Solution:
Problem Analysis:
Sample module: EKI-1222
OS: Windows 7 Professional 64-bit
Utility Version: Advantech Serial Device Server Configuration Utility 1.67
Note1: When we cannot EKI-1222, and open utility; the device will show up
automatically.
Note2: If you are using Windows 7 32/64-bit, please open utility with Administrator.
(Click utility icon, right click to start as Administrator)
Step2: IP address configuration
Note1: Select the IP mode; Static IP or Auto IP. Normally, we suggest Static IP. You
must have DHCP/Bootp server to use other IP mode.
Note2: Assign an IP and subnet for device module.
2) Add ID
Here I select Port 2, it depends on which serial port of PC you want to connect
to EKI-1221.
4) Set up the communication configuration OK
6) Connection:
Connect Using: TCP server, IP Address: EKIs IP, Service Port = 502
MODBUS/TCP service port normally is 502
7) Connecting
8) When connect successful, we can see there are start access data on ModScan.
When we connect successful, we can the check LED or EKIs TX and RX.
LEDs should be blink during data access.
ModSim and ModScan are not only simulate tool for MODBUS
communication, we can still use other standard MODBUS tool.
Referance:
EKI-1521_1522_1524_Manual_Ed3.pdf (Ed3)
http://support.advantech.com.tw/Support/DownloadSRDetail_New.aspx?SR_ID=1-2M3FZ
V&Doc_Source=Download
Written by Tony.Fu,
AOnline AE, Nov. 2013