Вы находитесь на странице: 1из 8

engineers newsletter

volume 352 providing insights for todays hvac system designer

handler with economizer controls has


keeping cool with outdoor air four operating modes.

Airside Economizers Heating mode. During very cold


weather, the air handler brings in
minimum outdoor airflow (for
many jurisdictions, by the building
from the editor
ventilation) and mixes it with return
code.
For the denizens of commercial air. The mixed air is then heated as
buildings, comfort cooling is one of lifes necessary to maintain the desired
Lets take a high-level look at airside
basic necessities. Without it, we quickly supply-air (or space) temperature.
become irritable, lethargic, and unable economizing: what it is, what it
to concentrate. But the cost of keeping requires, and how its done.
ASHRAE Standard 62.12004 [2]
us comfortably cool rises with each
passing day and that cost isnt (Standard 62) or building code
confined to the person or organization requirements determine the minimum
who pays the building utility bill. intake of outdoor air. This minimum
How does economizer may be reset downward from the
Using outdoor air to help cool a building
isnt a new concept. Thanks to energy cooling work? design value (to save heating energy)
standards and local building codes, its using various dynamic reset
no longer optional in many areas, either. Most commercial buildings have some approaches. But when its cold outside,
spaces that need cooling all year long. no more than minimum outdoor air
In this EN, Dennis Stanke (Trane staff If its colder outdoors than indoors, it enters the building, whether or not the
engineer and chair of ASHRAE SSPC often makes energy-sense to
62.1) reviews ASHRAE Standard 90.1s system includes airside economizer
requirements for airside economizers
economize by bringing in more-than- controls.
and discusses the underlying design minimum outdoor air to reduce the
decisions and benefits of effective airside hours of mechanical cooling system
economizer systems. Modulated economizer mode.
operation.
During cool weather (30F to 55F
A typical mixed-air air handler [1C to 13C], for example), the
Youre in your kitchen on a beautiful, includes dampers for outdoor air, return required space temperature can be
breezy fall day, with a pie baking in the air, and relief air (Figure 1). These maintained without any mechanical
oven. Would you rather cool off the dampers can be controlled to provide cooling or heating by simply adjusting
kitchen by opening your windows or by airside economizing. Usually, an air the mix of outdoor air and return air.
turning on your central air conditioner?
By opening the windows, of course!
Why? If the outdoor air is cool and dry, Figure 1. Typical air handler
it can cool the space nicely without
using electricity for compressors and
fans, and it ventilates the space with
fresh outdoor air in the bargain. The
same logic holds in non-residential
buildings. In fact, it not only makes
sense to introduce outdoor air when
conditions are right but its also
required by ASHRAE Standard
90.12004 [1] (Standard 90) and, in

2006 Trane All rights reserved 1


In this mode, the economizer system Figure 2. U.S. climate zones
adjusts both the outdoor- and return-air
dampers, modulating these airflows to
match cooling capacity with cooling
loadwithout mechanical cooling.
Intake airflow varies between the
minimum setting and a maximum value
(100% of supply airflow) to maintain
the supply-air (or space) temperature
at setpoint.

Integrated economizer mode.


During mild weather (55F to 75F
[13C to 24C], for example), outdoor
air can provide some cooling capacity,
but not enough to satisfy the load, so
mechanical cooling supplements the
economizer cooling provided by the
wide-open outdoor-air damper. We
refer to this mode as integrated
economizer because it combines
free cooling (100% outdoor air) downward from its design value to Standard. Figure 3 shows regional
with mechanical cooling to meet the save cooling energy. But, when its hot economizer requirements, which aim
required cooling capacity. The system outside, no more than minimum to minimize the ratio of economizer-
stays in integrated economizer mode outdoor air enters the building related costs to energy-related savings.
until outdoor conditions reach the high- whether the system includes an These requirements are based on
limit shutoff setting (discussed in more airside economizer or not. cooling system capacity and the
detail on p. 5), or until the outdoor expected number of hours with
conditions fall to the point where Note: Specific control sequences for outdoor conditions that are appropriate
modulated economizer operation the preceding operating modes may for economizing.
can handle the cooling load. vary with equipment configuration,
type of economizer control, and high- Potential energy savings are highest
limit settings. where the weather is dry or marine, so
Mechanical cooling mode.
systems with capacities larger than
Economizer operation is disabled
5 tons (65,000 Btu/h [19 kW]) in
during warm weather, when outdoor
these locations must include
conditions exceed the high-limit
What does economizer cooling. Moist, cool
shutoff setting. Minimum outdoor air
climates provide fewer opportunities
for ventilation (determined by Standard Standard 90 require? for free cooling, so the economizer
62 or the local building code) mixes
According to Standard 90, requirement only applies to systems
with return air. The mixed air then is
Section 6.5.1, economizer cooling with capacities larger than 11 tons
mechanically cooled as needed to
systems (either airside or waterside) (135,000 Btu/h [40 kW]).
maintain the supply-air (or space)
temperature at setpoint. must be used in all cooling systems
with fans. Theres also a long list of Potential benefits are lowest where
exceptions to this requirement (see the weather is moist and warm.
As in the heating mode, the
inset, p. 3) because the value of Economizer cooling is not required in
minimum outdoor airflow may be reset
economizer cooling depends on these climates (although it is allowed)
climate, building type, system type, because ASHRAE studies indicate that
and control settings. Nevertheless, the potential savings in mechanical
Standard 90 requires economizer
cooling in many locations for many * Appendix B of Standard 90 also identifies
buildings and many different systems. climate zones for various cities elsewhere in
North America and around the world.
Figure 2 shows the U.S. climate
zones * defined in Appendix B of the

2 Trane Engineers Newsletter volume 352 providing insights for todays HVAC system designer
Figure 3. Standard 90s regional economizer requirements based on cooling system capacity Figure 4a and Figure 4b (p. 4) show
typical economizer sequencing for
constant- and variable-volume
systems. Standard 90 does not
specifically require these operating
modes, but they result from logical
sequencing of mechanical and
economizer cooling. These diagrams
expand on the single diagram
presented in the Standard 90.12004
Users Manual. [3]

Figure 4a: Constant-volume


systems. In heating mode, minimum
outdoor-air intake flow enters the
system. Heating capacity decreases as
the outdoor-air heating load decreases.

As the weather warms, when the


cooling energy may not be sufficient to mechanical cooling to maximize energy system no longer needs heating, it
justify the additional cost of savings while avoiding wasteful enters the modulated economizer
implementing it. simultaneous cooling and heating. mode. Outdoor air and recirculated
To help assure proper sequencing, return air modulate to maintain space
Section 6.5.1.1.1: Design capacity. control of the economizer dampers (or supply-air) temperature at setpoint.
Airside-economizer systems must shouldnt be based on mixed-air Outdoor air provides the needed
include outdoor- and return-air conditions alone. cooling capacity without any
dampers that are sized and modulated mechanical cooling. The black area in
so that up to 100% of design supply Figure 4a represents the mechanical

airflow can be outdoor air. In other Warmer supply air increases the delivered airflow cooling energy thats saved during
words, the system must be designed (therefore fan energy) and space humidity levels modulated economizer operation or
while reducing both mechanical cooling and local
to allow outdoor airflow ranging from reheat energy. Thoroughly analyze the effects of
free cooling.
the minimum required for ventilation to a supply-air-temperature reset strategy before
the maximum delivered by the making it part of the system design. As the cooling load increases, the
supply fan. outdoor-air damper eventually opens

For VAV systems, the supply fan


usually delivers less than cooling-
Exceptions to Standard 90s economizer requirement
design airflow during the integrated
economizer modeeven though the Section 6.5.1 requires economizers for (d) Systems with condenser heat
all systems in all locations. But it also recovery.
outdoor-air damper is wide open. Of identifies the nine exceptions listed below.
course, supply fan airflow (and (e) Any residential space system with a
therefore, intake airflow) increases if Note: Economizer systems may be capacity thats less than five times the
the control resets the supply-air used even if not required, provided that applicable limit listed in Exception (a).
the economizer system conforms to the
temperature upward at part load.
requirements in Sections 6.5.1.1 through (f) Systems with space sensible cooling
6.5.1.4. loads (excluding transmission and
Section 6.5.1.1.2: Control signal. infiltration loads) equal to or less than
(a) Systems using fan-cooling units transmission and infiltration loads at 60F.
Airside economizer operation must
with individual capacities less than
be appropriately sequenced with 65,000 Btu/h (19 kW) in dry climates, less (g) Systems that are expected to operate
than 135,000 Btu/h (40 kW) in cool-moist less than 20 hours per week.
climates, and with any capacity, large or
small, in warm-moist climates (Figure 3). (h) Supermarket systems where outdoor
air for cooling affects open refrigerated
(b) Systems with gas-phase outdoor air cases.
cleaning to meet ASHRAE Standard 62.
(i) Systems with high mechanical cooling
(c) Systems that deliver more than 25% efficiencies (equal to or exceeding the
of the supply air to spaces humidified requirements of Table 6.3.2).
above 35F dew point for process needs.

providing insights for todays HVAC system designer Trane Engineers Newsletter volume 352 3
to 100% and the return-air damper Figure 4a. Typical economizer control sequence for constant-volume systems
closes completely. The system enters
integrated economizer mode, where
100% outdoor airflow provides part of
the required cooling capacity and
mechanical cooling provides the
balance, modulating or cycling as
necessary to maintain the required
space (or supply-air) temperature. The
red area in Figure 4a represents the
mechanical cooling energy thats saved
during integrated economizer
operation.

The system stays in integrated


economizer mode until the outdoor-air
condition reaches the high-limit shutoff
setting. At this point, the controls
disable economizer operation and the
system enters the mechanical cooling
mode, where a water valve modulates
or a compressor cycles to provide all
cooling capacity needed to maintain reheat terminals need less airflow The system enters mechanical cooling
space (or supply-air) temperature. In when cooling than when heating. mode when outdoor air reaches the
this mode, the outdoor-air damper When the cooling load starts to rise, high-limit shutoff condition. Intake
closes to allow only minimum the modulated economizer mode airflow drops to the minimum
intake airflow. begins. Supply airflow increases (that requirement, and supply and return
is, intake airflow increases while return airflows increase while the cooling coil
In some locations, direct expansion airflow decreases) to maintain the provides the required cooling capacity.
(DX) systems may be designed to required supply-air temperature
enter the mechanical cooling mode without mechanical cooling. In the Both constant-volume and VAV
directly from the modulated integrated economizer mode, the systems use linked outdoor- and
economizer mode. If 100% outdoor air outdoor-air damper stays wide open return-air dampers, which are operated
is unable to provide the required to provide some cooling capacity by a single actuator or by multiple
cooling capacity, then the outdoor-air while the mechanical system coordinated actuators. However, as
damper closes to its minimum position modulates to provide the balance. mentioned in the Standard 90 users
and mechanical cooling modulates to
provide all of the needed cooling
capacity. This non-integrated Figure 4b. Typical economizer control sequence for variable-volume (VAV) systems
economizer approach avoids unstable
refrigerant system operation and coil
frosting, which can occur when a DX
system cycles at low loads. But it also
reduces the potential savings in
mechanical cooling energy represented
by the red-shaded area in Figure 4a.

Figure 4b: Variable-volume


systems. Consider a single-duct,
chilled water VAV system with reheat
terminals: In heating mode, minimum
outdoor airflow enters the system and
recirculated return air provides the
balance of supply airflow. Supply
airflow usually decreases as the
heating load diminishes because the

4 Trane Engineers Newsletter volume 352 providing insights for todays HVAC system designer
manual and in Guideline 16, Selecting high-limit shutoff. In other words, the might actually differ from the
Outdoor, Return and Relief Dampers prescribed high-limit shutoff setting prescribed limit.
for Airside Economizer Systems [4] , acts as an economizer enable/
sequential or optimized damper disable setting. The prescribed high-limit setting
operation can save supply fan energy depends on location and the type of
by reducing mixing box pressure during Above the prescribed high-limit shutoff high-limit thats used. Table 6.5.1.1.3A
the modulated economizer mode. [5] a best compromise established by in the Standard allows six different
ASHRAE using computer simulations control types: fixed dry bulb,
for various control types in various differential dry bulb, fixed enthalpy,
Section 6.5.1.1.3: High-limit
climatesStandard 90 assumes that electronic enthalpy, differential
shutoff. Integrated airside-economizer
the system needs more mechanical enthalpy, and dew pointanddry bulb.
operation must be disabled (that is, the
cooling energy to condition 100%
outdoor-air damper must reduce intake In dry and marine climates and in very
outdoor air than to condition mixed air,
airflow from maximum to the minimum cold climates, fixed enthalpy control is
so economizer operation must be
airflow required for ventilation) not allowed (Figure 5, p. 6). Why?
disabled. Below the high-limit shutoff,
whenever outdoor air exceeds a Because it could result in 100%
the Standard assumes that the system
prescribed high-limit condition. This outdoor air during many hours when
needs less mechanical cooling to
makes sense: If it starts to rain or if it outdoor conditions are dry but very
condition 100% outdoor air. Of course,
gets really hot outside, you want to warm. If the cooling coil is dry, too,
since the prescribed limits are based
close the kitchen window, right? both sensible load and mechanical
on broad assumptions, the best
Conversely, economizer operation cooling energy increase rather than
economizer enable/disable condition
must be enabled when outdoor decrease. In cold climates, fixed
for a given building in a given location
conditions are equal to or below the

Decisions, Decisions

Standard 90 includes prescribed minimum High-limit shutoff type? Depending on Others: Standard 90 doesnt
requirements for economizer systems. But location, designers may choose from five permit other control types under the
within these requirements, designers still or six types of high-limit shutoff control, prescriptive approach to compliance.
must make several economizer-related ranging from lowest cost (fixed dry bulb)
decisions in addition to choosing the HVAC to perhaps lowest energy (differential Each permitted approach has a unique first
system type (CV-basic, CV-reheat, VAV) enthalpy): cost, operating cost, maintenance cost,
and size: to economize or not to and space relative-humidity performance.
Fixed dry bulb disables economizer
economize, whether to use an integrated To properly weigh the tradeoffs and make
operation when outdoor air exceeds a
or non-integrated economizer, which of six an informed choice, designers should use
fixed temperature.
types of high-limit shutoff control to an economic/performance analysis
implement, and perhaps an optimum high- Differential dry bulb (not allowed in program to compare at least fixed dry
limit shutoff setting as well. some climate zones) disables bulb, fixed enthalpy, and differential
economizer operation when the enthalpy, since these are common and
Economize? Even though economizer temperature outside is warmer than widely applicable.
cooling may not be required (because the the return air.
system is small or because its in a warm, High-limit shutoff setting? These
moist climate), a thorough engineering Fixed enthalpy (not allowed in some values are prescribed for different control
analysis may show that it reduces climate zones) disables economizer types in different climates. An economic/
operating costs enough to be worthwhile. operation when outdoor air exceeds a performance analysis may show that
fixed enthalpy (28 Btu/lb [65 kJ/kg]). higher or lower values offer better energy
Economizer type? Even though its not Electronic enthalpy disables economizer savings or better relative humidity
required in most locations, a designer may operation when outdoor air exceeds a performance for a particular building
choose integrated economizer control selected dry-bulb/dew-point curve, system. The authority having jurisdiction
anyway. Why use it? It always increases defined by electronic sensor may agree to approve a variance if such an
economizer hours and it doesnt increase manufacturers. analysis shows that a custom shutoff
first cost in chilled water systems. Why not setting results in lower energy use than the
use it? In simple DX systems, operating Differential enthalpy disables generic prescribed setting.
with 100% outdoor air may result in coil economizer operation when outdoor-air
frosting at low loads. And, at low outdoor enthalpy exceeds return-air enthalpy. Decisions about economizer systems can
air temperatures (low loads), it causes Dew pointanddry bulb disables be made spontaneously based on first-cost
compressor short-cycling, which may lead economizer operation when outdoor air considerations (for example) or they can
to refrigerant system instability and exceeds a fixed dry-bulb (75F [24C]) be made deliberately based on an analysis
possible reliability problems. The common OR a fixed dew-point (55F [13C]) of both life-cycle cost and relative-humidity
fix for low-load cycling usually involves temperature. performance. Many designers and their
hot gas bypass, which increases the first customers prefer the latter.
cost of integrated economizer control and
decreases the benefit.

providing insights for todays HVAC system designer Trane Engineers Newsletter volume 352 5
Figure 5. Standard 90s regional limitations for economizer control types building. Excessive building pressure
can cause doors to stand open,
creating a potential security risk.

Also, in small constant-volume


systems, relief airflow from a space
affects intake airflow. Imagine a
classroom that has an unlouvered door
and is served by a 1200-cfm (560 L/s)
unit ventilator. About 800 cfm (380 L/s)
leaks from the room at 0.3 in. wg
(75 Pa). With the outdoor-air damper
wide open, and assuming that the unit
fan can raise space pressure to 0.3 in.
wg (75 Pa), the economizer introduces
only 800 cfm (380 L/s) of outdoor air,
not 1200 cfm (560 L/s). This reduction
of intake airflow also reduces
economizer cooling capacity and
enthalpy control could disable airflow to/from the building when fans mechanical cooling energy savings.
economizer operation during cool, rainy are off or when they operate during
weather and miss valuable hours of unoccupied hours. Less obviously, but Building pressure can be controlled
integrated economizer operation and sometimes more importantly, return-air (for example) using barometric relief
forgo mechanical cooling savings. dampers also should close tightly to dampers, modulated relief fans, or
reduce return-air recirculation during return fans with modulated relief
In moist climates with warm to very integrated economizer operation. dampers. [6] Each approach has its
hot temperatures, differential dry-bulb Recirculating return air reduces the advantages and disadvantages, but
control is not allowed because it could cooling capacity of the outdoor air, using an airside economizer
result in many hours of economizer increasing mechanical cooling hours necessitates some method of building
operation when outdoor air is cool but and energy use. pressure control.
very damp. This would increase latent
load and mechanical cooling energy,
Section 6.5.1.1.5: Relief of excess Section 6.5.1.3: Integrated
and would result in an unacceptably
outdoor air. Airside economizer economizer control. To comply
high relative humidity in the space.
systems must be designed so that with Standard 90, economizer
The choice of control type depends excess building pressure can be operation must be integrated with
largely on the tradeoff between first relieved. When more-than-minimum mechanical cooling operation (as
cost and operating cost. However, outdoor air enters the building during discussed above), so that when
space relative humidity performance economizer cooling modes, more-than- conditions permit, outdoor air provides
also should be considered. In constant- minimum relief air must leave the part of the required cooling capacity
volume applications, it may rise
significantly during part-load cooling, Figure 6. Standard 90s requirement for integrated economizer operation
depending on both control type and
system type. (See the Decisions,
Decisions inset, p. 5.)

Section 6.5.1.1.4: Dampers.


Airside systems must use return- and
outdoor-air dampers selected for low
leakage. Obviously, outdoor-air
dampers should close tightly to reduce

6 Trane Engineers Newsletter volume 352 providing insights for todays HVAC system designer
while mechanical cooling provides the because outdoor air enters the
balance. In other words, economizer system via the cooling fan (rather References
systems must include both a than the heating fan). [1] ANSI/ASHRAE/IESNA Standard
modulated economizer mode AND an 90.12004. Energy Standard for
integrated economizer mode. One important exception to this Buildings Except Low-Rise
requirement allows VAV systems to Residential Buildings. Atlanta, GA:
ASHRAE.
The integrated economizer mode must use airside economizers even though
be used for all systems, with these lowering the supply-air temperature [2] ANSI/ASHRAE Standard 62.12004.
exceptions: may increase zone-level heating. This Ventilation for Acceptable Indoor Air
exception is justified because the fan Quality. Atlanta, GA: ASHRAE.
(a) some unloading DX systems that
uses less energy to deliver cooling air
reduce outdoor airflow to prevent [3] ASHRAE. 2004. Standard 90.12004
to those zones that need cooling. The Users Manual. Atlanta, GA:
coil frosting;
fan energy saved by lowering the ASHRAE.
(b) DX units with cooling capacities supply-air temperature offsets the
less than 65,000 Btu/h (19 kW); reheat energy used by those few zones [4] ASHRAE Guideline 162003.
Selecting Outdoor, Return, and
and, that need heat. Relief Dampers for Air-Side
(c) systems located in climates Economizer Systems. Atlanta, GA:
ASHRAE.
with limited hours of integrated
economizer operation (Figure 6). [5] Trane. 2000. Advanced System
Ultimately, you have Control Strategies. Engineers
Ironically, since Exception (c) covers Newsletter Live broadcast (APP-
choices APV004-EN, VHS format). Available
most climates in the continental United
States, Standard 90 only requires at www.trane.com/bookstore.
Should your kitchen window open? If
integrated economizer operation for so, when should you open it? When [6] Stanke, D. 2002. Managing the Ins
systems in the Southwest and on the should you close it? and Outs of Commercial Building
West Coast. Even so, integrated Pressurization. Engineers
economizer systems should still be Newsletter 31-2. La Crosse, WI:
For a given building in a given location
Trane.
considered because they do reduce with an established system cooling
mechanical cooling energy. Energy and capacity, Standard 90 either requires [7] Trane. 2006. HVAC Systems and
economics should be analyzed for each an economizer system or leaves that Airside Economizers. Engineers
specific building and its HVAC system decision to the designer. The type of Newsletter Live broadcast. Check
and economizer control type. After all, www.trane.com/bookstore for
high-limit control may be somewhat availability.
just because youre not required to restricted, but many options remain.
open the kitchen window doesnt Although high-limit shutoff settings are
mean that its a bad idea. prescribed, the designer might still be
able to justify a different high-limit
Section 6.5.1.4: Economizer heating settingone that saves more energy
system impact. Economizer system for the project at hand.
controls must not result in increased
building heating energy. This Altogether, the combination of a few
requirement may limit system choices. restrictions and so many options can
For instance, an airside economizer complicate the design of an effective
used with a single-fan, dual-duct VAV airside economizer system. Designers
system or multizone system would would do wellfor their clients, for
lower the air temperature entering the building occupants, and for Earthto
heating coil and increase the required thoroughly analyze the alternatives and
heating energy. On the other hand, an make economizer system choices
airside economizer does not impact using sound engineering judgment,
heating energy when used with a available systems, and accurate
dual-fan, dual-duct VAV system modeling tools.

By Dennis Stanke, staff applications engineer,


and Brenda Bradley, information designer, both of
Trane. You can find this and previous issues of the
Engineers Newsletter at http://www.trane.com/
engineersnewsletter. To comment, e-mail us at
comfort@trane.com.

providing insights for todays HVAC system designer Trane Engineers Newsletter volume 352 7
Trane
www.trane.com

For more information, contact your local Trane


office or e-mail us at comfort@trane.com

Trane believes the facts and suggestions presented here to be accurate. However, final design and
application decisions are your responsibility. Trane disclaims any responsibility for actions taken on
the material presented.

8 Trane Engineers Newsletter volume 352 ADM-APN020-EN (May 2006)

Вам также может понравиться