Apparatus Maintenance and Power Management


for Energy Delivery

oil testing. Perform maintenance where needed,


rather than by a time based schedule.

Laboratory Spend Your Maintenance Dollars Wisely


Services Weve spent decades-perfecting techniques for
Overview testing solid and liquid insulating materials to
determine their condition and to detect
apparatus problems. In fact, Doble pioneered
methods that have since become industry
standards. With over 50 tests to choose from,
selecting the right ones can be confusing. Let
Materials Laboratory - Long Before Dobles Materials Laboratories help you develop
Electrical Apparatus Fail, Signs of a comprehensive and cost-effective oil testing
Trouble Appear! program for continued condition assessment
helping you to extend the life of your apparatus
and optimize operations over the long haul.
Maintenance of your generation, transmission or
distribution system requires routine analysis of
the insulating liquid to assess the condition of Doble Survey
your equipment. Oil degrades as a simple result
of oxidation and operation. Degradation of the Be in the know about available transformer oils
oil produces sludge and other by-products that and their quality. Doble has been a leader in the
can cause your equipment to fail. And if oil testing of new transformer oils for specification
degradation was not enough, there are a variety requirements for many decades. The Doble
of other conditions that will affect the Survey, produced annually, provides the test
performance of the oil and the apparatus. data and information you need to evaluate
Condensation, leaking gaskets, internal arcing, transformer oil refined worldwide. Tests include
to name a few, can drastically affect the those in Dobles own Transformer Oil Purchase
dielectric properties of the liquid as well as the Specification (TOPS) and ASTM D 3487 tests.
physical condition of the insulation. Testing can Know the facts about the oils you purchase.
detect developing apparatus problems such as,
local overheating at a loose connection or Apparatus owners can also join the Doble Oil
electrical discharge between turns so problems Committee for the same fee and learn what is
can be managed. With proper diagnostic going on in technical societies about transformer
testing, catastrophic failures can be avoided. oil and about Doble's own research on electrical
insulating oils and more.
What Type of Condition Assessment
Program Do YOU Have? High Voltage Laboratory

The analytical services performed by Dobles The Doble High Voltage Laboratory is equipped
Materials Laboratories provide you with the to test materials, parts, components, and
accurate information you need to intelligently apparatus for electrical characteristics. All tests
diagnose any existing and potentially can be performed as received or after thermal or
devastating problems in your liquid-filled voltage-endurance aging, and under a variety of
equipment. Compared with the cost of conditions. Examples of AC and DC tests and
premature or catastrophic failure, regularly measurements include dielectric constant,
scheduled oil testing is a cost effective and resistivity, power factor, dielectric breakdown
sound maintenance practice that is used to strength, high potential tests, ramp to failure,
extend the life of your transformers and circuit and partial discharge measurements.
breakers. Optimize your maintenance practices We test apparatus with different waveforms
using the knowledge obtained from diagnostic including lightning and switching impulses, power
frequency and D.C.
critical factor in estimating the real aging of the main
Doble can help with specifications for compliance transformer insulation.
testing, problem detection, endurance testing,
research on dielectric behavior, failure analysis, Diagnostic Testing
and partial discharge detection.
Dissolved Gas Analysis (ASTM D 3612) - The
Accelerated aging and thermal cycling tests on single most important test you can perform to head-off
cables and life endurance testing on stator potential transformer failures. Monitors gas
winding coils are also routinely performed. generation in transformers for advance notice of
developing faults. Its a good way to detect thermal
and electrical problems before failure occurs
Condition Assessment of Electrical
Apparatus - Some Typical Tests Furanic Compounds (ASTM D 5837) - Since the
paper is the most important dielectric component of
the transformer, having the ability to assess its
Oil Quality Testing condition is a must. When the cellulose breaks down,
furanic compounds are generated.
Color (ASTM D 1500) - Insulating liquids darken with
the presence of oxidation byproducts and foreign Metals-In-Oil - Metals such as copper, iron, zinc, and
materials. lead can be detected which can be indicators of
incipient-fault conditions, potential bearing wear from
Dielectric Breakdown Voltage (ASTM D877 / 1816) pumps or other wear metals from vibration of
- A low value indicates the presence of contaminants components.
such as water, dirt or other conducting particles in the
insulating liquid. Data
Interfacial Tension (ASTM D 971) - Monitors the All test data is stored in our custom-designed
progression of oxidation and detects contaminants relational database. Reports are created in
such as soaps, paints, varnishes and byproducts of
Windows Excel for easy electronic transmittal via e-
insulation aging.
mail. Reports can also be supplied in TOA format.
Let Doble help you to customize a Condition
Acidity / Neutralization Number (ASTM D 974) -
Assessment Program that meets the specific needs of
Monitors the progression of oxidation by detecting
your system
acidic compounds which accelerates deterioration of
the solid insulation that are precursors to sludge
formation. For more information, contact one of three
laboratory facilities:
Visual (ASTM D 1524) - Visual inspection identifies
foreign material in the insulating liquid, which may
lower its dielectric strength.

Power Factor @ 25 C (ASTM D 924) - High power


factor indicates the presence of contaminants like
carbon, metal, soaps and byproducts of oxidation. Doble Engineering Company
85 Walnut Street
Water Content (ASTM D 1533) - Reporting results in Watertown, MA 02472 USA
percent relative saturation for more effective Tel: +1-617-926-4900 Fax: +1-617-926-0528
interpretation of results. Moisture is one of the www.doble.com
primary causes of insulating liquid dielectric or email to labservices@doble.com
breakdown. High water content may be detrimental to
the transformer under a variety of conditions. Doble Engineering Company
5335 West Minnesota Street
Specific Gravity (ASTM D 1298) - Identifies different
types of insulating liquid, by determining the ratio of
Indianapolis, IN 46241 USA
the weights of equal volumes of oil and water at the Tel: +1-317-381-0901 Fax +1-317-381-0867
same temperatures.
Doble Engineering Company
6905 S. 228th Street
Paper Quality Testing Kent, WA 98032-1834 USA
Degree of Polymerization of Paper (ASTM D 4243)
Tel: +1-253-872-7946 Fax: +1-253-872-7947
This test provides a measure of the aging of paper,
which correlates with important physical properties
like resistance to tearing and bursting. This is a