Вы находитесь на странице: 1из 10

providing insights for todays hvac system designer

Engineers Newsletter volume 42 2

Understanding Single-Zone VAV Systems

Traditionally, single-zone VAV has been packaged rooftop units or direct expansion
Single-zone variable-air-volume (VAV)
used for larger, densely occupied zones (DX) split systems, fan-coils, classroom unit
is not a new concept, but due to new
energy code requirements and greater that have variable cooling loads. Common ventilators, and water-source heat pumps.
attention to reducing energy use, it is examples include gymnasiums, cafeterias,
being applied more frequently. This EN lecture halls, auditoriums, large meeting
will review these new requirements, rooms, churches, and arenas. Therefore, it
discuss the benefits and challenges of
has been available primarily in larger air- Requirements of ASHRAE
single-zone VAV systems, and identify
common applications for this system. handling units and large, packaged rooftop Standard 90.1
equipment. This type of equipment has
long been available with variable-speed Requirements for VAV control in single-zone
A conventional, single-zone constant- fans and cooling/heating that can be systems were added to the 2010 edition of
volume system uses a temperature staged or modulated to control discharge- ANSI/ASHRAE/IESNA Standard 90.1,
sensor in the zone to vary cooling or air temperature. Energy Standard for Buildings Except Low-
heating capacity, while the supply fan Rise Residential Buildings.1 This is
delivers a constant quantity of air However, due to increased focus on especially significant because the U.S.
whenever the system is operating. reducing energy use, single-zone VAV is Department of Energy has mandated that
starting to be used more often in K-12 each state must update its commercial
In a single-zone VAV system, however, classrooms, retail stores, dormitories, and building code to meet or exceed Standard
the temperature sensor in the zone is even offices. As its popularity has 90.1-2010 by Oct. 18, 2013.
used to vary the cooling or heating increased for these smaller zones, this
capacity and the airflow delivered by functionality is beginning to be offered in These requirements are included in the
the supply fan to maintain supply-air smaller equipment, such as small mandatory provisions of Section 6.4. This
temperature at a desired setpoint means that projects must comply with the
(Figure 1). requirements for single-zone VAV control,
regardless of whether the Simplified
Figure 1. Single-zone VAV system Approach (by reference from Section 6.3),
prescriptive path (Section 6.5), or Energy
Cost Budget (Section 11) is used for
compliance.

Section 6.4.3.10 (see inset, p.2) includes


T
zone two parts: the first addresses systems that
use chilled water for cooling, while the
variable-speed second part addresses systems that use
supply fan direct expansion.
T

controller

2013 Trane, a business of Ingersoll Rand. All rights reserved. 1


Section 6.4.3.10 (Single Zone Figure 2. Example SZVAV control with variable-speed fan
Variable-Air-Volume Controls) of
design
ASHRAE Standard 90.1-2010. maximum SAT for heating airflow

supply-air temperature setpoint

w
HVAC systems shall have variable airflow

flo
controls as follows:

su

air
SA
pp

ly
se
ly

pp

supply fan airflow


t
(a) Air-handling and fan-coil units with

po
air

su
in
flo
chilled-water cooling coils and supply

t
w
fans with motors greater than or equal to
5 hp shall have their supply fans minimum
controlled by two-speed motors or airflow limit

SA
variable-speed drives. At cooling

T
se
demands less than or equal to 50%, the

t
po
supply fan controls shall be able to

in
t
reduce the airflow to no greater than the
larger of the following:
design SAT for cooling
One-half of the full fan speed, or
design zone design zone
The volume of outdoor air required to heating load zone sensible load cooling load
meet the ventilation requirements of
Standard 62.1.
System Operation Depending on the outdoor conditions, as
(b) Effective January 1, 2012, all air- the SAT setpoint increases, eventually
conditioning equipment and air-handling
Figure 2 depicts an example control no mechanical cooling is needed to
units with direct expansion cooling and a sequence for a single-zone VAV system make this temperature, so the
cooling capacity at AHRI conditions that uses a variable-speed fan. (Note compressors are turned off. And even
greater than or equal to 110,000 Btu/h that control can vary by manufacturer,
that serve single zones shall have their
the airside economizer modulates back
and there are nuances that depend on to bring in only the minimum outdoor
supply fans controlled by two-speed
motors or variable-speed drives. At whether chilled water or DX is used for airflow required for ventilation. When
cooling demands less than or equal to cooling and whether the type of heater that happens, and the load continues to
50%, the supply fan controls shall be used can support variable airflow.) decrease, the zone temperature begins
able to reduce the airflow to no greater
than the larger of the following: to drop below the zone cooling setpoint,
When the zone is at design sensible
into the deadband between cooling and
Two-thirds of the full fan speed, or cooling load (right-hand side of the
heating setpoints. The fan continues to
The volume of outdoor air required to chart), this system delivers maximum
operate at minimum airflow, with no
meet the ventilation requirements of supply airflow at the design supply-air
compressors or heaters operating, and
Standard 62.1. temperature (SAT) for cooling (e.g.,
the zone temperature is allowed to float
55F). As the zone cooling load
Note from the author: In part (a) above, within this deadband.
the phrase, At cooling demands less
decreases, supply airflow is reduced as
than or equal to 50% may be needed to maintain the desired Now consider what happens when the
confusing, so the Standard 90.1 Users temperature in the zone. This is zone eventually requires heatingthat
Manual clarifies by stating the following:2 accomplished by varying the speed of is, when the zone temperature drops to
the fan motor. Cooling capacity is then the heating setpoint. The fan continues
The term cooling demand refers
to the zone sensible cooling load. staged or modulated to maintain SAT to operate at minimum airflow and the
That is, when the zone sensible at the same design setpoint. If the SAT setpoint is reset even further
cooling load decreases to 50% of system has an airside economizer, the upward. Heating capacity is staged or
the design sensible cooling load for economizer may provide all or part of
the zone, the supply fan controls modulated to maintain this supply-air
shall have reduced airflow to the
the cooling needed to achieve the SAT temperature.
threshold described. setpoint.
Eventually, the zone heating load may
In addition, the Users Manual clarifies Eventually, the zone sensible cooling increase to the point where the SAT
that the supply fan can be controlled by load decreases to the point where
either a two-speed motor, an
reaches a pre-set maximum limit (also
supply airflow reaches a minimum limit discussed on p.3). As the zone heating
electronically commutated motor (ECM),
or a variable-frequency drive (VFD). (discussed on p.3). As the cooling load load continues to increase, supply
continues to decrease, the fan remains airflow is again increased, while heating
at minimum airflow, but now the SAT capacity is staged or modulated to
setpoint is gradually reset upward to maintain the SAT at this maximum limit.
avoid overcooling the zone.

2 Trane Engineers Newsletter volume 42-2 providing insights for todays HVAC system designer
Minimum airflow. The minimum airflow ventilation performance, requiring more Figure 4 depicts an example control
limit (Figure 2) might be determined by how outdoor air to be brought in through the sequence when using a two-speed fan.
far the variable-frequency drive (VFD) or system intake. When the thermostat calls for both stages
electronically commutated motor (ECM) of cooling, the supply fan operates at high
can be turned down. This will be equipment One way to limit or avoid this effect is to speed with both compressors on. When
specific, and might be to ensure motor deliver the air at a not-so-hot only one stage of cooling is needed, the
reliability, or in the case of DX equipment, temperature during heating. In this case, fan turns down to operate at low speed
to ensure reliability of the refrigeration the maximum supply temperature for with only one compressor on. Then when
system. Alternatively, for some applications heating might be set to 15F above the the thermostat calls for no cooling, the fan
this limit might need to be high enough to zone setpoint. continues to operate at low speed with
meet some air distribution requirement. both compressors shut off.
Constant airflow when heating. For
Standard 90.1 (see inset, p.2) requires this some equipment, the type of heater Finally, if the thermostat calls for heat, the
minimum airflow to be no higher than one- available may not be able to fan operates at high speed and the heater
half of design airflow for chilled-water accommodate variable airflow. In that turns on. When the zone warms up, the
equipment, or two-thirds of design airflow case, the control sequence will vary thermostat shuts off the heater and the
for DX. But if the outdoor airflow required to airflow when cooling, but then increase to fan returns to operate at low speed.
meet Standard 62.1 is higher than this some constant airflow whenever the
minimum threshold, the higher ventilation- heater is activated (Figure 3). Like with variable-speed fan control, the
related airflow can be used to avoid minimum airflow at low fan speed might
underventilating the zone. When the zone temperature drops to be determined by equipment design, for
heating setpoint, the fan ramps up to full safety or reliability reasons. But Standard
Maximum supply temperature when speed, and the heater is cycled on or 90.1 requires this minimum airflow to be
heating. The maximum supply-air staged to warm up the zone. Once the no higher than two-thirds of design airflow
temperature (Figure 2) might be zone temperature rises back up to the for DX equipment or one-half of design
determined by the equipment deadband between heating and cooling airflow for chilled water.
manufacturer, for safety or reliability setpoints, the heater turns off and the fan
reasons. Alternatively, for some again backs down to minimum speed.
applications this temperature might be Ventilation Control
limited to minimize stratification when Two-speed fan control. Standard 90.1
supplying hot air from overhead diffusers. states that the supply fan can use either a Another important aspect of system
variable-speed or two-speed motor. The control involves ensuring proper zone
When both supply-air diffusers and return most common implementation of a two- ventilation at all operating conditions.
grilles are mounted in the ceiling, and the speed motor is probably a DX unit that
supply air is hot, the buoyancy of this hot air With a constant-speed fan, proper
has either two compressors or one two-
causes some of it to stay up near the ventilation is achieved by setting the
stage compressor. This allows the
ceiling, and bypass from the supply position of the outdoor-air damper during
equipment to be used with a conventional
diffusers to the return grilles. This bypass startup and balancing. But with a variable-
thermostat (with COOL1/COOL2 control).
can cause comfort problems, and impacts speed fan, it is no longer that simple.

Figure 3. Example SZVAV control with variable-speed fan and constant airflow Figure 4. Example SZVAV control with two-speed fan
when heating
design design
supply airflow airflow high fan speed high fan speed airflow
stages of cooling or heating capacity
supply-air temperature setpoint

both compressors
flo

ON
air

heating capacity heater ON


ly

supply fan airflow


pp

supply fan airflow


su

low fan speed minimum


airflow

minimum one compressor ON


airflow limit
SA
T
se
tp
oi
n t

both compressors
OFF
design SAT for cooling

design zone design zone


heating load zone sensible load cooling load

providing insights for todays HVAC system designer Trane Engineers Newsletter volume 42-2 3
To demonstrate, Figure 5 depicts the the desired quantity of outdoor air enters necessary with a traditional, constant-
static pressure as air moves through through the outdoor-air damper. volume system.
the various components of simple,
single-zone VAV system. In a single-zone VAV system, supply To address this issue and ensure
airflow is reduced during part-load proper ventilation in a single-zone VAV
The supply fan must create a high operation. Pushing less air through the system, consider one of the following
enough pressure at the fan discharge supply ductwork and diffusers results in approaches.
(A) to overcome the pressure losses less pressure loss, so the fan does not
associated with pushing the air through have to create as high a pressure at the Two-position OA damper control.
the supply ductwork and diffusers, and fan discharge (D). For a system with two-speed fan
into the zone. control (Figure 4), two position
In the same manner, moving less air
setpoints can be used to control the
In addition, the fan must create a low through the return-air path also results in
outdoor-air damper.
enough pressure at its inlet (B) to less pressure loss. This causes the static
overcome pressure losses associated pressure inside the mixing box (E) to When the fan is operated at high
with drawing the return air out of the increase. In other words, it is not as speed, the OA damper position is set
zone and through the return-air path negative as at design airflow. to bring in the quantity of outdoor air
(which might include a return grille, required by code. Then, when the
ceiling plenum, and some ductwork), The static pressure inside the mixing box
controller switches the fan to low
and then to draw the air through the (E) has a direct effect on how much
speed, the OA damper is opened
return-air damper, filter, and coils inside outdoor air enters the system. If the
more, in order to bring in the same
the air-handling or rooftop unit. outdoor-air damper remains set at a fixed
quantity (cfm) of outdoor air.
position, the quantity of outdoor air
For this example system, the mixing entering through this damper will Note that these are minimum position
box is where outdoor air mixes with the decrease because the pressure inside the setpoints. If the system includes an
recirculated air. Due to the pressure mixing box is not as negative. The result is airside economizer, the OA damper
drop through the return-air path and that outdoor airflow will decrease as may be opened farther when
damper, the static pressure inside this supply airflow is reduced. conditions are suitable for
mixing box (C) is negative (lower than economizing.
the pressure outside the building). This To ensure that the same quantity (cfm) of
causes outdoor air to be drawn into this outdoor air enters the system, the
outdoor-air damper needs to be opened Proportional control of OA damper.
mixing box. During startup and
farther when supply airflow is reduced. For a system with variable-speed fan
balancing, the return damper is
This requires designing and programming control, one solution could be to
adjusted so that the pressure inside the
a control sequence that was not modulate the position of the outdoor-
mixing box is low enough to ensure that
air damper in proportion to the
changing supply fan speed (Figure 6).
This is a relatively inexpensive solution,
Figure 5. Need for ventilation control in SZVAV system
so it is likely to be used in many of the
smaller, single-zone VAV applications.
OA
mixing With the system operating at design
box
SA
supply airflow (maximum fan speed),
RA the OA damper position is set to bring
in the quantity of outdoor air required
return-air grille, filter, supply ductwork, by code. Then with the system
static pressure (relative to outside)

ceiling plenum, coil diffusers operating at minimum airflow


return ductwork
(minimum fan speed), the OA damper
is opened more, in order to bring in the
zone

zone

A des
ign same quantity of outdoor air.
su pply
D airf
+
return-air supply low During system operation, the controller
damper fan reduced modulates the position of the OA
supply a
E irflow
damper in proportion to the change in
supply airflow, which is determined
C
from the signal sent to the variable-
B speed drive on the fan. Again, this is the
Static pressure inside the mixing box (E) increases (less negative) as supply minimum damper position, so it may be
airflow is reduced, so the OA damper must open farther as supply airflow opened farther when conditions are
is reduced.
suitable for economizing.

4 Trane Engineers Newsletter volume 42-2 providing insights for todays HVAC system designer
This method is not perfectly accurate However, outdoor airflow
over the entire range of airflows, since measurement does increase the cost Fixed-position OA damper and
SZVAV
damper performance is nonlinear. And of the system, so it is more likely to be
it does not account for outside used in larger systems. ASHRAE Standard 62.1-2010, Section
influences like wind or stack effect. 5.3, states: 3

Therefore, it does result in some over- Dedicated OA delivered directly to The system shall be designed to
ventilation in the middle of the fan each zone. The three previous maintain no less than the
speed range, but much less over- approaches are suitable for a piece of minimum outdoor airflow as
ventilation than if a fixed-position required by Section 6 under any
equipment that has a mixing box and load condition. Note: Variable Air
damper were used (see inset). outdoor-air dampersuch as a Volume (VAV) systems with fixed
packaged rooftop unit, air-handling unit, outdoor air damper positions must
One way to minimize this inaccuracy is comply with this requirement at
or classroom unit ventilator.
to add a third damper position setpoint minimum system primary airflow.
for some intermediate fan speed But most models of fan-coils or water- This means that the OA damper position
(Figure 6). This ensures proper source heat pumps just have a single must be set to bring in the minimum
ventilation at this intermediate speed, inlet openingno mixing box or required outdoor airflow when the fan is
and minimizes any over-ventilation by operating at minimum speed, which
outdoor-air damper. Ventilation is results in significant over-ventilation and
shrinking the ranges between typically provided by a dedicated increased energy use when the fan
setpoints. outdoor-air system. operates at higher speeds (Figure 6).

Flow-measuring OA damper. In some applications, the dedicated OA


system delivers the conditioned is reduced. Therefore, outdoor airflow
Another method for controlling
outdoor air to the inlet side of each will decrease as supply airflow is
ventilation is to measure the outdoor
local heat pump or fan-coil (Figure 8). reduced.
airflow and control it directly. This is
typically accomplished by using a flow- An added challenge is that the outdoor
measuring device in the outdoor air For a horizontal-style unit, the air might
be ducted to discharge into the open air is delivered by a separate fan, and
stream, such as an airflow the pressure inside the ventilation
measurement station or a flow- ceiling plenum, near the intake of the
unit. For a vertical-style unit, it might be ductwork is influenced by the changing
measuring damper (Figure 7). operation of all the local fans served by
ducted to a closet where the unit is
installed. In either case, the outdoor air the ventilation system.
This method is more accurate over the
range of airflow, and can respond to mixes with recirculated air in the
With this configuration, to ensure that
pressure fluctuations caused by wind plenum or closet before being drawn in
the required quantity of outdoor air is
or stack effect. This approach has the through the intake of the heat pump or
delivered, a pressure-independent VAV
added benefit of providing a means to fan-coil.
terminal should be installed in the
document the outdoor airflow brought ventilation duct for each zone (Figure 8).
into the system over time. As described earlier (Figure 5), if the
local unit has a two-speed or variable- As the local fan speed changes, this
speed fan, the static pressure at its damper modulates to maintain the
inlet is not as negative when fan speed same outdoor airflow, regardless of
fan speed.

Figure 6. Proportional control of OA damper Figure 7. Flow-measuring OA damper

OA damper position
at minimum fan speed fixed-position OA damper
OA damper position

OA damper position
at intermediate fan speed intermediate
speed
OA damper position
min speed max speed
at maximum fan speed
supply fan speed

providing insights for todays HVAC system designer Trane Engineers Newsletter volume 42-2 5
Alternatively, consider delivering the lower than the building component of Figure 8. Conditioned OA delivered to
inlet of each local unit
conditioned outdoor air directly to each the ventilation rate (Ra Az) for that
zone, rather than to the inlet of the fan- zone. dedicated OA
OA
coils or heat pumps (Figure 9). In this unit
case, the local units condition only Section 8.3 clarifies that this applies
CA
recirculated air. whenever that zone is expected to
CA
be occupied. That is, the standard is
Because the outdoor air is not not requiring this building component CA
RA
SA
distributed through the local fan, that of the ventilation rate to be delivered to SA
fan can operate with a two-speed or the zone 24 hours a day, 7 days a
variable-speed motor, without week. Rather, it only requires this Pressure-independent VAV terminals
maintain constant outdoor airflow,
impacting the quantity of outdoor air during the normally scheduled regardless of local fan speed.
delivered to the zone. occupied period. RA

This direct-to-the-zone approach also Because the mixing box pressure WSHP or
fan-coil
affords the opportunity to deliver the varies as supply airflow changes
outdoor air at a cold temperature, (Figure 5), DCV must be combined
Figure 9. Conditioned OA delivered to
rather than reheated to neutral. This with either proportional damper control directly to each zone
has several installed cost and energy- or a flow-measuring damper in order to
saving benefits.4,5 prevent outdoor airflow from dropping OA
dedicated OA
below this minimum threshold. unit
CA
CO2-based DCV. Single-zone VAV
A previous EN and the Standard 62.1
systems are often used for densely
Users Manual both describe a CA CA
occupied zones with varying RA
proportional control sequence that can SA
population. This typically makes them
be used to implement DCV in a single- SA
good candidates for using CO2-based
zone system.6,7 Local fans can operate with
demand-controlled ventilation (DCV).
two-speed or variable-speed control,
With this approach, a sensor measures without impacting outdoor airflow.
RA
the concentration of CO2 in the zone, Potential Benefits of
and this concentration is then used by WSHP or
the controller to reset outdoor airflow
SZVAV fan-coil

as population changes. This saves Compared to a constant-volume


energy by not over-ventilating the zone system, typical benefits of single-zone
For this example, two-speed fan
during periods of partial occupancy. VAV include lower energy use, better
control (constant fan speed when
dehumidification at part load, and less
While Standard 62.1 allows the use of heating) reduced HVAC energy use by
fan-generated noise at reduced
DCV, it also includes a few about 25 percent, while variable-speed
speeds.
requirements to make it work:3 fan control (capable of variable fan
speed when heating) reduced HVAC
The breathing zone outdoor airflow Lower energy use. Compared to a energy use by about 30 percent.
shall be reset in response to current constant-volume system, a single-zone
occupancy and shall be no less than the VAV system can result in significant fan Of course, the impact of two-speed or
building component (Ra Az) of the energy savings at part-load conditions. variable-speed fan control on the
zone. (Section 6.2.7.1.2) energy use of a specific building
Figure 10 shows the potential energy depends on climate, building layout,
Systems shall be operated such that savings of using two-speed or variable- and operating hours. For this example,
spaces are ventilated in accordance speed fan control in an example single- high internal loads in the classrooms
with Section 6 when they are expected story K-12 school. TRACE 700 was resulted in systems operating in
to be occupied. (Section 8.3) used to model the building with a cooling mode for most occupied hours
packaged rooftop unit serving each (even in Minneapolis). Operation of the
While the people component of the zone.8 The baseline building uses heater was mostly limited to morning
ventilation rate (Rp Pz) can be varied, conventional, constant-volume warm-up mode.
Standard 62.1 states that the controller rooftops.
cannot reduce outdoor airflow any

6 Trane Engineers Newsletter volume 42-2 providing insights for todays HVAC system designer
For applications with more occupied reducing airflow delivered to the zone, Another method for improving part-
hours of operation in the heating while maintaining a constant supply-air load dehumidification could be to add
mode, the difference in energy use temperature. At this same example hot gas reheat (HGRH). In order to limit
between two-speed and variable- part-load condition, supply airflow is space relative humidity to 60 percent, a
speed fan control will likely be larger, reduced from 1500 cfm to 900 cfm, constant-volume system will over-cool
since the two-speed fan operates at while the system still delivers the air at the air to further dehumidify, and then
high speed whenever the heater is on. 55F. reheat it to prevent overcooling the
zone. This requires more compressor
Reducing the airflow allows the system energy, along with more fan energy
Better dehumidification at part
to continue supplying the air at a cool (Table 1).
load. Compared to a constant-volume
temperature, so the coil removes more
system, a single-zone VAV system
moisture. At this part-load condition, For many applications, the variable-
improves dehumidification
because the supply air is still cool and speed fan may do an adequate job of
performance because it continues to
dry, the relative humidity in the limiting indoor humidity levels, so that
deliver cool, dry air at part-load
classroom rises to only 57 percent with the system may not require any other
conditions.
the variable-speed fan, compared to 67 dehumidification enhancementssuch
To demonstrate this benefit, Figure 11 percent with the constant-speed fan as hot gas reheat.
compares the performance of two (Figure 11).
However, if a project requires lower
systems serving an example
In this comparison, for the variable- humidity levels than a single-zone VAV
classroom in Jacksonville, Florida.9 At
speed fan system, the load on the system can achieve, some types of
cooling design conditions, this system
cooling coil is 4 tons and the fan moves equipment can be equipped with hot
mixes 450 cfm of outdoor air with 1050
900 cfm. So achieving this lower gas reheat also. In that case, the
cfm of recirculated air, then delivers
humidity level requires a bit more variable-speed fan may limit humidity
the resulting 1500 cfm of supply air to
compressor energy, while benefitting most of the time, but the reheat can be
the classroom.
from much lower fan energy (Table 1). used if needed.
At the part-load, peak dew point
As another point of comparison, on a In the case of fan-coils or water-source
condition, it is not as hot outside, but
mild rainy day, the variable-speed fan heat pumps, a more efficient approach
more humid. The system with a
results in much better dehumidification would typically be to use the dedicated
constant-speed fan (CV) continues to
in this same example classroom60 outdoor-air system to dehumidify the
supply a constant volume of air to the
percent RH, compared to 73 percent outdoor air centrally, rather than equip
zone (1500 cfm). Meanwhile, as the
RH with a constant-speed fan (Table 1). each local unit with reheat.4,5
sensible cooling load in the zone
decreases, the compressor cycles on
and off, resulting in warmer air
delivered to the zone63F for this
example load condition.
Figure 10. Example energy savings from two-speed or variable-speed fan control
Although delivering this warmer air K-12 school
prevents over-cooling the zone, the 100
constant-speed fan
cycling compressor results in a warmer
HVAC energy consumption, % of base

average coil temperature and less 80


two-speed fan
moisture removed. This 63F air has
variable-speed fan
not been dehumidified as much as if it
was cooled down to 55F. This warmer, 60
wetter supply air causes zone relative
humidity to rise to 67 percent at this
40
part-load condition.

In contrast, at part-load conditions, as 20


the sensible cooling load in the zone
decreases, the system with a variable-
speed fan (SZVAV) responds by first 0
Atlanta Minneapolis St. Louis

providing insights for todays HVAC system designer Trane Engineers Newsletter volume 42-2 7
Less fan-generated noise at reduced Figure 11. Improved dehumidification at part load for an example classroom in
Jacksonville, FL
fan speeds. Air distribution
equipment, including fans, ductwork, 180
CV SZVAV
and diffusers, can have a significant OA 84F DB, 84F DB,
impact on background sound levels in 76F DP 76F DP 160
80
(450 cfm) (450 cfm) peak DP
occupied spaces.
140
RA 74F DB, 74F DB,
Because the fan operates at reduced 67% RH 57% RH 120
speed, a single-zone VAV system 70
MA 77F DB 79F DB MA
benefits from less fan-generated noise MA 100

at part-load conditions. The actual SA 63F DB 55F DB


(1500 cfm) (900 cfm) 60 80
sound level depends on the type of (3.7 tons) (4.0 tons) RA
SA
fan, operating conditions, and 50
RA 60
installation. But, in general, as fan SA
40 40
speed decreases, the sound level will
30
also decrease. 20

30 40 50 60 70 80 90 100 110

Application Considerations
In order to realize these benefits, the
specific application must be well-suited Design air distribution system to Ensure proper ventilation as supply
to using single-zone VAV. Following are accommodate variable airflow. Use airflow changes. For smaller
some of the challenges or diffusers that will provide proper air systems, two-position or proportional
considerations when applying this type distribution at reduced airflows. damper control is more likely to be
of system. Diffusers that are appropriate for used, while larger systems may use an
conventional VAV systems are probably airflow-measurement device, such as a
Loads throughout a large zone must best suited. flow-measuring damper.
be fairly uniform. This is a single-zone
Keeping duct runs as short and When a dedicated outdoor-air system
system, responding to a single
symmetric as possible is good general is used, consider delivering the
temperature sensor, so it does not
guidance. Systems with longer or conditioned outdoor air directly to each
have the capability to satisfy
asymmetric duct runs do not zone, rather than to the inlet of the
simultaneous heating and cooling
necessarily prohibit the use of single- local equipment.
requirements.
zone VAV, but they are more
susceptible to unequal airflows If implementing demand-controlled
If the loads throughout a large zone are
between diffusers as the supply fan ventilation, be sure to provide some
not fairly uniform, it may result in
modulates. method to vary relief (exhaust) airflow
undesirable temperature variations in
to prevent negative building pressure
some areas of the zone that are farther
when DCV reduces the intake airflow.
away from the temperature sensor.
Likewise, if a zone has some type of
minimum exhaust requirementsuch
Table 1. Part-load dehumidification comparison: CV versus SZVAV as a restroom, kitchen, or locker
constant-speed variable-speed constant-speed fan roomDCV should not be allowed to
fan fan with HGRH reduce intake airflow any lower than
peak DPT the required exhaust, unless the zone
(84F DBT, 76F DPT) receives makeup air from some other
zone humidity, %RH 67% 57% source.
cooling load, tons 3.7 4.0
fan airflow, cfm 1500 900
mild, rainy
(70F DBT, 69F WBT)
zone humidity, %RH 73% 60% 60%
cooling load, tons 1.6 1.9 2.4
fan airflow, cfm 1500 750 1500

8 Trane Engineers Newsletter volume 42-2 providing insights for todays HVAC system designer
Consider system operation when
heating. ASHRAE 90.1 addresses References
single-zone VAV during cooling
[1] American Society of Heating, Refrigerating, Engineers
operation. If variable airflow is also
desired during heating operation, the
and Air-Conditioning Engineers (ASHRAE).
ANSI/ASHRAE/IESNA Standard 90.1-2010:
Newsletter
equipment will likely require some type
of modulating heat, such as a
Energy Standard for Buildings Except Low-
Rise Residential Buildings.
LIVE!
For event details and registration
modulating gas heater or a hot-water [2] American Society of Heating, Refrigerating contact your local Trane office.
heating coil. and Air Conditioning Engineers, Inc.
(ASHRAE). Standard 90.1-2010 Users Manual. Upcoming 2013
Otherwise, if the equipment has on/off
gas or electric heat, the manufacturer [3] American Society of Heating, Refrigerating,
may require it to operate at full airflow and Air-Conditioning Engineers (ASHRAE).
ANSI/ASHRAE Standard 62.1-2010: Ventilation
Single-Zone VAV
whenever the heater is activated for Acceptable Indoor Air Quality. Systems
(Figure 3). Therefore, check with the
manufacturer when specifying or [4] Murphy, J. and B. Bakkum. Water-Source and
purchasing single-zone VAV equipment. Ground-Source Heat Pump Systems, All-Variable-Speed
application manual SYS-APM010-EN, 2011.
Plant Control
Variable-speed fan control requires a [5] Murphy, J., P. Solberg, M. Schwedler, and J.
zone temperature sensor. A Harshaw, Energy-Saving Strategies for Water-
Source and Ground-Source Heat Pump
conventional thermostat (with COOL1/ Systems, Engineers Newsletter Live program
COOL2 control) can typically be used (2012).
for two-speed fan control, but variable-
speed control requires a zone [6] Murphy. J. and B. Bradley. CO2-Based
Demand-Controlled Ventilation with ASHRAE
temperature sensor connected to the
Standard 62.1. Engineers Newsletter 34-5
unit controller. (2005).

This is important to communicate [7] American Society of Heating, Refrigerating


when specifying or purchasing single- and Air Conditioning Engineers, Inc.
zone VAV equipment. If replacing an (ASHRAE). Standard 62.1-2010 Users Manual.

older piece of equipment (controlled by [8] Trane Air-Conditioning and Economics


a conventional thermostat) with a new, (TRACE 700). Available at www.trane.com/
variable-speed fan unit, this will likely TRACE
require replacing the thermostat with a
[9] Murphy, J. and B. Bradley. Dehumidification in
zone sensor. Wireless zone sensors
HVAC Systems, application manual SYS-
make this much easier, especially for APM004-EN, 2002.
those projects where pulling wires may
be difficult.

By John Murphy, applications engineer, and


Beth Bakkum, information designer, Trane. You
can find this and previous issues of the Engineers
Newsletter at www.trane.com/
engineersnewsletter. To comment, e-mail us at
comfort@trane.com.

providing insights for todays HVAC system designer Trane Engineers Newsletter volume 42-2 9
www.Trane.com/bookstore
Learn HVAC design strategies and earn credit

Air conditioning clinics. A series of educational presentations that teach


HVAC fundamentals, equipment, and systems. The series includes full-
color student workbooks, which can be purchased individually. Approved
by the American Institute of Architects for 1.5 (Health, Safety and
Welfare) learning units. Contact your local Trane office to sign up for
training in your area.

Engineers Newsletter Live. A series of 90-minute programs that provide


technical and educational information on specific aspects of HVAC design
and control. Topics range from water- and airside system strategies to
ASHRAE standards and industry codes. Contact your local Trane office for
a schedule or view past programs by visiting www.trane.com/ENL.

On-demand continuing education credit for LEED and AIA . These 90-
minute on-demand programs are available at no charge. The list of HVAC
topics includes many LEED-specific courses. All courses available at
www.trane.com/continuingeducation.
Application manuals. Comprehensive reference guides that can
Engineers Newsletters. These quarterly articles cover timely topics increase your working knowledge of commercial HVAC systems. Topics
related to the design, application and/or operation of commercial, range from component combinations and innovative design concepts to
applied HVAC systems. Subscribe at www.trane.com/EN system control strategies, industry issues, and fundamentals. The
following are just a few examples. Please visit www.trane.com/
bookstore for a complete list of manuals available to order.
Central Geothermal Systems discusses proper design and control of
central geothermal bidirectional cascade systems that use borefields.
This manual covers central geothermal system piping, system design
considerations, and airside considerations. (SYS-APM009-EN, February
2011)
Chilled-Water VAV Systems focuses on chilled-water, variable-air-
volume (VAV) systems. To encourage proper design and application of a
chilled-water VAV system, this manual discusses the advantages and
drawbacks of the system, reviews the various components that make up
the system, proposes solutions to common design challenges, explores
several system variations, and discusses system-level control.
(SYS-APM008-EN, updated May 2012)
Water-Source and Ground-Source Heat Pump Systems examines
chilled-water-system components, configurations, options, and control
strategies. The goal is to provide system designers with options they
can use to satisfy the building owners desires.
(SYS-APM010-EN, November 2011)

Trane, Trane believes the facts and suggestions presented here to be accurate. However, final design and
A business of Ingersoll Rand application decisions are your responsibility. Trane disclaims any responsibility for actions taken on
the material presented.
For more information, contact your local Trane
office or e-mail us at comfort@trane.com

10 Trane Engineers Newsletter volume 42-2 ADM-APN047-EN (April 2013)

Вам также может понравиться