Академический Документы
Профессиональный Документы
Культура Документы
FUJITSU LIMITED
Before You Begin
All product or service names mentioned in this document are trademarks or registered trademarks of their
respective companies.
This document and its contents are provided by FUJITSU Limited (FUJITSU) for guidance purposes only. This document is
provided as is with no warranties or representations whatsoever, either express or implied, including without limitation the
implied warranties of merchantability and fitness for purpose. FUJITSU does not warrant or represent that the contents of
this document are error free. Furthermore, the contents of this document are subject to update and change at any time
without notice by FUJITSU, since FUJITSU reserves the right, without notice, to make changes in equipment design or
components as progress in engineering methods may warrant. No part of the contents of this document may be copied,
modified, or otherwise reproduced without the express written consent of FUJITSU.
Keep the manual set at hand so that you can refer to it at any time.
Observe the notices and instructions provided in this manual set for your proper and
safety installation, use and maintenance of the equipment.
Elevated voltages are inevitably present at specific points in this electrical equipment.
Some of the parts may also have elevated operating temperatures. Systems with
forced ventilation have rotating items.
Non-observance of these conditions and the safety instructions can result in personal
injury or in property damage.
The system complies with the standard EN 60950-1 / IEC 60950-1. All equipment
connected has to comply with the applicable safety standards.
Mount the systems in areas with restricted access only. Only trained and qualified
personnel may install, operate, and maintain the systems.
Contents
List of Illustrations
Figure 4-1 Topology of Traffic Frame Loss Scenario ........................................................... 4-2
Figure 4-2 Topology of Traffic Block Scenario ..................................................................... 4-3
Figure 4-3 Loop on WAN Port ............................................................................................. 4-5
Figure 5-1 SC 1+1 Working Status .................................................................................... 5-11
List of Tables
Table 1-1 List of Used Conventions..................................................................................... 1-3
Table 1-2 History of Changes.............................................................................................. 1-4
Table 2-1 Equipment Alarms ............................................................................................... 2-2
Table 2-2 Communication Alarms ....................................................................................... 2-5
Table 2-3 Environmental Alarms ......................................................................................... 2-5
Table 2-4 Quality of Service Alarms .................................................................................... 2-7
Table 2-5 Security Alarms ................................................................................................... 2-7
Table 4-1 Incorrect Configuration of Traffic Block Scenario.................................................. 4-3
Table 5-1 Switch Priority of SC 1+1................................................................................... 5-12
CHAPTER 1
Preface
This document is intended for anyone tasked with clearing fault conditions to restore normal
system operation. Personnel performing these procedures must have general experience
with Synchronous Digital Hierarchy (SDH) transport networks as well as specific experience
with Fujitsu FLASHWAVE 4570 hardware components and network management software.
Personnel must also comply with all relevant safety practices whenever working with
FLASHWAVE 4570 equipment.
Alarm lists
When a fault condition occurs, the relevant alarm notification will be generated and displayed
on craft terminal screens. All FLASHWAVE 4570 alarms are listed in the Alarm lists in
Chapter 2. The alarm lists are divided into separate tables that match the fault categories as
presented on craft terminal screens. These categories are as follows:
Equipment alarms
Communication alarms
Environment alarms
Quality of Service (QoS) alarms
Security alarms
Troubleshooting
For each entry in the Alarm lists, specific fault-clearing procedures are contained in Chapter
3, Troubleshooting.
Described Features
Some features described in this document may not be available. To identify the features
i released for your project, please refer to the Release Note delivered together with the
product.
Danger This symbol identifies notes which, if ignored, can result in bodily harm.
!
Warning This symbol identifies notes which, if ignored, can result in damage to the equipment.
!
Caution This symbol identifies notes which, if ignored, can result in service interruption.
!
i This symbol stands for an important note to be paid extra attention to, or additional
information which extends beyond the immediate context.
This symbol stands for a cross reference to other chapters in this manual or reference to
other manuals.
Help This symbol stands for a reference to the online help system of the FLEXR L local craft
terminal or FLEXR C subnetwork management system software.
Representation Meaning
Inverted commas Window or wizard titles are represented in inverted commas.
Example: Open the Help and Support Center window. The New
Connection wizard is displayed.
Bold Any field or text in the GUI is represented in bold type. Example:
Click Shutdown and then click OK to turn off the computer.
Italic Variables and file extensions are represented in italic.
Example: Enter 192.168.0.1 in the IP address field. Click OK to
produce a .pdf rendition.
Courier Commands, screen output, file names and paths are represented
in courier.
Example: # ping -t 192.168.0.1
<Angle brackets> Used for keyboard actions or place holders for concrete names or
values are represented in <angle brackets>. If used for a filename
the courier font must be used also.
Example: The naming convention for the log files is
<NEname>.txt, where <NEName> is the name of the NE sending
the messages. Press <CTRL>+<ALT><DEL> to open the task
manager.
CHAPTER 2
Alarm Lists
CHAPTER 3
Troubleshooting
This chapter describes the general troubleshooting instructions for each alarm.
3.1.1 Communication_Fail
Troubleshooting instructions
1 Reboot or replace the traffic card.
2 Reboot or replace the SC card.
3 If the alarm persists, contact the next higher level of technical support.
i If the communication failure happens between two SC cards in the 1+1 rendundant
SC system, follow the procedure below to solve the problem.
i When replacing an SC card, remember to take out the CF card from the original SC
card and insert it into the new SC card.
3.1.2 Equipment_Overheating
Alarm object SC, HOCC, LOCC, and all service cards (not
including IO cards)
General information and causes The temperature of the equipment is not in the
normal working range which is specified in the card
properties configuration.
Troubleshooting instructions
1 Verify that the fan unit is working normally.
2 Verify that the filter unit is clean.
3 Verify that the air-conditioning (if any) is working correctly.
4 Verify that the equipment is working normally.
5 Verify that the card temperature threshold is configured properly.
6 If the alarm persists, contact the next higher level of technical support.
3.1.3 Fan_Failure
Troubleshooting instructions
1 Verify the fans in the fan unit are working normally.
2 Replace the fan unit. Changing the upper faulty fan unit must be finished within 2
minutes.
3 If the alarm persists, contact the next higher level of technical support.
3.1.4 Loss_of_Power_Input
Troubleshooting instructions
1 Verify that the power cables to the power module are connected correctly.
2 If the alarm persists, contact the next higher level of technical support.
3.1.5 Low_Board_Flash_Card_Capacity
Troubleshooting instructions
1 Delete some information in the CF card.
2 If the alarm persists, contact the next higher level of technical support.
3.1.6 Low_Order_Capacity_Mismatch
Troubleshooting instructions
1 Download a backup MIB from the PC into the CF card of the newly inserted SC card.
For more information on MIB download, please refer to CHAPTER 6.
2 If the alarm persists, contact the next higher level of technical support.
Caution If there is no backup MIB, the system will have to be reconfigured.
3.1.7 No_Free_Low_Order_Capacity
Troubleshooting instructions
1 Upgrade the LOCC capacity.
2 Delete some existing low order mapping.
3 If the alarm persists, contact the next higher level of technical support.
3.1.8 NO.XFan_Failure
Troubleshooting instructions
1 Replace the failed fan unit. Replacement of the faulty fan unit must be finished within 2
minutes. To ensure this, prepare the new fan unit before starting the exchange process
(e.g. unpack the unit, check the part numbers, visual inspection of the unit).
2 If the alarm persists, contact the next higher level of technical support.
3.1.9 OA-Power_Failure
Troubleshooting instructions
1 Replace the OA card.
2 If the alarm persists, contact the next higher level of technical support.
3.1.10 OA-Pump_Bias_out_of_Range
Troubleshooting instructions
1 Verify that the OA pump bias threshold is configured properly.
2 Verify that the OA input power is normal.
3 Verify that the OA card is not aging.
4 If the alarm persists, contact the next higher level of technical support.
3.1.11 OA-Temperature_out_of_Range
Troubleshooting instructions
1 Verify that the fan unit is working correctly.
2 Verify that the OA temperature threshold is configured properly.
3 If the alarm persists, contact the next higher level of technical support.
3.1.12 PLL_Unlock
Troubleshooting instructions
1 If fault occurs during the card boot or synchronization, wait till the initialization process of
the card is complete.
2 If the alarm continues after the initialization is complete, replace the card.
3 If the alarm persists, contact the next higher level of technical support.
3.1.13 Power_Failure
Troubleshooting instructions
1 Change the power module.
2 If the alarm persists, contact the next higher level of technical support.
3.1.14 SC_CF_Module_Absent
Troubleshooting instructions
1 Insert the CF card.
For more detailed instruction, refer to The FLASHWAVE 4570 Installation and Test
Manual (ITMN).
2 If the alarm persists, contact the next higher level of technical support.
3.1.15 SC_CF_Module_Failure
Troubleshooting instructions
1 Replace the CF card.
For more detailed instruction, refer to The FLASHWAVE 4570 Installation and Test
Manual (ITMN).
2 If the alarm persists, contact the next higher level of technical support.
3.1.16 SC_SW_Version_Mismatch
Troubleshooting instructions
1 Find which SC card contains the wrong version of the software and replace the wrong
card with a new SC with correct version of the software, or upgrade or downgrade the
software of the wrong one to the correct version.
2 If the alarm persists, contact the next higher level of technical support.
i Make sure that there is a CF card within the SC card. If the software version is
unknown, contact technical support for help.
3.1.17 SFP_Absent
Troubleshooting instructions
1 Insert the proper SFP module.
2 If the alarm persists, contact the next higher level of technical support.
3.1.18 SFP_Failure
Troubleshooting instructions
1 Replace the SFP module.
2 If the alarm persists, contact the next higher level of technical support.
3.1.19 SFP_Mismatch
Troubleshooting instructions
1 Replace the SFP module with a suitable one.
2 If the alarm persists, contact the next higher level of technical support.
3.1.20 SPI-Temperature_out_of_Range
Troubleshooting instructions
1 Verify the refrigeration part and the bias current part of the laser are working normally.
2 Replace the 10 Gigabit Small Form Factor Pluggable (XFP) module.
3 If the alarm persists, contact the next higher level of technical support.
3.1.21 Unit_Failure
Troubleshooting instructions
1 Replace the card.
2 If the alarm persists, contact the next higher level of technical support.
3.1.22 Unit_Removal
Troubleshooting instructions
1 Insert the card.
2 If the alarm persists, contact the next higher level of technical support.
3.1.23 Unit_Type_Mismatch
Troubleshooting instructions
1 Replace the card with the correct one.
2 Verify that the card type set in SEEPROM is correct through the mini USB port on the
card.
3 If the alarm persists, contact the next higher level of technical support.
3.1.24 VCXO_Failure
General information and causes The VCXO component on the HOCC card has
failed.
Troubleshooting instructions
1 Replace the HOCC card.
2 If the alarm persists, contact the next higher level of technical support.
3.2.1 AU_AIS
Troubleshooting instructions
1 Troubleshoot the SPI, RS, MS, or AU-LOP alarms in the upstream node.
2 If the alarm persists, contact the next higher level of technical support.
3.2.2 AU_LOP
Troubleshooting instructions
1 Verify that the upstream external fiber connections are correct.
2 If the alarm persists, contact the next higher level of technical support.
Troubleshooting instructions
1 Check the routing configuration for any error.
2 If the alarm persists, contact the next higher level of technical support.
3.2.4 HCOC27-DCC_Connection_Failure
Troubleshooting instructions
1 Verify that the HCOC27-DCC is enabled and working normally at both ends of the DCC
link.
2 If the alarm persists, contact the next higher level of technical support.
3.2.5 HCOC9-DCC_Connection_Failure
Troubleshooting instructions
1 Verify the HCOC9-DCC is enabled and working normally at both ends of the DCC link.
2 If the alarm persists, contact the next higher level of technical support.
3.2.6 HP-DEG
Troubleshooting instructions
1 Verify that the upstream external cabling and equipment are normal.
3.2.7 HP-EXC
Troubleshooting instructions
1 Verify that the upstream external cabling and equipment are normal.
2 Verify that the threshold is set correctly.
3 If the alarm persists, contact the next higher level of technical support.
3.2.8 HP-GFP_Customer_Signal_Failure
Troubleshooting instructions
1 Check the upstream external cabling and equipment for any error.
2 If the alarm persists, contact the next higher level of technical support.
3.2.9 HP-GFP_Loss_of_Frame_Delineation
Troubleshooting instructions
1 Verify that the upstream connection and equipment are normal.
2 If the alarm persists, contact the next higher level of technical support.
3.2.10 HP-PLM
Troubleshooting instructions
1 Change the mapping mode of the local node to the same mode as that of the remote
node.
2 Change the expected payload value of the local node to the same one as the actual
payload value of the remote node.
3 If the alarm persists, contact the next higher level of technical support.
3.2.11 HP-RDI
Troubleshooting instructions
1 React to the far-end alarms.
2 If the alarm persists, contact the next higher level of technical support.
3.2.12 HP-TIM
Troubleshooting instructions
1 Verify that the expected path trace identifier is correct.
2 If the alarm persists, contact the next higher level of technical support.
3.2.13 HP-UNEQ
Troubleshooting instructions
1 Verify that the cross connection are the same at the both end.
2 If the alarm persists, contact the next higher level of technical support.
3.2.14 HP-Virtual_Concatenation_LOA
Troubleshooting instructions
1 Check the SDH path for each VCG member to see which member passes through the
most nodes or is taking the longest time, and configure the shorter route.
2 If the alarm persists, contact the next higher level of technical support.
3.2.15 HP-Virtual_Concatenation_LOM
Troubleshooting instructions
1 Check the VCG member of the relevant terminal point for alarms.
2 Check the performance monitoring of the relevant VCG member terminal point for errors.
3 If the alarm persists, contact the next higher level of technical support.
3.2.16 HP-Virtual_Concatenation_PLCR
Troubleshooting instructions
1 Check upstream external cabling and equipment for any error.
2 If the alarm persists, contact the next higher level of technical support.
3.2.17 HP-Virtual_Concatenation_PLCT
Troubleshooting instructions
1 Check the upstream external cabling and equipment for any error.
2 If the alarm persists, contact the next higher level of technical support.
3.2.18 HP-Virtual_Concatenation_TLCR
Troubleshooting instructions
1 Check the upstream external cabling and equipment for any error.
2 If the alarm persists, contact the next higher level of technical support.
3.2.19 Link_Failure
Troubleshooting instructions
1 Verify that the connections of the physical layer are correct.
2 Verify that the fiber cable connectors are clean.
3 Verify that the fiber type is correct.
4 If the alarm persists, contact the next higher level of technical support.
3.2.20 Loss_of_Timing_Input
General information and causes No incoming signal on the 2048 KHz/Kbps station
clock port. This is detected by the absence of
pulses in the signal.
Fault in the equipment producing the station
clock.
Discontinuity in the cabling between the station
clock equipment and the node or erroneous
routing
Troubleshooting instructions
1 Verify that the connections of the physical layer are correct.
2 Verify that the fiber cables are not damaged and the connectors are not dirty.
3 If the alarm persists, contact the next higher level of technical support.
3.2.21 Loss_of_Timing_Output
Troubleshooting instructions
1 Verify that the synchronization configuration is correct.
2 Verify that the external timing input is normal.
3 Replace the HOCC card.
4 If the alarm persists, contact the next higher level of technical support.
3.2.22 LP-DEG
Troubleshooting instructions
1 Check the upstream external cabling and equipment for error.
2 Verify that the threshold configuration is correct.
3 If the alarm persists, contact the next higher level of technical support.
3.2.23 LP-EXC
Troubleshooting instructions
1 Check the upstream external cabling and equipment for error.
2 Verify that the threshold configuration is correct.
3 If the alarm persists, contact the next higher level of technical support.
3.2.24 LP-GFP_Customer_Signal_Failure
Troubleshooting instructions
1 Check the upstream external cabling and equipment for error.
2 If the alarm persists, contact the next higher level of technical support.
3.2.25 LP-GFP_Loss_of_Frame_Delineation
Troubleshooting instructions
1 Check the upstream connection and equipment for error.
2 If the alarm persists, contact the next higher level of technical support.
3.2.26 LP-PLM
Troubleshooting instructions
1 Verify that the traffic bandwidth structure of the local node is the same as that of the
remote node.
2 Change the expected traffic type of the local node using the TP Configuration menu of
the FLEXR L to match the actual payload value in remote node.
3 If the alarm persists, contact the next higher level of technical support.
3.2.27 LP-RDI
Troubleshooting instructions
1 No error in the reporting node. Troubleshoot the failure that caused the LP-RDI
generation at the far-end node.
2 If the alarm persists, contact the next higher level of technical support.
3.2.28 LP-RFI
Troubleshooting instructions
1 No error in the reporting node. Troubleshoot the failure that caused the LP-RFI
generation at the far-end node.
2 If the alarm persists, contact the next higher level of technical support.
3.2.29 LP-TIM
Troubleshooting instructions
1 Check the cross-connections for any error.
2 Check the tributary cables and tributary units for any error.
3 Verify that the provisioned expected trace ID is correct
4 If the alarm persists, contact the next higher level of technical support.
3.2.30 LP-UNEQ
Troubleshooting instructions
1 Confirm or create the cross connection settings at the remote side to be consistent with
the local side.
2 If the alarm persists, contact the next higher level of technical support.
i When defining or changing a cross-connection this alarm will almost inevitably come
up as it is practically impossible to validate the changes at both sides at the same
moment.
Warning The LP-UNEQ cannot be reported from 126 E1 (W/P) cards monitored ports if
there is no cross-connection card equipped in NE.
!
3.2.31 LP-Virtual_Concatenation_LOA
Troubleshooting instructions
1 Check the SDH path for each VCG member to see which member passes through the
most nodes or is taking the longest time, and configure the shorter route.
2 If the alarm persists, contact the next higher level of technical support.
3.2.32 LP-Virtual_Concatenation_LOM
Troubleshooting instructions
1 Check the VCG member of the relevant terminal point for alarms..
2 Check the performance monitoring of the relevant VCG member terminal point for errors.
3 If the alarm persists, contact the next higher level of technical support.
3.2.33 LP-Virtual_Concatenation_TLCR
Troubleshooting instructions
1 Check the upstream external cabling and equipment for error.
2 If the alarm persists, contact the next higher level of technical support.
3.2.34 MS_AIS
Troubleshooting instructions
1 Check the upstream external cabling and equipment for any error.
2 If the alarm persists, contact the next higher level of technical support.
3.2.35 MS-DCC_Connection_Failure
Troubleshooting instructions
1 Verify that the MS-DCC is enabled and working normally at both ends of the MS DCC
link.
2 If the alarm persists, contact the next higher level of technical support.
3.2.36 MS_DEG
Troubleshooting instructions
1 Check the upstream external cabling and equipment for any error.
2 Verify that the threshold is configured correctly.
3 If the alarm persists, contact the next higher level of technical support.
3.2.37 MS_EXC
Troubleshooting instructions
1 Check the upstream external cabling and equipment for any error.
2 Verify that the threshold is configured correctly.
3 If the alarm persists, contact the next higher level of technical support.
3.2.38 MS-K1/K2_Mismatch
Troubleshooting instructions
1 Verify that the conditions of protection switching are normal.
2 If the alarm persists, contact the next higher level of technical support.
3.2.39 MS_RDI
i RS-TIM (enable TIM and enable TIM AIS) will cause MS-RDI.
RS-TIM (enable TIM and disable TIM AIS) will not cause MS-RDI.
Troubleshooting instructions
1 Check the upstream external cabling and equipment for any error.
2 Verity that the local transmitting equipment is working normally.
3 Troubleshoot the faults reported in the far-end node.
4 If the alarm persists, contact the next higher level of technical support.
3.2.40 OA-Gain_High
General information and causes Gain of OA is too high and has exceeded the
following threshold:
20 dB POA: > 21 dB
13 dBm BOA: > 19 dB
15 dBm BOA: > 21 dB
18 dBm BOA: > 24 dB
Troubleshooting instructions
1 Verify that the output power of the OA is set properly.
2 Verity that the input power of the OA is normal.
3 If the alarm persists, contact the next higher level of technical support.
3.2.41 OA-Input_LOS
Troubleshooting instructions
1 Verify that the connections of the physical layer are correct.
2 Verity that the transmitter in the far-end is working normally.
3 Verify that the fibers and connectors are not damaged.
4 Measure the input power and verify that the pre-defined input power threshold is correct.
5 Clean the optical connector if it is dirty.
6 If the alarm persists, contact the next higher level of technical support.
3.2.42 OA-Output_LOS
Troubleshooting instructions
1 Verify that the local transmitting module is working normally.
3.2.43 OA-Output_Power_High
Troubleshooting instructions
1 Verify that the gain of the OA is configured properly.
2 Verify the input power of the OA is proper.
3 If the alarm persists, contact the next higher level of technical support.
3.2.44 ODU_AIS
Troubleshooting instructions
1 Verify that the transmitter in the far-end is working normally.
2 If the alarm persists, contact the next higher level of technical support.
3.2.45 ODU_BDI
Troubleshooting instructions
1 Check the upstream external cabling and equipment for any error.
2 Verify that the local transmitter is working normally.
3 Troubleshoot the reported receivers fault in the far-end.
4 If the alarm persists, contact the next higher level of technical support.
3.2.46 ODU_DEG
Troubleshooting instructions
1 Check the upstream external cabling and equipment for error.
2 Verify that the degraded monitor (DEGM) interval and threshold are configured correctly.
3 If the alarm persists, contact the next higher level of technical support.
3.2.47 ODU_LCK
Troubleshooting instructions
1 Verify that the transmitter in the far-end is working normally.
2 If the alarm persists, contact the next higher level of technical support.
3.2.48 ODU_LOFLOM
Troubleshooting instructions
1 Verify that the transmitter in the far-end is working normally.
2 If the alarm persists, contact the next higher level of technical support.
3.2.49 ODU_MSIM
Troubleshooting instructions
1 Reconfigure the mapping mode of the local side to the same as that of the remote node.
2 If the alarm persists, contact the next higher level of technical support.
3.2.50 ODU_OCI
Troubleshooting instructions
1 Verify that the ODU connection of the far-end node is correct.
2 If the alarm persists, contact the next higher level of technical support.
3.2.51 ODU_PLM
Troubleshooting instructions
1 Verify that the mapping mode of the local node is the same as that of the remote node.
2 Reconfigure the expected payload value of the local node to match the actual payload
value in the remote node.
3 If the alarm persists, contact the next higher level of technical support.
3.2.52 ODU_TIM
Troubleshooting instructions
1 Verify that the fiber cable connection is correct.
2 Verify that the expected trace identifier is configured correctly.
3 If the alarm persists, contact the next higher level of technical support.
3.2.53 OTU-BDI
Troubleshooting instructions
1 Check the upstream external fibers and equipment for any error.
2 Verify that the local node is working normally.
3 Troubleshoot the indicated receive side faults in the far-end node..
4 If the alarm persists, contact the next higher level of technical support.
3.2.54 OTU-DEG
General information and causes DEGM consecutive bad intervals (which is 1 second
period used for performance monitoring) are
detected.
A degraded signal defect (dDEG) is detected
Troubleshooting instructions
1 Check the upstream external cabling and equipment for error.
2 Verify that the degraded monitor (DEGM) interval and threshold are configured correctly.
3 If the alarm persists, contact the next higher level of technical support.
3.2.55 OTU-LOF
Troubleshooting instructions
1 Verify that the transmitter in the far-end is working normally.
2 If the alarm persists, contact the next higher level of technical support.
3.2.56 OTU-LOM
Troubleshooting instructions
1 Verify that the transmitter in the far-end is working normally.
2 If the alarm persists, contact the next higher level of technical support.
3.2.57 OTU-TIM
General information and causes The received OTU trace identifier does not match the
provisioned value.
Fiber cable connection is not correct.
Configuration of the expected trace identifier is
not correct
Troubleshooting instructions
1 Verify that the fiber cable connection is correct.
2 Verify that the expected trace identifier is configured correctly.
3 If the alarm persists, contact the next higher level of technical support.
3.2.58 PPI-AIS
Troubleshooting instructions
1 Check the upstream external cabling and equipment for error.
2 If the alarm persists, contact the next higher level of technical support.
3.2.59 PPI-LOF
Troubleshooting instructions
1 Verify that the transmitter in the far-end is working normally.
2 If the alarm persists, contact the next higher level of technical support.
3.2.60 PPI-LOM
General information and causes There is loss of multi-frame in E1. It is not possible
to align the multi-frame structure of the E1 signal
received to the Cyclic Redundancy Check (CRC)
multiframe.
Troubleshooting instructions
1 Verify that the transmitter in the far-end is working normally.
2 If the alarm persists, contact the next higher level of technical support.
3.2.61 PPI-LOS
Troubleshooting instructions
1 Check the connections of the physical layer for error.
2 Verify there is no cable breaks or dirty connectors (measure it with power meter and
clear it).
3 If the alarm persists, contact the next higher level of technical support.
3.2.62 PPI-RDI
Troubleshooting instructions
1 Verify that the transmitter in the local node is working normally.
2 If the alarm persists, contact the next higher level of technical support.
3.2.63 RPR-Exceed_Max_Stations
Troubleshooting instructions
1 Reduce the station number of the ring to 32.
2 If the alarm persists, contact the next higher level of technical support.
3.2.64 RPR-Link_Failure_East
Troubleshooting instructions
1 Verify that the optical fiber or the SDH cross-connection used for the east RPR path has
no problem.
2 If the alarm persists, contact the next higher level of technical support.
3.2.65 RPR-Link_Failure_West
Troubleshooting instructions
1 Verify that the optical fiber or the SDH cross-connection used for the west RPR path has
no problem.
2 If the alarm persists, contact the next higher level of technical support.
3.2.66 RPR-Miscabling_East
Troubleshooting instructions
1 Re-configure the RPR link direction of one of the links, either local or far end, to make
sure the west (east) link connects to the east (west) link. Ensure this change is
consistent with the rest of the topology structure.
2 If the alarm persists, contact the next higher level of technical support.
3.2.67 RPR-Miscabling_West
Troubleshooting instructions
1 Re-configure the RPR link direction of one of the links, either local or far end, to make
sure the west (east) link connects to the east (west) link. Ensure this change is
consistent with the rest of the topology structure.
2 If the alarm persists, contact the next higher level of technical support.
3.2.68 RPR-Protection_Misconfig
Troubleshooting instructions
1 Verify that the protection mode in all of the RPR stations of the ring is the same.
2 If the alarm persists, contact the next higher level of technical support.
3.2.69 RPR-Ringlet0_ReservedA0_Exceeding
Troubleshooting instructions
1 Re-configure the A0 bandwidth reserved on RPR ringlet0 and make sure that it does not
exceed the available link rate.
2 If the alarm persists, contact the next higher level of technical support.
3.2.70 RPR-Ringlet1_ReservedA0_Exceeding
Troubleshooting instructions
1 Re-configure the A0 bandwidth reserved on RPR ringlet1 and make sure it does not
exceed the available link rate.
2 If the alarm persists, contact the next higher level of technical support.
3.2.71 RPR-Topology_Inconsistent
Troubleshooting instructions
1 Re-configure the duplicated RPR stations MAC address.
2 If the alarm persists, contact the next higher level of technical support.
3.2.72 RPR-Topology_Instability
General information and causes Topology instability is caused by the topology not
being discovered correctly, because of reasons
such as the incorrect configuration of RPR links
and stations.
Troubleshooting instructions
1 Reconfigure the RPR networks topology (such as the cross connection (CC), the WAN
port trigger, the optical link, etc.) and make sure the configuration is correct.
2 If the alarm persists, contact the next higher level of technical support.
3.2.73 RS-DCC_Connection_Failure
Troubleshooting instructions
1 Verify the RS-DCC is enabled and working normally at both ends of the RS DCC link.
2 If the alarm persists, contact the next higher level of technical support.
3.2.74 RS-DEG
Troubleshooting instructions
1 Check the upstream external cabling and equipment for any possible errors.
2 Verify that the threshold is configured correctly.
3 If the alarm persists, contact the next higher level of technical support.
3.2.75 RS-EXC
Troubleshooting instructions
1 Check the upstream external cabling and equipment for error.
2 Verify that the threshold is set correctly.
3 If the alarm persists, contact the next higher level of technical support.
3.2.76 RS-LOF
Troubleshooting instructions
1 Verify that the intermediate fiber is normal.
2 Verify that the connectors are clean.
3 Loop the signal from the transmitter to the receiver. Verify that no LOF fault is reported.
If there is LOF, replace the card.
4 Verify that the incoming signal rate is correct.
5 Verify that the transmitter in the far-end is normal.
6 If the alarm persists, contact the next higher level of technical support.
i This alarm can be enabled or disabled in the Alarm Rule Switch Configuration
window of the FLEXR L by selecting Fault > Alarm Rule Switch Configuration.
3.2.77 RS-TIM
Troubleshooting instructions
1 Verify that the fiber cables are connected correctly by interpreting the received STM-N
RS trace identifiers.
2 Verify that the expected RS trace identifier is correct.
3 If the alarm persists, contact the next higher level of technical support.
3.2.78 Signal_Error_Fail
Troubleshooting instructions
1 Verify the connections of the physical layer are correct..
2 Verify that the transmitter in the far-end is working normally.
3 Verify that the connectors are clean.
4 Check whether there is fiber breaks or dirty connector.
5 Verify that the card state is normal.
6 If the alarm persists, contact the next higher level of technical support.
3.2.79 SPI-LOS
Troubleshooting instructions
1 Verify that the connections of the physical layer are correct.
2 Verify that the transmitter in the far-end is working normal.
3 Verify that the connectors are clean.
4 Check whether there is fiber breaks or dirty connector.
5 If the alarm persists, contact the next higher level of technical support.
3.2.80 Synchronization_Signal_Message_Mismatch
Troubleshooting instructions
1 Verify that the SSM byte value is valid.
2 If the alarm persists, contact the next higher level of technical support.
3.2.81 System_Clock_Holdover_Longer
Troubleshooting instructions
1 Repair the failed timing reference.
2 Re-lock the system clock to a valid timing reference.
3 If the alarm persists, contact the next higher level of technical support.
3.2.82 System_Clock_Unlocked
Troubleshooting instructions
1 Verify the selected timing reference works normally.
2 Re-select a valid timing reference.
3 Set the system clock working mode as locked
4 If the alarm persists, contact the next higher level of technical support.
3.2.83 Timing_Reference_Degrade
Troubleshooting instructions
1 Verify that the upstream equipment is working normally.
2 Verify that the local timing input equipment is working normally.
3 If the alarm persists, contact the next higher level of technical support.
3.2.84 Timing_Reference_Failure
Troubleshooting instructions
1 Check the upstream external cabling and equipment for any error.
2 Verify that the local timing input equipment is working normally.
3 If the alarm persists, contact the next higher level of technical support.
3.2.85 TU-AIS
Troubleshooting instructions
1 Check the upstream external cabling and equipment for any error.
2 If the alarm persists, contact the next higher level of technical support.
3.2.86 TU-LOM
Troubleshooting instructions
1 Check the upstream external cabling and equipment for error.
2 Using the management system, check if the card generating the multi-frame alignment
signal has a unit failure. If so, replace it with a new one.
3 If there is no unit failure found, loop the STM-1 signal at the transmitting NE and at the
receiving NE. In this condition, the NE reporting VC-4 loss of multiframe contains the
faulty unit.
4 If the alarm persists, contact the next higher level of technical support.
i This alarm can be enabled or disabled in the Alarm Rule Switch Configuration
window of the FLEXR L by selecting Fault > Alarm Rule Switch Configuration.
3.2.87 TU-LOP
Troubleshooting instructions
1 Check the upstream external cabling and equipment for any error.
2 Verify that the TP multiplexer structure of the both ends of the path is the same.
3 If the alarm persists, contact the next higher level of technical support.
i This alarm can be enabled or disabled in the Alarm Rule Switch Configuration
window of the FLEXR L by selecting Fault > Alarm Rule Switch Configuration.
3.3.1 ENV_MDI<n>
Troubleshooting instructions
1 Revert the MDI associated condition to the original state.
2 Verify that the MDI associated condition is provisioned properly.
3 If the alarm persists, contact the next higher level of technical support.
3.4.1 AU-PJCN_TCA_15m/24h
Troubleshooting instructions
1 Set the all the relevant NEs to synchronize with each other.
2 If the alarm persists, contact the next higher level of technical support.
3.4.2 AU-PJCP_TCA_15m/24h
Troubleshooting instructions
1 Set the all the relevant NEs to synchronize with each other.
2 If the alarm persists, contact the next higher level of technical support.
Troubleshooting instructions
1 Check the upstream external cabling and equipment for errors.
2 Check whether the upstream NE sent out excessive bad bytes intentionally.
3 If the alarm persists, contact the next higher level of technical support.
Troubleshooting instructions
1 Check the upstream external cabling and equipment for errors.
2 Check whether the upstream NE sent out excessive bad bytes intentionally.
3 If the alarm persists, contact the next higher level of technical support.
3.4.5 E1-Negative_Bit-slip_TCA_15m/24h
Troubleshooting instructions
1 Verify the clock frequency of E1 ports is correct.
2 Verify that the system clock is in locked status.
3 If the alarm persists, contact the next higher level of technical support.
3.4.6 E1-Positive_Bit-slip_TCA_15m/24h
General information and causes The number of positive bit-slip during a 15-minute
or 24-hour period is greater than or equal to the
threshold. The alarm only applies to E1 retiming
ports.
The clock frequency of the E1 service is faster than
the frequency of the system clock.
Troubleshooting instructions
1 Verify the clock frequency of E1 ports is correct.
2 Verify that the system clock is in locked status.
3 If the alarm persists, contact the next higher level of technical support.
3.4.7 HP-FE_BBE_TCA_15m/24h
Troubleshooting instructions
1 Check the downstream external cabling for error.
2 If the alarm persists, contact the next higher level of technical support.
3.4.8 HP-FE_ES_TCA_15m/24h
Troubleshooting instructions
1 Check the downstream external cabling for error.
2 If the alarm persists, contact the next higher level of technical support.
3.4.9 HP-FE_SES_TCA_15m/24h
Troubleshooting instructions
1 Check the downstream external cabling for error.
2 If the alarm persists, contact the next higher level of technical support.
3.4.10 HP-FE_UAS_TCA_15m/24h
Troubleshooting instructions
1 Check the downstream external cabling for error.
2 If the alarm persists, contact the next higher level of technical support.
3.4.11 HP-NE_BBE_TCA_15m/24h
Troubleshooting instructions
1 Check the upstream external cabling and equipment for error.
2 If the alarm persists, contact the next higher level of technical support.
3.4.12 HP-NE_ES_TCA_15m/24h
Troubleshooting instructions
1 Check the upstream external cabling and equipment for error.
2 If the alarm persists, contact the next higher level of technical support.
3.4.13 HP-NE_SES_TCA_15m/24h
Troubleshooting instructions
1 Check the upstream external cabling and equipment for error.
2 If the alarm persists, contact the next higher level of technical support.
3.4.14 HP-NE_UAS_TCA_15m/24h
Troubleshooting instructions
1 Check the upstream external cabling and equipment for error.
2 If the alarm persists, contact the next higher level of technical support.
3.4.15 LP-FE_BBE_TCA_15m/24h
Troubleshooting instructions
1 Check the downstream external cabling for error.
2 If the alarm persists, contact the next higher level of technical support.
3.4.16 LP-FE_SES_TCA_15m/24h
General information and causes The LP far-end performance monitor counter SES
exceeded the provisioned threshold during a 15-
minute or 24-hour period.
An indication returned to the upstream node to
notify that the errored blocks have been detected at
the downstream node. The LP SES value of the
downstream node exceeded the provisioned
threshold.
Troubleshooting instructions
1 Check the downstream external cabling for error.
2 If the alarm persists, contact the next higher level of technical support.
3.4.17 LP-FE_UAS_TCA_15m/24h
Troubleshooting instructions
1 Check the downstream external cabling for error.
2 If the alarm persists, contact the next higher level of technical support.
3.4.18 LP-NE_BBE_TCA_15m/24h
Troubleshooting instructions
1 Check the upstream external cabling and equipment for error.
2 If the alarm persists, contact the next higher level of technical support.
3.4.19 LP-NE_ES_TCA_15m/24h
Troubleshooting instructions
1 Check the upstream external cabling and equipment for error.
2 If the alarm persists, contact the next higher level of technical support.
3.4.20 LP-NE_SES_TCA_15m/24h
Troubleshooting instructions
1 Check the upstream external cabling and equipment for error.
2 If the alarm persists, contact the next higher level of technical support.
3.4.21 LP-NE_UAS_TCA_15m/24h
Troubleshooting instructions
1 Check the upstream external cabling and equipment for error.
2 If the alarm persists, contact the next higher level of technical support.
3.4.22 MS-FE_BBE_TCA_15m/24h
Troubleshooting instructions
1 Check the downstream external cabling for error.
2 If the alarm persists, contact the next higher level of technical support.
3.4.23 MS-FE_ES_TCA_15m/24h
Troubleshooting instructions
1 Check the downstream external cabling for error.
2 If the alarm persists, contact the next higher level of technical support.
3.4.24 MS-FE_SES_TCA_15m/24h
Troubleshooting instructions
1 Check the downstream external cabling for error.
2 If the alarm persists, contact the next higher level of technical support.
3.4.25 MS-FE_UAS_TCA_15m/24h
Troubleshooting instructions
1 Check the downstream external cabling for error.
2 If the alarm persists, contact the next higher level of technical support.
3.4.26 MS-NE_BBE_TCA_15m/24h
Troubleshooting instructions
1 Check the upstream external cabling and equipment for error.
2 If the alarm persists, contact the next higher level of technical support.
3.4.27 MS-NE_ES_TCA_15m/24h
Troubleshooting instructions
1 Check the upstream external cabling and equipment for error.
2 If the alarm persists, contact the next higher level of technical support.
3.4.28 MS-NE_SES_TCA_15m/24h
Troubleshooting instructions
1 Check the upstream external cabling and equipment for error.
2 If the alarm persists, contact the next higher level of technical support.
3.4.29 MS-NE_UAS_TCA_15m/24h
Troubleshooting instructions
1 Check the upstream external cabling and equipment for error.
2 If the alarm persists, contact the next higher level of technical support.
3.4.30 PPI-FE_BBE_TCA_15m/24h
Troubleshooting instructions
1 Check the upstream external cabling and equipment for error.
2 If the alarm persists, contact the next higher level of technical support.
3.4.31 PPI-FE_ES_TCA_15m/24h
Troubleshooting instructions
1 Check the upstream external cabling and equipment for error.
2 If the alarm persists, contact the next higher level of technical support.
3.4.32 PPI-FE_SES_TCA_15m/24h
General information and causes The PDF far-end performance monitor counter SES
exceeded the provisioned threshold during a 15-
minute or 24-hour period.
Troubleshooting instructions
1 Check the upstream external cabling and equipment for error.
2 If the alarm persists, contact the next higher level of technical support.
3.4.33 PPI-FE_UAS_TCA_15m/24h
Troubleshooting instructions
1 Check the upstream external cabling and equipment for error.
2 If the alarm persists, contact the next higher level of technical support.
3.4.34 PPI-NE_ES_TCA_15m/24h
Troubleshooting instructions
1 Check the upstream external cabling and equipment for error.
2 If the alarm persists, contact the next higher level of technical support.
3.4.35 PPI-NE_SES_TCA_15m/24h
Troubleshooting instructions
1 Check the upstream external cabling and equipment for error.
2 If the alarm persists, contact the next higher level of technical support.
3.4.36 PPI-NE_UAS_TCA_15m/24h
Troubleshooting instructions
1 Check the upstream external cabling and equipment for error.
2 If the alarm persists, contact the next higher level of technical support.
3.4.37 RS-BBE_TCA_15m/24h
Troubleshooting instructions
1 Check the upstream external cabling and equipment for error.
2 If the alarm persists, contact the next higher level of technical support.
3.4.38 RS-ES_TCA_15m/24h
Troubleshooting instructions
1 Check the upstream external cabling and equipment for error.
2 If the alarm persists, contact the next higher level of technical support.
3.4.39 RS-SES_TCA_15m/24h
Troubleshooting instructions
1 Check the upstream external cabling and equipment for error.
2 If the alarm persists, contact the next higher level of technical support.
3.4.40 RS-UAS_TCA_15m/24h
Troubleshooting instructions
1 Check the upstream external cabling and equipment for error.
2 If the alarm persists, contact the next higher level of technical support.
3.5.1 Account_Expired_Disabled
Troubleshooting instructions
1 If the account has expired - enable the account using the FLEXR L and set a new
expiration date.
2 If the account was automatically disabled by SNMPv3 - verify the security log for reason
of account suspension and if desired re-enable the user.
3 If the alarm persists, contact the next higher level of technical support.
3.5.2 Log_Is_Full
Troubleshooting instructions
1 Upload the log file to a PC or storage device to empty space for more log files.
2 Increase the size of security file log using the FLEXR L.
3 If the alarm persists, contact the next higher level of technical support.
3.5.3 Log_Occupancy_Threshold_Reached
General information and causes Security log for tracking security and configuration
related events has reached the user defined
threshold (default 80%).
Troubleshooting instructions
1 Upload the log file to a PC or storage device to empty space for more log files.
2 Increase the size of security file log using the FLEXR L.
3 If the alarm persists, contact the next higher level of technical support.
3.5.4 Unauthorized_Access_Attempt
Troubleshooting instructions
1 Track down the source of the attempt.
2 In the FLEXR L, go to the User Administration window by selecting NE Security > NE
User Management. Clear the alarm manually by right-clicking the desired user and
selecting Reset Unauthorized Access Counter from the context menu.
3 If the alarm persists, contact the next higher level of technical support.
3.5.5 Unsuccessful_Logins_Exceeded
Troubleshooting instructions
1 In the FLEXR L, go to the User Administration window by selecting NE Security > NE
User Management. Check the desired user or user who exceeded the maximum
numbers of login attempt (which is 5 by default). Re-enable the user by right-clicking the
user and selecting Enable from the context menu or click Modify and deselecting the
check box for Account is disabled in the Modify User window.
2 If the alarm persists, contact the next higher level of technical support.
CHAPTER 4
Common Incorrect Ethernet Configuration Cases
This chapter provides some common incorrect Ethernet configuration cases, which the
customer should avoid when setting up the product in the network. Ethernet data cards
include the 8 x GE/T, 1 x 10 GE/T, 6 x GE + 4 x FEGE/A, and 1 x 10 GE + 10 x GE/L2 cards.
Ethernet is based on blocks of frames (also called packets) to transmit the traffic (a series of
data flow). The loss of frame can pose a negative impact on the data (e.g. video or audio)
being communicated. Incorrect configuration of the 6 x GE + 4 x FEGE/A, and 1 x 10 GE +
10 x GE/L2 cards will cause frame loss for Ethernet traffic.
Figure 4-1 shows the topology in which this case may occur..
Description for the incorrect configuration:
There is a 1000 Mbps bandwidth connection between port B and port C.
Port A receives 100 Mbps of untagged frame traffic from the egress of the counterpart
equipment.
Port B is configured as Tag mode.
If port A receives 1000 Mbps untagged frames traffic from the egress of the counterpart
equipment, an additional Port VLAN Identifier (PVID) (with a length of four bytes) will be
added into the traffic. It will cause congestion in the egress direction of port B. Frame
loss will occur on port B if flow control is not enabled on port A.
At Port A At Port B
1) Flow control: disabled 1) Tag mode: Tag
2) Untagged frame received
A B C D
Frame Loss
There are two methods to solve the frame loss problem in this situation:
Change tag mode from Tag to Untag on port B, or
Enable flow control on port A.
For more information on configuring tag mode and flow control, refer to the
Configuring LAN port properties and Configuring WAN port properties sections
of the FLASHWAVE 4570 Operating Manual.
A B C D
Pause Frame
1000 Mbps Traffic 1 x 10GE + 10xGE/L2 1000 Mbps Traffic 1000 Mbps Traffic
1 x 10GE + 10xGE/L2
Card X Card Y
Pause Frame
If this configuration has been used to set up the product in the network, and the traffic rate
reaches close to 1000 Mbps, pause frames (a frame used by flow control to tell the opposite
port to stop transmitting traffic) will be sent between port B and C bidirectionally.
Consequently, all bidirectional traffic between port B and port C will be blocked except pause
frames themselves. This can cause bidirectional traffic block triggered by the pause frame.
There are several methods to recover the traffic from such a situation:
It is highly recommended to configure the same tag mode (all tagged or all untagged) on
all ports, and then remove and insert the Ethernet/optical cables for both port A and port
D to reset and activate this change. Alternatively, the user can also reset and activate
this change from the FLEXR L software:
1. Right-click the corresponding LAN port from the FLASHWAVE 4570 Chassis View.
Select LAN Port Property Configuration from the context menu.
2. In the LAN Port Property Configuration window, select Disable from the Admin
mode drop-down list. Click Apply. Click Yes and then click OK in the
Confirmation window to confirm the settings.
3. Select Enable from the Admin mode drop-down list. Click Yes and click OK in the
Confirmation window to confirm the settings.
4. The user needs to repeat the above mentioned steps for each port (i.e., port A and
D).
Disable the flow control on port B and port C and then remove and insert the Ethernet
cables for both port A and port D to reset and activate this change. Alternatively, the user
can also reset and activate this change from the FLEXR L software. Refer to procedures
in method one as described above.
This method can cause traffic frame loss. Refer to Chapter 4.1 for details.
Enable the flow control on the port A and port D, and make sure that flow control is also
enabled on the downstream systems connected, and then remove and insert the
Ethernet cables for both port A and port D to reset and activate this change. Alternatively,
the user can also reset and activate this change from the FLEXR L software. Refer to
procedures of method one as described above.
Loopbacks are created when the incoming path and outgoing path which are supposed to be
independent on each other are arbitrarily connected for testing purpose or by accident.
Users should establish a loopback free topology of layer 2 card transmission because,
otherwise, a loopback may cause flooding and massive congestion in the network.
For layer 2 cards, a loopback (e.g., on the same WAN port via CC) on any LAN or WAN port
will cause failure to the layer 2 functionality. For example, it may cause broadcast storm,
traffic blockage, or frame duplication. To restore the layer 2 functionality, the user should
avoid the following three actions that lead to loopback.
A loopback between the transmitter and receiver on the same LAN port via cable or fiber.
This will cause a loopback in which, in an enclosed circle, the transmitter will
continuously send message to a receiver.
A loopback created by a cross-connection between source and sink on the same VC.
This will create a loopback on the WAN port.
Enabling the loopback function on any SDH port, which contains cross-connection(s) to
any layer 2 card WAN port(s).
Figure 4-3 shows a loopback on the WAN port by creating a cross-connection between
source and sink in the same Virtual Container (VC) to WAN port 1.
VC Source
VC Sink
For more information about the management of loopback, refer to the Testing
loopback and Managing synchronization section of the FLASHWAVE 4570
Operating Manual (OMN).
The function of the pause frame is to request the network element which is sending frames
to stop transmitting frame for a period of time.
The pause frame will influence transmission of all frames, including protocol frames (such as
protocol frames in GARP VLAN Registration Protocol (GVRP), Link Aggregation Control
Protocol (LACP), and MSTP). If there are lots of pause frames repeatedly received in a short
time, the egress traffic may be blocked completely (a situation as described in Subchapter
4.2). In this case, protocol frames will also be blocked, which may lead to protocol interaction
failure. To restore the protocol interaction in this case, the congestion condition should be
eliminated (e.g., by reducing the amount of traffic flow or enlarging the bandwidth) or, as an
alternative, the flow control should be disabled.
VLAN ID 1 is the default VLAN ID for all ports. GVRP cannot automatically register ports to
VLAN ID 1 for management and security reasons. As a result, the network administrator
should manually configure ports in VLAN ID 1, even though the GVRP function is enabled.
On the Ethernet cards, VCGs can be used to configure the bandwidth of a port. The user can
configure the bandwidth by establishing a symmetrical VCG arrangement between sink and
source (in other words, the bandwidth configured is always equal between source and sink
of one VCG) to create a port that has the same transmitting and receiving capacity. This
symmetrical VCG arrangement is done in the bidirection mode, which is the default mode.
In the bidirection mode, the bandwidth configured for either one of the sink and
i source will be applied to the other as well automatically.
The user can also create a port that has different transmitting and receiving capacity by
establishing an asymmetrical VCG arrangement between sink and source (in other words,
the bandwidth configured can be different between source and sink of one VCG). This
asymmetrical VCG arrangement is done in the unidirection mode.
This flexibility of symmetrical and asymmetrical VCG arrangement makes asymmetrical
bandwidth configuration possible for one VCG.
For more information on setting the bidirection and unidirection and how to
manage VCG, refer to the Managing virtual concatenation groups section of
FLASHWAVE 4570 Operating Manual.
Caution
In unidirection mode, user should not leave either source or sink configuration
! unassigned with any VC. If there is no bandwidth assigned for either source or
sink of one VCG, the traffic will be blocked.
CHAPTER 5
Card Replacement
This section contains instructions for removing a faulty card and replacing it with a spare of
the same type
i All optical fibers, transmitters, and ports are classified as hazard level 1 as
defined by EN 60825-1/ IEC 60825-1. Nevertheless, in view of possible
malfunction, laser transmission systems which contain optical amplifier modules
are classified as hazard level 1M. To avoid damage to health, the user must
observe the regulations regarding protection against radiation from laser devices
(EN 60825-1/IEC60825-1).
i The user has to wait about 10 to 30 minutes for the NE to complete rebooting
For the detailed procedures on how to execute many of the instructions described
in this chapter, refer to the FLASHWAVE 4570 Installation and Test Manual
(ITMN), Commissioning Manual (COMN), and Operating Manual (OMN)
Caution
The SC card replacement instructions described in the following subchapters
! presume all the SC cards is loaded with the same version of NE software
(Release 4.2).
Caution
When an SC card is removed from the single SC system, the management
! system will lose connectivity to the NE. During this time, the management
interface is not functional.
Before the replacement, the MIB file should be prepared in a PC. Follow the procedures
given in Chapter 5.2.1.
Also if the failure is present in the active SC card, and/or the active CF card (in the active SC
card) of the 1+1 redundant SC system, additional procedure is required to switch the SC
card to the standby side before the replacement procedure. Refer to Chapter 5.2.2.
The SC card and/or CF card replacement procedures vary depending on the failure scenario
as follows.
SC card failure: see Chapter 5.2.3
CF card failure: see Chapter 5.2.4
Both the SC and CF cards fail: see Chapter 5.2.5.
i Unless the CF card is damaged, when replacing the old SC card with a new SC
card, it is recommended to remove the original CF card in the old SC card and
put it into the new SC card to ensure the data information for the new card is
consistent with the peer SC card.
The following instructions include the FLEXR L operation. For the detailed
instructions on how to use the FLEXR L for the specific operation, refer to
FLASHWAVE 4570 Operating Manual (OMN).
3 A File Transport Protocol (FTP) server program should be installed and properly set on
the PC. For convenience, it is suggested to use the built-in FTP server on Windows XP.
To activate this server, follow the procedures below:
Insert Windows XP Service Pack 2 (SP2) installation CD into CD/DVD drive.
To install the FTP server, select Start > Control Panel > Add/Remove Programs >
Add/Remove Windows Components.
Select the Internet Information Service (IIS) check box. Click Details to
open the Internet Information Service (IIS) window.
Select the Common Files and File Transfer Protocol (FTP) Service check
boxes and click OK.
To configure the FTP server, select Start > Control Panel > Administrative Tools >
Internet Information Service > XXXX (local computer) > FTP Sites > Default FTP Site.
Right-click the Default FTP Site item and select FTP properties to open the
Default FTP Site Properties window. It is suggested to select the Allow
Anonymous Connections check box.
Ensure FTP Site Directory is where the MIB and software load files are
located. By default, the location is at C:Inetpubfproot.
After the above procedures are completed, the operator should verify the FTP server by
clicking Start > Run.
Enter ftp 127.0.0.1 to open the command prompt.
Enter anonymous as the user name and any words as passwords.
Enter dir to check the software load file and MIB file in the folder.
4 The unzip software like winzip or winrar should be installed on the PC.
5 The boot image file (e.g., <SC.bin>) and software load file (e.g.,
<PBm1r42bxxx.bld>) should be saved in the FTP server user directory.
For the boot image file and software load file, please contact Fujitsu Technical Support.
6 The MIB file saved by the FLEXR L with the extension .mib should be changed into
a .zip file and unzipped to the local working directory on the PC.
The unzipped MIB file package on the PC includes the following files:
%Local_working_drive%<ghead.txt>
%Local_working_drive%<headfile.txt>
%Local_working_drive%ne*.*
%Local_working_drive%gmpls*.*
%Local_working_drive% specifies the drive letter of the hard disk drive containing
the local working directory on the PC.
The procedure in this subchapter is only applied when the failure is present in the active SC
card or the active CF card (in the active SC card) of the 1+1 redundant SC system.
When the FLASHWAVE 4570 is equipped with two SC cards for SC 1 + 1 protection, in the
event of the active card failure, the automatic switching is executed from the active to the
standby to offer system protection and system stability. With this feature, the user has time
to isolate and troubleshoot faults of an SC card encountering problems without losing control
of the system.
Two switch modes exist when the system is equipped with two SC cards: one is the
automatic switch, the other is the manual switch. Automatic switch is triggered by faults in
the active SC card, while the manual switch is triggered by the operators command from the
FLEXR L and usually used to conduct the system upgrading or testing.
i Not all faults will trigger SC 1 + 1 switch and they include cases such as
mechanical breakdown, software version upgrading, malfunction of individual
integrated circuit, etc.
i If the ACT LEDs on both SC cards are off, refer to Chapter 5.3.
The following procedures only apply to the replacement of the active SC card, CF card (in
the active SC card), and both the active SC card and its CF card.
1. Using the FLEXR L, perform a switch request for the active SC cards.
2. If Step 1 does not work, using the FLEXR L warm reboot the active SC card.
3. If both Step 1 and Step 2 do not work, or if the FLASHWAVE 4570 cannot be managed
by the FLEXR L, remove the active SC card to activate the switching to the standby SC
card eventually.
4 Insert the new SC card in the slot. The system will automatically start rebooting.
5 During the system reboot, press <b> to stop the boot process when the Hyper Terminal
shows the countdown 5 4 3 2 1 ... .
Caution If the boot process is not stopped in time and the system comes into the
normal startup process, the NE configuration may be lost and the traffic may
! be interrupted. If this happens, remove the SC card immediately and
execute Steps 2 and 3 above again.
The Boot Mode window is opened in the Hyper Terminal.
6 Press <f> to enter the Flash Commands window.
7 Press <1> to format the board flash in the SC card.
8 After the formatting finishes, press <x> to return to the Boot Mode window.
9 Press <0> to enter System Maintain window
10 Press <b> to check the current boot image version and ensure the version is 2.2.2.2.
11 If it is not version 2.2.2.2, download the boot image according to Chapter 5.2.6.
12 Press <r> to reboot the system and press <y> to confirm.
13 After the system reboot finishes, verify the software version is correct through the
FLEXR L.
PROCEDURE COMPLETE!
4 Insert the SC card with the new CF card. The system will automatically start rebooting.
5 During the system reboot, press <b> to stop the boot process when the Hyper Terminal
shows the countdown 5 4 3 2 1 ... .
Caution If the boot process is not stopped in time and the system comes into the
normal startup process, the NE configuration may be lost and the traffic may
! be interrupted. If this happens, remove the SC card immediately and
execute Steps 2 and 3 above again.
The Boot Mode window is opened in the Hyper Terminal.
6 Press <f> to enter the Flash Commands window.
7 Press <2> to format the CF in the SC card.
8 After the formatting finishes, press <x> to return to the Boot Mode window.
9 Press <0> to enter the System Maintain Window.
10 Press <b> to check the current boot image version and ensure the version is 2.2.2.2.
11 If it is not version 2.2.2.2, download boot image according to Chapter 5.2.6.
12 Press <r> to reboot the system and press <y> to confirm.
13 After the system reboot finishes, verify the software version is correct through the
FLEXR L.
Refer to The FLASHWAVE 4570 Operating Manual (OMN).
PROCEDURE COMPLETE!
To replace the SC and CF card, complete the following steps. In case the user is not sure
whether the failure is caused by the SC card or CF card, follow this procedure.
1 Remove the faulty SC card.
PROCEDURE COMPLETE!
To download the boot image from the PC to the SC card, complete the following steps:
1 Launch the Boot Mode window in the Hyper Terminal by pressing <b> during the
system reboot when the Hyper Terminal shows the countdown 5 4 3 2 1 ...
i Ensure the IP address is unique and not in conflict with any other IP address and
sub-network in the DCN environment.
8 Press <8> and enter the FTP password which is used for the NE to login into the FTP
server.
9 Press <9> and type up to enable the uplink port.
10 Press <x> to return to the Boot Mode window.
11 Press <0> to enter the System Maintain window.
12 Press <f> to enter the Boot image window.
13 Enter the corresponding boot image file name (e.g., <sc.bin>) and press <Enter>.
The File Size prompt is displayed.
14 When all items show OK, the boot image file is downloaded to the SC card.
Press <Enter> to return to the System Maintain window.
15 Press <x> to return to the Boot Mode window.
16 Press <i> to enter the IP Configuration window.
17 Press <1> to modify the boot device as auto.
18 Press <9> and type down to disable the uplink port.
19 Press <x> to return to the Boot window.
PROCEDURE COMPLETE!
To download the boot image from the PC to the SC card, complete the following steps:
1. Launch the Boot Mode window in the Hyper Terminal by pressing <b> during the
system reboot when the Hyper Terminal shows the countdown 5 4 3 2 1 ...
2. Press <i> to enter the IP Configuration window.
3. Press <1> and set the boot device as mottsec.
4. Press <2> and enter the NE Ethernet Internet Protocol (IP) address.
i Ensure the IP address is unique and not in conflict with any other IP address and
sub-network in the DCN environment.
6. Press <4> and enter the PC IP address. In order to communicate with the NE, the PC
IP address needs to be in the same sub-network as the NE Ethernet IP address.
7. Press <7> and enter the FTP user account name which is used for the NE to login into
the FTP server on the PC.
The PC is an FTP server. Refer to Step 3 in Chapter 5.2.1 for the FTP server setup.
8. Press <8> and enter the FTP password which is used for the NE to login into the FTP
server.
9. Press <9> and type up to enable the uplink port.
10. In the IP Configuration window, press <6> and enter the corresponding software load
file name (e.g., <PBm1r40bxxx.bld>).
11. Press <x> to return to the Boot Mode window.
12. Press <c> to enter the Command Mode window and type @ to download the load.
PROCEDURE COMPLETE!
To download the MIB from the PC to the SC card, complete the following steps:
1. Launch the Boot Mode window in the Hyper Terminal by pressing <b> during the
system reboot when the Hyper Terminal shows the countdown 5 4 3 2 1 ...
2. Press <i> to enter the IP Configuration window.
3. Press <2> and enter the NE Ethernet Internet Protocol (IP) address.
i Ensure the IP address is unique and not in conflict with any other IP address and
sub-network in the DCN environment.
If the ACT LEDs of the both SC cards are off, please check whether the FLEXR L is still
online or not.
If the FLEXR L is online, perform a switch request for the active SC card. To determine if
an SC card is active or not, the user needs to open the SC 1+1 Protection window by
selecting Configuration > SC 1+1 Protection and checking at the Active SC area to
see if any SC card is available. If there is no SC card being displayed in the Active SC
area, the user should perform a warm reboot. If this switch command still does not work,
perform a warm reboot to both the active and standby SC cards.
If the FLEXR L is offline, remove and insert both SC cards so that the FLEXR L can
automatically log in again.
i The time needed for the FLEXR L to go online may be as long as 15 minutes
depending on the system configuration.
If the manual switch between the active and standby SC fails, check the SC status area of
the SC 1+1 Protection window. Make sure the settings and parameters are set as
illustrated in the figure below.
There are several parameters that the user should pay attention to and double check in the
SC 1+1 Protection window.
Active SC: It can be SC1 or SC2 depending on which card is active at the moment.
Last switch reason: The user should ensure it is in No Request state before manual
switch.
Switch request: It indicates whether the user or system has issued a command to
switch between SC cards. The user will not be able to perform a manual switch if this
area shows any other parameter than No Request.
In the SC status area, the user should check:
Slot: The slot where each SC card is located.
Role: Shows which card is in Active state and which card is in Standby state.
Present: Tells the user either of the slots contains a SC1 card or SC2 card and shows
the card is in place and works properly.
Latch: There are two states, Close or Open.
Close: The latch of the card is closed. The user should ensure the latch of the
card is closed for normal operation.
Open: The latch of the card is open. When the latch is opened, control system
will switch to another SC card.
The failure to perform a manual switch can result from switch priority rules. If there are
multiple switches performed at the same time, the switch type with higher priority will take
precedence over the switch type with lower priority. In other words, if manual switch and
automatic switch are executed at the same time, manual switch will not be available for
users to perform because automatic switch takes the priority. Table 5-1 lists the priority of
each of the available switch types.
If the above settings in the SC 1+1 Protection window are correct, but automatic switch still
fails, follow the procedure described in Chapter 5.3.3.
If the automatic switch between the active and standby SC fails and if the FLEXR L is still
online, execute the following procedure:
1. Repeat checking the parameters in the SC 1+1 Protection window and ensure that
both Active and Standby cards are allocated and they are present. Check that the
Latch is also in a Close state and the Switch request shows No request. Make sure
the settings are configured as listed in Table 5-1.
2. If the automatic switch still does not work, check system alarms and troubleshoot them
based on the instructions listed in CHAPTER 3. SC related alarms include:
SC_SW_Version_Mismatch
Communication_Fail
3. If the automatic switch still does not work, cold reboot both SC cards.
4. Contact Technical support for further assistance if the corrective procedure above fails.
Each NE has CC cards, which function as the cross-connection and timing management
controller. Replacement of the CC card requires special care since it deals with all traffic of
the NE.
To replace the CC card, complete the following steps:
1. Before replacing the CC card, verify that the CC card to be replaced is not active via the
FLEXR L.
i When the working CC card fails, the traffic will switch to the protection card
automatically.
i Take at least three-minute interval between the first CC card switch in Step 1 and
the second CC card switch in Step 4 to ensure no traffic hit.
PROCEDURE COMPLETE!
FLASHWAVE 4570 shelf is equipped with two fan units to cool the system. Replacement of
the fan unit requires special care.
Observe the following rules:
The whole fan unit must be replaced even if only one of the fans in the unit fails.
The system cannot work with no fan units.
The system can still work normally for 16 hours when only one fan unit fails and that the
failed unit is still inserted in the NE.
The system cannot work when either one of fan units is absent for more than two
minutes. Complete exchanging the faulty fan unit within two minutes.
Detailed instructions for replacing the fan unit can be found in the FLASHWAVE
4570 Installation and Test Manual (ITMN).
FLASHWAVE 4570 shelf is equipped with one filter unit to protect the system from the
environmental dust or other airborne contaminants. Replacement of the fan unit requires
special care.
Observe the following rules:
The filter unit replacement must be treated as a periodic maintenance procedure to
ensure that the fans are able to sustain optimum shelf operating temperature.
It is recommended to clean the filter unit every two months, otherwise the efficiency of
the fan unit may be reduced.
The filter unit can be cleaned by water, but must be dry when placed back.
The filter unit must be placed back within 24 hours, otherwise the system may be
polluted by the dust.
Detailed instructions for replacing the fan unit can be found in the FLASHWAVE
4570 Installation and Test Manual (ITMN).
CHAPTER 6
MIB Switching
This section contains instructions for switching between the active MIB and the backup MIB.
Normally the MIB is saved in the active Board Flash (BF) in the SC card. There are three
additional copies for backup purposes, including:
Active CF
Backup CF
The MIB collects:
Data managed by the external interfaces
Data used in the cards settings
Data used by the SC card for internal activities
MIB switching procedures vary, depending on the following different scenarios:
The data configuration is different between the old and new MIB.
The data configuration is the same between the old and new MIB.
The following instructions include the FLEXR L operation. For the detailed
instructions on how to use the FLEXR L for the specific operation, refer to
FLASHWAVE 4570 Operating Manual (OMN).
To switch between the two MIBs whose data is different from each other, complete the
following steps using the FLEXR L:
1. Upload the MIB of the old configuration from the NE to the local PC to backup the old
configuration.
2. Download the MIB of the new configuration from the local PC to the NE.
3. Switch the new MIB into the active MIB.
4. Activate the new configuration in the MIB in the following two methods:
Method 1
Cold reboot the NE to activate all the new configuration in the MIB.
Caution All traffic will be dropped while the NE is cold rebooting.
!
Method 2
1. Warm reboot the NE to activate the configuration in the MIB except the new
data configuration.
Caution The Ethernet traffic related to the new data configuration will not be normal
! after the NE warm reboots.
2. Cold reboot all the Ethernet cards related to the new data configuration to
activate the new data configuration.
Caution
The Ethernet traffic will be dropped while the card is cold rebooting.
!
PROCEDURE COMPLETE!
To switch between the two MIBs which contain the same data, complete the following steps:
1. Upload the MIB of the old configuration from the NE to the local PC to backup the old
configuration.
2. Download the MIB of the new configuration from the local PC to the NE.
3. Switch the new MIB into the active MIB.
4. Warm reboot the NE to activate the new configuration in the MIB.
PROCEDURE COMPLETE!
To switch the two MIBs on the 1 + 1 redundant SC system, complete the following steps via
FLEXR L:
1. Upload the MIB of the old configuration from the NE to the local PC to backup the old
configuration.
It is recommended that the user should empty the MIB before performing
i downloading.
2. In the Download tab (Configuration > NE > MIB Management), configure all the
settings in the Download page to download the MIB of the new configuration from the
local PC to the NE.
3. Configure all the settings in the Synchronize page to copy the new MIB from the Active
SC card to the Standby SC card.
4. Configure all the settings in the Switch MIB on standby SC page to switch the new
MIB into the active MIB for the Standby SC.
5. Configure all the settings in the Switch MIB on active SC page to switch the new MIB
into the active MIB for the Active SC.
6. Configure all the settings in the Reboot NE page to activate the new MIB configuration
for both Active SC and Standby SC.
PROCEDURE COMPLETE!
When using FTP server to upload MIB files, most of the problems occurred during
replacing SC and CF card, which only one SC card available on the node. The operator
can upload the MIB file onto the node through the FTP server.
For the detailed operation procedure, refer to Chapter 5.2.
CHAPTER 7
Abbreviations
NE Network Element
OA Optical Amplifier
OMN Operating Manual
PC Personal Computer
PDH Plesiochronous Digital Hierarchy
PLM PayLoad Mismatch
POA Pre-Optical Amplifier
PLL Phase Lock Loop
PPI PDH Physical Interface
QoS Quality of Service
RDI Remote Defect Indication
RFI Remote Failure Indication
RPR Resilient Packet Ring
RS Regeneration Section
SC System Controller
SDH Synchronous Digital Hierarchy
SES Severely Errored Second
SFP Small Factor Pluggable
SI-E System Interface with Engineering Order Wire
SNMP Simple Network Management Protocol
SPI Synchronous Physical Interface
SSM Synchronization Signal Message
TCA Threshold Crossed Alarm
TIM Trace Identifier Mismatch
TLCT Total Loss of Capacity Transmit
TP Terminal Point
TU Tributary Unit
UAS UnAvailable Second
UNEQ UNEQuipped
VCG Virtual Concatenation Group
VCXO Voltage Control Crystal Oscillator
WAN Wide Area Network
XFP 10 Gigabit Small Form Factor Pluggabl