LNL-1320 Dual Reader Interface Module

Quick Reference Guide


1.0 Introduction
The Dual Reader Interface Module board
contains the following components (Refer to
Figure 1):
A. eight (8) supervised/non-supervised alarm
inputs
B. one (1) RS-485 interface
C. two (2) reader interfaces
D. six (6) relay outputs
E. one (1) power input
F. one (1) cabinet tamper
G. five (5) jumpers
H. eight (8) DIP switches
I. two (2) status LEDs

2.0 Specifications
The Dual Reader Interface Module is for use in
low voltage, class 2 circuit only. Figure 1: LNL-1320
Power DC input 12 to 24 VDC +10%, 550 mA maximum (plus reader current)
12 VDC @ 450 mA
24 VDC @ 270 mA
Communication Ports Port 1 RS-485 (2-wire or 4-wire), 2400 to 38400 bps async
Inputs Eight (8) supervised, EOL resistors, 1k/1k ohm standard
Two (2) non-supervised
Wire Requirements Power 1 twisted pair, 18 AWG
RS-485 24 AWG twisted pair(s) with shield, 4000 ft (1200 m) maximum
Inputs twisted pair per input, 30 ohms maximum
Outputs 5 A 28 VDC
Reader Power Output Regulated Mode 125 mA maximum each reader
Environmental Temperature +32F to +158F (0C to +70C), operating
-67F to +185F (-55C to +85 C), storage
Humidity 0% to 95% RHNC
Mechanical Dimension 1 in. x 6 in. x 8 in.
(HxWxD) (25 mm x 152 mm x 203 mm)
Weight 10 oz. (290 g) nominal
Table 1: LNL-1320 Specifications
LNL-1320

3.0 Wiring
Supervised Alarm Inputs - Standard wiring configuration is
as follows (Alarm Contacts 1-4 are for Door #1, Alarm Door 1 Door Contact In 1
Contacts 5-8 are for Door #2), see Figure 3.
Door 1 REX In 2
Wire the IN1 IN8 inputs using a twisted pair cable, 30
ohms maximum.
Door 1 Aux 1 In 3
Terminate each of these inputs with two (2) 1000-ohm
resistors (1% tolerance 0.25 watt) for supervised inputs.
(See Figure 2) Door 1 Aux 2 In 4
Supervised
Door 2 Door Contact In 5
NC 1K, 1%
1K, 1%
Door 2 REX In 6
1K, 1%
NO
1K, 1%
Door 2 Aux 1 In 7

NC Door 2 Aux 2 In 8

NO Cabinet Tamper In 9
Power Failure GND
Unsupervised
In 10

Figure 2: Supervised/Unsupervised Figure 3: DRI Alarm Input Contact Wiring

4.0 Upstream Controller Communication


The RS-485 is TR 2+
TR2+
asynchronous, TR 2-
TR2- GND
half-duplex, using GND
LNL-500
TR 3+
LNL-500
1 start bit, 8 data TR3+
TR 3-
GND
bits, 1 stop bit. TR3-
GND

TR+
TR-
TR+ TR- R- R+ SG
R+
R-
GND

Figure 5: RS-485 4-Wire Communication


Figure 4: RS-485 2-Wire Communication

LNL-1320 Quick Reference Guide


49309C Page 2 2006 Bosch Security Systems, Inc.
LNL-1320

5.0 Power 6.3 Reader Communications


Wire the power input with an 18 AWG Wire the J1 interface using a 24 AWG
(minimum) twisted pair cable. (minimum) cable.

+ VIN RED
VO
BRN
12 to 24 VDC LED
- GND ORG 0 1
BZR
WHT 2 3
D1/CLK 4 5
Figure 6: Power Input Wiring D0/DAT
GRN 6 7
8 9
BLK
GND * #
6.0 Relay Outputs
6.1 Control Output Wiring Figure 9: Reader Wire Connections
NC FUSE +
DC SOURCE 6.4 Configuration
C
- The Dual Reader Interface Module board
NO
contains (8) DIP switches and (3) jumpers that
NC must be configured for your system.
C 6.5 Setting DIP Switches
LOAD
NO
FUSE
The default positions for DIP switches is:
Address 00; 38,400 bps (switches 6 and 7 are
MOV
AC SOURCE on, others are off).

LOAD

Figure 7: Control Output Wiring 1 2 3 4 5 6 7 8

6.2 Relay Outputs


Figure 10: DIP Switch Settings
NC
Door 1 Strike DIP Used to configure:
C RLY 1
Relay Switch(es)
NO
NC
1, 2, 3, 4, 5 Device Communication address (0-31)
C RLY 2 Door 1 Aux 1 6, 7 Communication baud rate
NO (38400, 19200, 9600 bps)
8 Not used
NC
Door 1 Aux 2
C RLY 3 Table 2: DIP Switch explanations
NO
NC 6.6 Communication Baud Rate
C RLY 4 Door 2 Strike
Relay To configure the communication baud rate, set
NO
DIP switches 6 and 7 according to Table 3.
NC Baud Rate DIP SWITCH
C RLY 5 Door 2 Aux 1 (bps) 6 7
NO
38400 ON ON
NC
C
19200 OFF ON
RLY 6 Door 2 Aux 2
NO 9600 ON OFF
0 OFF OFF
Figure 8: DRI Alarm Output Contact Wiring Table 3: Setting Baud Rate

LNL-1320 Quick Reference Guide


2006 Bosch Security Systems, Inc. Page 3 49309C
6.7 Device Addresses
To configure the device communication address, set DIP switches 1, 2, 3, 4, and 5 according to Table 4.
DIP SWITCH DIP SWITCH
ADDRESS 5: 4: 3: 2: 1: ADDRESS 5: 4: 3: 2: 1:
0 OFF OFF OFF OFF OFF 16 ON OFF OFF OFF OFF
1 OFF OFF OFF OFF ON 17 ON OFF OFF OFF ON
2 OFF OFF OFF ON OFF 18 ON OFF OFF ON OFF
3 OFF OFF OFF ON ON 19 ON OFF OFF ON ON
4 OFF OFF ON OFF OFF 20 ON OFF ON OFF OFF
5 OFF OFF ON OFF ON 21 ON OFF ON OFF ON
6 OFF OFF ON ON OFF 22 ON OFF ON ON OFF
7 OFF OFF ON ON ON 23 ON OFF ON ON ON
8 OFF ON OFF OFF OFF 24 ON ON OFF OFF OFF
9 OFF ON OFF OFF ON 25 ON ON OFF OFF ON
10 OFF ON OFF ON OFF 26 ON ON OFF ON OFF
11 OFF ON OFF ON ON 27 ON ON OFF ON ON
12 OFF ON ON OFF OFF 28 ON ON ON OFF OFF
13 OFF ON ON OFF ON 29 ON ON ON OFF ON
14 OFF ON ON ON OFF 30 ON ON ON ON OFF
15 OFF ON ON ON ON 31 ON ON ON ON ON
Table 4: DIP Switch Device Addresses

6.8 Installing Jumpers


6.8.1 RS-485 Type 2W 4W 2W 4W
Jumper J3 is used to configure the RS-485 type J3 J3
for Port 1 on the READYKEYPRO Dual Reader
Interface Module board. There are two possible
2-Wire 4-Wire
configuration options that can be used to install
this jumper: 2-wire configuration, and 4-wire Figure 11: RS-485 configuration for Jumper J3
configuration.
Jumpers J4 need to be configured. J4 controls
Reader 1 and Reader 2 voltage output. J4 J4

J4 in ON position (5 volts) J4 in OFF position (12 volts)

Figure 12: Jumper J4 configuration

With unregulated mode, the supply voltage is J2 J2


passed through the readers with no regulation.
J2 in regulated mode J2 in unregulated mode
(default)

Figure 13: Jumper J2 configuration


J5
6.8.2 RS-485 EOL Terminator EOL Termination ON EOL Termination Not ON J5

Status Configuration for J5, J6 Configuration for J5, J6


J6 J6

Figure 14: Jumper J5 & J6 Configuration

2006 Bosch Security Systems, Inc. 49309C 10/06


130 Perinton Parkway, Fairport, NY 14450-9199 USA Quick Reference Guide LNL-1320
Customer Service: (800) 289-0096; Technical Support: (888) 886-6189 Page 4 of 4