5 M Water sump

Design Data

Ground level = 100


Top of wall = 100
Water level = 100
Top of base slab = 95
Length of tank = 1.25
Width of tank = 1.25

Grade of concrete = 25
Grade of steel = 415
Density of water = 10
Density of Soil = 18

Pressure at base due to water = 50


Equivalent water pressure at base = 50

5 5
=

50 50.00

From IS 3370:1967 , Table 3


Design of Long Wall b/a = 0.25

Moment Due to water


Max Horizontal B.M. -ve Mh - = 2.64
Max Horizontal B.M. +ve Mh + = 1.32

Moment Due to Soil


Max Horizontal B.M. -ve Mh - = 3.87
Max Horizontal B.M. +ve Mh + = 1.93

Thickness required d reqd = 59.03


Provide thk D = 150
d = 75

Area of steel required For water


Ast h - = 261
Ast h + = 131
For Soil
Ast h - = 382
Ast h + = 191
Area of steel provided
Ast h - = provide 8T+8 T @200 c/c
Ast h + = provide 8 T @200 c/c

provide 8 T @200 c/c IN VERTICAL DIRECTION


Ht of wall = 5
Ht of water = 5
ht of soil = 5

m
m

N/mm2
N/mm2
kN/m3
kN/m3

kN/m2 Water force = 125 = 2.5


kN/m2 x = 50

5 5
=

29.7 29.70

mm
mm
mm

mm2
mm2

mm2
mm2

ovide 8T+8 T @200 c/c


ovide 8 T @200 c/c
x