23 (see page 143), the programming unit
display flashes one of the following messages.
Please note:
Set coding 24 : 1 and then coding 24 : 0, if maintenance is implemented before a maintenance message is displayed; the
set maintenance parameters for run hours and periods are then reset to 0.
Please note:
If coding address 24 is not reset, a
new maintenance message will be
displayed on Monday morning.
1234567
2. If required:
Press
Reset burner run hours and burner
starts with D
(see page 88)
Press
3. If required:
Press 9 and rw simultaneously
1234567
for approx. four seconds
Reset maximum flue gas
temperature (8) with D
(see page 86)
Press
5581 750 v1.3
89
Downloaded from www.Manualslib.com manuals search engine
Service scans Vitotronic 300-K, MW1S
90
Downloaded from www.Manualslib.com manuals search engine
Service scans Vitotronic 300-K, MW1S
3. Press
The following values can be scanned subject to the actual equipment level:
91
Downloaded from www.Manualslib.com manuals search engine
92
3 Operating mode Software version Operating mode Software version Operating mode Software version
sys. circuit A1 remote control mixing valve remote control mixing valve remote control
0 w/o remote system circuit circuit M2 mixing valve circuit M3 mixing valve
control A1 0 w/o remote circuit M2 0 w/o remote circuit M3
1 with control control
Vitotrol 200 1 with 1 with
2 with Vitotrol 200 Vitotrol 200
Vitotrol 300 2 with 2 with
Vitotrol 300 Vitotrol 300
4 N//A
5 LON participant nu
umber Subnet address/system number Node address
6 SNVT Software version Software version Number of
configuration communication neuron chip LON participants
0 = Auto co-processor
1 = Tool
7 on*1
Device identificatiio N/A N/A N/A N/A
hexa-decimal: b8 / decimal: 184
8 N/A N/A N/A md
Maximum system urre
design temperatu
1 1. Press .
Outside temperature
2
12
3
2. Select the required scan
with or .
3. Press .
The following values can be scanned subject to the actual equipment level:
Outdoor temperature
Boiler sequence
Common supply temperature
Boiler temp. 1 to 4 Actual value boilers 1 to 4
Sensor 17A Display only if a sensor is connected
Sensor 17B
DHW temperature Display only if a DHW tank sensor
is connected
DHW temperature 1 Display only if two DHW tank
DHW temperature 2 temperature sensors are connected
93
Downloaded from www.Manualslib.com manuals search engine
Service scans Vitotronic 300-K, MW1S
94
Downloaded from www.Manualslib.com manuals search engine
Troubleshooting Vitotronic 100, GC1
95
Downloaded from www.Manualslib.com manuals search engine
Troubleshooting Vitotronic 100, GC1
38 Open circuit
Boiler temperature sensor
b0 Short circuit
Flue gas temperature sensor
Check flue gas temperature sensor
(see page 124)
b1 Communication error
programming unit
Check connections and replace
programming unit if necessary
b4 Emissions test mode Internal electronics fault Check Printed Circuit Board or
replace if necessary
b5 Control mode
b6 Constant mode Invalid hardware recognised Check the control software circuit
board and confirm the coding address:
- Enter coding 2 (see page 140
for instructions).
- Change code 8A to 176.
- Confirm coding 92:160
5581 750 v1.3
96
Downloaded from www.Manualslib.com manuals search engine
Troubleshooting Vitotronic 100, GC1
c9 Error
Maximum pressure limiter
Check system pressure; reset
maximum pressure limiter
cf Error
LON communication module
Replace communication module
(see page 121)
d6
d7 to DE2
d8 to DE3
5581 750 v1.3
97
Downloaded from www.Manualslib.com manuals search engine
Troubleshooting Vitotronic 100, GC1
.. ..
. .
10th last fault
10 code
3. Press .
98
Downloaded from www.Manualslib.com manuals search engine
Troubleshooting Vitotronic 300-K, MW1S
1
Fault
2 57
Fr
3
DBG- 1 1 10
Finding the fault
1. Press .
99
Downloaded from www.Manualslib.com manuals search engine
Troubleshooting Vitotronic 300-K, MW1S
18 Open circuit
Outdoor temperature sensor
100
Downloaded from www.Manualslib.com manuals search engine
Troubleshooting Vitotronic 300-K, MW1S
44 Short circuit
Strap-on temperature sensor
of mixing valve circuit M3
48 Open circuit
Strap-on temperature sensor
of mixing valve circuit M2
4c Open circuit
Strap-on temperature sensor
of mixing valve circuit M3
101
Downloaded from www.Manualslib.com manuals search engine
Troubleshooting Vitotronic 300-K, MW1S
92 Control mode
Only solar control unit fault codes
Short circuit
Collector temperature sensor
Check solar control unit sensor
will be displayed
93 Short circuit
Collector return temperature sensor
94 Short circuit
DHW tank temperature sensor
9a Open circuit
Collector temperature sensor
9b Open circuit
Collector return temperature sensor
9c Open circuit
DHW tank temperature sensor
9f Error
Solar control unit; displayed if an
Check solar control unit
b1 Communication error
Programming unit
Check connections and replace
programming unit if necessary
b4 Emissions test mode Internal electronics fault Check Printed Circuit Board and
replace if necessary
b5 Control mode
b6 Constant mode Invalid hardware recognised Check the control software circuit
board and confirm the coding address:
- Enter coding 2 (see page 151
for instructions).
- Change code 8A to 176.
- Confirm coding 92:184
5581 750 v1.3
102
Downloaded from www.Manualslib.com manuals search engine
Troubleshooting Vitotronic 300-K, MW1S
bd Communication error
Vitotrol remote control,
Mixing valve circuit M2
be Communication error
Vitotrol remote control,
Mixing valve circuit M3
c2 Open circuit
KM BUS to solar control unit
Check KM BUS cable and solar
control unit
Without solar control unit:
Set coding 54 : 0
cf Error
LON communication module
Replace communication module
d6
d7 to DE2
d8 to DE3
5581 750 v1.3
103
Downloaded from www.Manualslib.com manuals search engine
Troubleshooting Vitotronic 300-K, MW1S
db Short circuit
Room temperature sensor,
Mixing valve circuit M2
dc Short circuit
Room temperature sensor,
Mixing valve circuit M3
dd Open circuit
Room temperature sensor,
System circuit A1
de Open circuit
Room temperature sensor,
Mixing valve circuit M2
df Open circuit
Room temperature sensor,
Mixing valve circuit M3
104
Downloaded from www.Manualslib.com manuals search engine
Troubleshooting Vitotronic 300-K, MW1S
Error history .. ..
. .
F11 18 10th last fault
10 code
3. Press .
Error history
F101 d5
5581 750 v1.3
105
Downloaded from www.Manualslib.com manuals search engine
Function description Vitotronic 100
Brief description
The boiler water temperature is Coding addresses which influence
regulated by controlling a two stage the boiler temperature control
or modulating burner. 02 to 06, 08 to 0b, 13 to 1C
The set boiler water temperature For a description, see the coding
set-point is controlled by Vitotronic overview.
300-K, MW1S.
Functions
The boiler water temperature is
monitored by three sensors separately,
which are inserted into a multiple
sensor well:
Fixed high limit (STB)
(liquid expansion)
Adjustable high limit TR
(liquid expansion)
Boiler temperature sensor KTS
(changes in resistance PT500)
Control sequence
Boiler goes cold Boiler heats up
(set value 2 K) The burner shutdown point is
The burner is activated if the oiler determined by the switch-off
termperature is 2 C / 3.6 F below differential (coding address 13).
the calculated set point temperature.
The burner may be delayed a few
minutes depending on the connected
auxilliary equipment and the fuel type.
5581 750 v1.3
106
Downloaded from www.Manualslib.com manuals search engine
Function description Vitotronic 300-K, MW1S
Brief description
The supply temperature is regulated by Subject to the system design, you
starting or stopping the burner or by may select between one gross
starting/stopping individual burner calorific strategy and two net
stages. calorific strategies.
Depending on the type of control The boiler sequence (see page 112)
the boilers will be controlled to can be determined via coding 2 and
the set boiler water temperature the boiler sequence selection.
determined by the cascade control
(stand-alone type of control) Coding addresses which influence the
or cascade control
the cascade controls the boilers by 35 to 3F, 41 to 4A
pre-setting an individual boiler output For a description, see the coding
(sequential control strategy). overview.
107
Downloaded from www.Manualslib.com manuals search engine
Function description Vitotronic 300-K, MW1S
Control sequence
Stand-alone (Autonomous) type of control sequence
The control sequence is subject to the start-up and shutdown criteria set by the control strategy (coding address 3C):
Gross calorific strategy
Net calorific strategy 1
Net calorific strategy 2.
108
Downloaded from www.Manualslib.com manuals search engine
Function description Vitotronic 300-K, MW1S
The control sequence is subject to the start-up and shutdown criteria set by the control strategy (coding address 3C):
Gross calorific strategy
Net calorific strategy 1
Net calorific strategy 2.
Condensing strategy
109
Downloaded from www.Manualslib.com manuals search engine
Function description Vitotronic 300-K, MW1S
page 112).
110
Downloaded from www.Manualslib.com manuals search engine
Function description Vitotronic 300-K, MW1S
Boiler 1
Boiler 1
100 100
66 66
33 33
0 0
Boiler 2
Boiler 2
Rated output in kW
Rated output in kW
100 100
33 33
0 0
200 200
150 150
Total
Total
100 100
33 33
0 0
Time Time
100 100
50 50
33 33
0 0
Boiler 2
Boiler 2
Rated output in kW
Rated output in kW
100 100
50 50
0 0
200 200
150 150
Total
Total
100 100
33 33
0 0
Time Time
5581 750 v1.3
111
Downloaded from www.Manualslib.com manuals search engine
Function description Vitotronic 300-K, MW1S
Boiler 1
Boiler 1
100 100
66
50
33 33
0 0
Boiler 2
Boiler 2
Rated output in kW
Rated output in kW
100 100
50
33
0 0
200 200
150 150
Total
Total
100 100
33 33
0 0
Time Time
Boiler sequence
The boiler sequence is determined by 39 Boiler 1, 2, 3 or 4 permanent
the boiler sequence selection and the lead boiler
following coding addresses (see also 3A Boiler 1, 2, 3 or 4 permanent
page 152): last boiler
38 Changing the lead boiler and the 41 ECO threshold boiler 1
boiler sequence 42 ECO threshold boiler 2
38 : 1 Every 1st day of the 43 ECO threshold boiler 3
month, the boiler with 44 ECO threshold boiler 4
the burner which has
operated for the shortest Via the ECO threshold, every boiler
number of hours becomes can be blocked or enabled subject to
lead boiler the outdoor temperature. The ECO
38 : 2 After 200 to 20000 control becomes disabled, if the boiler
run hours, the boiler with is required to achieve the set supply
the next higher number temperature, when enabled boilers
(coding address 07 of have failed. At least the lead boiler
Vitotronic 100) becomes remains active if all boilers in a system
lead boiler are blocked by the ECO control. 5581 750 v1.3
112
Downloaded from www.Manualslib.com manuals search engine
Function description Vitotronic 300-K, MW1S
Brief description
The control unit provides control system supply temperature. Coding addresses which influence the
circuits for one high temperature The supply temperature of the heating circuit control
(boiler) circuit and two mixing valve mixing valve circuits is regulated 9F, A2 to A7, A9, C4 to C7, C8, F1,
circuits. by the stepped opening or closing F2.
The set supply temperature of every of the mixing valves. For a description, see the coding
heating circuit results from the outdoor overview.
temperature, the set room temperature, The mixing motor control changes
the operating mode and the heating the actuating and pause times subject
curve. to the control difference
The supply temperature of the system (control deviation).
circuit corresponds to the common
Functions
The high temperature (boiler) circuit is Time program Outdoor temperature
subject to the boiler water temperature The control unit timer changes in A heating curve must be set up
and its control range limits. accordance with the times programmed for matching the control unit to
The heating circuit pump is the in the room heating and DHW heating the building and the heating system.
controlling element. The mixing valve program between the heating with The heating curve characteristics
circuit supply temperature is recorded normal room temperature and heating determine the set boiler water
by the supply temperature sensor. with reduced room temperature temperature subject to outdoor
operating modes. temperature. An average outdoor
Every operating mode has its own set temperature (dampened) is used
level. for control purposes. This comprises
the actual and the adjusted outdoor
temperature.
5581 750 v1.3
113
Downloaded from www.Manualslib.com manuals search engine
Function description Vitotronic 300-K, MW1S
Domestic hot water temperature Room temperature Heating circuit pump logic
With priority control: in conjunction with remote control (economy circuit)
The set supply temperature will be and room temperature input (observe The heating circuit pump is switched
set to 0 C / 32 F during DHW coding address b0). OFF (set supply temperature set to 0 C/
heating. 32 F), when the outdoor temperature
The mixing valve closes, and the Compared to the outdoor temperature, exceeds the value selected via coding
heating circuit pumps are switched the room temperature has a greater address A5.
OFF. influence on the common set supply
Without priority control: temperature. This influence may be
The heating circuit control unit adjusted via coding address b2.
continues to operate with the same In conjunction with the mixing valve
set value. circuit:
With modulating DHW priority (only For control differences (actual value
in conjunction with a mixing valve deviation) above 2 C / 3.6 F room
circuit): temperature, the influence can be
The heating circuit pump remains increased again (via coding address b6,
switched ON. The set supply quick heat-up/quick setback).
temperature of the heating circuits Quick heat-up:
will be reduced, for as long as the The set room temperature must be
set boiler water temperature has not raised by a minimum of 2 C / 3.6 F
been reached during DHW tank by:
heating. The set supply temperature Pressing party button
is subject to the difference between Changing from heating with reduced
the set and the actual boiler water temperature to heating with normal
temperature, the outdoor temperature
temperature, the heating curve slope Start-up optimisation
and coding address A2. Quick heat-up will stop when the set
room temperature has been reached.
Quick setback:
The set room temperature must be
reduced by a minimum of 2 C / 3.6 F
by:
Pressing economy button
Changing from room heating with
normal temperature to heating with
reduced temperature
Shutdown optimisation
Quick setback will stop when the set
room temperature has been reached.
114
Downloaded from www.Manualslib.com manuals search engine
Function description Vitotronic 300-K, MW1S
115
Downloaded from www.Manualslib.com manuals search engine
Function description Vitotronic 300-K, MW1S
Supply temperature C / F
The differential temperature is that 87
189
minimum temperature differential by
which the common supply temperature
should be higher than the currently
8K
required supply temperature of the
mixing valve circuit.
+8K
Control sequence
Mixing valve circuit Supply temperature falls Supply temperature rises
The mixing valve motor will not be (set value 1 C / -2 F) (set value +1 C / 2 F)
activated within the neutral zone The mixing valve motor receives The mixing valve motor receives
(1 C / 2 F). the open signal. the close signal.
The signal duration lengthens with The signal duration lengthens with
an increasing control differential. an increasing control differential.
The duration of pauses reduces with The duration of pauses reduces
5581 750 v1.3
116
Downloaded from www.Manualslib.com manuals search engine
Function description Vitotronic 300-K, MW1S
Brief description
The DHW tank control logic is a During DHW tank heating, a constant Coding addresses which influence
set-point control. It is the result of boiler supply temperature will be set the DHW tank control
starting and stopping the DHW pump. (20 C / 36 F higher than the set 54 to 75, 7F, A2.
The switching differential is 2.5 C / DHW tank temperature, adjustable via For a description, see the coding
4.5 F. coding address 60) and space heating overview.
is switched OFF (optional DHW tank
priority).
Functions
Time program In conjunction with coding address 7F 7F : 0 Apartment building:
An automatic program or an individual 7F : 1 Detached house: Automatic mode
time program may be selected for DHW Automatic mode For systems with two or three
heating and the control of the DHW For systems with two or three space heating circuits, the heating times
recirculation pump. heating circuits, the heating times for the respective heating circuit
Compared with the space heating for the first of the existing heating will be applied.
circuits heat-up phase, DHW heating circuits will be applied. Individual time program
in automatic mode starts 30 minutes Individual time program The switching times for DHW heating
earlier. The switching times for DHW heating can be adjusted separately for each
The individual time program enables up and the DHW recirculation pump heating circuit.
to four switching periods per day to be have the same effect on all heating
set via the time switch to control the circuits.
DHW heating/heating and the DHW
recirculation pump.
Any DHW tank heating sequence will
be completed, independent of the time
program.
117
Downloaded from www.Manualslib.com manuals search engine
Function description Vitotronic 300-K, MW1S
Control sequence
Pump delay Coding 55 : 1: Coding 55 : 3:
The DHW pump continuous operation Adaptive DHW tank heating DHW tank control DHW heating (for
(coding 62 : 10) after the DHW tank DHW heating systems only)
heating, until With adaptive DHW tank heating, the The DHW tank goes cold
the difference between the boiler speed of the temperature rise during (set value 2.5 C / -4.5 F, adjustable
water and the DHW temperature DHW heating is taken into account. via coding address 59),
is less than 7 C / 13 F or Also taken into account is the question The common set supply temperature
the common supply temperature of whether the boiler will be required to is adjusted 20 C / 36 F higher than
is achieved based on outdoor reset supply heat after the DHW tank has the set DHW temperature (adjustable
calculations or been heated or whether residual boiler via coding address 60).
the actual temperature is 5 C / heat should be transferred to the DHW The primary DHW pump is switched
9 F higher than the set DHW tank. ON.
temperature or Accordingly, the control unit The three-way mixing valve opens
the maximum time delay (adjustable determines the burner and DHW and then regulates to the defaulted
via coding address 62) has been recirculation pump shutdown point set value.
reached. to prevent the set DHW temperature The DHW pump cycles (short term
Without the pump time-delay for being substantially exceeded after the ON and OFF) until the set supply
DHW tank heating DHW tank has been heated. temperature has been reached, then
(coding 62 : 0) it runs constantly. If, during DHW
tank heating, the actual value stays
Coding 55 : 2: below the required set supply
Coding 55 : 0: DHW tank temperature control with temperature, then the DHW pump
DHW heating 2 DHW tank temperature sensors will temporarily cycle again.
The DHW tank goes cold The 1st DHW tank temperature sensor The DHW tank is hot
(set value 2.5 C / 4.5 F, adjustable enables the DHW pump, and is (1st DHW tank temperature sensor:
via coding address 59) evaluated for stop conditions during Actual value set value
The common supply temperature is the pump run-on time. The 2nd DHW and
adjusted 20 C / 36 F higher than the tank temperature sensor (inside the 2nd DHW tank temperature sensor:
set DHW (adjustable via coding address cold water inlet) is designed to Actual value > set value 1.5 C /
60). prematurely start DHW tank heating -2.7 F)
when large quantities of DHW are the common set supply temperature
The DHW tank is hot drawn off as well as to prematurely is returned to the weather-
(set value +2.5 C / 4.5 F) stop DHW tank heating if no DHW compensated value;
The common set supply temperature is drawn. the DHW pump
is returned to the weather- is immediately switched OFF, if
compensated value. the three-way mixing valve is open
or
is switched OFF after run-on time
adjustable via coding 62.
5581 750 v1.3
118
Downloaded from www.Manualslib.com manuals search engine
Components Vitotronic 300-K, MW1S
Extension module
119
Downloaded from www.Manualslib.com manuals search engine
Components Vitotronic 300-K, MW1S
Fuse
F1 T4 A, 250 V,
max. power loss x 1.6 W
A1 A1 Power supply module
F1
120
Downloaded from www.Manualslib.com manuals search engine
Components Vitotronic 100, GC1
121
Downloaded from www.Manualslib.com manuals search engine
Components Vitotronic 100, GC1
660
Electrical connection
640 The sensors are ready to plug in.
Insert the boiler temperature sensor
in socket 3 of the boiler control.
620
600
580
Resistance in
560
400
540
0 20 40 60 80 100 120 140
32 68 104 141 176 212 248 284
Boiler temperature in C / F
122
Downloaded from www.Manualslib.com manuals search engine
Components Vitotronic 100, GC1
Electrical connection
The sensor is inserted in socket
17A or 17B 17A or 17B on the boiler control.
Return Resistance
temperature in
in C / F
30 / 86 569
17A or 17B 40 / 104 592
60 / 140 643
640
620
600
580
Resistance in
560
5581 750 v1.3
540
20 30 40 50 60 70 80 90 100
68 86 104 122 140 158 176 194 212
Return temperature in C / F
123
Downloaded from www.Manualslib.com manuals search engine
Components Vitotronic 100
Electrical connection
The sensor is inserted in socket 15
on the boiler control.
660
620
580
540
Resistance in
500
0 40 80 120 160 200 240 280
5581 750 v1.3
124
Downloaded from www.Manualslib.com manuals search engine
Components Vitotronic 300-K, MW1S
580
560
540
0 20 40 60 80 100
32 68 104 140 176 212
DHW tank temperature in C / F
5581 750 v1.3
125
Downloaded from www.Manualslib.com manuals search engine
Components Vitotronic 300-K, MW1S
740 Connection
See page 58 and 59.
720
Check sensor
1. Remove plug ?, aJA or aJB.
700
2. Check the sensor resistance at
terminals 1 and 2 of the plug.
680
severe deviation.
560
Specification
Protection: IP 32
540 Permiss. ambient
20 30 40 50 60 70 80 90 100
68 86 104 122 140 158 176 194 212 temperature
during operation:
Return temperature in C / F
0 to +100 C
32 to + 212 F
during storage and transport:
20 to + 70 C
4 to + 158 F
126
Downloaded from www.Manualslib.com manuals search engine
Components Vitotronic 300-K, MW1S
600 Connection
See page 58 and 59.
127
Downloaded from www.Manualslib.com manuals search engine
Components Vitotronic 300-K, MW1S
128
Downloaded from www.Manualslib.com manuals search engine
Components Vitotronic 300-K, MW1S
Installation examples
Mixing valve insert conversion (if required), see mixing valve installation instructions.
Factory supplied
of the mixing valve motor rotational Change the mixing valve motor rotational
direction direction for these installation examples
HV HV
KV HR HR KV
KR KR
KV KV
KR HV HV KR
HR HR
HR HR
HV KR KR HV
KV KV
HV HV
HR HR
KV KV
129
Downloaded from www.Manualslib.com manuals search engine
Components Vitotronic 300-K, MW1S
Remote control
Function changes can be made via coding addresses A0, b0 to b9, C0 to C2, E1 and E2 (see coding overview).
Connection
2-wire cable 164 ft / 50m
13b
B C
130
Downloaded from www.Manualslib.com manuals search engine
Components Vitotronic 333, MW1S
Specification
Power supply via KM BUS.
Safety class: III
Protection: IP 30
Permiss. ambient
temperature
ON during operation:
S6 0 to +40 C
D
32 to 104 F
1234
in storage and transport:
20 to +65 C
4 to +149 F
131
Downloaded from www.Manualslib.com manuals search engine
Components Vitotronic 300-K, MW1S
Function changes can be made via coding addresses A0, b0 to b9, C0 to C2, E1 and E2 (see coding overview).
Connection
A
2-wire cable 164 ft / 50 m.
13b
B C
132
Downloaded from www.Manualslib.com manuals search engine
Components Vitotronic 300-K, MW1S
Specification
Power supply via KM BUS.
Safety class: III
Protection: IP 30
Permiss. ambient
temperature
D in use:
0 to +40 C
32 to 104 F
in storage and transport:
D Printed Circuit Board DIP switches 20 to +65 C
(rear of the top casing) 4 to +149 F
Setting range for
Remote control DIP switch normal set room temp:
affects setting 10 to 30 C
50 to +86 F
System circuit A1 Factory setting adjustable between
(Heating circuit 3 to 23 C
selection 37 to 73 F
button !) or
17 to 37 C
63 to 97 F
via coding address E1
Mixing valve reduced set room temp:
circuit M2 3 to 37 C
(Heating circuit 37 to 97 F
selection
button ?) Battery type: Use alkaline
Mixing valve manganese
circuit M3 batteries
(Heating circuit type MICRO-
selection LR03 (AAA) which
button ) do not contain
pollutants
S30
5581 750 v1.3
133
Downloaded from www.Manualslib.com manuals search engine
Components Vitotronic 300-K, MW1S
Version 1
C D E
134
Downloaded from www.Manualslib.com manuals search engine
Components Vitotronic 300-K, MW1S
Version 2
max. 15 m / 50 ft max. 15 m / 50 ft
max.
C D E
15 m / 50 ft
A F
135
Downloaded from www.Manualslib.com manuals search engine
Components Vitotronic 300-K, MW1S
The room temperature sensor measures the actual room temperature, if the remote Vitotrol unit cannot be installed in a
suitable location.
600 Connection
See page 58 and 59.
560
Room temperature Resistance in
in C / F
550
10 / 50 522
15 / 59 534
540 25 / 77 557
Specification
500
Protection: IP 30
0 5 10 15 20 25 30 35 40
32 41 50 59 68 77 86 95 104 Permiss. ambient
temperature
Room temperature in C / F during operation:
0 to +40 C
32 to 104 F
in storage and transport:
20 to +65 C
4 to +149 F
136
Downloaded from www.Manualslib.com manuals search engine
Components Vitotronic 300-K, MW1S
From software version 7 of Vitotronic 300-K, MW1S, the Input Module can be connected (software version via scan 2:
1st digit, display 7).
Electronics
B
F1 ON
50mA
(slow)
OFF 1 2 3 4
L1 N S P 1 2 3 1 2 3
40
120 VAC _ +
A
157 144 145
Please note:
Amongst switches 1 to 3, only one switch may be set to ON.
2. Press D.
137
Downloaded from www.Manualslib.com manuals search engine
Coding Vitotronic 100, GC1
Coding 1
Calling up coding 1
1. Press 9 and w simultaneously 3. Change the value with or ;
1234567 for approx. two seconds, until the confirm with .
first arrow appears in the display. The value is transferred and does
not flash for approx. 2 seconds.
2. Select the required coding address Then the display flashes again.
with or ; Call up further addresses
the address flashes; with or .
confirm with ,
the value flashes. 4. Press 9 and w simultaneously
for approx. 1 second.
Summary
138
Downloaded from www.Manualslib.com manuals search engine
Coding Vitotronic 100, GC1
Coding 1 (cont.)
139
Downloaded from www.Manualslib.com manuals search engine
Coding Vitotronic 100, GC1
Coding 2
Calling up coding 2
1. Press w and rw simultaneously 3. Change the value with or ;
1234567 for approx. 2 seconds, until the first confirm with .
two arrows appear in the display; The value is saved and does
confirm with not flash for approx. 2 seconds.
Then the display flashes again.
2. Select the required coding address Call up further addresses
with or ; with or .
the address flashes;
confirm with , 4. Press w and rw simultaneously
the value flashes. for approx. 1 second.
Overall summary
140
Downloaded from www.Manualslib.com manuals search engine
Coding Vitotronic 100, GC1
Coding 2 (cont.)
141
Downloaded from www.Manualslib.com manuals search engine
Coding Vitotronic 100, GC1
Coding 2 (cont.)
142
Downloaded from www.Manualslib.com manuals search engine
Coding Vitotronic 100, GC1
Coding 2 (cont.)
143
Downloaded from www.Manualslib.com manuals search engine
Coding Vitotronic 100, GC1
Coding 2 (cont.)
144
Downloaded from www.Manualslib.com manuals search engine
Coding Vitotronic 100, GC1
Coding 2 (cont.)
145
Downloaded from www.Manualslib.com manuals search engine
Coding Vitotronic 100, GC1
Coding 2 (cont.)
146
Downloaded from www.Manualslib.com manuals search engine
Coding Vitotronic 100
OFF Time
+2
Set
-2
Lower Average Higher
heat demand heat demand heat demand
OFF Time
+9
+3
Set
-3
Lower Average Higher
heat demand heat demand heat demand
OFF Time
+17
+3
Set
-3
Lower Average High
heat demand heat demand heat demand
The heat demand-dependent switching differential takes the boiler load into account.
The switching differential, i.e. the burner operating time, changes based on current heat demand.
2. Press D.
Confirm Base setting? Yes with
.
5581 750 v1.3
147
Downloaded from www.Manualslib.com manuals search engine
Coding Vitotronic 300-K, MW1S
Coding 1
Calling up coding 1
Summary
148
Downloaded from www.Manualslib.com manuals search engine
Coding Vitotronic 300-K, MW1S
Coding 1 (cont.)
149
Downloaded from www.Manualslib.com manuals search engine
Coding Vitotronic 300-K, MW1S
Coding 1 (cont.)
150
Downloaded from www.Manualslib.com manuals search engine
Coding Vitotronic 300-K, MW1S
Coding 2
The summary from page 152 lists all possible coding addresses.
General
Cod. 40
General
Cod. 4A to 4F
DHW
Cod. 54 to 75
General
Cod. 76 to 9F
System circuit A1
Cod. A0 to F2
Mixer circuit M2
Cod. A0 to F2 Initially the possible coding addresses
A0 to F2 for the system circuit A1 are
Mixer circuit M3 scrolled, then those for mixing valve
Cod. A0 to F2 circuits M2 and M3, again starting with
coding address A0.
Calling up coding 2
151
Downloaded from www.Manualslib.com manuals search engine
Coding Vitotronic 300-K, MW1S
Coding 2 (cont.)
Overall summary
152
Downloaded from www.Manualslib.com manuals search engine
Coding Vitotronic 300-K, MW1S
Coding 2 (cont.)
153
Downloaded from www.Manualslib.com manuals search engine
Coding Vitotronic 300-K, MW1S
Coding 2 (cont.)
154
Downloaded from www.Manualslib.com manuals search engine
Coding Vitotronic 300-K, MW1S
Coding 2 (cont.)
155
Downloaded from www.Manualslib.com manuals search engine
Coding Vitotronic 300-K, MW1S
Coding 2 (cont.)
156
Downloaded from www.Manualslib.com manuals search engine
Coding Vitotronic 300-K, MW1S
Coding 2 (cont.)
73: 7 Constantly ON
75: 0 DHW recirculation pump during
economy mode:
ON acc. to time program 75: 1 OFF
157
Downloaded from www.Manualslib.com manuals search engine
Coding Vitotronic 300-K, MW1S
Coding 2 (cont.)
158
Downloaded from www.Manualslib.com manuals search engine
Coding Vitotronic 300-K, MW1S
Coding 2 (cont.)
159
Downloaded from www.Manualslib.com manuals search engine
Coding Vitotronic 300-K, MW1S
Coding 2 (cont.)
160
Downloaded from www.Manualslib.com manuals search engine
Coding Vitotronic 300-K, MW1S
Coding 2 (cont.)
161
Downloaded from www.Manualslib.com manuals search engine
Coding Vitotronic 300-K, MW1S
Coding 2 (cont.)
162
Downloaded from www.Manualslib.com manuals search engine
Coding Vitotronic 300-K, MW1S
Coding 2 (cont.)
163
Downloaded from www.Manualslib.com manuals search engine
Coding Vitotronic 300-K, MW1S
Coding 2 (cont.)
164
Downloaded from www.Manualslib.com manuals search engine
Coding Vitotronic 300-K, MW1S
Coding 2 (cont.)
165
Downloaded from www.Manualslib.com manuals search engine
Coding Vitotronic 300-K, MW1S
Coding 2 (cont.)
166
Downloaded from www.Manualslib.com manuals search engine
Coding Vitotronic 300-K, MW1S
Coding 2 (cont.)
167
Downloaded from www.Manualslib.com manuals search engine
Coding Vitotronic 300-K, MW1S
50
40
30
Supply
20
10
1 5 10 15 20 25 30
Days
Temperature-time profile 2 (coding F1 : 2)
temperature C
50
40
30
Supply
20
10
1 5 10 15 20 25 30
Days
Temperature-time profile 3 (coding F1 : 3)
temperature C
50
40
30
Supply
20
10
1 5 10 15 20 25 30
Days
Temperature-time profile 4 (coding F1 : 4)
temperature C
50
40
30
Supply
20
10
1 5 10 15 20 25 30
Days
5581 750 v1.3
168
Downloaded from www.Manualslib.com manuals search engine
Connection and wiring diagrams Vitotronic 100, GC1
Summary
169
Downloaded from www.Manualslib.com manuals search engine
Connection and wiring diagrams Vitotronic 100, GC1
34-pin
Boiler temperature sensor
% No function
aG Flue gas temperature sensor
aJA
A1
Temperature sensor T1
1
equipment
LON Interconnecting cable for data
transfer between control units
S3 Override switch S
V1 Fault indicator (red)
V2 ON/OFF indicator (green)
A9
A6
A2
A7
A10
170
Downloaded from www.Manualslib.com manuals search engine
Connection and wiring diagrams Vitotronic 100, GC1
s Control output
sA DHW pump
sL Shunt or boiler circuit pump
f Power supply, 120 VAC
fA Burner, connection
to DIN 4791
g Compiled failure alarm
gS Boiler isolation valve
or
Boiler return valve
l Burner stage 2/mod.
aB External connections
a External safety equipment
(remove jumper
when connecting)
b External disable
(remove jumper
when connecting)
c External burner activation
aBA Safety circuit
aBH Power supply for connection
accessories
F1, F2 Fuses
F6 Fixed high limit E 120 C/
248 F
(99 or 110 C/210 or 230 F)
F7 Adjustable high limit R
95 C / 203 F
(100 C, 110 C /
212 F, 230 F)
K1-K10 Relays
S1 ON/OFF switch 8
S2 Test switch
5581 750 v1.3
171
Downloaded from www.Manualslib.com manuals search engine
Connection and wiring diagrams Vitotronic 100. GC1
floating
ON ON
A11
A3
172
Downloaded from www.Manualslib.com manuals search engine
Parts List Vitotronic 300-K, MW1S
Parts
001 Power supply module 120VAC
002 Cascade electronics module
004 Power module
005 Extension module
006 Frame for programming unit
007 Programming unit
010 Front panel with heating circuit
selector
013 Empty housing
018 Outdoor temperature sensor
019 Strap-on temperature sensor
020 DHW tank temperature sensor
021 Connecting cable
022 Ribbon cable
173
Downloaded from www.Manualslib.com manuals search engine
Appendix
174
Downloaded from www.Manualslib.com manuals search engine
Appendix
Applicability
175
Downloaded from www.Manualslib.com manuals search engine
Additional information
Quick Reference
-40 -40
-35 -31
-25 -13
-20 -4
-18 0
-16 +3
-14 +7
-12 +10
-10 +14
-9 +16
-8 +18
-7 +19
-6 +21
-5 +23
-4 +25
-3 +27
-2 +28
-1 +30
0 +32
+1 +34
+2 +36
+3 +37
+4 +39
+5 +41
176
Downloaded from www.Manualslib.com manuals search engine