NOTES: INSERT DESIGN VALUES IN YELLOW BOX

DESIGN FOR STRIP FOOTING

Depth of strip footing


Width of strip footing
Selfweight
Length under consideration, say
Self load of strip footing
Assume 1m strip of ground slab constribute to UDL on strip footing

LOADING

beam selfweight

Roofing Material DL

Roofing Material LL

Brickwall

Self load strip footing

Grd Slab (DL)

Grd Slab (LL)

Column No. of Nos ( If Stated / Have)


Total Load

Area of strip footing in contact with ground


Length of strip footing
Width of strip footing

Thus, pressure on ground

CHECK REINFORCEMENT

CASE 1 Minimum Reinforcement

Minimum reinforcement provided on B x D

Therefore, provide 3T12 (top & bottom ) Asprov = 339 mm 2 >

CASE 2 Longitudinal Bending & Shear Due To Local Depression

Assuming a local depression occurs, the strip footing is acting like a suspended beam,
Thus
Service load = 456.23
Ultimare Load, P = 684.342
= 27.16
Ultimate moment due to strip footing spanning say

Moment, Mult = PL^2/8 =

Effective Depth, d = 244

K = M / bd2fcu = 0.0264

As = M / 0.95fyZ = 209.44

Therefore, provide 4T12 (top & bottom ) Asprov = 452 mm2 >

100As / bd = 0.41

Allowable Shear Stress , Vc =


Shear Force, V =

Shear Stress, Vu = V / bd =

Critical of Shear
Vu =

Ok! = Shear is not Critical Not Ok! = Shear is Critical

Minimum link provided, Asv / Sv req. = 0.4bv / (0.87fyv) =

For R10 links, Asv = 2 x (D^2/4) =


Asv / Sv req. = 0.90

Asv/Sv prov. > As/Sv req.

Asv/Sv prov. = 0.90

Thus Provide R10 at 175 mm c/c

GROUND SLAB

Minimum Reinf, As req = 13% bh =

Provide BRC A7, As prov =

As prov = 193
ERT DESIGN VALUES IN YELLOW BOX

D 300 mm Unit Weight


B 450 mm
3.24 kN/m Concrete
25.2 m Brick
81.65 kN
to UDL on strip footing

0 kN

9.45 kN N 0.25
B 1.5
L 25.2

9.45 kN N 0.25
B 1.5
L 25.2

196.56 kN N 2.6
H 3
L 25.2

0.1m x 0.1m x 25.2m x 24 kN/m3 81.65 kN

60.48 kN N 24
B 1
L 25.2
T 0.1

75.60 kN N 3
B 1
L 25.2

s ( If Stated / Have) 23.04 kN N 24


H 3
Nos 8
B 0.2
D 0.2

456.23 kN

g in contact with ground 11.34 m2


L 25.2
B 0.45

ground 40.23 kN/m2 Soil Bearing Pressure

40.23 < 75 OK!

As min = 0.13 % bh
B 450 mm
D 300 mm

175.50 mm2

rov = 339 mm2 > 175.50Rebar Tables BS 8666:2005

To Local Depression

ooting is acting like a suspended beam,

kN
kN 1.5
kN/m L 25.2
spanning say L 2.5

21.22 kN.m P 27.16


L2 6.25

mm2 D 300
40
10
6

< K' = 0.156 d 244


b 450

mm2 Z 231.8

rov = 452 mm2 > 209.44 mm2

As 452
b or B 450
d 244

0.57 N/mm2 Refer BS 8110 Table 3.3


33.95 kN P 27.16
L 2.5

0.31 N/mm2 b or B 450


d 244

0.31 < 0.57 = Vc OK!

Ok! = Shear is Critical

0.4bv / (0.87fyv) = 0.83 bv 450


fyv 250

157.1 mm2 D 10
Asv 157.1
Sv 175

> Asv/Sv req. = 0.83 OK!

130 mm2/m b 1000


h 100

193 mm2/m Reinf. Area of BRC according to BRC Standard & Manufactu

> As req = 130 OK!


Material Strength

24 kN/m3 fcu 30 N/mm2


2.6 kN/m2 fyk 460 N/mm2

kN/m2
m
m

kN/m3
m
m

kN/m2 one layer brick, if two layer brick x 2


m
m

kN/m3 Concrete weight /m3


m Assume 1m strip of ground slab constribute to UDL on strip footing
m
m thickness slab

kN/m2 Imposed Load


m Assume 1m strip of ground slab constribute to UDL on strip footing
m

kN/m3 Concrete weight /m3


m

m
m

m
m 1000 convert mm to m

earing Pressure 75 kN/m2


m

mm
mm Dia. Cover
mm Dia. Link Bar
mm Dia. Main Bar / 2

mm 0.95d

mm
mm
mm

kNm
m

mm
mm

mm
N/mm2 Reinf. Mild Steel

mm
mm2
mm Spacing for Link Dia. need to be used

mm Assume 1m strip of ground slab constribute to UDL on strip footing


mm Thickness slab

BRC Standard & Manufacturer