PVSYST V5.

74 Srikanth Reddy &Sangu 11/01/16 Page 1/3

Grid-Connected System: Simulation parameters

Project : Grid-Connected Project at Pune


Geographical Site Pune Country India
Situation Latitude 18.5N Longitude 73.9E
Time defined as Legal Time Time zone UT+6 Altitude 560 m
Albedo 0.20
Meteo data : Pune , Synthetic Hourly data

Simulation variant : PYC CLUB


Simulation date 11/01/16 12h02

Simulation parameters
Collector Plane Orientation Tilt 18 Azimuth 0
Horizon Free Horizon
Near Shadings No Shadings

PV Array Characteristics
PV module Si-poly Model ZT 240S
Manufacturer Zytech
Number of PV modules In series 20 modules In parallel 10 strings
Total number of PV modules Nb. modules 200 Unit Nom. Power 300 Wp
Array global power Nominal (STC) 60.0 kWp At operating cond. 57.0 kWp (38C)
Array operating characteristics (50C) U mpp 714 V I m pp 80 A
Total area Module area 387 m Cell area 219 m

Inverter Model Sunny Tripower 20000 TLEE


Manufacturer SMA
Characteristics Operating Voltage 580-800 V Unit Nom. Power 20.0 kW AC
Inverter pack Number of Inverter 3 units Total Power 60.0 kW AC

PV Array loss factors


Thermal Loss factor Uc (const) 20.0 W/mK Uv (wind) 0.0 W/mK / m/s
=> Nominal Oper. Coll. Temp. (G=800 W/m, Tamb=20C, Wind=1 m/s.) NOCT 56 C
Wiring Ohmic Loss Global array res. 142 mOhm Loss Fraction 1.5 % at STC
Module Quality Loss Loss Fraction 2.5 %
Module Mismatch Losses Loss Fraction 2.0 % at MPP
Incidence effect, ASHRAE parametrization IAM = 1 - bo (1/cos i - 1) bo Parameter 0.05

User's needs : Unlimited load (grid)


PVSYST V5.74 Srikanth Reddy &Sangu 11/01/16 Page 2/3

Grid-Connected System: Main results


Project : Grid-Connected Project at Pune
Simulation variant : PYC CLUB

Main system parameters System type Grid-Connected


PV Field Orientation tilt 18 azimuth 0
PV modules Model ZT 240S Pnom 300 Wp
PV Array Nb. of modules 200 Pnom total 60.0 kWp
Inverter Model Sunny Tripower 20000 TLEEPnom 20.00 kW ac
Inverter pack Nb. of units 3.0 Pnom total 60.0 kW ac
User's needs Unlimited load (grid)

Main simulation results


System Production Produced Energy 90387 kWh/year Specific prod. 1506 kWh/kWp/year
Performance Ratio PR 76.0 %

Normalized productions (per installed kWp): Nominal power 60.0 kWp Performance Ratio PR
8 0.8
PR : Performance Ratio (Yf / Yr) : 0.760
Lc : Collection Loss (PV-array losses) 1.22 kWh/kWp/day
Ls : System Loss (inverter, ...) 0.08 kWh/kWp/day
7 Yf : Produced useful energy (inverter output) 4.13 kWh/kWp/day 0.7

6 0.6
Normalized Energy [kWh/kWp/day]

Performance Ratio PR

5 0.5

4 0.4

3 0.3

2 0.2

1 0.1

0 0.0
Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec

PYC CLUB
Balances and main results

GlobHor T Amb GlobInc GlobEff EArray E_Grid EffArrR EffSysR


kWh/m C kWh/m kWh/m kWh kWh % %
January 157.5 24.00 192.5 187.2 9054 8875 12.16 11.92
February 161.0 25.00 183.7 178.8 8579 8415 12.07 11.84
March 200.9 27.00 212.8 207.2 9824 9635 11.93 11.70
April 205.8 27.50 202.0 196.3 9281 9106 11.87 11.65
May 203.7 26.80 189.4 183.4 8730 8565 11.91 11.69
June 130.2 25.30 121.4 117.1 5630 5511 11.99 11.74
July 109.1 24.40 103.7 99.7 4821 4712 12.02 11.75
August 110.4 23.90 106.9 103.1 5009 4899 12.11 11.85
September 134.4 23.80 136.2 131.7 6398 6267 12.15 11.90
October 158.4 25.40 174.0 169.1 8090 7929 12.02 11.78
November 149.7 25.50 177.9 173.0 8294 8133 12.05 11.82
December 146.9 24.10 180.7 175.7 8503 8339 12.17 11.93

Year 1867.9 25.22 1981.1 1922.3 92210 90387 12.03 11.79

Legends: GlobHor Horizontal global irradiation EArray Effective energy at the output of the array
T Amb Ambient Temperature E_Grid Energy injected into grid
GlobInc Global incident in coll. plane EffArrR Effic. Eout array / rough area
GlobEff Effective Global, corr. for IAM and shadings EffSysR Effic. Eout system / rough area
PVSYST V5.74 Srikanth Reddy &Sangu 11/01/16 Page 3/3

Grid-Connected System: Loss diagram


Project : Grid-Connected Project at Pune
Simulation variant : PYC CLUB

Main system parameters System type Grid-Connected


PV Field Orientation tilt 18 azimuth 0
PV modules Model ZT 240S Pnom 300 Wp
PV Array Nb. of modules 200 Pnom total 60.0 kWp
Inverter Model Sunny Tripower 20000 TLEEPnom 20.00 kW ac
Inverter pack Nb. of units 3.0 Pnom total 60.0 kW ac
User's needs Unlimited load (grid)

Loss diagram over the whole year

1868 kWh/m Horizontal global irradiation


+6.1% Global incident in coll. plane

-3.0% IAM factor on global

1922 kWh/m * 219 m Cells Effective irradiance on cells


efficiency at STC = 27.35% PV conversion

115319 kWh Array nominal energy (at STC effic.)


-3.7% PV loss due to irradiance level

-11.8% PV loss due to temperature

-2.7% Module quality loss


-2.2% Module array mismatch loss
-1.1% Ohmic wiring loss
92211 kWh Array virtual energy at MPP

-2.0% Inverter Loss during operation (efficiency)


0.0% Inverter Loss over nominal inv. power
0.0% Inverter Loss due to power threshold
0.0% Inverter Loss over nominal inv. voltage
-0.0% Inverter Loss due to voltage threshold
90387 kWh Available Energy at Inverter Output

90387 kWh Energy injected into grid