Protection and Control for Transmission Networks

IED 670 Selection Guide

Innovation from ABB


More than
just a device
How to use the most powerful
relayever designed.....
ABB proudly present the first truly open and future Our new Protection & Control Manager (PCM) is an equally
proof substation automation product family on the powerful and easy-to-use tool for engineering,
market. This new concept will allow you to design more configuration, setting, monitoring and disturbance
efficient, reliable and flexible substation automation evaluation. Finally MicroSCADA has been further
solutions. This will furthermore give you a more user developed to MicroSCADA Pro with additional
friendly, informative and future proof installation. functionality, improved graphics and full IEC 61850
support.
IED 670 is the most powerful Intelligent Electronic
Device for Substation Automation & Protection Based on our Innovation, Experience and Commitment we
available today. It is the first truly hardware are offering you the state-of-the-art IED 670 Protection,
independent modular concept for ALL applications Monitoring & Control Solution Provider, Made in ABB.
in Power Transmission Systems. IED 670 is fully
designed for IEC 61850, TCP/IP and high speed
Efficient
Ethernet but also support other protocols.
Reliable
IED 670 is an evolution from our experienced 316
and 500 series and is based on well proven algorithms Flexible
and our modular I/O concept. Accuracy, speed,
functionality, flexibility and information handling has
been significantly improved. Protection, monitoring
and control can be integrated or distributed in any
IED. The possibility to combine cycle fault clearing
with typical 0.25 % measuring accuracy and at the
same time connect the IED to both protection cores
and metering cores of the instrument transformers
makes IED 670 unique in its high performance.

ONE common Application Function Library, ONE


modular and state-of-the-art IED with a 600 MHz CPU
give the freedom-of-choice and unique flexibility to
design your own optimum solution. This future proof
concept allows you to keep your assets forever young.
With IED 670 you can migrate with the rapid CPU
and communication development while staying with
the well proven algorithms in our Application
Function Library.

2
..to further improve the performance and
grid reliability of your power system
IED 670 is available as pre-configured and ready-to- For even more flexibility you can design your own IED
use IED and are designated REB, REC, RED, REL and just selecting your preferred functions from the
RED depending on each major application. In our Pre- comprehensive Application Function Library and I/O
configured Buyers Guides you will find all available modules in our Buyers Guide. You can either start from a
versions with basic functionality which are ready-to-use pre-configured version and just add options or you can start
without any additional configuration needed. With the from our open IED versions and tailor the functionality
PCM tool it is very easy to re-adjust the links for each input from the options available in the Open Buyers Guides.
and output with your external circuits and re-adjust the In both cases you will need the PCM tool with the
pre-set values according to you selectivity plan. This gives configuration option according to IEC 61131-3 in order to
fast installation and commissioning. PCM is configure your selected options.
furthermore a powerful tool for substation monitoring
and disturbance evaluation especially if the fast Ethernet As an alternative and on your optional request we can
connection can be utilized. together with you identify the most optimum solution to
configure for your specific application and requirements.
User friendly This customized IED will then be identified with a unique
number which can be re-ordered at any time by you.
Informative

Future proof + REL 670 with true full scheme distance function, excellent phase selection and
load discrimination for maximum selectivity of HV & EHV lines and cable
protection (optional additional algorithms & control functionality)

+ RED 670 with phase segregated current differential and route switching
capability for absolute selectivity of up to 5 lines ends with up to 6 three phase
current restrained inputs. (optional additional algorithms & control
EHV functionality)

+ RET 670 with multi differential functions for high speed (1/2 cycle) and
selective protection of 2 or 3 winding transformers with up to 6 three phase
current restrained inputs. (optional additional algorithms & control
functionality)

+ RET 670 can be configured for auto transformers, phase shifters or composite
objects such as generator/transformer blocks, transformers + bus bars + lines.
HV + REC 670 with select before execute command for single, double or breaker &
half bay control (optional additional algorithms & protection functionality)

+ REC 670 with multi page HMI (6 single line diagrams) can be configured for
multi bay and/or H-station control with optional protection functionality

+ REB 670 is a further improvement of our well known


RADSS/REB100/RED521 bus differential protection for up to 24 feeders and
two zones. This provides a unique reliability with ultra high speed fault detection
and stability for CT saturation. (optional additional algorithms such as breaker
failure)

3
We are stepping
out of the box.....
Our new concept is an evolution from our well proven This unique functionality and flexibility provides
RE.316 and REx5xx IED range in a truly global reliable and efficient solutions for basically any
development by ABB. All existing protection, control protection, control and monitoring application in High
and monitoring algorithms has been modelled and further Voltage Substations. We may proudly state that our
improved according to the new IEC 61850 open complete and global know-how and experience now is
standard into our Application Function Library. available at the fingertips of the user.

The IED670 is based on our experienced REx5xx design ABB has for the last twenty years been leading the
utilizing the same modular and scalable I/O boards but development of digital protection and control.
with increased analogue input capability up to 24 24 Communicating relays via SPA, numerical control via
currents/voltages. The state-of-heart 600 MHz CPU Ethernet and the function library concept in 216/316 series
allows higher functionality and still will process the were all introduced in the 80ies and further developed with
algorithms from our common library even faster the 500 series and LON during the 90ies. Now we take the
compared to today. All algorithms can be combined in next step in this evolution.
basically any IED exactly according to your desired
architecture and redundancy requirement. All IEDs can IED 670 is the first IED on the market, which is fully
be provided with full control functionality and the fully designed for the new IEC 61850 standard allowing an
graphical multi page / multi bay HMI. open structure with free allocations of functions instead
of a locked hard ware box. This allows optimised design
from fully integrated to fully decentralized solutions
depending on your preferences and application.

ONE powerful and open IED


for ALL applications

4
.....to give you
the magic IED!
With IED 670 you have the freedom of choice to design communication for C37.94 and G 703 is furthermore
your protection & control solution exactly as you need. available in IED 670 for sampled values and transfer trip.
Our new range includes all products needed to efficiently
design and operate your future proof Substation For full details and continuous update on available
Automation System. The modular IED, the user friendly products and solutions we refer to
PCM and the informative MicroSCADA Pro. www.abb.com/substationautomation.

What differs ABB from other brands is that we are This gives you a step-by-step approach when you can
leaving the box. Instead of a large number of different introduce the new products with the existing protocols
hardware boxes, software and protocol converters to learn and then migrate to IEC 61850 when you are ready. But
and maintain we are introducing ONE modular and you can already start today by using the High Speed
open concept - independent of hardware, which is Ethernet for your Substation Monitoring with remote
designed for and fully implement the new IEC 61850 parameterization and disturbance evaluation.
open standard.
Both IEC 870-5-103 and IEC 61850 allows you to
In addition we fully support the present protocols such combine different vendors. But with the hardware
as SPA, LON and IEC 870-5-103 within the substation independent IED 670 you can furthermore move,
and a large number of additional remote protocols change and upgrade functions even after installations. This
through MicroSCADA Pro or our Remote Terminal is what we mean with an open and future proof concept
Units. We have additionally implemented IEC 61850 in to ensure that your investment is forever young.
REB 500 as well as COM581. Existing products such as
REL 521/531 can be connected to IEC 61850 via a
converter. IEC 61850 is also implemented for our
So it still matters which vendor you choose!
distribution range of IEDs. Multiple end remote end data

ABB MicroSCADA Pro HSI Separate Gateway Office/Mobile PC


with optional gateway or RTU to NCC For SMS/PCM

IEC 61850-8-1 IED 670 includes two optical Ethernet LAN


connections for disturbance free
TCP/IP LAN/WAN communication within the substation and
interface to the Network Control Center via
Gateway/RTU and to any location for SMS
G37.94
(Disturbance record, events, settings etc.)
G.703 via WAN, WWW or modem. Additional SPA,
LON and IEC 870-5-103 is available as
option in IED 670.

IED 670 is furthermore prepared for


additional optional connection to IEC
SPA, LON & IEC 870-5-103 618509-2 process bus.

5
A major
leap In Grid
Reliability

The main requirement =


Always operate correctly
Reliable Power Supply
G No chain is stronger than its weakest link. This truth is valid also for the power system.
In order to ensure continuous power transmission each link has to be in operation. This
means that the transmission lines and transformers have to be continuous available.

Unavailability can be stated as MTTR/MTBF. MTBF = Mean Time Between Failure and
MTTR = Mean Time To Repair. In short we need to minimize the probability of a fault
and the time to restore operation. Faults will however always occur due to lightning
strokes, pollution, ageing and other reasons. Therefore we need reliable and fast
protection and control to clear the fault and restore operation. And equally important is
not to cause an unnecessary interruption. IED 670 provides fast and reliable protection
and control. This is what we mean with Always operate correctly.

Reliability = Dependability + Security


The IED shall operate correctly with dependable detection of all internal faults but at
the same time be secure for external faults and during normal operating conditions
without any false operation. In a similar way the IED shall guarantee dependable and
secure control including interlocking, auto-re-closing and efficient information
handling to minimize the effect of any disturbance. Duplicated protection, local or
remote back-up can be used to improve the dependability. What is important is to select
and co-ordinate the protection for the overall availability for the complete power
system.

The fault clearing chain


The IED is an integral part of the fault clearing chain. The IED requires information
about currents and voltages during load and fault conditions. It should however operate
correctly even at distorted signals due to CT transients, CT saturation or extremely low
values. If a breaker fail to operate, the IED shall provide reliable breaker failure protection
but at the same time be stable for remaining flux current. Finally certain line protection and
remote tripping capability as well as substation automation require reliable
communication.

IED670 is designed to always operate correctly


IED670 is designed to operate correctly during CT saturation and CVT transients
and includes an advanced breaker failure algorithm for multiple breakers. It can
furthermore handle multiple sets of three phase current transformers for improved
security. Finally the adaptive communication can handle route switching as well as GPS
M interruption.

6
Power system know-how
and experience
High Current & Faults with large DC component Weak End Infeed Faults
A IA IL IB B SB
ZsA p*ZL 1-p*ZL ZsB

Rf Faults during high load (IL)


Z< Z<

High Resistance Faults

Optimizing Dependability and Security Security = Selectivity + Stability


In order to optimize dependability AND security Security requires to optimize selectivity AND
for maximum grid reliability it is necessary to stability for ALL objects. Differential current
design, select, test and verify the protection and measurement used for bus, transformer and line
control IED for each type of fault, each type of differential protection will during ideal conditions
application, all source-to-line ratios, different provide absolute selectivity. But a false operation can
instrument transformers and operating conditions. give a big disturbance. High stability for through
The IED is NOT an island. The IED is an going currents, CT-saturation and inrush currents
integral part of the power system. This means we is therefore mandatory especially for bus, breaker
need to fully know and understand the power failure and transformer protection. Phase selectivity
system i.e. the complete chain. and stability for load and power swings is essential
for transmission line protection.
Dependability = Speed + Sensitivity
Dependability requires to optimize speed AND ABB power system competence
sensitivity for ALL faults. High speed is especially ABB is the worlds leading supplier in Power
important for busbar and transformer protection Technology for Transmission and Distribution. This
to limit damages from high current faults. High means we have a wide competence with deep know-
sensitivity is important for transmission line how and global experience for all major parts in the
protection since the majority of the faults are single power grid from power transformers and circuit
phase-to-earth faults with moderate fault current due breakers to instrument transformers and substation
to high fault resistance and/or weak-end infeed. automation. In addition we are the leading supplier of
advanced system solutions for HVAC and HVDC. The
Built in power system know-how design of IED 670 is based on this unique
competence and further verified in advanced
Well proven algorithms simulator studies and global experience for ALL
types of applications and conditions. That is why we
State-of-the-art IED proudly state that IED 670 is a major leap for grid
reliability.
Maximum reliability

Evolving faults

2-phase faults
3-phase faults

1-phase faults
7
IED 670 = Perfecting
your selectivity plan
With the state-of-the art IED 670 you have a unique Constant operating time independent of source to line
solution provider to design and adjust the protection ratio and for all fault locations together with reliable phase
& control solution to exactly meet your application and selection independent of load is the main requirement for
requirement. All necessary protection, monitoring the line protection. Single phase faults on heavily loaded
and control algorithms are available in our common transmission lines, parallel lines, multi terminal lines, weak
Application Function Library. IED 670 is ensuring both end infeed and high fault resistance can be correctly tripped
maximum dependability and security. This means to and re-closed by REL 670 and RED 670. Close in line faults
provide fast and sensitive detection of ALL faults can be detected in cycle with the high speed over current
independent of type and location but at the same time function.
ensure selectivity and stability for external faults,
load, and transients. Our well proven algorithms have been further improved to
operate correctly even during CT saturation and CVT
Accuracy and speed are often contradictory and all design transients. With up to 24 analog inputs you can connect
requires a balance between the two requirements. the transformer and line protection to both sets of CTs
However the IED 670 high performance CPU enables which are used for breaker-and-a-half, ring or double
both faster and more accurate execution of the breaker switchgear allowing high sensitivity and stability.
algorithms. As an example REL 670 and RET 670 is
faster compared to REL 521 and RET 521. Damaging
bus or transformer faults with high fault current can be
detected in less than half a cycle with RET 670 and REB An efficient solution provider
670 with maintained stability for transients and CT- for all applications
saturation.
Op. Time ms
RED 670

REC 670
REB 670

RET 670
REL 670

IED 670 Main functionality and applications


Full-scheme distance protection with advanced phase selection & load enchroachment 20

Phase segregated line differential protection with adaptive communication 20

High speed & high sensitivity transformer differential protection with adaptive stabilization 10

High speed phase segregated bus differential protection with extremely low CT requirements 10

High speed summation type bus differential protection with extremely low CT requirements 10

High speed high impedance differential protection 10

High speed and high sensitivity restricted earthfault differential protection 20

High speed instantaneous phase and earth over current protection 10

4-step phase over current protection n.a.

4-step residual over current protection n.a.

4-step directional phase and earth over current protection n.a.

Adaptive breaker failure protection n.a.

Over/Under frequency n.a.

Over/Under voltage n.a.

Rate of change frequency n.a.

General Voltage/Current Protection n.a.

Auto reclosing n.a.

Synchrocheck n.a.

High performance disturbance recorder (40 analog channels/100 disturbancies) n.a.

High accuracy fault locator n.a.

Bay control with interlocking and select before execute n.a.

Measuring and event recording n.a.

Programmable logic n.a.

Maximum number of breakers/bays 24 2 2 6 6 n.a.

8 24 analog input channels n.a.


For maximum
grid reliability
Perfecting the Kirchhoff Law
The well known Kirchhoff law is the base for all RED 670 is the further development of REL 551/561 line
differential protection and has many advantages. The well differential protection extended to 6 sets of three phase
proven algorithms in RET 316/RET 521 and REB current restraint, e.g. up to five line ends and two breaker
100/RED 521 have been further improved to ensure both application in one end. It operate correctly for route
high speed operation, typically to cycle and full switching and shorter GPS interruptions. Additional
stability for CT saturation and inrush currents. This back up functions e.g. over current protection or distance
unique dependability and security of RET 670 and protection can be added.
REB 670 will give you a valuable insurance of your
substation. We dare to state that this is the most high Perfecting Ohms Law
performing and reliable IED for busbars and All impedance measuring relays are based on Ohms Law by
transformers available today. In addition you can add measuring Z = U/I. Accurate impedance measurement
other functions such as breaker failure protection from the depends both on the CT and VT response as well as the
library. source to line ratio. Capacitive Voltage Transformers (CVT)
are common in High Voltage systems and can generate
RET 670 can handle 6 sets of three phase current restraint, errors. REL 670 has further developed the full scheme
e.g. a three winding power transformer with double distance measurement from the REL 5xx series. This has
breaker arrangement for each winding. RET 670 can be resulted in even shorter and constant operating time
further extended with additional high impedance and including CVT applications and high source-to-line
restricted earth fault differential protection to give even ratios.
faster and more sensitive protection of auto transformers,
reactors and primary windings. RET 670 can cover several The phase selection has been further improved with an
objects and several functions integrated in the same advanced load enchroachment characteristic. This
IED, e.g. line, bus, transformer and feeders. This makes unique dependability and security of REL 670 can be
RET 670 ideal for small substation applications since also further improved with additional functions such as a
the control functionality can be integrated. four step directional phase and earth protection as well as
the General Function (current/voltage) protection which
can be customized for rapid single phase detection of very
high resistance earth faults. The high speed overcurrent
The perfect differential protection function can be applied for close in and heavy current faults
and a four step overcurrent protection can be used as back-
The perfect distance protection
up during at a fuse failure or loss of measuring voltage.

3-winding Bus Multi terminal line Bus Parallel Line/Cable Transformer


Transformer cycle 1 cycle (Single pole) cycle 1 cycle cycle
cycle

Long transmission line


1 cycle (Single pole) Current Transformer Location
Breaker-and-half Station
cycle (High speed O/C) Circuit Breaker Location
cycle

9
Exactly what you
need
Modular and scalable IED
IED 670 is available in three different sizes for rack or maximum 14 I/O modules. (Maximum 224 BI or 96 BO and
flush mounting but all with 259,9 mm height (6U) and 160 BI). Please consult the table below or our Buyers Guide
201,1 depth. There are three alternative width: 19 for exact number of different modules depending of size.
(205.7 mm) , 19 ( 318.0 mm) and 1/1 19 ( 430.3 mm) All IED 670 can be equipped with none or several
Combitest test switches depending on requirements.
IED 670 can be equipped with maximum two analog
input modules (Maximum 24 analog inputs) and
Design your own perfect IED

Maximum quantity of I/O boards per type


Basic quantity defined in application table for available products.

Case (TRM= Transformer module) BIM/BIMp IOM BOM MIM GSM Total max in case Restriction
1/2 19" case 3 3 3 0 1 3
3/4 19" case with 1TRM 8 6 3 1 1 8
3/4 19" case with 2 TRMs 5 5 3 1 1 5
1/1 19" case with 1 TRM 14 6 4 4 1 14 BOM+MIM max 4
1/1 19" case with 2 TRMs 11 6 4 4 1 11 BOM+MIM max 4

BIM Binary Input Module 16 binary inputs, 24-30, 48-60, 110-125 or 220-250 VDC
BIMp Binary Input Module with enhanced pulse counting capabilities 16 binary inputs, 24-30, 48-60, 110-125 or 220-250 VDC, 40 pulses/s
IOM Binary In/Output Module 8 binary inputs, 24-30, 48-60, 110-125 or 220-250 VDC, 10 trip + 2 fast signal output relays
BOM Binary Output Module 24 trip and signal output relays
MIM mA Input Module 6 channels, 5, 10, 20 mA, 0-5, 0-10, 0-20 or 4-20 mA
GSM GPS Synchronization Module

10
Exactly what you want
IED 670 can be configured to exactly fit to your application and requirements. In most
cases you will find the best alternative in our pre-configured Buyers Guides (BG) which
are divided depending on application. All basic functionality is pre-configured with de-
fault setting which gives you a ready-to-use IED. You may still add options according to
the BG and configure the IED using PCM600. We additionally can provide
customized variants allowing you to configure an equal to an existing 316/500 IED as
seen from the table below. Finally you have the freedom of choice to tailor your own
IED by selecting from the options in the Open Configuration BG.

= Basic = Basic, 1-of = Optional 3 = Number of modules

Application Arrangement Sub-arrangement Busbar Bay Line Line Transformer


Differential Distance

REC 670-C30
REC 670-B30

RED 670-B31
RED 670-B32
REB 670-B20
REB 670-B21
REB 670-B31

REC 670-A10
REC 670-A20
REC 670-A30

RED 670-A31
RED 670-A32
REB 670-A20
REB 670-A31

RET 670-B30
RET 670-B40
REL 670-B31
REL 670-B32

RET 670-A10
RET 670-A11
RET 670-A20
RET 670-A30
RET 670-A31
RET 670-A40
REL 670-A10
REL 670-A31
REL 670-A32
REC 670

RED 670

RET 670
REL 670
Busbar 4 bays/2 zones 3 phase
8 bays/2 zones 3 phase
12 bays/ 1 zone 1 phase
12 bays/ 2 zones 1 phase
24 bays/ 2 zones 1 phase
12 bays/1 zone 3 phase Summation
12 bays/2 zones 3 phase Summation
24 bays/ 2 zones 3 phase Summation
Bay control Open options To be customized
1 Circuit Breaker Breaker Protection
1 Circuit Breaker Bay Control
1 Circuit Breaker Control & Protection
2 Circuit Breakers Control & Protection
1 Circuit Breaker Control & Protection
Transmission Line Open options To be customized
Station Back up
1 Circuit Breaker 3 phase trip
1 Circuit Breaker 1 phase trip
2 Circuit Breakers 3 phase trip
2 Circuit Breakers 1 phase trip
Transformer Open options (24 AI) To be customized
Station (12AI) Back up
Station (12 AI) Load shedding
2 winding (12/24 AI) 1 Circuit Breaker
2 winding (24 AI) 2 Circuit Breakers/W
3 winding (12I) 1 Circuit Breaker
3 winding (9I+3U) 1 Circuit Breaker
3 winding (24 AI) 1 Circuit Breaker
3 winding (24 AI) 2 Circuit Breakers/W
Casing 1/2 19"
3/4 19"
1/1 19"
HMI Text only
Large graphic display 15 object /page
Analog inputs 6 Analog inputs
12 Analog inputs
24 Analog inputs
Input/output modules BIM 16 inputs basic 1 1 1 2 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

BOM 24 output relays basic 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

See other table optional


Buyers Guide Pre-configured 1MRK 505172-BEN 1MRK 511176-BEN 1MRK 505164-BEN 1MRK 505164-BEN 1MRK 504080-BEN

Buyers Guide Open configurations 1MRK 511154-BEN 1MRK 505137-BEN 1MRK 505137-BEN 1MRK 504953-BEN

Customized Available Q1 2006 Earlier on request


Preconfigured Available Q1 2006 Earlier on request
Preconfigured Available Q2 2006 Earlier on request

11
Main
protection functions

The IED 670 Application Function Library includes the different differential protection functions with parallel
advanced and well proven protection algorithms from the distance protection functions in RET or RED. In addition
500-series. The further improved A/D conversion, CPU back-up phase-and-earth overcurrent protection can be
capacity and increased number of analog inputs has included giving an efficient back-up protection for
resulted in even higher speed, accuracy and reliability. In communication or voltage circuit failure.
addition the increased functionality allows the integration
of parallel algorithms with advanced logic and
communication. It is even possible to integrate several Select the perfect protection

= Basic = Basic, 1-of = Optional 3 = Maximum no. of options

IEC ANSI Application Arrangement Sub- Busbar Bay Line Line Transformer
arrangement Differential Distance

REC 670-C30
REC 670-B30

RED 670-B31
RED 670-B32
REB 670-B20
REB 670-B21
REB 670-B31

REC 670-A10
REC 670-A20
REC 670-A30

RED 670-A31
RED 670-A32
REB 670-A20
REB 670-A31

RET 670-B30
RET 670-B40
REL 670-B31
REL 670-B32

RET 670-A10
RET 670-A11
RET 670-A20
RET 670-A30
RET 670-A31
RET 670-A40
REL 670-A10
REL 670-A31
REL 670-A32
REC 670

RED 670

RET 670
REL 670
Main Protection
Function

B4 87B Bus differential 4 bays, 2 zones 3 phase


PDIF protection
B8 87B Bus differential 8 bays, 2 zones 3 phase
PDIF protection
B12 87B Bus differential 12 bays, 2 zones 1 phase
PDIF protection
B24 87B Bus differential 24 bays, 2 zones 1 phase
PDIF protection
B12 87B Bus differential 12 bays, 2 zones 3 phase
PDIF protection Summation
B24 87B Bus differential 24 bays, 2 zones 3 phase
PDIF protection Summation
L3C 87L Line differential 3x3 CT inputs 2- 3 line ends
PDIF protection
L3C 87L Line differential 3x3 CT inputs Transformer in
PDIF protection zone
L6C 87L Line differential 6x3 CT inputs 3- 5 line ends
PDIF protection
L6C 87L Line differential 6x3 CT inputs Transformer in
PDIF protection zone
T2W 87T Transformer 2 winding 1 set
2
PDIF differential protection
T3W 87T Transformer 3 winding 1 set
2
PDIF differential protection
REF 87N Low impedance Earth fault 2 sets
3
PDIF differential protection
HZ 87 High impedance Single phase 3 sets
6
PDIF differential protection
ZMQ 21 Distance protection Full scheme 5 Phase-phase
PDIS zones zones and phase-earth
ZMQ 21 Distance protection Full scheme 4 Phase-phase
PDIS zones zones and phase-earth
ZMQ 21 Distance protection Full scheme 3 Phase-phase
PDIS zones zones and phase-earth
FDPS 21 Phase selection with
PDIS load enchroachment
ZM 78 Power swing
RPSB detection
Z Automatic switch
PSOF onto fault

12
Back-up
protection functions

A number of current and voltage based back-up functions Adaptive breaker failure protection for one, two or six
can be integrated. This includes one (or several) four step breakers can be added depending on IED. Several
directional earth fault protection schemes with a over/under voltage and over/under frequency functions
permissive overreaching transfer trip (POTT) for can be used for load shedding and other functions. Over
directional comparison of high resistance earth faults. In a excitation and rate-of-change frequency protection makes
similar way it is possible to integrate one (or several) four IED 670 the complete solution provider for ALL your
step directional or un-directional over current protection. applications. Finally a unique Customizer consisting of a
Furthermore high speed phase and earth over current flexible general current and voltage protection for
protection can be added for close-in heavy current faults. symmetrical components be tailored for special functions
and specific applications.

= Basic = Basic, 1-of = Optional 3 = Maximum no. of options

IEC ANSI Application Arrange- Sub- Busbar Bay Line Line Transformer
ment arrangement Differential Distance
REC 670-C30
REC 670-B30

RED 670-B31
RED 670-B32
REB 670-B20
REB 670-B21
REB 670-B31

REC 670-A10
REC 670-A20
REC 670-A30

RED 670-A31
RED 670-A32
REB 670-A20
REB 670-A31

RET 670-B30
RET 670-B40
REL 670-B31
REL 670-B32

RET 670-A10
RET 670-A11
RET 670-A20
RET 670-A30
RET 670-A31
RET 670-A40
REL 670-A10
REL 670-A31
REL 670-A32
REC 670

RED 670

RET 670
REL 670

Main Protection
Function

PH 50 Overcurrent protection Undir/High Instant/3 phase


3 3
PIOC speed
PH4 51/67 Overcurrent protection Dir/Undir. 4-step/3 phase
6 3
POCM
PH4 51/67 Overcurrent protection Dir/Undir. 4-step/1 phase
POCM
EF 50N Overcurrent protection Undir/High Instant/residual
3 3
PIOC speed
EF4 51N/67N Overcurrent protection Dir/Undir. 4-step/residual
PEFM 6 3

L 26 Thermal overload
PTTR protection 2 2 2 3

CC 50BF Breaker failure protection 3 phase


6 2 2 6
RBRF
CC 50BF Breaker failure protection 1 phase
RBRF
STB 50STB Stub protection
2
PTOC
CC 52PD Pole discordance
3 2 2 2
RPLD protection
POVM 27 Two step undervoltage
2 2 2 3
protection
POVM 59 Two step overvoltage
protection 2 2 2 3

POVM 59N Two step residual


2 2 2 3
overvoltage protection
PVPH 24 Overexcitation protection 2
PTUF 81 Underfrequency protection 6 2 2 6

PTOF 81 overfrequency protection 6 2 2 6

PFRC 81 Rate-of-change frequency


6 2 2 6
protection
PGPF General current and
9 4 4 12
voltage protection

13
Designed to
communicate
Control & Monitoring functions
The complete IED 670 family has an outstanding
functionality for monitoring, measurement, event and
disturbance recording for up to 30+10 externaly and
internaly derived analog channels per IED. The same IED
can be connected to the protection and measuring cores
of the instrument transformers at the same time.

REC 670 is available as bay control for different


switchgear arrangements including breaker-and-a-half
stations. Control functionality is however available as
option for the complete IED 670 range except REB 670.
This allows either a distributed approach with a dedicated
REC 670 controller for one or several bays or an
integrated approach with combined control and back-up
protection up to a fully integrated protection and control
IED.
REC 670 for six bays with phase-and-earth protection
( 4-step), auto-reclosing, bay control and breaker failure.

= Basic = Basic, 1-of = Optional 3 = Maximum no. of options

Application Arrangement Busbar Bay Line Line Transformer


Differential Distance
REC 670-C30
REC 670-B30

RED 670-B31
RED 670-B32
REB 670-B20
REB 670-B21
REB 670-B31

REC 670-A10
REC 670-A20
REC 670-A30

RED 670-A31
RED 670-A32
REB 670-A20
REB 670-A31

RET 670-B30
RET 670-B40
REL 670-B31
REL 670-B32

RET 670-A10
RET 670-A11
RET 670-A20
RET 670-A30
RET 670-A31
RET 670-A40
REL 670-A10
REL 670-A31
REL 670-A32
REC 670

RED 670

RET 670
REL 670

Control & Supervision

Current circuit supervision 5 2 2 5

Fuse failure supervision 4 3 3 4

Synchrocheck and energizing check 6 2 2 6

Autorecloser 2 6 2 2

Apparatus control for single bay max. 8 apparatuses


Apparatus control for single bay max 15 apparatuses
Apparatus control for up to 6 bays max 30 apparatuses
Logic rotating switch for function
selection and LMHI presentation
Tripping logic
Trip matrix logic
Configurable logic blocks
Fixed signal function blocks
Event counter
Fault locator
Measurements
Event function
Disturbance report
Logic signal status report
Pulse counter logic

14
Communication functions
IED 670 is designed to communicate. This includes the The current differential function in RED 670 is utilizing the
necessary remote communication for the protection sampled current values from up to four remote ends in addition
schemes and the bay/station level communication for to one/two local ends in order to perform the 6x3 current
control and interlocking as well as remote communication differential evaluation. This means that all analog sampled
to SMS and/or SCADA. IED 670 is designed for IEC current values are continuous communicated to all line
61850 open communication and TCP/IP but can also ends together with the possible trip signals in each phase.
support SPA, LON and IEC 80870-5-103 in up to 4 Since the disturbance recorder in each IED 670 can handle 40
parallel channels as shown in the below table. analog channels and 96 digital channels it is possible to analyze
information from all line ends in one IED. You can create your
Communication is essential for the overall reliability. And own disturbance report the way you want and send your file as
communication signals can be distorted when exposed to an e-mail.
the severe disturbance environment in a substation. This is
why disturbance free OPTICAL communication is In addition a binary signal transfer to each remote end of
built into the design of IED 670 minimizing the risk for eight signals is possible. E.g for transfer trip from a breaker
communication errors. failure protection or other binary signals. If no analog values
are needed it is possible to transfer 6x32 binary signals to the the
IED 670 is verified for IEC 61850. But in addition IED remote ends.
670 together with other ABB and non-ABB IEDs has
The right information
been comprehensively tested in our unique ABB IEC
to the right person at the right time.
61850 System Verification Center.
= Basic = Basic, 1-of = Optional 3 = Number of modules/Maximum no. of options

Application Arrangement Sub- Busbar Bay Line Line Transformer


arrangement Differential Distance
REC 670-C30
REC 670-B30

RED 670-B31
RED 670-B32
REB 670-B20
REB 670-B21
REB 670-B31

REC 670-A10
REC 670-A20
REC 670-A30

RED 670-A31
RED 670-A32
REB 670-A20
REB 670-A31

RET 670-B30
RET 670-B40
REL 670-B31
REL 670-B32

RET 670-A10
RET 670-A11
RET 670-A20
RET 670-A30
RET 670-A31
RET 670-A40
REL 670-A10
REL 670-A31
REL 670-A32
REC 670

RED 670

RET 670
REL 670

Control & Supervision

SPA communication protocol


LON communication protocol
IEC 60870-5-103 communication protocol
IEC 61850 generic communication I/O
functions, parameter setting
Horizontal communication via GOOSE for
interlocking
FTP access with password
Single command
Multiple command and transmit
SPA/IEC 60870-5-103 and LON (SLM) 2 channels plastic, plastic/
communication ports glass or glass
IEC 61850-8-1 (OEM) communication 1 channel or glass
ports 2 channels
Binary signal transfer
Analog data transfer
Scheme communication logic Distance
Scheme communication logic DEF
Line data communcation module C37.94 3/65/130 km basic 1 1 2 1 2

optional 2 2 4 4 4 2 1 1 1 1 1 3 3 2 3 2 2 1 1 1 1 1 2 1 1 1 1 1 1 1 1

15
Easy to handle
Built in HMI Direct interaction without any tools
The local HMI of the IEDs gives you a quick yet detailed overview of the process
with setting and control capabilities in any situation. The user-friendly navigation
structure of the HMI allows you to access desired function or important data, such
as event and disturbance information as well as settings fast and easy.

With the large HMI you can control and visualize locally up to 30 primary
apparatuses. Measured service values are displayed and fault values from the two
latest disturbances will be shown. You can easily draw the single line diagram to be
displayed on the the HMI corresponding to your switchgear arrangement by using
the Graphical Display Editor of the PCM600 tool. The symbols needed are
available in a library according to both IEC and ANSI standards. Up to six
different pages for up to six switchgear bays are available. This mean that the built
in HMI can replace the need for a substation computer.
PCM 600 Engineering Pro
PCM 600 IED Manager

PCM 600 Engineering


HMI (Large display)
HMI (Text display)

1MRK003395-CA
1MRK003395-BA
1MRK003395-AA

Function
Read on-line measuring values
Read stored events (1000) IED 670 includes a unique feature
Read stored fault locator values to simplify the setting procedure
Read stored disturbance recorder values and to facilitate the commissioning.
Upload stored disturbance recorder values (Manual) The pre-configured variants of
Upload stored disturbance recorder values (Automatic) IED 670 includes de-fault settings.
Disturbance report generation (Automatic) The shown settings is filtered out
Read setting groups parameters (6)
depending on selected options. In
Change setting groups
addition the setting is divided in two
Write setting group parameters
user groups. One for normal users
Change lock (Block via BI)
Test mode selection (Block/Activate functions)
which only includes typical
IED diagnostics (Internal events)
application settings and for expert
Object status (closed, open, value) users which includes all settings. It is
Object control (close, open) furthermore possible to store six
Authorization (Password for Local/Remote) different setting groups.
Bay graphical display
Multi page (6) bay graphical display
Multi page (6) bay graphical display editor
Signal matrix tool (Link I/O)
IEC 61850-8 communication configuration (CCT)
IEC 61131-3 graphical configuration

16
Protection and Control IED Manager
PCM 600 the optimum user tool
The easy-to-use software tool, Protection and Control analysis of complex disturbances analysis instead of data
IED Manager PCM 600, provides all required manipulation. Up to 40 analog channels and 96 digital can
functionality throughout the life cycle of the IED670 be included per IED. As an example this makes it possible
as well as selected older products. This includes parameter to analyze all line ends simultaneously from a multi-
setting, configuration, on-line monitoring and event terminal application in each location of RED 670.
viewing during engineering, commissioning, operation,
testing and maintenance. It also provides you with an PCM 600 fully supports the new IEC 61850 standard in
efficient tool for disturbance evaluation and function terms of GOOSE messaging, engineering and information
analysis after primary system faults. management. PCM 600 includes both the CAP IEC 61131-
3 and the CCT IEC 61850-8 functionality which means a
With PCM 600 you can easily create application complete IED Capability Description (ICD) and
specific configurations by combining function blocks, Substation Configuration Description (SCD) will be
logical elements, timers, etc. in the IED. The new tool also generated.
includes graphical display editor for creating single line
diagrams for the local HMI. The built in Signal Matrix PCM 600 can be run from a standard PC connected to
Tool supports efficient configuration of the analog and the front or via fast and reliable TCP/IP communication
digital I/O signals for fast adaptation to your primary on LAN or WAN, which enables quick up- and
circuits. downloading of settings and configurations to the IEDs,
and upload of dozens of disturbance files from the IEDs in
The advanced PCM 600 tool paves the way for a new era just a few seconds. PCM 600 can also be used together with
of disturbance handling. Through automatic detection CAP540 for modem or PC to PC connections for remote
and reporting of disturbances it allows fast and efficient communication to IED 670 and older products via SPA.

17
Transmission
Lines & Cables IEDs
REL 670 Line differential protection Remote communication based on the IEEE C37.94
REL 670 is used for the protection, control and standard can be redundant when required for important
monitoring of overhead lines and cables in transmission installations. Route switching and short GPS failure will be
and sub-transmission networks. Its excellent phase compensated. Charging current compensation allows high
selection and load enchroachment makes it ideal for sensitivity also on long overhead lines and cables. A four step
heavily loaded and/or parallel lines where the requirement overcurrent or full scheme distance protection is optional in
for tripping is one, two-, and/or three pole. Auto- RED 670 as back-up for remote end or communication
reclosing, synchrocheck , breaker failure protection and failures. The following 64 kbit communication alternatives
bay control can be included for 1 or 2 breakers. The IED is are available:
also suitable as back-up protection of power transformers,
reactors etc. 1. Telecommunication systems with specified route
switching using echo timing. Typical distances < 200 km
(< 300 km state of the art)
The well proven full scheme distance protection with 2. Telecommunication systems with unspecified route
quadrilateral characteristics provides the main protection switching using GPS satellite timing (Echo timing as fall
function in REL 670. The five zones have fully back system) Typical distances < 200 km
independent measuring and setting for phase-to-earth as (< 300 km state of the art)
well phase-to-phase loops which allows optimized 3. Back- to back communication, typical distances < 2 or 3 km
protection for all types of lines and applications. Speed multimode, < 80 or 150 km single mode
and accuracy has been significantly improved compared (According to the optical budget)
to REL 316 and REL 5xx series. Additional high speed
instantaneous phase and earth overcurrent can be used for Redundant Line Protection
close in faults and a separate four step phase and earth The possibility to include redundant algorithms in one IED
over current protection can be used as back up. Complete (e.g. differential and distance or distance and directional
scheme communication logic is available both for distance phase and earth over current) will improve the performance
and directional earth fault as well as transfer trip. both for single (with remote back-up) and duplicated
protection arrangement (Local back-up). Still the
RED 670 Line differential protection combination REL 670 and RED 670 will give an optimum
RED 670 is used for the protection, control and redundant scheme. If totally separate hardware is required
monitoring of overhead lines and cables in in for the two redundant schemes REL 670 or RED 670 can be
transmission and sub-transmission networks. It is suitable combined with REL521 or REL531. Finally the IED 670
for the protection of heavily loaded lines and multi- concept makes it possible to include a back-up line distance
terminal lines where the requirement for tripping is one-, protection in RET 670. By utilization of the 24 analog inputs
two-, and/or three pole. RED 670 is also suitable for it is possible to include the protection for two objects in one
protection of cable feeders to generator block IED but with separate test switches. This give the possibility
transformers. The phase segregated current differential to reduce the number of IEDs but with remaining
protection provides an excellent sensitivity for high functionality and redundancy.
resistive faults and gives a secure phase selection. The
availability of six stabilized current inputs allows use on
multi-breaker arrangements in three terminal applications
or up to five line ends applications with single breaker
arrangements and one double breaker.

18
For all line protection
applications
45 x
40 Load compensation
35
Forward
30 operation

25

20
Load
15 enchroachment
x ohm/ph

10

5
R
0
* Reverse
-5 operation
-10

-15

-20

-25 Adaptive mesurement for heavy load:


-30 - Load compensation of Zone 1
-40 -20 0 20 40 60 80
- Load enchroachment compensation
Up to five zones with separate setting for R, X and for zones and phase selection
direction allows optimum setting from short lines - Power swing detection
to very long lines.

+ 2, 3, 4 or 5 line ends
+ Segregated phase differential protection
+ Full-scheme distance protection available to cater for communication failure
and/or back-up protection
+ Single or redundant channels
+ Route switching
+ Single, Breaker-and-a-half or two breaker
+ With or without transformer
+ Distance protection back-up
+ Charging current compensation included
+ GPS and / or Echo synchronization
+ Protection, Monitoring & Control

+ With a transformer in the zone:


+ Negative sequence fault discriminator
+ 2nd and 5th harmonic restrain as in normal transformer differential protection

+ RED 670 with 24 analogue inputs


+ Enables internal summation
+ Enables control/breaker function
+ Parallel line application functions

+ Communication interfaces
+ C37.94 multimode, optical budget; 9 dB for 50/125 mm, 13 dB for 62,5/125
mm
+ Back-to back
+ C37.94 directly to PCM/MUX
+ G703 64 kbit; transceiver Fibersystem type 21-216
+ G 703 E1 2 Mbit; transceiver Fibersystem type 21 - 219
+ C37.94 single mode (9/125 mm), optical budget ; 26 dB (1310 nm), 30 dB
(1550 nm)
+ Back-to back
+ Galvanic communication interfaces with X21/X27, V36/V11, RS530/RS 422
+ Maximum distance 100 m

19
Transformer and
substations
RET 670 Transformer IED
RET 670 provides fast and selective protection, negative and zero sequence over current functions, which
monitoring and control for two- and three-winding can optionally be made directional and/or voltage
transformers, autotransformers, generator-transformer controlled, provide further alternative backup protection.
units, phase shifting transformers, special railway Thermal overload, volts per hertz, over/under voltage and
transformers and shunt reactors. RET 670 is designed to over/under frequency protection functions are also
operate correctly over a wide frequency range in order to available.
accommodate power system frequency variations during
disturbances and generator start-up and shut-down. RET 670 Substation IED
RET 670 can include both protection, monitoring and
A very fast differential protection function, with control for several objects. This includes transformer
automatic CT ratio matching and vector group differential protection, high impedance differential
compensation, makes this IED the ideal solution even for protection, distance protection and up to 3 pcs phase &
the most demanding applications. RET 670 has very low earth overcurrent protection. Control with 6 separate HMI
requirements on the main CTs, no interposing CTs are pages and 6 breaker failure protection can furthermore be
required. It is suitable for differential applications with included. REC 670 can handle up to 6 breakers with control,
multi-breaker arrangements due to up to six restraint CT breaker failure protection and phase & earth overcurrent
inputs which gives increased through fault stability. The protection. This means that smaller substations can be
differential protection function is provided with 2nd designed with one IED per breaker but with full n-1
harmonic and wave-block restraint features to avoid redundancy meaning that one IED may fail and the station is
tripping for magnetizing inrush, and 5th harmonic still fully protected by the other IEDs.
restraint to avoid tripping for over excitation.
REB 500 Distributed Busbar Protection
The differential function offers a high sensitivity for low- If a distributed busbar protection is preferred ABB can
level internal faults. RET 670's unique and innovative offer the well proven REB 500 together with the IED 670
sensitive differential protection feature, based on well- family. REB 500 has been further developed to support IEC
known theory of symmetrical components provide best 61850 and can be delivered with two Ethernet ports, one for
possible coverage for winding internal turn-to-turn faults. 61850 to a Substation Automation System and one TCP/IP
A low impedance restricted earth-fault protection port for connection to LAN/WAN for remote comm-
function is available as complimentary sensitive and fast unication. As an alternative REB 500 can support LON and
main protection at earth faults. This function includes a IEC 870-5-103.
directional zero-sequence current criterion for additional
security. Alternatively a high impedance differential
function is available. It can be used as restricted earth fault
or, as three functions are included, also as differential
protection on autotransformers, as differential protection
for a tertiary connected reactor, as T-differential
protection for the transformer feeder in a mesh-corner or
ring arrangement, as tertiary bus protection etc.

Distance protection functionality for phase to phase


and/or phase to earth faults is available as back-up
protection for faults within the transformer and in the
connected power system. Versatile phase, earth, positive,

20
For all
applications
G

+ RET 670 provides restrained, un restrained, high impedance and restricted earth fault differential
protection. This gives both high speed (1/2 cycle) , high sensitivity (earth faults) and full stability
and selectivity. Other functions such as distance, over current, over load, over excitation,
over/under voltage and over/under frequency as well as control can be included.
Generator and
transformer block + RET 670 provides fast and selective protection, monitoring and control for two- and three-
winding transformer, autotransformers, generator-transformer units, railway transformers,
capacitor banks and shunt reactors.
+ RET 670 as a single IED can protect both the transformer and the MV switchgear protection in a
H-station.
+ RET 670 has a wide application area in power stations for generator and block transformer. A
number of different functions are available within the same IED.
Substation with + RET 670 for protection of 2 and 3 winding transformers with up to 6 restraint inputs with optional
autotransformer
and reactor bank
control functionality. Two bias differential protection functions of low and several high impedance
protection functions can be included in one single IED.
+ RET 670 has accurate voltage protection with excellent returning ratio for shunt reactor
applications.
+ RET 670 has voltage control for single and up to eight parallel transformers, line drop
compensation and load shedding based on voltage reduction are included.
+ RET 670 can together with other products from the 600 series be combined with existing 500
Substation of
product range for Transmission and Distribution securing future proof migration for Substation
H-type
Automation applications.

Examples of two winding and three winding power Example of generator/transformer/auxilary


transformers with up to 6 breakers and three phase transformer block which can be protected
restraint inputs which can be protected by RET 670. by RET 670.

Small substation A (N-1 Small substation B (N-1


redundancy with 3 IED) redundancy with 3 IED)
REL 670 is used as main line One RET 670 is used as main
protection including autoreclosing + protection for one transformer,
syncrocheck as well as back up O/C busbar section and one line. One
and EF for the transformer.One REC 670 is used as O/C and EF
RET 670 includes two differential back up protection for two lines
protection functions for transformer (with AR and SC) and two
and bus as well as back up O/C and transformers as well as BFR and bay
EF for the two lines.One RET 670 control for three breakers.
includes BFR and bay control for for
the three breakers.

21
Bus and
breakers
REB 670 Bus and breaker failure protection
REB 670 is based on the well proven ultra high speed Advanced Zone Selection logic accompanied by optionally
algorithm from RADSS, REB 100 and RED 521. This available end-fault and/or circuit breaker failure protections
ensures both speed, sensitivity and reliability. REB 670 is ensure minimum possible tripping time and selectivity for
designed for the selective, reliable and fast differential faults within the blind spot or the end zone between main
protection of busbars, T-connections, meshed corners, CT and affiliated circuit breaker. Therefore REB 670 offers
generators and autotransformers. REB 670 can be used best possible coverage for such faults in feeder and bus-
for different switchgear layouts, including single and section/bus-coupler bays.
double busbar with or without transfer bus, double circuit
breaker or one-and-half circuit breaker stations. The IED It is normal practice to have just one set of busbar
can detect all types of internal phase-to-phase and phase- protection relays per busbar. Nevertheless some utilities do
to-earth faults in solidly earthed or low impedance earthed apply two independent busbar protection relays per zone of
power systems, as well as all internal multi-phase faults in protection. REB 670 fits both solutions. A simplified bus
isolated or high-impedance earthed power systems. differential protection for multi-phase faults and earth faults
can be obtained by using a single, one-phase REB 670
REB 670 has very low requirements on the main current terminal with external auxiliary summation current
transformers and no interposing current transformers are transformers.
necessary. For all applications, it is possible to include and
mix main CTs with 1A and 5A rated secondary current Co-ordination with other objects
within the same protection zone. Typically, CTs with up to RET 670 includes both low impedance and high impedance
10:1 ratio difference can be used within the same differential functions which can be applied to protect
differential protection zone. Adjustment for different transformers, reactors, generators, T applications and H-
main CT ratios is achieved numerically by a parameter stations. For certain applications this means that either REB
setting. 670 or RET 670 can be used. REB 670 can furthermore
include four step overcurrent protections and breaker
The numerical, low-impedance differential protection failure protections for up to eight bays. This means that REB
function is designed for fast and selective protection for 670 can be used as back up protection for outgoing feeders.
faults within protected zone. All connected CT inputs are Finally the breaker failure function (BFR) can be integrated
provided with a restraint feature. The fast tripping time of in REB, RET, RED, REL or REC according to customer
the low-impedance differential protection function is preference.
especially advantages for power system networks with
high fault levels or where fast fault clearance is required
for power system stability.

The advanced open CT detection algorithm detects


instantly the open CT secondary circuits and prevents
differential protection operation without a need of an
additional check zone. Integrated overall check zone
feature, independent from any disconnector position, is
however available. It can be used in double busbar stations
to secure stability of the busbar differential protection in
case of entirely wrong status indication of busbar
disconnector in any of the feeder bays.

22
For all
applications

ZA ZA ZB

Single busbar protection up to 4/8 H type station with bus-section


bays (3-phase) or up to 12/24 bays CB or sectionalizing
(3 pcs 1-phase IEDs) with O/C and disconnector
BFR Generator Motor Capacitor Reactor

ZA ZA

ZB ZB

1 Breaker Stations up to 4 diameters (3-phase) 1 Breaker Stations up to 8 diameters


or up to 12 diameters (3 pcs 1-phase IEDs) (3-phase) or up to 24 diameters (6 pcs 1-phase IEDs)

ZA

Double Busbars with


ZB
bus coupler CB and
Transfer Bus up to
Transfer Bay 22/23 feeder bays

Transfer Bus

Main 1 Main 2

Reserve 1 Reserve 2

Four Zone Double Bus with two bus-coupler CBs and two bus-section CBs and up to 20/21 feeder bays on each side

23
Future proof
concept
REC 670 Bay control
REC 670 is used for the control, protection and A number of protection
monitoring of different types of bays in power networks. functions are available for
REC 670 is especially suitable for applications in flexibility in use for
distributed control systems with high demands on different station types and
reliability. REC 670 can be calibrated to typical 0.25 % busbar arrangements. This
measuring accuracy and can be connected to both includes phase-and-earth
measuring cores and protection cores. REC 670 is fully overcurrent protection, breaker failure protection and auto-
designed for IEC 61850 but also supports LON. reclosing for a complete breaker and-a-half diameter or for
The control is performed from remote (SCADA/Station) up to six separate feeders.
through the communication bus or locally from a
graphical HMI on the front of the IED showing the single Integrated Protection and Control
line diagram. Up to six HMI pages for different bays can IED 670 is designed and mapped for the open IEC 61850
be used. Different control configurations can be standard as a hard ware independent concept. The IED 670
implemented e.g. one control IED can be used per bay or family therefore allows the distribution of protection
one IED can be common for several bays. Interlocking functionality to REC 670 and of control functionality to
modules are available for all common types of switchgear REL, RED and RET. This gives a unique flexibility to design
arrangements. The control is based on the select-before optimized solutions. But it also give the possibility to re-
execute principle to give highest possible reliability. A configure, update and even move functionality between
synchrocheck function is available to interlock breaker different IEDs at a later stage when the substation is
closing. extended or modified.

Migration into the future


= Basic = Available as option with process bus
IED 670 is designed for IEC 61850 and is
IEC 60870-5-101

IEC 60870-5-103

IEC 60870-5-104

prepared for the full functionality from


implementation

process bus to stations bus. IED 670 provides


IEC 61850

free allocation of functions to any IED. This


DNP 3.0
IED 670

offers a unique opportunity to invest in an


LON

Information management open and future proof solution. Instead of


Basic real time values
raw data flow of Megabites IEC 61850 offers
Protection
an Integrated Information Management. IEC
Control
61850 has besides interoperability and self
Real time sampled values
description a much higher functionality
Real time bay-to-bay commands
Fixed functionality
compared conventional SCADA protocols. It
Free allocation of functions to any IED
can therefore be foreseen that IEC 61850 is
Data modelling the first step to a seamless architecture from
Self description the process bus all the way up to the Network
Vendor independent data interoperability Control Center. Finally IED 670 is prepared
Vendor independent application interoperability for the next step in the evolution with the
Parameter group setting possibility with additional ports for IEC
Parameter setting 61850-9-2 process bus. That is why IED 670 is
Disturbance recorder upploading fully designed for IEC 61850 and NOT an
IEC open standard
after thought with only protocol conversion.
Future proof

24
For all substation automation
applications
+ Apparatus control for up to 6 bays and 30 apparatuses Single circuit breaker, Double circuit
several bays breaker
+ Control and protection of a full breaker-and-a-half diameter with three breakers

+ Pre-configured, type tested and ready to use interlocking modules for different
1U 1U

1U 1U

switchgear arrangements 3l
REC REC 3l

670 670
+ Counter for number of switching operations
3l

3U 3U

+ Automatic control sequences

+ Autoreclosing and synchrocheck

+ Breaker failure protection and complementary protection functions 1 circuit breaker

+ Data acquisition, e.g. status of the apparatuses and measured values


1U
3l
+ Event handling and powerful disturbance recording 3U

+ U, I, P, Q, S, f, and cos measurement REC


670
3l

+ Class 1.0 or 0.5 accuracy 3U

3l

+ Input for mA measuring


1U

+ Pulse counting for energy metering

New Substations Retrofit and extension of an old substations


IED 670 together with MicroSCADA Pro and/or gateway IED 670 can be supplied with SPA, LON and IEC 80870-5-
for IEC 61850 is the natural choice. If LAN or WAN is 103 for integration into an existing installation with for
available in the station it is also possible to connect the example MicroSCADA 8.4.4. Or 4.4.5. An other alternative
PCM SMS functionality directly to the office. ABB can is to upgrade to MicroSCADA Pro which handles both LON
supply the complete Substation Automation System or and IEC 61850. Selected 500 series products are available for
supply products separately for integration into a user built IEC 61850 via an optional converter.
or third party substation.

ABB MicroSCADA Pro


Third party HSI with optional gateway ABB Gateway or RTU ABB SMS/PCM Each IED has 2 + 2 Ethernet
ports for IEC 61850 station and
process bus or TCP/IP

Optional LON, SPA,


IEC 60870-5-103, (DNP 3.0)*

Selected REx5xx IEDs is


IEC 61850-8-1 available with IEC 61850 adapter
on request

LON IEC 61850 or TCP/IP Detailed ABB IEC 61850


configuration depending on
application & system verification

*) Available end 2006


SPA or IEC 60870-5-103

25
Migration to
670
Line Trf Bay Bus

REL 316 REL 670

REL 511,512,521,531 REL 670

REL 551, 561 RED 670

RET 316 RET 670

RET 521 RET 670

REC 316 REC 670

REC 561/580/REB551 REC 670

RED 521 REB 670

Any missing product? Customized

Future proof migration Pre-configured & customized IED 670


The first option is to chose a pre-configured variant
specified in the Buyers Guide. If an identical functionality
The well-known Moors law which predicts a fast and I/O to a specified 316 or 500 series IED variant is
development of micro processor capacity is still valid. required it is possible to create a customized IED from the
The technical and economical life for a CPU or a PC as open options of REL, RET, RED and REC. Since IED 670
well as the available communication speed is in the range has a higher functionality compared to other vendor
of 5 years while the algorithms and I/O has a much longer products on the market it is naturally also possible to
life. So how can a utility then standardize without the configure a one-to-one replacement of third party products.
costly and time consuming procedure to verify, engineer
and maintain different product generations? When to use 670/316/500 series
Since IED 670 can provide a number of different protection
The CPU in IED 670 has a higher functionality compared algorithms and also distribute functions to different IEDs it
to existing equivalent IEDs from the 316 or 500 series for is possible to optimize both reliability and cost. IED 670
transmission applications. Since 670 is based on the same therefore can provide both main and back-up protection but
well proven algorithms and the same modular I/O as the with different algorithms. If a completely different
500-series, IED 670 we can therefore provide a direct hardware and software design is required between main and
migration for most applications. The same instrument back-up protection we can still offer our present ABB IED
transformers, the same I/O interface, the same range. Selected products are available with IEC 61850
algorithms and the same protection schemes can be used converter.
as before. But at the same time IED 670 gives a state-of- Specific applications such as distributed busbar protection
the-art CPU and communication. This is the first step in a (REB 500), High Speed Bus Transfer (REC 316), railway
future proof migration since the hard ware independent protection (REO 517) and Phasor Measurement Units (RES
functional library of IED 670 together with IEC 61850 521) as well as generator protection (REG 216 and REG
will allow future step-by-step modifications, up-grades 316) are not covered in this release of IED 670.
and extensions.
26
Support and
Service
Application and new Solutions
The IED 670 future proof concept offers many new provides easy and fast commissioning. The advanced self
possibilities to design more efficient protection and supervision, disturbance recording and communication
control systems. As an example we use a breaker-and-a- minimize the need for secondary injection testing. Still each
half substation. This requires line, transformer, bus, T- IED 670 can be equipped for the well proven Combitest.
connection and breaker failure protection as well as auto- The test switch RTXP 24 is used to make it possible to test a
reclosing, synchro check, disturbance recorder and bay IED in a fail-safe way. It is even possible to include two
control. With a conventional box approach we need up separate test switches for a multifunction IED 670.
to fifteen boxes. With a functional approach we can Inserting the test-plug handle RTXH 24 into the test switch
achieve the same performance with only five IED 670. automatically makes all preparations for a secure secondary
Other examples is protection and control of up to six bays injection test in proper sequence. One example of test set is
with one IED and integrated solutions for a complete H- OMICRON which can communicate with IED 670 over
stations. IEC 61850 GOOSE messages.

Our experienced application engineers are available to Training and Support


discuss suitable migration strategies and propose efficient Please consult www.abb.com/substationautomation
solutions. With our advanced RTDS simulator and EMTP where you can find our training program as well as your
models as well as COMTRADE recordings we can local ABB contact. You can from this web page also access
together with our customers evaluate and verify different and down load technical information and access relevant
applications. update and links for IEC 61850. With the introduction of
IED 670 we have expanded our training to include
Commissioning and Maintenance configuration and integration into IEC 61850 applications
The pre-configured and pre-set versions of IED 670 utilizing our powerful PCM600 tool and MicroSCADA Pro.

Box approach Functional approach

CB1
REB REB + REC REL REB 670

REL REL 670

CB2
REL 670
TFR REB + REC
RET

RET 670

REB REB + REC RET


CB3
REL Main and back-up line protection RET 670
RET Main and back-up transformer protection
RET T- protection (1 or 2)
REB Busbar protection (2)
REB Breaker failure protection (3)
REC Bay control (3)
TFR Transient Fault Recorder (1)
27
This is ABB in Substation Automation
ABB supplies products, services and systems for the protection, monitoring and ONE state-of-the-art and modular IED
control of transmission & distribution networks and plants. Through more than ONE common Application Function Library
100 years of experience our relays have evolved to todays Intelligent Electronic ONE open IEC 61850 standard fully implemented
Device (IED) and Substation Automation System (SAS). Now we take the next ONE user friendly and interactive IED tool
step in this evolution to help utilities and industries to ensure an efficient and ONE informative MicroSCADA Pro
reliable power supply.
ONE powerful solution provider for ALL applications
Based on our well proven 316 and 500 series, ABB introduces the future proof
IED 670 series as the first Protection AND Control concept for transmission

byBrick
applications fully designed for IEC 61850 open standard with free allocation of
functions to any IED.

The IED670 ensures grid reliability through innovation,


experience and commitment Made in ABB.

670 Features Customer


CustomerBenefit
Benefit REL670
for subtransmission
A major leap in grid reliability: Reliable: and lines & cables
Buyer's Guide
Unique high performance & world class Ensures grid reliability through innovation,
1MRK 506 264-BEN
concept for ALL transmission applications experience and commitment, Made in ABB
in ONE IED

More than just a device: Efficient: RED670


Unique modular solution provider with Provides efficient substation automation for multi terminal
ONE extensive function library & ONE solutions for any high voltage application circuits
expandable I/O for protection and control Buyer's Guide
1MRK 505 164-BEN
Exactly what you need: Flexible:
Unique open system which can be You can tailor the protection & control of your
configured for integrated or distributed substation for the performance, redundancy RET670
protection & control architecture and cost you want to have. for transformers
Designed to communicate: Informative: & composite objects
Buyer's Guide
Unique information management of data, Improved availability and asset management
1MRK 504 080-BEN
disturbances & events with seamless through right information, in right time, to the
integration to TCP/IP, MicroSCADA Pro and right user, for right decisions
via ABB powerful gateway concept
REC670
Easy to handle: User friendly: for single and
Unique, simple and fast interaction via built Simple to select, set, operate and maintain multi bay control
in multi page HMI, fast PC Ethernet through preconfigured IEDs with built in multi Buyer's Guide
connection on the front & LAN TCP/IP with page HMI and advanced PCM tool 1MRK 511 176-BEN
different access for each user

Future proof concept: Forever young: REB670


A unique & OPEN concept with ONE Adds value to your investment for the total life
for bus and breakers
common IED, ONE common library, ONE cycle through simple re-configuration, Buyer's Guide
common MicroSCADA Pro and ONE evergreen upgrades and interoperability 1MRK 505 172-BEN
common tool designed for IEC 61850

Subject to change without notice. Please consult the Buyers Guide for detailed data.
Sample specification
The IED shall be of modular 19 design with up to 24 analog inputs, Two optical Ethernet interfaces for IEC 61850-8-1 and TCP/IP, one front
75 BO and 100 BI (simultaneously). The CPU capacity shall be port and one separate IEC 870-5-101 port shall be included. The IED
minimum 600 MHz and capable to execute multiple high speed shall be prepared for an additional port for IEC 61850-9-2. The IED shall
algorithms in parallel. The common application function library shall have a large HMI with capacity of 6 different single line diagrams and six
include all protection, control and monitoring functions required. The setting groups. Each IED shall have a build in disturbance recorder for up
IED shall be fully designed for IEC 61850 with free allocation of to 40 channels and 100 disturbances. A tool for configuration, setting,
functions to any IED and it shall be possible to modify and add event and disturbance uploading shall be included for local or remote
functionality from the library after installation. connection via TCP/IP.

ABB Power Technologies AB


Substation Automation Products
1MRK 500 078-SEN

SE-721 59 Vsters
Sweden
Telephone: +46 21 34 20 00
Telefax: +46 21 14 69 18
www.abb.com/substationautomation