2.0 Specifications
The Dual Reader Interface Module is for use in
low voltage, class 2 circuit only. Figure 1: LNL-1320
Power DC input 12 to 24 VDC +10%, 550 mA maximum (plus reader current)
12 VDC @ 450 mA
24 VDC @ 270 mA
Communication Ports Port 1 RS-485 (2-wire or 4-wire), 2400 to 38400 bps async
Inputs Eight (8) supervised, EOL resistors, 1k/1k ohm standard
Two (2) non-supervised
Wire Requirements Power 1 twisted pair, 18 AWG
RS-485 24 AWG twisted pair(s) with shield, 4000 ft (1200 m) maximum
Inputs twisted pair per input, 30 ohms maximum
Outputs 5 A 28 VDC
Reader Power Output Regulated Mode 125 mA maximum each reader
Environmental Temperature +32F to +158F (0C to +70C), operating
-67F to +185F (-55C to +85 C), storage
Humidity 0% to 95% RHNC
Mechanical Dimension 1 in. x 6 in. x 8 in.
(HxWxD) (25 mm x 152 mm x 203 mm)
Weight 10 oz. (290 g) nominal
Table 1: LNL-1320 Specifications
LNL-1320
3.0 Wiring
Supervised Alarm Inputs - Standard wiring configuration is
as follows (Alarm Contacts 1-4 are for Door #1, Alarm Door 1 Door Contact In 1
Contacts 5-8 are for Door #2), see Figure 3.
Door 1 REX In 2
Wire the IN1 IN8 inputs using a twisted pair cable, 30
ohms maximum.
Door 1 Aux 1 In 3
Terminate each of these inputs with two (2) 1000-ohm
resistors (1% tolerance 0.25 watt) for supervised inputs.
(See Figure 2) Door 1 Aux 2 In 4
Supervised
Door 2 Door Contact In 5
NC 1K, 1%
1K, 1%
Door 2 REX In 6
1K, 1%
NO
1K, 1%
Door 2 Aux 1 In 7
NC Door 2 Aux 2 In 8
NO Cabinet Tamper In 9
Power Failure GND
Unsupervised
In 10
TR+
TR-
TR+ TR- R- R+ SG
R+
R-
GND
+ VIN RED
VO
BRN
12 to 24 VDC LED
- GND ORG 0 1
BZR
WHT 2 3
D1/CLK 4 5
Figure 6: Power Input Wiring D0/DAT
GRN 6 7
8 9
BLK
GND * #
6.0 Relay Outputs
6.1 Control Output Wiring Figure 9: Reader Wire Connections
NC FUSE +
DC SOURCE 6.4 Configuration
C
- The Dual Reader Interface Module board
NO
contains (8) DIP switches and (3) jumpers that
NC must be configured for your system.
C 6.5 Setting DIP Switches
LOAD
NO
FUSE
The default positions for DIP switches is:
Address 00; 38,400 bps (switches 6 and 7 are
MOV
AC SOURCE on, others are off).
LOAD