ABSTRACT
Applying a sinusoidal voltage to a distribution transformer results in a non-sinusoidal
magnetizing current due to the non-linear relationship between magnetizing force H and flux density
B, also known as magnetizing curve. Although the no-load current in modern transformers is very low
(0.1-0.5% of the rated current), it is generally responsible for the no-load losses. Considering the
number of distribution transformers connected to the power grid, these no-load losses are constantly
generated regardless of the transformers load, thus introducing significant energy consumption.
According to the no-load losses, transformers are classified in several categories described in IEEE
519-2014 Standard and EcoDesign Directive 2009/125/EC. This paper presents the measurements of
voltage and current harmonics, conducted for several three-phase distribution transformers with
different rated apparent power and same voltage level, operating at no-load conditions. The current
and voltage waveforms are examined, as well as the total harmonic distortion when the rated voltage
is applied to the primary side of the transformer. This paper provides a detailed view of the
transformers no-load harmonic impacts, with several methods proposed for their reduction. The
transformers were tested at the Testing station at Rade Koncar Service and Repairs of Electrical
Products in Skopje.
Keywords: voltage harmonics, no-load current harmonics, total harmonic distortion.
1 INTRODUCTION
The magnetic circuit is one of the most important active parts of the transformer. It consists of
laminated iron core and carries magnetic flux linked to the windings, thus enabling energy flow from
one electrical circuit to another. The iron core provides a low reluctance path to the magnetic flux
thereby reducing magnetizing current to a particular level [1]. When the transformer operates at no-
load conditions, meaning that rated voltage is applied to the primary windings and the secondary
circuit is opened, the generated losses consist of two parts: hysteresis losses and eddy current loses.
Hysteresis losses originate from the molecular magnetic domains in the core laminations,
resisting being magnetized and demagnetized by the alternating magnetic field. Each time the
magnetising force produced by the primary winding changes because of the applied AC voltage, the
domains realign in the same direction as the force. The energy to accomplish this realignment comes
from the input power and is not transferred to the secondary winding, thus being considered as a loss.
Because various types of core materials have different magnetizing abilities, the selection of core
material is an important step in reducing core losses. These losses depend upon the area of the
magnetizing B-H loop, shown in Fig. 1, and of the frequency [2, 3]. The specific hysteresis losses per
unit mass of the core can be calculated by using Eq. (1):
Ph K h f Bms (W/kg) , (1)
where Kh is the hysteresis constant depending on the material characteristics, f is the frequency in
Hz, and Bm is the maximum flux density in T.
The alternating magnetic flux induces an EMF in the transformer core, proportional to the flux
density and the frequency. The resulting circulating current depends inversely upon the resistivity of
the material and directly to the thickness of the core. By using a laminated core, i.e. thin sheets of
silicon steel instead of a solid core, the path of the eddy current is broken up without increasing the
reluctance of the magnetic circuit [2]. The difference between eddy current paths is shown in Fig. 2.
Figure 1. Nonlinear B-H loop and magnetizing Figure 2. Eddy currents in different magnetic
current determination core types
The voltage and current waveforms for the first transformer (160kVA), obtained with the power
analyzer, together with the total harmonic distortions are shown in Fig. 4 and Fig. 5 respectively.
Figure 4. Primary voltage waveform (left) and voltage harmonic spectrum (right) for 160kVA
transformer at U10=10.237V
Figure 5. Primary current waveform (left) and current harmonic spectrum (right) for 160kVA
transformer at U10=10.237V
From Fig. 4 and Fig. 5 can be discussed that the total voltage harmonic distortion is highest for
the 7th and the 5th harmonics, although they are within the limits allowed by standards (< 5%, [6]). The
triple voltage harmonics are mitigated, while the 11th harmonic is slightly greater than the 9th. The
voltage does not experience significant waveform distortions and it is very close to the ideal sine
wave. For the entire measured harmonic spectrum THD(U)=1.3%.
On the other hand, the no-load current harmonics exceed the allowed limits: the 5th harmonic as
the highest and the 7th are distorted more than the limit of 8% [6]. The total current distortion is
THD(I)=28.0%, which can be discussed from two different perspectives. Since the root mean square
value of the no-load current is very small (< 0.01A), the measured distortion is most likely not to
cause any significant troubles to the power grid. However, this distortion increases the losses in the
transformer core, and can cause protection relays reaction unless they are properly configured. All
high order current harmonics above the 7th are difficult to be measured, therefore they can be
disregarded in the calculations.
In Fig. 6 and Fig. 7 are shown the waveforms of the voltage and no-load current for the second
transformer (400kVA) and the harmonic spectrums respectively.
Figure 6. Primary voltage waveform (left) and voltage harmonic spectrum (right) for 400kVA
transformer at U10=10.
Figure 7. Primary current waveform (left) and current harmonic spectrum (right) for 400kVA
transformer at U10=10.237V
The situation is similar to the previous case. Total voltage distortion is THD(U)=1.25%, and the
highest harmonic components are the 7th and the 5th. All of these distortions are within the standard
limits, which is not the case with the no-load current. The total distortion is THD(I)=29.85%, and the
highest harmonic components are the 5th and the 7th.
The third transformer (1000kVA) also showed similar results. The waveforms and the harmonic
spectrum distributions for primary voltage and no-load current are shown in Fig. 8 and Fig. 9
respectively. The voltage waveform is almost ideal, with a distortion of only THD(U)=1.27%, with
the 7th harmonic being the highest. The no-load current again is significantly distorted, with
THD(I)=27.3%, and the 5th and the 7th harmonic components being the highest.
Figure 8. Primary voltage waveform (left) and voltage harmonic spectrum (right) for 1000kVA
transformer at U10=10.
Figure 9. Primary current waveform (left) and current harmonic spectrum (right) for 1000kVA
transformer at U10=10.237V
Three phase transformers vector group has an important impact on the harmonic spectrum.
When the primary windings are delta (D) connected, the triple harmonics are restricted to flow only
within the phase windings, and hence they will not appear in the line currents. However, they might
increase the winding temperature above the allowed limits, and much attention must be paid. This also
refers to the voltage harmonics. In star (y) connection, the neutral point can be grounded, therefore
providing no path for the triple harmonics. They flow through the neutral line to the ground, and are
not reflected on the other side of the transformer [7].
In the recent years much attention is paid to the transformer no-load losses by the customers.
That led to creating a special standard for transformer losses reduction, EN 50464-1 [8]. According to
this standard, distribution transformers up to 2500kVA depending on their no-load losses can be
classified in 5 categories, and each of them has particulary specified the value of no-load losses, as
shown in Fig.10. From these measurements can be concluded that tested transformers belong to Co
category, and actually show smaller losses than guranteed, which is on the right way to reaching even
greater energy efficiency.
4 CONCLUSION
In this research the voltage and current waveforms and harmonic distortions were analyzed for
three different three-phase distribution transformers, operating at no-load conditions. The
measurement of harmonic spectrum was done with a power quality analyzer during the standard no-
load test. According to the expected theoretical assumptions, the voltage waveform is almost ideal
sine wave, experiencing slight distortions of about 1.25-1.3%. The highest high order harmonics in
the spectrum were noticed to be the 7th and the 5th. Due to the vector group of the transformers, the
triple harmonics are mitigated. The no-load current showed notable total harmonic distortion of about
28%. The waveforms were almost exactly the same, regardless of the rated power. This was due to the
5th harmonic being most dominant in the spectrum, and then the 7th and the 3rd. Although these
currents might not be a threat to the power system, they increase transformer no-load losses, which
are constant regardless of the load.
5 REFERENCES
[1] Daut I., Hasan S., Taib S. Magnetizing Current, Harmonic Content and Power Factor as the Indicators
of Transformer Core Saturation. Journal of Clean Energy Technologies, Vol. 1, No.4, October 2013,
pp.304-307.
[2] Digalovski M., Najdenkoski K., Rafajlovski G. Impact of Current High Order Harmonics to Core
Losses of Three-Phase Distribution Transformer. EuroCon 2013, Zagreb, Croatia, 1-4 July 2013. pp.
1531-1535.
[3] Rao N.M., Mandal M., Distribution Transformers Impact of Harmonics, Estimation of Losses and
Life-Expectancy and Mitigation of Ill Effects, NTPC Electric Supply Company Ltd.
[4] Desai R., Patel A., Gupta V., Identification of Various Internal Faults of Transformer Based on No-load
Current Analysis, International Journal of Emerging Technology and Advanced Engineering, Vol. 2,
Issue 2, February 2012, pp.222-226.
[5] Odoglu H. Transformer Tests, Balikesir Elektromekanik Sanayi Tesisleri A.S., June 2009.
[6] IEEE Recommended practice and Requirements for Harmonic Control in Electric Power Systems 519-
2014, IEEE Power and Engineering Society, August 2014.
[7] Baghzouz Y., Gong X.D., Analysis of Three-Phase Transformer No-Load Characteristics. IEEE
Transactions on Power Systems, Vol. 10 No. 1, February 1995, pp. 18-26.
[8] European Standardisation for Transformer Losses Reduction EN 50464-1, 2007.