Академический Документы
Профессиональный Документы
Культура Документы
3 - 40-50mm
Pressure Independent Control Valves
SPECIFICATIONS
Static pressure: 2500 kPa / 360 psi
Ambient temperature: +2C to +50C / +36F to +122F
Media temperature1: -20C to +120C / -4F to +248F
Material:
- Flow regulation unit (internal): Glass-reinforced PSU/PPS/POM
- Metal components (internal): Stainless steel
- O-rings and seats: EPDM
- Diaphragm: Hydrogenated acrylonitrile-butadiene-rubber
- Housing and covers: Forged brass ASTM CuZn40Pb2
End connections2: ISO or NPT
Maximum close off pressure: 600 kPaD / 87 psid
Maximum operational P: 400 kPaD / 58 psid
Shut-off leakage: ANSI / FCI 70-2 2006 / IEC 60534-4 - Class IV
Flow rate range: 0.528-3.79 l/sec / 8.36-60.0 GPM
Note 1: Stated temperature rating is defined due to no external condensation.
Note 2: NPT only available ex. US-factory
H2 H3 Weight4 Kvs5
Model no. Valve model Valve size L H1
FH.0.X actuator FH.1.X actuator (kgs.) (m/hr)
H2 H3
H1 H1
L L
Example: G.3.52.40.B.I=40mm FlowCon Green with a 24V electrically modulating actuator, p/t plugs and ISO female-female threaded.
WIRING INSTRUCTION
Red
Feedback signal
Input signal 0(2)-10V DC
0(2)-10V DC
Power 24V AC/DC
Ground/common
FlowCon FH.0.4
FH.0.4 Actuator FH.0.4 Actuator
FN.0.4 / 5.4 Actuator FN.0.4 / 5.4 Actuator
2-Position, Normally Closed 2-Position, Normally Open
White
White
Black
Black
Red
Red
Ground/common Ground/common
White
Black
Black
Red
Red
Stop Stop
Close Open Open Close
Ground/common Ground/common
FlowCon FH.1.4
3-point-floating, NC 3-point-floating, NC
Green
White
White
Black
Black
Red
Red
Ground/common Ground/common
Green
White
White
Black
Black
Red
Red
Stop Stop
Close Open Open Close
Ground/common Ground/common
Tech note NC
3-point-floating, FlowCon Green.3 - 40-50mm july3-point-floating,
2015 www.flowcon.com
NC Page 3 of 6
DESCRIPTION
The FlowCon Green serie is pressure independent control valves that are two-way, modulating to accept digital or
analog input signals. The valves accept 0(2)-10V, 3-point floating or ON/OFF input signals. Each valve has an
adjustable maximum flow rate setting maintaining a full stroke to enable flow limitation and balancing to the coil or
zone that the valve is controlling.
For use in fan-coil units, VAV applications and cooling ceilings for activation of the heating or cooling.
FlowCon Green.3
Setting
16-400 kPad 2.3-58 psid
RETURN RETURN
COIL
COIL
SUPPLY
SUPPLY
UPDATES