Академический Документы
Профессиональный Документы
Культура Документы
TI NO. 07/201
0 11
AIR
R CON
NDIT
TIONIING PLAN
P NTS
TECHNICAL INSTRUCTIONS
ON
AIR CONDITIONING
WORKS DIRECTORATE
ENGINEER-IN-CHIEF BRANCH
MILITARY ENGINEER SERVICES
INTEGRATED HQ OF MOD (ARMY)
TINo07/2011
TINo07/2011
TINo07/2011
CONTENTS
1 INTRODUCTION 1
2 DEFINITION 1
11 TABLES 39
TINo07/2011
1. INTRODUCTION
2. DEFINITIONS
2.6 ENTHALPY A thermal property indicating the quantity of heat in the air
above an arbitrary datum, in kilo Joules per kg of dry air (or in Btu per pound
of dry air).
TINo07/2011
2.8 FIRE DAMPER A closure which consists of a normally held open damper
installed in an air distribution system or in a wall or floor assembly and
designed to close automatically in the event of a fire in order to maintain the
integrity of the fire separation.
2.9 FIRE SEPARATION WALL The wall providing complete separation of one
building from another or part of a building from another part of the same
building to prevent any communication of fire or heat transmission to wall
itself which may cause or assist in the combustion of materials of the side
opposite to that portion which may be on fire.
2.11 FRESH AIR CHANGE/ HOUR A certain quantity of fresh air from
uncontaminated ambient source, has to be inducted into system, to provide for
metabolic needs of occupants, to maintain freshness and to make up inevitable
loss of conditioned air by leakages through cracks/ door openings. The fresh
air so admitted replaces continuously the air in circulation and provides
certain number of fresh air changes in the conditioned space every hour which
equals.
TINo07/2011
3.1.2 Capacity
3.1.3 Suitability
Window air conditioners are suitable for bedrooms, office cabins, general
office area, hotel rooms and similar applications where normal comfort
conditions are required upto a distance of 6 m from window air conditioner.
Noise level of window air conditioner inside the conditioned room should
be as low as possible. However it should not exceed 65 dBA for 5250 W (1.5 TR)
or smaller capacity window air conditioners. Air conditioners with rotary
compressors will have lower noise level as compared to those provided with
reciprocating compressors.
TINo07/2011
3.1.6 Location
3.1.7 LIMITATIONS
Room air conditioners are not generally recommended in the following
situations:
a) The width of the area to be conditioned exceeds 6 m or reward the
paragraph.
e) Special applications like sterile rooms for hospitals and clean room
applications where high filtration efficiency is desired.
f) Operation theatres where 100 percent fresh air is needed and fire
hazard exists depending on the type of anaethesia being used.
3.2.1 Split air conditioner has an indoor unit and an outdoor unit
interconnected with refrigerant piping and power/ control wiring Indoor unit
comprises of a filter, evaporator and evaporator fan for circulation of air in the
conditioned space. Outdoor unit has a compressor, air-cooled condenser with
condenser fan housed in a suitable cabinet for outdoor installation. Split air
conditioner includes primary source of refrigeration for cooling and
dehumidification and means for circulation and cleaning of air, with or without
external air distribution ducting. Split air conditioners may be provided with
either reciprocating compressor or scroll compressor. Scroll compressor
generally consumes about 10 to 12 percent less power compared to
reciprocating compressor. Various split air conditioners available may be
categorised as under
4
TINo07/2011
3.2.2 Capacity
3.2.3 Suitability
Split air conditioners are suitable for wide range of applications including
residences, small offices, clubs, restaurants, showrooms, departmental stores,
etc.
3.2.4 Location
Split air conditioner indoor unit is mounted within the air conditioned
space or above the false ceiling from where the air distribution duct is taken to
the conditioned space to distribute the air. When the indoor unit is mounted in
the false ceiling, inspection panel must be kept in the false ceiling to attend to
the indoor unit including periodic cleaning of air filter. Outdoor unit is
mounted at the nearest open area where unobstructed flow of outside air is
available for air cooled condenser.
TINo07/2011
3.2.5 Installation
3.2.6 Limitations
a) Where forced fresh air changes are required for conditioned space.
(c) For larger ducted split air conditioners, the vertical distance
between the indoor unit and the outdoor unit should not exceed about 6
m for units with reciprocating compressors. The horizontal distance
between the indoor unit and outdoor unit should not exceed about 10 m
for reciprocating compressors.
(e) Sound recording rooms where criteria for acoustics are stringent
(f) Special applications like sterile rooms for hospitals and clean room
applications where high filtration efficiency is desired.
TINo07/2011
3.3.2 Suitability
3.3.3 Capacity
3.3.4 Location
The packaged unit can be mounted within the air conditioned space with
discharge air plenum or in a separate room from where the air distribution
duct is taken to the conditioned space. While deciding location for the
packaged unit, provision must be kept for proper servicing of the unit.
TINo07/2011
3.3.5 Installation
3.3.6 LIMITATIONS
d) Special applications like sterile rooms for hospitals and clean room
applications where high filtration efficiency is desired.
e) Operation theatres where 100 percent fresh air is needed and fire
hazard exists depending on the type of anesthesia being used.
3.4.3 Air handling equipments comprise of evaporator coils, air filters, electric
motor driven blowers, humidification equipments and air distribution/
collection network.
3.4.4 Central air conditioning plants work either on direct expansion system
(DX type) or on chilled water system (CW type).
TINo07/2011
condenser units are located in plant room separated from the space that
is to be conditioned.
TINo07/2011
4.1.2 Ventilation and air conditioning installation shall aim at controlling and
optimizing following factors in the building:
4.1.3 The plans for air conditioning, heating and mechanical ventilation
systems shall include all details and data necessary for review of installation
such as:
b) owner: name;
10
TINo07/2011
k) layout showing the location, size and layout showing the location, size
and construction of the cooling tower (apparatus), ducts, distribution
system;
4.2.1.1 In selecting the location for plant room, the aspects of efficiency,
economy and good practice should be considered and wherever possible it shall
be made contiguous with the building. This room shall be located as centrally
as possible with respect to the area to be air conditioned and shall be free from
obstructing columns. In the case of large installations (500 TR and above), it is
advisable to have a separate isolated equipment room where possible. The clear
headroom below soffit of beam should be minimum 4.5 m for centrifugal
plants, and minimum 3.6 m for reciprocating and screw type plants.
4.2.1.2 The floors of the equipment rooms should be light coloured and
finished smooth. For floor loading, the air conditioning engineer should be
consulted .
11
TINo07/2011
4.2.1.3 Supporting of pipe within plant room spaces should be normally from
the floor. However, outside plant room areas, structural provisions shall be
made for supporting the water pipes from the floor/ceiling slabs. All floor and
ceiling supports shall be isolated from the structure to prevent transmission of
vibrations.
4.2.1.8 Air conditioning plant room should preferably be located close to main
electrical panel of the building in order to avoid large cable lengths.
4.2.2 Planning Equipment Room for Air Handling Units And Package Units
12
TINo07/2011
4.2.2.3 Provision should be made for the entry of fresh air. The fresh air intake
shall have louvers having rain protection profile, with volume control damper
and bird screen.
4.2.2.5 Exterior openings for outdoor air intakes and exhaust outlets shall
preferably be shielded from weather and insects.
4.2.2.6 No air from any dwelling unit shall be circulated directly or indirectly to
any other dwelling unit, public corridor or public stairway.
4.2.2.7 All air handling rooms should preferably have floor drains and water
supply. The trap in floor drain shall provide a water seal between the air
conditioned space and the drain line.
4.2.2.8 Supply/return air duct shall not be taken through emergency fire
staircase. However, exception can be considered if fire isolation of ducts at wall
crossings is carried out.
4.2.2.9 Waterproofing of air handling unit rooms shall be carried out to prevent
damage to floor below.
4.2.2.10 The floor should be light coloured, smooth finished with terrazzo tiles
or the equivalent. Suitable floor loading should also be provided after
consulting with the air conditioning engineer.
4.2.2.12 The air handling unit rooms may be acoustically treated, if located in
close proximity to occupied areas.
4.2.2.13 Access door to air handling unit room shall be single/double leaf type,
airtight, opening outwards and should have a sill to prevent flooding of
adjacent occupied areas. It is desired that access doors in air conditioned
spaces should be provided with tight sealing, gaskets and self closing devices
for air conditioning to be effective.
13
TINo07/2011
4.2.2.14 It should be possible to isolate the air handling unit room in case of
fire. The door shall be fire resistant and fire/smoke dampers shall be provided
in supply/return air duct at air handling unit room wall crossings and the
annular space between the duct and the wall should be fire-sealed using
appropriate fire resistance rated material.
4.2.2.15 For buildings with large structural glazing areas, care should be taken
for providing fresh air intakes in air handling unit rooms. Fire isolation shall be
provided for vertical fresh air duct, connecting several air handling units.
4.2.3 Planning of Pipe Shafts
4.2.3.1 The shafts carrying chilled water pipes should be located adjacent to air
handling unit room or within the room.
4.2.3.3 All shafts shall be provided with fire barrier at floor crossings
4.2.4.1 Duct supports, preferably in the form of angles of mild steel supported
using stud anchors shall be provided on the ceiling slab from the drilled hole.
Alternately, duct supports may be fixed with internally threaded anchor
fastners and threaded rods without damaging the slabs or structural members.
4.2.4.2 If false ceiling is provided, the supports for the duct and the false
ceiling, shall be independent. Collars for grilles and diffusers shall be taken out
only after false ceiling/boxing framework is done and frames for fixing grilles
and diffusers have been installed.
4.2.4.3 Where a duct penetrates the masonry wall it shall either be suitably
covered on the outside to isolate it from masonry, or an air gap shall be left
around it to prevent vibration transmission. Further, where a duct passes
through a few resisting compartment barrier, the annular space shall be sealed
with fire sealant to prevent smoke transmission.
4.2.5.1 Cooling towers are used to dissipate heat from water cooled
refrigeration, air conditioning and industrial process systems. Cooling is
achieved by evaporating a small proportion of re-circulating water into outdoor
14
TINo07/2011
air stream. Cooling towers are installed at a place where free flow of
atmospheric air is available.
4.2.5.4 The recommended floor area requirement for various types of cooling
tower is as given below:
a) Natural draft cooling tower 0.15 to 0.20m2/ TR
15
TINo07/2011
4.2.5.5 Any obstruction to free flow of air to the cooling tower shall be avoided.
4.2.5.6 Structural provision for the cooling tower shall be taken into account
while designing the building, Vibration isolation shall be an important
consideration in structural design.
4.2.5.7 Special design requirements are necessary where noise to the adjoining
building is to be avoided.
4.2.5.8 As given below, certain amount of water is lost from circulating water in
the cooling tower:
4.2.5.9 Provision for make-up water tank to the cooling tower shall be made.
Make-up water tank to the cooling tower shall be separate from the tank
serving drinking water.
TINo07/2011
4.2.6 Glazing
4.2.6.2 Day light transmittance for various type of glass is given in given in
TABLE-1.
4.2.7.1 The overall thermal transmittance from the exposed roof should be kept
as minimum as possible and under normal conditions, the desirable value
should not exceed 0.58 W/(m2 C).
4.2.7.2 The ceiling surface of floors which are not to be air conditioned may be
suitably insulated to give an overall thermal transmittance not exceeding 1.16
W/(m2 C).
(a) Primary type air filter: The basic dry and viscous air filters arrest
only the larger size particles and possess very nominal filtering
capabilities. They are suitable for use in air conditioning of offices,
theaters, conference halls and briefing rooms, hotels etc. They are also
very useful as pre-filters to the more efficient air filters. These are
generally effective for particle size over 10 microns.
(b) Microvee dry type air filters: The next higher degree of air filtration
can be obtained from the use of certain dry filters commonly known since
long as microvee filters. Nowadays, an equivalent filter in called
Micromatic . The filter media is supported by GI wire mesh and is folded
to form an accordion pleats configuration. Aluminium spacers are used
to separate the pleats. These are 99.9% efficient down to 5 microns and
can operate under 120 deg C, 100% RH conditions. Their life is enhanced
greatly if pre-filters are also used. This filter can act as a pre-filter to the
HEPA filters described in the succeeding paragraph.
17
TINo07/2011
(c) High efficiency particulate air filter (HEPA filter): Some times also
known as absolute filter. This is a dry type of air filter possessing and
extremely high efficiency between 99.97% and 99.99% for filtering
particles of 0.3 micron size. The filter media is glass asbestos fibre paper
which is water repellent and fire retardant. It has excellent resistance to
chemicals and does not stretch or swell. It is suitable for use over the
complete range of temperatures in air-conditioning with relative humidity
upto 100%. HEPA filter is always assisted by one or two pre-filters on the
entering side which prolongs the life of this extremely fine filter.
(d) Electrostatic precipitator: For air filtration below 0.3 micron level,
electrostatic precipitators will have to be used. A self-contained console
model is portable and can be placed directly inside the room. This has a
charcoal after-filter to absorb odours. These filters are capable of filtering
particles of 0.01 micron size and larger with high efficiency.
The filtration level obtainable from commercial air filters could therefore
be summarized as follows:-
(c) For air filtration down to 0.3 micro-HEPA filter assisted by normal
filter of the type in (a) above and microvee filter of the type in (b) above.
5.1 GENERAL
18
TINo07/2011
Special air filters may be required to remove contaminants or smells when air
is recirculated.
19
TINo07/2011
Two types of screw compressors are available, that is, single and twin
screw, and both are positive displacement machines. Compression of the
refrigerant vapour is achieved by the progressive reduction of the volume
contained with in the helical flutes of the cylindrical rotor(s) as they rotate. Oil
is injected into the rotor chamber for sealing and lubrication purposes and is
removed from the refrigerant discharge gas in an oil separator before the
refrigerant passes onto the condenser. No oil separator is 100 percent efficient
and so a small quantity of oil always passes through with the refrigerant. On
systems using a direct expansion evaporator the oil is trapped in the
evaporator and an oil recovery system is necessary. With some systems oil
cooler is required in the oil circulation system, to remove the heat gathered by
the oil during compression cycle. On other systems liquid refrigerant is injected
into the compressor to remove the heat of compression instead of using the
conventional oil cooler. Such an arrangement can impose a small penrdty on
the plant capacity. The condenser most commonly used on packaged units is
the watercooled shell-and-tube type, but equipment with air cooled condensers
is also available. The expansion device used will depend on the evaporator type
but it is often a electronic expansion valve (single or in multiple) of
conventional or modified form. Screw compressors are available in open and
semihermetic form and are generally coupled direct to two-pole motors. The
capacity of the compressor can be modulated down to 10 percent of full load
capacity.
These are available in a wide range of sizes and designs. They are almost
invariably used in packages up to 120 TR cooling capacity. Because the
cylinders have automatic valves, a single compressor may be used over wide
range of operating conditions with near optimum efficiency, whereas other
types of compressor require detailed modification to give optimum efficiency at
different conditions. This is, however, of minor importance for normal air
conditioning duties.
20
TINo07/2011
The evaporator is normally of the dry expansion type, to permit oil from
the compressor to circulate round the system with the refrigerant. Shell-and-
tube water cooled condensers are common, but any type of condenser can be
used. With air cooled condensers it is normal practice to build the machine
package so that it may be located on the roof in a package including the
condenser.
It is common for the electric drive motors to be built into the compressor
assembly; this is known as a semihermetic drive to distinguish it from the
hermetic, in which the compressor and motor are enclosed within a pressure
vessel and cannot therefore be serviced. The semi-hermetic compressor is
more compact and is quieter in operation than the open drive compressor, but
involves a more difficult service operation in the event of a motor failure. It
gains in reliability, however, by avoiding the shaft seal of the open compressor.
21
TINo07/2011
5.3.2.1 Materials
Steel piping with welded or flanged joints is commonly used. Flanges for
flanged joints are welded to pipes. The choice of materials or any installation
will be governed by economic considerations, but care should be taken to
minimize the possibility of corrosion when choosing material combinations.
The inside design condition for some of the applications works are
indicated in TABLE-2.
5.4.4 Users data sheet for designing air conditioning systems is indicated in
TABLE-7.
TINo07/2011
Ionization type detectors are sensitive to high velocity air streams and if
used in ductwork the manufacturer should be consulted. Activation of smoke
detector should stop the air handling unit supply air fan, close the fire damper
in supply and return air duct and operate a suitable alarm system.
In all the above instances the appropriate controls would require manual
re-setting.
23
TINo07/2011
The pressurization systems for staircases use large volumes of outside air.
The system may be designed to operate continuously at low speed, being
increased to high speed in the event of fire, or to operate only in emergency.
Noise and droughts are not considered a problem in an emergency situation.
Fan motor and starter should be protected from fire and connected to the
emergency electrical supply through cables with special fire resistant coating.
In many cases proper air conditioning can be a factor in the therapy of the
patient and in some instances part of the major treatment. For special
application areas of hospitals such as operation theatres, reference may be
made to specialist literature.
The main difference in application compared with other applications are:
a) Restriction of air movement between various departments and control of air
movement within certain departments, to reduce the risk of airborne cross
infection;
b) Specific need for the ventilation and filtration equipment to dilute and/or
remove particulate or gaseous contynination and airborne microorganisms;
c) Close tolerances in temperatures and humidities may be required for
various areas; and
d) The design should allow for accurate control of environmental conditions.
For (a) and (b) the air movement patterns should minimize the spread of
contaminants as for instance, in operating departments where the airflow
should be such as to reduce the risk of periphery or floor-level air returning to
the patient owing to secondary air currents whilst the general pressurization
pattern should cause air to flow through the department from sterile to less
sterile rooms in progression. In operating theatres 100 percent fresh air system
is normally provided and air pressures in various rooms are set by use of
pressure stabilizers. Many types of air distribution pattern within operation
theatres are in use but generally they conform to high-level supply and low-
level pressure relief or exhaust. There is also need for a separate scavenging
system for exhaled and waste anesthetic gases with in theatre suites where
general anesthetic may be administered.
TINo07/2011
(a) The factors involved in locating the plant room and selecting the
type of airconditioning system are somewhat inter-dependent and
demand careful consideration. All decisions should be towards ensuring
safety from fire hazard, because the building will contain explosives and
the plant room will have electrically operated machinery/controls.
Incidence of fire in any one of them, which is very much possible, will
pose danger to both of them simultaneously.
25
TINo07/2011
26
TINo07/2011
(l) In all cases considered above, the wathermaker room shall have
the same specifications as air-conditioned buildings served by them. All
electrical items in the wathermaker room(s) shall be of the same
category/specifications as adopted for those in conditioned buildings.
6.1 The source of noise in the air conditioning system could be from the
following:
a) Chillers,
b) Pumps,
c) External noise infiltration though openings,
d) Fans,
e) Air noise through ducts, and
f) Compressors.
6.2 The approach must always be to reduce the source noise rather than
controlling them in the path.
7.1.1 The scheme of colour code for painting of pipe work services for air
conditioning installation shall be as per TABLE-6.
For duct work services and its insulation, colour triangle may be
provided. The size of the triangle will depend on the size of the duct and
viewing distance but the minimum size should not be less than 150 mm length
per side.
The colour for various duct work services shall be as given below:
__________________________________________________________________
Services Colour
__________________________________________________________________
Conditioned Air Red and Blue
Ward Air Yellow
27
TINo07/2011
TINo07/2011
b) To adjust to regulate for specified fluid flow rates and air patterns
at terminal equipment (for example reduce fan speed, throttling etc); and
TINo07/2011
Both supply and return air distribution for each air handling unit and for
areas served by the air handling unit shall be determined and adjusted as
necessary to provide design air quantities. It shall cover balancing of air
through main and branch ducts.
Balancing work for both chilled water system and condenser water system
shall be carried out in a professional manner and test reports in the specified
format shall be prepared.
30
TINo07/2011
Measurements should be taken with a sound level meter either using the
A weighting scale or to draw up a noise criteria curve. Measurements should
be taken in the following locations:
a) Plant rooms;
b) Occupied rooms adjacent to plant rooms;
c) Outside plant rooms facing air intakes and exhausts and condenser
discharge, to assess possible nuisance to adjacent occupied areas;
d) In the space served by the first grille or diffuser after a fan outlet;
e) In at-least two of the spaces served by fan coil units or high velocity
system terminal units (where applicable);
f) In any space; and
g) Air handling unit (AHU) rooms and adjoining areas.
Chillers
31
TINo07/2011
32
TINo07/2011
9.2 CONTROLS
(a) Can start and stop the system under different schedules for three
different day-types per week.
(c) Includes and accessible manual override that allows temporary operation
of the system for up to 2 hours.
9.2.3.1 Proper site selection and sizing of the tower can reduce fan speed,
capacity & sound and help to conserve energy.
9.2.3.2 Centrifugal fans in favor of lower energy axial fans can reduce
horsepower by 50 % or more for the same capacity.
33
TINo07/2011
Cooling System
Designed Operation temperature Insulation with minimum R-
of piping value (m2 K/W)
Below 15 C0 0.35
Refrigerant suction Piping
Split system 0.35
Source : ECBC 2007
9.3.2 Ductwork
Ductwork Insulation
34
TINo07/2011
roof insulation
Unconditioned Spaceb R-0.6 No Requirement
Indirectly Conditioned No Requirement No Requirement
Spacec
Buried R-0.6 No Requirement
aInsulation R-valve is measured on a horizontal plane in accordance with
9.4.1 General
System balancing is a process for maintaining the performance of an air
conditioning system, and for providing the occupants with a comfortable
conditioned space.
Balancing an air or water based air condition system of buildings will
make it more energy- efficient, provide improved thermal comfort, extend the
life of the building equipment and reduce the cost of operating it. Balancing is
achieved by optimizing the air/water distribution rated for the HVSC system.
35
TINo07/2011
Exceptions to above:
(a) Impellers need not be trimmed nor pump speed adjusted for
pumps with pump motors of 7.5 kW (10 hp) or less.
9.4.4 Condensers
36
TINo07/2011
All high-rise buildings using centralized cooling water system shall use
soft water for the condenser and chilled water system.
i) R-11 1.000
ii) R-12 0.820
iii) R-22 0.050
iv) R-134a 0.000
v) R-407a 0.000
vi) R-407c 0.000
37
TINo07/2011
Due to high ODP of R-11, R- 12 and R-22, their use in the air conditioning
and refrigeration is being phased out. R-123 is also in the phase-out category
of refrigerants.
10.2 Depletion of stratospheric ozone layer and global warming are the two
greatest challenges of present time with regards to protection of environment.
Hydro -carbon compounds with cl2 atoms have been found responsible for
ozone layer depletion . These have also been found responsible for global
warming along with other gases such as carbon dioxide (CO2), methane (CH4),
Nitrous oxide (N2O). Some of such compounds particularly CFCs and HCFCs
are being used as refrigerants in HVAC industry . Road map for phasing out of
these substances has been drawn in various international conferences starting
with Montreal protocol(1987), koyoto protocol (1997) and subsequent recent
deliberations at Copenhagen.
10.3 HQ Technical Group EME under the aegis of Directorate General of EME,
Delhi Cantt, New Delhi 110010 has been nominated as nodal agency to
coordinate all issues related to mgt of ODS in Indian Army. 95 ODS have been
identified and published in the Gazette of India Notification Extraordinary No.
471 dated 19 Jul 2000 published in HQ E-in-Cs Branch policy letter No
95284/CFC/E4(U2) dated 10 May 2011.
38
TINo07/2011
10.4.2 All new central plants should be CFC and HCFC free ensuring nil
consumption of HCFC-22 by 2030. A large number of substances were
investigated to find non-chlorinated refrigerants as HCFC-22 replacements.
Amongst them, hydro fluorocarbons (HFCs) compounds that contain no
chlorine atoms have shown the greatest potential . However, none of them
replicates the performance of HCFC-22 in all applications. Currently, there are
four leading replacements: HFC-407C, HFC-404A, HFC-134a, and HFC-410A.
R-410A and R-407C are blends, while R-134a is composed of a single
constituent.
10.5 Ministry of Environment & Forest in association with World Bank has
launched India Chiller Energy Efficiency Project (ICEEP) for providing
financial incentives from Global Environment Facility, and Multilateral Fund
Grant for expediting replacement of inefficient CFC based chillers with energy
efficient non CFC based chillers. IDBI is nodal agency for monitoring and
39
TINo07/2011
granting incentive which would require registering with IDBI and incentives will
be available to support the phase-out of use of CFC, an Ozone Depleting
Substance, under the Montreal Protocol. The project also would provide,
financial incentives directly to chiller owners to encourage them to overcome
barriers such as up-front capital costs and perceived technology risks. ICEEP
will primarily target CFC based (R11 and R12) centrifugal chillers with cooling
capacity of 100TR and above which have been installed after 1993, with a
residual technical life of more than 5 years for replacement to non-CFC (HCFC
123 or HFC 134a) Centrifugal /Screw type chillers with energy consumption of
not more than 0.63 kW/TR. The CEEP will offer two financial incentives
options on first cum- first serve basis. The Chiller owners (including public
sector) would be eligible to receive around 60% of the CDM revenues to be
generated from actual energy savings achieved by the new chillers. Under the
project, taking into account energy savings upto 30% on replacement of
existing inefficient CFC- based centrifugal chillers by new non-CFC based
energy efficient chillers, it is expected that, the beneficiaries would recover
initial investment within simple payback period of three to three and half years.
10.6 Ensuring correct disposal and handling of used refrigerant during service
and after the plant is removed from service is equally important to reduce
refrigerant emissions into the environment by instituting suitable procedures
for Recovery, recycling and reclamation.
40
TINo07/2011
41
TINo07/2011
42
TINo07/2011
Rooms 260C
RH 40 to
50%
Source: National Building Code, 2005
43
TINo07/2011
44
TINo07/2011
Source:NationalBuildingCode:2005
45
TINo07/2011
46
TINo07/2011
Source:NationalBuildingCode,2005
47
TINo07/2011
TINo07/2011
49
TINo07/2011
_____________________________________________________________________________________________________________________
Source: National Building Code, 2005
50
TINo07/2011
1 Name of Project:
2. Name of room and usage:
3 Inside Design conditions (as required by the users):
(a) Dry Bulb Temperature - ___ Deg C( + )to__Deg
C
(b) Relative Humidity - ___% ( + )to ______ %
(c) If recirculation is permitted, No of air
charges per hour to be specified - (1 Air charge/hr)
(d) Occupancy ( state max & min figures) - ____Persons very
active
OR
___Persons
moderately
OR
Persons at
rest
51
TINo07/2011
(Signature of users)
Rep with seal)
1. Location
2. Establishment
3. Number of building
4. Purpose of the building
5. Category of explosives handled
6. Building category A/B/C
7. Explosive vapour/dust generated in conditioned space.
8. Building traversed/untravered.
9. Safety distance adopted/ NOT adopted.
10. Building isolated/one of a group conditioned
11. Type of roof proposed.
12. Provision of false ceiling proposed/ NOT proposed; Material of false
ceiling.
13. Thermal insulation type and thickness.
14. Provision of vapour barrier proposed/ NOT proposed.
15. Provision of air lock (s) proposed /NOT proposed.
16. Electric fitments and fittings in building:
Flameproof/ Dust-tight/ Totally Enclosed.
52
TINo07/2011
53
TINo07/2011
Type Walls
ROOM LATENT
(i) Infiltration
HEAT (RLH)
54
TINo07/2011
Type Watts
(i) Sensible Heat
(ii) Latent Heat
(iii) Return duct heat gain
(iv) Return duct leakage gain
(v) Dehumidifier pump heat gain
(vi) Dehumidified piping heat gain
C. OUTDOOR TOTAL HEAT
(sum of (i) to (iv) above)
55
TINo07/2011
56