Accuracy class: 3
Voltage error is less than 3% -the error between the actual primary
voltage and the same measured, shown, used and sent to remote
end by the numerical relay.
(As the output voltage of 2/3 is inside the secondary convertor the
error is measured with output display of primary voltage itself in the
numerical relay)
Phase displacement error-is mainly applicable for energy
measurement the same is compensated inside firmware for those
units in which energy is measured.
Rated voltage for auxiliary power supply: 18-75 v dc or 88-280vdc
Highest voltage for voltage sensor Um: Rated voltage *1.9 volts
RMS phase to earth
Rated Voltage Highest Voltage for
Volts the voltage sensor
in K.volts
11000/3 12.1
22000/3 24.2
33000/3 36.2
25000 47.5
Earth Fault factor: 1.9