Вы находитесь на странице: 1из 337

Worked example of cable calculation

(see Fig. G65)

The installation is supplied through a 630 kVA transformer. The process requires a high degree of
supply continuity and part of the installation can be supplied by a 250 kVA standby generator. The
global earthing system is TN-S, except for the most critical loads supplied by an isolation transformer
with a downstream IT configuration.

The single-line diagram is shown in Figure G65 below. The results of a computer study for the circuit
from transformer T1 down to the cable C7 is reproduced on Figure G66. This study was carried out
with Ecodial (a Schneider Electric software).

This is followed by the same calculations carried out by the simplified method described in this
guide.
Fig. G65: Example of single-line diagram

Calculation using software Ecodial

General network characteristics Number of poles and 4P4d


protected poles

Earthing system TN-S Tripping unit Micrologic 2.3

Neutral distributed No Overload trip Ir (A) 510

Voltage (V) 400 Short-delay trip Im / Isd (A) 5100

Frequency (Hz) 50 Cable C3

Upstream fault level (MVA) 500 Length 20

Resistance of MV network (m) 0.0351 Maximum load current (A) 509

Reactance of MV network (m) 0.351 Type of insulation PVC

Transformer T1 Ambient temperature (C) 30

Rating (kVA) 630 Conductor material Copper

Short-circuit impedance voltage 4 Single-core or multi-core Single


(%) cable

Transformer resistance RT (m) 3.472 Installation method F

Transformer reactance XT (m) 10.64 Phase conductor selected csa 2 x 95


(mm2)

3-phase short-circuit current 21.54 Neutral conductor selected 2 x 95


Ik3 (kA)
csa (mm2)

Cable C1 PE conductor selected csa 1 x 95


(mm2)

Length (m) 5 Cable voltage drop U (%) 0.53

Maximum load current (A) 860 Total voltage drop U (%) 0.65

Type of insulation PVC 3-phase short-circuit current 19.1


Ik3 (kA)

Ambient temperature (C) 30 1-phase-to-earth fault current 11.5


Id (kA)

Conductor material Copper Switchboard B6

Single-core or multi-core cable Single Reference Linergy 800

Installation method F Rated current (A) 750

Number of layers 1 Circuit-breaker Q7

Phase conductor selected csa 2 x 240 Load current (A) 255


(mm2)

Neutral conductor selected csa 2 x 240 Type Compact


(mm2)

PE conductor selected csa 1 x 120 Reference NSX400F


(mm2)

Voltage drop U (%) 0.122 Rated current (A) 400

3-phase short-circuit current 21.5 Number of poles and 3P3d


Ik3 (kA) protected poles

Courant de dfaut phase-terre Id 15.9 Tripping unit Micrologic 2.3


(kA)

Circuit-breaker Q1 Overload trip Ir (A) 258

Load current (A) 860 Short-delay trip Im / Isd (A) 2576

Type Compact Cable C7

Reference NS1000N Length 5

Rated current (A) 1000 Maximum load current (A) 255

Number of poles and protected 4P4d Type of insulation PVC


poles

Tripping unit Micrologic 5.0 Ambient temperature (C) 30

Overload trip Ir (A) 900 Conductor material Copper

Short-delay trip Im / Isd (A) 9000 Single-core or multi-core Single


cable

Tripping time tm (ms) 50 Installation method F

Switchboard B2 Phase conductor selected csa 1 x 95


(mm2)

Reference Linergy 1250 Neutral conductor selected -


csa (mm2)

Rated current (A) 1050 PE conductor selected csa 1 x 50


(mm2)

Circuit breaker Q3 Cable voltage drop U (%) 0.14

Load current (A) 509 Total voltage drop U (%) 0.79

Type Compact 3-phase short-circuit current 18.0


Ik3 (kA)

Reference NSX630F 1-phase-to-earth fault current 10.0


Id (kA)

Rated current (A) 630

Fig. G66: Partial results of calculation carried out with Ecodial software (Schneider Electric). The calculation is

performed according to Cenelec TR50480

The same calculation using the simplified method recommended in this guide

Dimensioning circuit C1

The MV/LV 630 kVA transformer has a rated no-load voltage of 420 V. Circuit C1 must be suitable for
a current of:

per phase

Two single-core PVC-insulated copper cables in parallel will be used for each phase.These cables
will be laid on cable trays according to method F.

Each conductor will therefore carry 433A. Figure G21a indicates that for 3 loaded conductors with
PVC isolation, the required c.s.a. is 240mm2.

The resistance and the inductive reactance, for the two conductors in parallel, and for a length of 5
metres, are:

(cable resistance: 23.7 m.mm2/m)

(cable reactance: 0.08 m/m)


Dimensioning circuit C3

Circuit C3 supplies two 150kW loads with cos = 0.85, so the total load current is:

Two single-core PVC-insulated copper cables in parallel will be used for each phase. These cables
will be laid on cable trays according to method F.

Each conductor will therefore carry 255A. Figure G21a indicates that for 3 loaded conductors with
PVC isolation, the required c.s.a. is 95mm2.

The resistance and the inductive reactance, for the two conductors in parallel, and for a length of 20
metres, are:

(cable resistance: 23.7 m.mm2/m)

(cable reactance: 0.08 m/m)

Dimensioning circuit C7

Circuit C7 supplies one 150kW load with cos = 0.85, so the total load current is:

One single-core PVC-insulated copper cable will be used for each phase. The cables will be laid on
cable trays according to method F.

Each conductor will therefore carry 255A. Figure G21a indicates that for 3 loaded conductors with
PVC isolation, the required c.s.a. is 95mm2.

The resistance and the inductive reactance for a length of 20 metres is:

(cable resistance: 23.7 m.mm2/m)

(cable reactance: 0.08 m/m)

Calculation of short-circuit currents for the selection of circuit-breakers Q1, Q3, Q7

(see Fig. G67)

Circuit components R (m) X (m) Z (m) Ikmax (kA)


Upstream MV network, 500MVA fault level (see Fig. G34) 0,035 0,351

Transformer 630kVA, 4% (see Fig. G35) 2.9 10.8

Cable C1 0.23 0.4

Sub-total 3.16 11.55 11.97 20.2

Cable C3 2.37 1.6

Sub-total 5.53 13.15 14.26 17

Cable C7 1.18 0.4

Sub-total 6.71 13.55 15.12 16

Fig. G67: Example of short-circuit current evaluation

The protective conductor

When using the adiabatic method, the minimum c.s.a. for the protective earth conductor (PE) can be
calculated by the formula given in Figure G58:

For circuit C1, I = 20.2kA and k = 143.

t is the maximum operating time of the MV protection, e.g. 0.5s

This gives:

A single 120 mm2 conductor is therefore largely sufficient, provided that it also satisfies the
requirements for indirect contact protection (i.e. that its impedance is sufficiently low).
Generally, for circuits with phase conductor c.s.a. Sph 50 mm 2, the PE conductor minimum c.s.a.
will be Sph / 2. Then, for circuit C3, the PE conductor will be 95mm 2, and for circuit C7, the PE
conductor will be 50mm2.

Protection against indirect-contact hazards

For circuit C3 of Figure G65, Figures F41 and F40, or the formula given TN system - Protection
against indirect contact may be used for a 3-phase 4-wire circuit.

The maximum permitted length of the circuit is given by:

(The value in the denominator 630 x 11 is the maximum current level at which the instantaneous
short-circuit magnetic trip of the 630 A circuit-breaker operates).

The length of 20 metres is therefore fully protected by instantaneous over-current devices.

Voltage drop

The voltage drop is calculated using the data given in Figure G28, for balanced three-phase circuits,
motor power normal service (cos = 0.8).

The results are summarized on Figure G68

The total voltage drop at the end of cable C7 is then: 0.77%.

C1 C3 C7

c.s.a. 2 x 240mm2 2 x 95mm2 1 x 95mm2

0.22 0.43 0.43


U per conductor(V/A/km)

see Fig. G28

Load current (A) 866 509 255


Length (m) 5 20 5
Voltage drop (V) 0.48 2.19 0.55
Voltage drop (%) 0.12 0.55 0.14

Fig. G68: Voltage drop introduced by the different cables.


3-phase short-circuit current (Isc) at any point within a LV installation.

In a 3-phase installation Isc at any point is given by:

where

U20 = phase-to-phase voltage of the open circuited secondary windings of the power supply
transformer(s).

ZT = total impedance per phase of the installation upstream of the fault location (in )

Method of calculating ZT

Each component of an installation (MV network, transformer, cable, busbar, and so on...) is
characterized by its impedance Z, comprising an element of resistance (R) and an inductive
reactance (X). It may be noted that capacitive reactances are not important in short-circuit current
calculations.

The parameters R, X and Z are expressed in ohms, and are related by the sides of a right angled
triangle, as shown in the impedance diagram of Figure G33.

Fig. G33: Impedance diagram

The method consists in dividing the network into convenient sections, and to calculate the R and X
values for each.
Where sections are connected in series in the network, all the resistive elements in the section are
added arithmetically; likewise for the reactances, to give RT and XT.

The impedance (ZT) for the combined sections concerned is then calculated

from

Any two sections of the network which are connected in parallel, can, if predominantly both resistive
(or both inductive) be combined to give a single equivalent resistance (or reactance) as follows:

Let R1 and R2 be the two resistances connected in parallel, then the equivalent resistance R3 will
be given by:

or for reactances

It should be noted that the calculation of X3 concerns only separated circuit without mutual
inductance. If the circuits in parallel are close togother the value of X3 will be notably higher.

Determination of the impedance of each component

Network upstream of the MV/LV transformer

(see Fig. G34)

The 3-phase short-circuit fault level PSC, in kA or in MVA[1] is given by the power supply authority
concerned, from which an equivalent impedance can be deduced.

Psc Uo (V) Ra (m) Xa (m)

250 MVA 420 0.07 0.7

500 MVA 420 0.035 0.351

Fig. G34: The impedance of the MV network referred to the LV side of the MV/LV transformer
A formula which makes this deduction and at the same time converts the impedance to an
equivalent value at LV is given, as follows:

where

Zs = impedance of the MV voltage network, expressed in milli-ohms


Uo = phase-to-phase no-load LV voltage, expressed in volts
Psc = MV 3-phase short-circuit fault level, expressed in kVA

The upstream (MV) resistance Ra is generally found to be negligible compared with the
corresponding Xa, the latter then being taken as the ohmic value for Za. If more accurate
calculations are necessary, Xa may be taken to be equal to 0.995 Za and Ra equal to 0.1 Xa.

Figure G36 gives values for Ra and Xa corresponding to the most common MV[2] short-circuit levels
in utility power-supply networks, namely, 250 MVA and 500 MVA.

Transformers

(see Fig. G35)

The impedance Ztr of a transformer, viewed from the LV terminals, is given by the formula:

where:

U20 = open-circuit secondary phase-to-phase voltage expressed in volts


Sn = rating of the transformer (in VA)
Usc = the short-circuit impedance voltage of the transformer expressed in %

The transformer windings resistance Rtr can be derived from the total load-losses as follows:

so that in milli-ohms
where

Pcu = total load-losses in watts


In = nominal full-load current in amps
Rtr = resistance of one phase of the transformer in milli-ohms (the LV and corresponding MV
winding for one LV phase are included in this resistance value).

Note: for an approximate calculation, in the absence of more precise information on transformer
characteristics, Cenelec 50480 suggests to use the following guidelines:

if U20 is not known, it may be assumed to be 1.05 Un

in the absence of more precise information, the following values may be used: Rtr = 0.31 Ztr
and Xtr = 0.95 Ztr

Example: for a transformer of 630kVA with Usc=4% / Un = 400V, approximate calculation gives:

U20 = 400 x 1.05 = 420V

Ztr = 4202 / 630000 x 4% = 11 m

Rtr = 0.31 x Ztr = 3.5 m and Xtr = 0.95 x Ztr = 10.6 m

Rated Power kVA) Oil-immersed Cast-resin

Usc (%) Rtr (m) Xtr (m) Ztr (m) Usc (%) Rtr (m) Xtr (m) Ztr (m)

100 4 37.9 59.5 70.6 6 37.0 99.1 105.8

160 4 16.2 41.0 44.1 6 18.6 63.5 66.2

200 4 11.9 33.2 35.3 6 14.1 51.0 52.9

250 4 9.2 26.7 28.2 6 10.7 41.0 42.3


315 4 6.2 21.5 22.4 6 8.0 32.6 33.6

400 4 5.1 16.9 17.6 6 6.1 25.8 26.5

500 4 3.8 13.6 14.1 6 4.6 20.7 21.2

630 4 2.9 10.8 11.2 6 3.5 16.4 16.8

800 6 2.9 12.9 13.2 6 2.6 13.0 13.2

1,000 6 2.3 10.3 10.6 6 1.9 10.4 10.6

1,250 6 1.8 8.3 8.5 6 1.5 8.3 8.5

1,600 6 1.4 6.5 6.6 6 1.1 6.5 6.6

2,000 6 1.1 5.2 5.3 6 0.9 5.2 5.3

Fig. G35: Resistance, reactance and impedance values for typical distribution 400 V transformers (no-load voltage =

420 V) with MV windings 20 kV

Busbars

The resistance of busbars is generally negligible, so that the impedance is practically all reactive,
and amounts to approximately 0.15 m/metre[3] length for LV busbars (doubling the spacing between
the bars increases the reactance by about 10% only).

In practice, it's almost never possible to estimate the busbar length concerned by a short-circuit
downstream a switchboard.

Circuit conductors

The resistance of a conductor is given by the formula:


where

= the resistivity of the conductor material at the normal operating temperature

has to be considered:

at cold state (20C) to determine maximum short-circuit current,

at steady state (normal operating temperature) to determine minimum short-circuit current.

L = length of the conductor in m


S = c.s.a. of conductor in mm2

20 C PR/XLPE 90 C PVC 70 C

Copper 18.51 23.69 22.21

Alu 29.41 37.65 35.29

Fig. G35b: Values of as a function of the temperature, cable insulation and cable core material, according to

IEC60909-0 and Cenelec TR 50480 (in m mm2/m).

Cable reactance values can be obtained from the manufacturers. For c.s.a. of less than 50
mm2 reactance may be ignored. In the absence of other information, a value of 0.08 m/metre may
be used (for 50 Hz systems) or 0.096 m/metre (for 60 Hz systems). For busways (busbar trunking
systems) and similar pre-wired ducting systems, the manufacturer should be consulted.

Motors

At the instant of short-circuit, a running motor will act (for a brief period) as a generator, and feed
current into the fault.
In general, this fault-current contribution may be ignored. However, if the total power of motors
running simultaneously is higher than 25% of the total power of transformers, the influence of motors
must be taken into account. Their total contribution can be estimated from the formula:

Iscm = 3.5 In from each motor i.e. 3.5m In for m similar motors operating concurrently.

The motors concerned will be the 3-phase motors only; single-phase-motor contribution being
insignificant.

Fault-arc resistance

Short-circuit faults generally form an arc which has the properties of a resistance. The resistance is
not stable and its average value is low, but at low voltage this resistance is sufficient to reduce the
fault-current to some extent. Experience has shown that a reduction of the order of 20% may be
expected. This phenomenon will effectively ease the current-breaking duty of a CB, but affords no
relief for its fault-current making duty.

Recapitulation table

(see Fig. G36)

Parts of power-supply system R (m) X (m)

Xa = 0.995 Za
Supply network

Figure G34

Transformer

where
Figure G35

Rtr is often negligible compared to Xtr for transformers

> 100 kVA

Circuit-breaker Not considered in practice

Busbars Negligible for S > 200 mm2 in the XB = 0.15 m/m


[a]
formula:

Circuit Cables: Xc = 0.08 m/m


conductors[b]
[a]

Motors See 3-phase short-circuit current (Isc) at any point


within a LV installation Motors
(often negligible at LV)

Three-phase
maximum
circuit current in
kA

[a] = resistivity at 20C

[b] If there are several conductors in parallel per phase, then divide the resistance of one conductor by the number of

conductors. The reactance remains practically unchanged.

U20: Phase-to-phase no-load secondary voltage of MV/LV transformer (in volts).

Psc: 3-phase short-circuit power at MV terminals of the MV/LV transformers (in kVA).

Pcu: 3-phase total losses of the MV/LV transformer (in watts).

Sn: Rating of the MV/LV transformer (in kVA).

Usc: Short-circuit impedance voltage of the MV/LV transfomer (in %).

RT : Total resistance. XT: Total reactanc

Fig. G36: Recapitulation table of impedances for different parts of a power-supply system

Example of short-circuit calculations

(see Fig. G37)

LV installation R (m) X (m) RT XT


(m) (m)

0.035 0.351
MV network

Psc = 500

MVA
Transformer 20 2.35 8.5
kV / 420 V
Pn = 1000 kVA
Usc = 5%
Pcu = 13.3 x
103 watts

Single-core Xc = 2.48 9.25 Isc1 = 25 kA


cables 0.08 x 5
5 m copper = 0.40
4 x 240
mm2/phase

Main circuit- Not considered in practice


breaker

Busbars 10 m Not considered in practice

Three-core Xc = 22 17.3 Isc3 = 8.7 kA


cable 100 x
100 m 0.08 = 8
95 mm2copper

Three-core Xc = 20 59 18.9 Isc4 = 3.9 kA


cable x 0.08 =
20 m 1.6
10 mm2copper
final circuits

RT : Total resistance. XT: Total reactance. Isc : 3-phase maximum short-circuit current Calculations made a

G36

Fig. G37: Example of maximum short-circuit current calculations for a LV installation supplied at 400 V (nominal)
from a 1000 kVA MV/LV transformer

Notes

1. ^ Short-circuit MVA: EL Isc where:

EL = phase-to-phase nominal system voltage expressed in kV (r.m.s.)

Isc = 3-phase short-circuit current expressed in kA (r.m.s.)

2. ^ up to 36 kV

3. ^ For 50 Hz systems, but 0.18 m/m length at 60 Hz.


Location of protective devices.
General rule

(see Fig. G7a)

A protective device is necessary at the origin of each circuit where a reduction of permissible
maximum current level occurs.

Possible alternative locations in certain circumstances

(see Fig. G7b)

The protective device may be placed part way along the circuit:

If AB is not in proximity to combustible material, and

If no socket-outlets or branch connections are taken from AB

Three cases may be useful in practice:

Consider case (1) in the diagram

AB 3 metres, and

AB has been installed to reduce to a practical minimum the risk of a short-circuit


(wires in heavy steel conduit for example)

Consider case (2)

The upstream device P1 protects the length AB against short-circuits in accordance

Consider case (3)

The overload device (S) is located adjacent to the load. This arrangement is
convenient for motor circuits. The device (S) constitutes the control (start/stop) and overload
protection of the motor while (SC) is: either a circuit-breaker (designed for motor protection) or
fuses type aM

The short-circuit protection (SC) located at the origin of the circuit conforms with the
principles of Calculation of minimum levels of short-circuit current .
Circuits with no protection

(see Fig. G7c)

Either

The protective device P1 is calibrated to protect the cable S2 against overloads and short-
circuits

Or

Where the breaking of a circuit constitutes a risk, e.g.

Excitation circuits of rotating machines

circuits of large lifting electromagnets

the secondary circuits of current transformers

No circuit interruption can be tolerated, and the protection of the cabling is of secondary importance.

a. b.
c.

Short-circuit current at the secondary terminals of a MV/LV distribution


transformer.
The case of one transformer

In a simplified approach, the impedance of the MV system is assumed to be negligibly small,


so that:

where

and:

S = kVA rating of the transformer


U20 = phase-to-phase secondary volts on open circuit
In = nominal current in amps
Isc = short-circuit fault current in amps
Usc = short-circuit impedance voltage of the transformer in %.

Typical values of Usc for distribution transformers are given in Figure G31

Transformer rating (kVA) Usc in %

Oil-immersed Cast-resin dry type

50 to 750 4 6
800 to 3,200 6 6

Fig. G31: Typical values of Usc for different kVA ratings of transformers with MV windings 20 kV

Example

400 kVA transformer, 420 V at no load

Usc = 4%

The case of several transformers in parallel feeding a busbar

The value of fault current on an outgoing circuit immediately downstream of the busbars
(see Fig. G32) can be estimated as the sum of the Isc from each transformer calculated separately.

It is assumed that all transformers are supplied from the same MV network, in which case the values
obtained from Figure G31when added together will give a slightly higher fault-level value than would
actually occur.

Other factors which have not been taken into account are the impedance of the busbars and of the
cable between transformers and circuit breakers.

The conservative fault-current value obtained however, is sufficiently accurate for basic installation
design purposes. The choice of circuit breakers and incorporated protective devices against short-
circuit and fault currents is described in Selection of a circuit-breaker .
Fig. G32: Case of several transformers in parallel.

Conductor sizing: methodology and definition.


Methodology

(see Figure G1)

Following a preliminary analysis of the power requirements of the installation, as described in The
consumer substation with LV metering, a study of cabling[1] and its electrical protection is undertaken,
starting at the origin of the installation, through the intermediate stages to the final circuits.

The cabling and its protection at each level must satisfy several conditions at the same time, in order
to ensure a safe and reliable installation, e.g. it must:

Carry the permanent full load current, and normal short-time overcurrents

Not cause voltage drops likely to result in an inferior performance of certain loads, for
example: an excessively long acceleration period when starting a motor, etc.

Moreover, the protective devices (circuit-breakers or fuses) must:

Protect the cabling and busbars for all levels of overcurrent, up to and including short-circuit
currents

Ensure protection of persons against indirect contact hazards, particularly in TN- and IT-
earthed systems, where the length of circuits may limit the magnitude of short-circuit currents,
thereby delaying automatic disconnection (it may be remembered that TT- earthed installations
are necessarily protected at the origin by a RCD, generally rated at 300 mA).

The cross-sectional areas of conductors are determined by the general method described
in Practical method for determining the smallest allowable cross-sectional area of circuit
conductors of this Chapter. Apart from this method some national standards may prescribe a
minimum cross-sectional area to be observed for reasons of mechanical endurance. Particular loads
(as noted in Chapter Characteristics of particular sources and loads) require that the cable supplying
them be oversized, and that the protection of the circuit be likewise modified.
Fig. G1: Flow-chart for the selection of cable size and protective device rating for a given circuit

Definitions

Maximum load current: IB

At the final circuits level, this design current (according to IEV "International Electrotechnical
Vocabulary" ref 826-11-10) corresponds to the rated kVA of the load. In the case of motor-starting,
or other loads which take a high in-rush current, particularly where frequent starting is concerned
(e.g. lift motors, resistance-type spot welding, and so on) the cumulative thermal effects of the
overcurrents must be taken into account. Both cables and thermal type relays are affected.
At all upstream circuit levels this current corresponds to the kVA to be supplied, which takes
account of the diversity and utilization factors, ks and ku respectively, as shown in Figure G2.

Fig. G2: Calculation of maximum load current IB

Maximum permissible current: Iz

Current carrying capacity Iz is the maximum permissible that the cabling for the circuit can carry
indefinitely, without reducing its normal life expectancy.

The current depends, for a given cross sectional area of conductors, on several parameters:

Constitution of the cable and cable-way (Cu or Alu conductors; PVC or EPR etc. insulation;
number of active conductors)

Ambient temperature

Method of installation

Influence of neighbouring circuits

Overcurrents

An overcurrent occurs each time the value of current exceeds the maximum load current IB for the
load concerned.
This current must be cut off with a rapidity that depends upon its magnitude, if permanent damage to
the cabling (and appliance if the overcurrent is due to a defective load component) is to be avoided.

Overcurrents of relatively short duration can however, occur in normal operation; two types of
overcurrent are distinguished:

Overloads
These overcurrents can occur in healthy electric circuits, for example, due to a number of
small short-duration loads which occasionally occur co-incidentally: motor starting loads, and
so on. If either of these conditions persists however beyond a given period (depending on
protective-relay settings or fuse ratings) the circuit will be automatically cut off.

Short-circuit currents
These currents result from the failure of insulation between live conductors or/and between
live conductors and earth (on systems having low-impedance-earthed neutrals) in any
combination, viz:

3 phases short-circuited (and to neutral and/or earth, or not)

2 phases short-circuited (and to neutral and/or earth, or not)

1 phase short-circuited to neutral (and/or to earth).

Overcurrent protection principles.


A protective device is provided at the origin of the circuit concerned (see Fig. G3 and Fig. G4 ).

Acting to cut-off the current in a time shorter than that given by the I2t characteristic of the
circuit cabling

But allowing the maximum load current IB to flow indefinitely

The characteristics of insulated conductors when carrying short-circuit currents can, for periods up to
5 seconds following short-circuit initiation, be determined approximately by the formula:

I2t = k2 S2

which shows that the allowable heat generated is proportional to the squared cross-sectional-area of
the condutor.

where
t = Duration of short-circuit current (seconds)
S = Cross sectional area of insulated conductor (mm2)
I = Short-circuit current (A r.m.s.)
k = Insulated conductor constant (values of k2 are given in Figure G52)

For a given insulated conductor, the maximum permissible current varies according to the
environment. For instance, for a high ambient temperature (a1 > a2), Iz1 is less than Iz2
(see Fig. G5). means temperature.

Note:

ISC: 3-phase short-circuit current


ISCB: rated 3-ph. short-circuit breaking current of the circuit-breaker
Ir (or Irth)[1]: regulated nominal current level; e.g. a 50 A nominal circuit-breaker can be
regulated to have a protective range, i.e. a conventional overcurrent tripping level
(see Fig. G6) similar to that of a 30 A circuit-breaker.

Fig. G3: Circuit protection by circuit breaker


Fig. G4: Circuit protection by fuses

Fig. G5: I2t characteristic of an insulated conductor at two different ambient temperatures.

Practical values for a protective scheme.


General rules

A protective device (circuit-breaker or fuse) functions correctly if:


Its nominal current or its setting current In is greater than the maximum load current IB but
less than the maximum permissible current Iz for the circuit, i.e. IB In Iz corresponding to zone
a in Figure G6

Its tripping current I2 conventional setting is less than 1.45 Iz which corresponds to zone b
in Figure G6
The conventional setting tripping time may be 1 hour or 2 hours according to local
standards and the actual value selected for I2. For fuses, I2 is the current (denoted If) which
will operate the fuse in the conventional time.

Its 3-phase short-circuit fault-current breaking rating is greater than the 3-phase short-circuit
current existing at its point of installation. This corresponds to zone c in Figure G6.

Fig. G6: Current levels for determining circuir breaker or fuse characteristics IB In Iz zone a I2
1.45 Iz zone b ISCB ISC zone c

Applications
Protection by circuit-breaker

Criteria for circuit-breakers: IB In Iz and ISCB ISC.

By virtue of its high level of precision the current I2 is always less than 1.45 In (or 1.45 Ir) so that the
condition I2 1.45 Iz (as noted in the general rules above) will always be respected.

Particular case
If the circuit-breaker itself does not protect against overloads, it is necessary to ensure that,
at a time of lowest value of short-circuit current, the overcurrent device protecting the circuit
will operate correctly. This particular case is examined in Calculation of minimum levels of
short-circuit current.

Protection by fuses

Criteria for fuses: IB In Iz/k3 and ISCF ISC.

The condition I2 1.45 Iz must be taken into account, where I2 is the fusing (melting level) current,
equal to k2 x In (k2 ranges from 1.6 to 1.9) depending on the particular fuse concerned.

A further factor k3 has been introduced such that I2 1.45 Iz

will be valid if In Iz/k3.

For fuses type gG:

In < 16 A k3 = 1.31

In 16 A k3 = 1.10

Moreover, the short-circuit current breaking capacity of the fuse ISCF must exceed the level of 3-
phase short-circuit current at the point of installation of the fuse(s).

Association of different protective devices

The use of protective devices which have fault-current ratings lower than the fault level existing at
their point of installation are permitted by IEC and many national standards in the following
conditions:

There exists upstream, another protective device which has the necessary short-circuit
rating, and
The amount of energy allowed to pass through the upstream device is less than that which
can be withstood without damage by the downstream device and all associated cabling and
appliances.

In pratice this arrangement is generally exploited in:

The association of circuit-breakers/fuses

The technique known as cascading or series rating in which the strong current-limiting
performance of certain circuit-breakers effectively reduces the severity of downstream short-
circuits

Possible combinations which have been tested in laboratories are indicated in certain manufacturers
catalogues.

General method for cable sizing.


Possible methods of installation for different types of conductors or cables

The different admissible methods of installation are listed in Figure G8, in conjonction with the
different types of conductors and cables.

Conductors cables Method of installation

Cable Cable On Sup


Without Clipped Condu Cable trunking ducting ladder, insulat port
fixings direct it systems systems ors wire
syste (including skirting Cable
ms trunking,
tray,

flush floor Cable

trunking) rackets

Bare conductors - - - - - - + -
[b] [a]
Insulated conductors - - + + + - + -
Sheathed Multi- + + + + + + 0 +
cables core
Single 0 + + + + + 0 +
(including -core
armoured and

mineral
insulated)
+ : Permitted.

: Not Permitted.

0 : Not applicable, or not normally used in practice.

[a] Insulated conductors are admitted if the cable trunking systems provide at least he degree of protection IP4X or

IPXXD and if the cover can only be removed by means of a tool or a deliberate action.

[b] Insulated conductors which are used as protective conductors or protective bonding conductors may use any

appropriate method of installation and need not be laid in conduits, trunking or ducting systems.

Fig. G8: Selection of wiring systems (table A.52.1 of IEC 60364-5-52)

Possible methods of installation for different situations:

Different methods of installation can be implemented in different situations. The possible


combinations are presented in Figure G9.

The number given in this table refer to the different wiring systems considered.

Situations Method of installation

Without Clipped Conduit Cable Cable Cable On Support


fixings direct Systems trunking ducting ladder, insulators wire
(including systems cable
skirting tray,
trunking, cable
flush floor brackets
trunking)

Building Accessible 40 33 41, 42 6, 7, 8, 43, 44 30, 31, - 0


voids 9,12 32, 33,
34

Not 40 0 41, 42 0 43 0 0 0
accessible

Cable channel 56 56 54, 55 0 30, 31, - -


32, 34

Buried in ground 72, 73 0 70, 71 - 70, 71 0 - -


Embedded in structure 57, 58 3 1, 2, 59, 50, 51, 52, 46, 45 0 - -
60 53

Surface mounted - 20, 21, 4, 5 6, 7, 8, 9, 6, 7, 8, 9 30, 31, 36 -


22, 23, 12 32, 34
33

Overhead/free in air - 33 0 10, 11 10, 11 30, 31, 36 35


32, 34

Window frames 16 0 16 0 0 0 - -

Architrave 15 0 15 0 0 0 - -

Immersed 1 + + + - + 0 - -

: Not permitted.

0 : Not applicable or not normally used in practice.

+ : Follow manufacturers instructions.

Note: The number in each box, e.g. 40, 46, refers to the number of the method of installation in Table A.52.3.

Fig. G9: Erection of wiring systems (table A.52.2 of IEC 60364-5-52)

Examples of wiring systems and reference methods of installations

An illustration of some of the many different wiring systems and methods of installation is provided
in Figure G10.

Several reference methods are defined (with code letters A to G), grouping installation methods
having the same characteristics relative to the current-carrying capacities of the wiring systems.

Item Methods of installation Description Reference method of installation to be


No. used to obtain current-carrying capacity

1 Insulated conductors or single-core A1


cables in conduit in a thermally
insulated wall

Room
2 Multi-core cables in conduit in a A2
thermally insulated wall

Room

4 Insulated conductors or single-core B1


cables in conduit on a wooden, or
masonry wall or spaced less than
0,3 x conduit diameter from it

5 Multi-core cable in conduit on a B2


wooden, or mansonry wall or
spaced less than 0,3 x conduit
diameter from it

20 Single-core or multi-core cables: - C


fixed on, or sapced less than 0.3 x
cable diameter from a wooden wall

C
30 Single-core or multi-core cables:

On unperforated tray run

horizontally or vertically
31 Single-core or multi-core cables: E or F

On perforated tray run horizontally

or vertically

36 Bare or insulated conductors on G


insulators

70 Multi-core cables in conduit or in D1


cable ducting in the ground

71 Single-core cable in conduit or in D1


cable ducting in the ground

Fig. G10: Examples of methods of installation (part of table A.52.3 of IEC 60364-5-52)

Maximum operating temperature:

The current-carrying capacities given in the subsequent tables have been determined so that the
maximum insulation temperature is not exceeded for sustained periods of time.

For different type of insulation material, the maximum admissible temperature is given
in Figure G11.

Type of insulation Temperature limit


C

Polyvinyl-chloride (PVC) 70 at the conductor

Cross-linked polyethylene (XLPE) and ethylene propylene rubber 90 at the conductor


(EPR)

Mineral (PVC covered or bare exposed to touch) 70 at the sheath

Mineral (bare not exposed to touch and not in contact with 105 at the seath
combustible material)

Fig. G11: Maximum operating temperatures for types of insulation (table 52.1 of IEC 60364-5-52)

Correction factors

In order to take environment or special conditions of installation into account, correction factors have
been introduced.

The cross sectional area of cables is determined using the rated load current IB divided by different
correction factors, k1, k2, ...:

IB is the corrected load current, to be compared to the current-carrying capacity of the considered
cable.

Ambient temperature

The current-carrying capacities of cables in the air are based on an average air temperature equal to
30 C. For other temperatures, the correction factor is given in FigureG12 for PVC, EPR and XLPE
insulation material.

The related correction factor is here noted k1.

Ambient temperature C Insulation

PVC XLPE and EPR

10 1.22 1.15

15 1.17 1.12
20 1.12 1.08

25 1.06 1.04

30 1 1

35 0.94 0.96

40 0.87 0.91

45 0.79 0.87

50 0.71 0.82

55 0.61 0.76

60 0.50 0.71

65 - 0.65

70 - 0.58

75 - 0.50

80 - 0.41

Fig. G12: Correction factors for ambient air temperatures other than 30 C to be applied to the current-carrying

capacities for cables in the air (from table B.52.14 of IEC 60364-5-52)

The current-carrying capacities of cables in the ground are based on an average ground
temperature equal to 20 C. For other temperatures, the correction factor is given in Figure G13 for
PVC, EPR and XLPE insulation material.

The related correction factor is here noted k2.


Ground temperature C Insulation

PVC XLPE and EPR

10 1.10 1.07

15 1.05 1.04

20 1 1

25 0.95 0.96

30 0.89 0.93

35 0.84 0.89

40 0.77 0.85

45 0.71 0.80

50 0.63 0.76

55 0.55 0.71

60 0.45 0.65

65 - 0.60

70 - 0.53

75 - 0.46
80 - 0.38

Fig. G13: Correction factors for ambient ground temperatures other than 20 C to be applied to the current-carrying

capacities for cables in ducts in the ground (from table B.52.15 of IEC 60364-5-52)

Soil thermal resistivity

The current-carrying capacities of cables in the ground are based on a ground resistivity equal to 2.5
Km/W. For other values, the correction factor is given in Figure G14.

The related correction factor is here noted k3.

Thermal resistivity, Km/W 0.5 0.7 1 1.5 2 2.5 3

Correction factor for cables in buried ducts 1.28 1.20 1.18 1.1 1.05 1 0.96

Correction factor for direct buried cables 1.88 1.62 1.5 1.28 1.12 1 0.90

Note 1: The correction factors given have been averaged over the range of conductor sizes and types of installation

included in Tables B.52.2 to B.52.5. The overall accuracy of correction factors is within 5 %.

Note 2: The correction factors are applicable to cables drawn into buried ducts; for cables laid direct in the ground the

correction factors for thermal resistivities less than 2.5 Km/W will be higher. Where more precise values are required

they may be calculated by methods given in the IEC 60287 series.

Note 3: The correction factors are applicable to ducts buried at depths of up to 0.8 m.

Note 4: It is assumed that the soil properties are uniform. No allowance had been made for the possibility of moisture

migration which can lead to a region of high thermal resistivity around the cable. If partial drying out of the soil is

foreseen, the permissible current rating should be derived by the methods specified in the IEC 60287 series.

Fig. G14: Correction factors for cables in buried ducts for soil thermal resistivities other than 2.5 K.m/W to be applied

to the current-carrying capacities for reference method D (table B.52.16 of IEC 60364-5-52)

Based on experience, a relationship exist between the soil nature and resistivity. Then, empiric
values of correction factors k3 are proposed in Figure G15, depending on the nature of soil.

Nature of soil k3
Very wet soil (saturated) 1.21

Wet soil 1.13

Damp soil 1.05

Dry soil 1.00

Very dry soil (sunbaked) 0.86

Fig. G15: Correction factor k3 depending on the nature of soil

Grouping of conductors or cables


The current-carrying capacities given in the subsequent tables relate to single circuits
consisting of the following numbers of loaded conductors:

Two insulated conductors or two single-core cables, or one twin-core cable (applicable to
single-phase circuits);

Three insulated conductors or three single-core cables, or one three-core cable (applicable
to three-phase circuits).

Where more insulated conductors or cables are installed in the same group, a group reduction factor
(here noted k4) shall be applied.

Examples are given in Figures G16 to G18 for different configurations (installation methods, in free
air or in the ground).

Figure G16 gives the values of correction factor k4 for different configurations of unburied cables or
conductors, grouping of more than one circuit or multi-core cables.

Arrangement Number of circuits or multi-core cables Reference methods


(cables
touching)

1 2 3 4 5 6 7 8 9 12 16 20

Bunched in air, on 1.00 0.8 0.7 0.6 0.6 0.5 0.54 0.5 0.5 0.4 0.41 0.38 Methods A
a surface,
embedded
orenclosed 0 0 5 0 7 2 0 5 to F

Single layer on 1.00 0.8 0.7 0.7 0.7 0.7 0.72 0.7 0.7 No further Method C
wall, floor or 5 9 5 3 2 1 0 reduction factor
unperforated tray for more than
nine circuits or
multi-core cables

Single layer fixed 0.95 0.8 0.7 0.6 0.6 0.6 0.63 0.6 0.6
directly under a 1 2 8 6 4 2 1
wooden ceiling

Single layer on a 1.00 0.8 0.8 0.7 0.7 0.7 0.73 0.7 0.7 Methods E and F
perforated 8 2 7 5 3 2 2
horizontal or
vertical tray

Single layer on 1.00 0.8 0.8 0.8 0.8 0.7 0.79 0.7 0.7
ladder support or 7 2 0 0 9 8 8
cleats etc.

Fig. G16: Reduction factors for groups of more than one circuit or of more than one multi-core cable (table B.52.17 of

IEC 60364-5-52)

Figure G17 gives the values of correction factor k4 for different configurations of unburied cables or
conductors, for groups of more than one circuit of single-core cables in free air.

Method of installation Number of Number of three-phase Use as a


tray circuits multiplier to
rating for

1 2 3

Perforated trays 31 1 0.98 0.91 0.87 Three cables


in horizontal
formation

2 0.96 0.87 0.81

3 0.95 0.85 0.78

Vertical perforated trays 31 1 0.96 0.86 Three cables


in vertical
2 0.95 0.84 formation

Ladder supports, cleats, 32 1 1.00 0.97 0.96 Three cables


etc... formation in horizontal
formation

33 2 0.98 0.93 0.89

34 3 0.97 0.90 0.86

Perforated trays 31 1 1.00 0.98 0.96 Three cables


in trefoil
formation

2 0.97 0.93 0.89

3 0.96 0.92 0.86

Vertical perforated trays 31 1 1.00 0.91 0.89

2 1.00 0.90 0.86

Ladder supports, cleats, 32 1 1.00 1.00 1.00


etc...

33 2 0.97 0.95 0.93

34 3 0.96 0.94 0.90

Fig. G17: Reduction factors for groups of more than one circuit of single-core cables to be applied to reference rating

for one circuit of single-core cables in free air - Method of installation F. (table B.52.21 of IEC 60364-5-52)
Figure G18 gives the values of correction factor k4 for different configurations of cables or
conductors laid directly in the ground.

Number of Cable to cable clearance(a)


circuits

Nil (cables One cable 0.125 0.25 m 0.5 m


touching) diameter m

2 0.75 0.80 0.85 0.90 0.90

3 0.65 0.70 0.75 0.80 0.85

4 0.60 0.60 0.70 0.75 0.80

5 0.55 0.55 0.65 0.70 0.80

6 0.50 0.55 0.60 0.70 0.80

7 0.45 0.51 0.59 0.67 0.76

8 0.43 0.48 0.57 0.65 0.75

9 0.41 0.46 0.55 0.63 0.74

12 0.36 0.42 0.51 0.59 0.71

16 0.32 0.38 0.47 0.56 0.38

20 0.29 0.35 0.44 0.53 0.66


(a) for Multi-
core cables

(a) for Single-


core cables

Fig. G18: Reduction factors for more than one circuit, single-core or multi-core cables laid directly in the ground.

Installation method D. (table B.52.18 of IEC 60364-5-52)

Harmonic current

The current-carrying capacity of three-phase, 4-core or 5-core cables is based on the assumption
that only 3 conductors are fully loaded.

However, when harmonic currents are circulating, the neutral current can be significant, and even
higher than the phase currents. This is due to the fact that the 3 rd harmonic currents of the three
phases do not cancel each other, and sum up in the neutral conductor.

This of course affects the current-carrying capacity of the cable, and a correction factor noted here
k5 shall be applied.

In addition, if the 3rd harmonic percentage h3 is greater than 33%, the neutral current is greater than
the phase current and the cable size selection is based on the neutral current. The heating effect of
harmonic currents in the phase conductors has also to be taken into account.

The values of k5 depending on the 3rd harmonic content are given in Figure G19.

Third harmonic content of Correction factor


phase current %

Size selection is based on Size selection is based on


phase current neutral current

0 - 15 1.0

15 - 33 0.86
33 - 45 0.86

> 45 1.0[a]

[a] If the neutral current is more than 135 % of the phase current and the cable size is selected on the basis of the

neutral current then the three phase conductors will not be fully loaded. The reduction in heat generated by the phase

conductors offsets the heat generated by the neutral conductor to the extent that it is not necessary to apply any

reduction factor to the current carrying capacity for three loaded conductors.

Fig. G19: Correction factors for harmonic currents in four-core and five-core cables (table E.52.1 of IEC 60364-5-52)

Admissible current as a function of nominal cross-sectional area of conductors

IEC standard 60364-5-52 proposes extensive information in the form of tables giving the admissible
currents as a function of cross-sectional area of cables. Many parameters are taken into account,
such as the method of installation, type of insulation material, type of conductor material, number of
loaded conductors.

As an example, Figure G20 gives the current-carrying capacities for different methods of installation
of PVC insulation, three loaded copper or almunium conductors, free air or in ground.

Nominal cross-sectional Installation methods of Table B.52.1


area of
conductors(mm2)

A1 A2 B1 B2 C D1 D2

1 2 3 4 5 6 7 8

Copper

1.5 13.5 13 15.5 15 17.5 18 19


2.5 18 17.5 21 20 24 24 24

4 24 23 28 27 32 30 33

6 31 29 36 34 41 38 41

10 42 39 50 46 57 50 54

16 56 52 68 62 76 64 70

25 73 68 89 80 96 82 92

35 89 83 110 99 119 98 110

50 108 99 134 118 144 116 130

70 136 125 171 149 184 143 162

95 164 150 207 179 223 169 193

120 188 172 239 206 259 192 220

150 216 196 262 225 299 217 246

185 245 223 296 255 341 243 278

240 286 261 346 297 403 280 320

300 328 298 394 339 464 316 359


Aluminium

2.5 14 13.5 16.5 15.5 18.5 18.5

4 18.5 17.5 22 21 25 24

6 24 23 28 27 32 30

10 32 31 39 36 44 39

16 43 41 53 48 59 50 53

25 57 53 70 62 73 64 69

35 70 65 86 77 90 77 83

50 84 78 104 92 110 91 99

70 107 98 133 116 140 112 122

95 129 118 161 139 170 132 148

120 149 135 186 160 197 150 169

150 170 155 204 176 227 169 189

185 194 176 230 199 259 190 214

240 227 207 269 232 305 218 250


300 261 237 306 265 351 247 282

Note: In columns 3, 5, 6, 7 and 8, circular conductors are assumed for sizes up to and including 16 mm2. Values for

larger sizes relate to shaped conductors and may safely be applied to circular conductors.

Fig. G20: Current-carrying capacities in amperes for different methods of installation, PVC insulation, three loaded

conductors, copper or aluminium, conductor temperature: 70 C, ambient temperature: 30 C in air, 20 C in ground

(table B.52.4 of IEC 60364-5-52).

3-phase short-circuit current (Isc) at any point within a LV installation.


In a 3-phase installation Isc at any point is given by:

where

U20 = phase-to-phase voltage of the open circuited secondary windings of the power supply
transformer(s).

ZT = total impedance per phase of the installation upstream of the fault location (in )

Method of calculating ZT

Each component of an installation (MV network, transformer, cable, busbar, and so on...) is
characterized by its impedance Z, comprising an element of resistance (R) and an inductive
reactance (X). It may be noted that capacitive reactances are not important in short-circuit current
calculations.

The parameters R, X and Z are expressed in ohms, and are related by the sides of a right angled
triangle, as shown in the impedance diagram of Figure G33.
Fig. G33: Impedance diagram

The method consists in dividing the network into convenient sections, and to calculate the R and X
values for each.

Where sections are connected in series in the network, all the resistive elements in the section are
added arithmetically; likewise for the reactances, to give RT and XT.

The impedance (ZT) for the combined sections concerned is then calculated

from

Any two sections of the network which are connected in parallel, can, if predominantly both resistive
(or both inductive) be combined to give a single equivalent resistance (or reactance) as follows:

Let R1 and R2 be the two resistances connected in parallel, then the equivalent resistance R3 will
be given by:

or for reactances

It should be noted that the calculation of X3 concerns only separated circuit without mutual
inductance. If the circuits in parallel are close togother the value of X3 will be notably higher.

Determination of the impedance of each component

Network upstream of the MV/LV transformer

(see Fig. G34)

The 3-phase short-circuit fault level PSC, in kA or in MVA[1] is given by the power supply authority
concerned, from which an equivalent impedance can be deduced.

Psc Uo (V) Ra (m) Xa (m)

250 MVA 420 0.07 0.7

500 MVA 420 0.035 0.351

Fig. G34: The impedance of the MV network referred to the LV side of the MV/LV transformer

A formula which makes this deduction and at the same time converts the impedance to an
equivalent value at LV is given, as follows:
where

Zs = impedance of the MV voltage network, expressed in milli-ohms


Uo = phase-to-phase no-load LV voltage, expressed in volts
Psc = MV 3-phase short-circuit fault level, expressed in kVA

The upstream (MV) resistance Ra is generally found to be negligible compared with the
corresponding Xa, the latter then being taken as the ohmic value for Za. If more accurate
calculations are necessary, Xa may be taken to be equal to 0.995 Za and Ra equal to 0.1 Xa.

Figure G36 gives values for Ra and Xa corresponding to the most common MV[2] short-circuit levels
in utility power-supply networks, namely, 250 MVA and 500 MVA.

Transformers

(see Fig. G35)

The impedance Ztr of a transformer, viewed from the LV terminals, is given by the formula:

where:

U20 = open-circuit secondary phase-to-phase voltage expressed in volts


Sn = rating of the transformer (in VA)
Usc = the short-circuit impedance voltage of the transformer expressed in %

The transformer windings resistance Rtr can be derived from the total load-losses as follows:

so that in milli-ohms

where

Pcu = total load-losses in watts


In = nominal full-load current in amps
Rtr = resistance of one phase of the transformer in milli-ohms (the LV and corresponding MV
winding for one LV phase are included in this resistance value).

Note: for an approximate calculation, in the absence of more precise information on transformer
characteristics, Cenelec 50480 suggests to use the following guidelines:
if U20 is not known, it may be assumed to be 1.05 Un

in the absence of more precise information, the following values may be used: Rtr = 0.31 Ztr
and Xtr = 0.95 Ztr

Example: for a transformer of 630kVA with Usc=4% / Un = 400V, approximate calculation gives:

U20 = 400 x 1.05 = 420V

Ztr = 4202 / 630000 x 4% = 11 m

Rtr = 0.31 x Ztr = 3.5 m and Xtr = 0.95 x Ztr = 10.6 m

Rated Power kVA) Oil-immersed Cast-resin

Usc (%) Rtr (m) Xtr (m) Ztr (m) Usc (%) Rtr (m) Xtr (m) Ztr (m)

100 4 37.9 59.5 70.6 6 37.0 99.1 105.8

160 4 16.2 41.0 44.1 6 18.6 63.5 66.2

200 4 11.9 33.2 35.3 6 14.1 51.0 52.9

250 4 9.2 26.7 28.2 6 10.7 41.0 42.3

315 4 6.2 21.5 22.4 6 8.0 32.6 33.6

400 4 5.1 16.9 17.6 6 6.1 25.8 26.5

500 4 3.8 13.6 14.1 6 4.6 20.7 21.2

630 4 2.9 10.8 11.2 6 3.5 16.4 16.8

800 6 2.9 12.9 13.2 6 2.6 13.0 13.2


1,000 6 2.3 10.3 10.6 6 1.9 10.4 10.6

1,250 6 1.8 8.3 8.5 6 1.5 8.3 8.5

1,600 6 1.4 6.5 6.6 6 1.1 6.5 6.6

2,000 6 1.1 5.2 5.3 6 0.9 5.2 5.3

Fig. G35: Resistance, reactance and impedance values for typical distribution 400 V transformers (no-load voltage =

420 V) with MV windings 20 kV

Busbars

The resistance of busbars is generally negligible, so that the impedance is practically all reactive,
and amounts to approximately 0.15 m/metre[3] length for LV busbars (doubling the spacing between
the bars increases the reactance by about 10% only).

In practice, it's almost never possible to estimate the busbar length concerned by a short-circuit
downstream a switchboard.

Circuit conductors

The resistance of a conductor is given by the formula:

where

= the resistivity of the conductor material at the normal operating temperature

has to be considered:

at cold state (20C) to determine maximum short-circuit current,

at steady state (normal operating temperature) to determine minimum short-circuit current.


L = length of the conductor in m
S = c.s.a. of conductor in mm2

20 C PR/XLPE 90 C PVC 70 C

Copper 18.51 23.69 22.21


Alu 29.41 37.65 35.29

Fig. G35b: Values of as a function of the temperature, cable insulation and cable core material, according to

IEC60909-0 and Cenelec TR 50480 (in m mm2/m).

Cable reactance values can be obtained from the manufacturers. For c.s.a. of less than 50
mm2 reactance may be ignored. In the absence of other information, a value of 0.08 m/metre may
be used (for 50 Hz systems) or 0.096 m/metre (for 60 Hz systems). For busways (busbar trunking
systems) and similar pre-wired ducting systems, the manufacturer should be consulted.

Motors

At the instant of short-circuit, a running motor will act (for a brief period) as a generator, and feed
current into the fault.

In general, this fault-current contribution may be ignored. However, if the total power of motors
running simultaneously is higher than 25% of the total power of transformers, the influence of motors
must be taken into account. Their total contribution can be estimated from the formula:

Iscm = 3.5 In from each motor i.e. 3.5m In for m similar motors operating concurrently.

The motors concerned will be the 3-phase motors only; single-phase-motor contribution being
insignificant.

Fault-arc resistance

Short-circuit faults generally form an arc which has the properties of a resistance. The resistance is
not stable and its average value is low, but at low voltage this resistance is sufficient to reduce the
fault-current to some extent. Experience has shown that a reduction of the order of 20% may be
expected. This phenomenon will effectively ease the current-breaking duty of a CB, but affords no
relief for its fault-current making duty.

Recapitulation table

(see Fig. G36)

Parts of power-supply system R (m) X (m)


Xa = 0.995 Za
Supply network

Figure G34

Transformer
with
Figure G35 where

Rtr is often negligible compared to Xtr for

transformers > 100 kVA

Circuit-breaker Not considered in practice


Busbars Negligible for S > 200 mm2 in the XB = 0.15 m/m

[a]
formula:
Circuit Cables: Xc = 0.08 m/m
conductors[b]
[a]

Motors See 3-phase short-circuit current (Isc) at


any point within a LV installation Motors
(often negligible at LV)
Three-phase
maximum
circuit current in
kA

[a] = resistivity at 20C

[b] If there are several conductors in parallel per phase, then divide the resistance of one conductor by the number of

conductors. The reactance remains practically unchanged.

U20: Phase-to-phase no-load secondary voltage of MV/LV transformer (in volts).

Psc: 3-phase short-circuit power at MV terminals of the MV/LV transformers (in kVA).

Pcu: 3-phase total losses of the MV/LV transformer (in watts).

Sn: Rating of the MV/LV transformer (in kVA).

Usc: Short-circuit impedance voltage of the MV/LV transfomer (in %).

RT : Total resistance. XT: Total reactanc

Fig. G36: Recapitulation table of impedances for different parts of a power-supply system

Example of short-circuit calculations

(see Fig. G37)


LV installation R (m) X (m) RT XT
(m) (m)

0.035 0.351
MV network

Psc = 500

MVA

Transformer 20 2.35 8.5


kV / 420 V
Pn = 1000 kVA
Usc = 5%
Pcu = 13.3 x
103 watts
Single-core Xc = 2.48 9.25 Isc1 = 25 kA
cables 0.08 x 5
5 m copper = 0.40
4 x 240
mm2/phase
Main circuit- Not considered in practice
breaker
Busbars 10 m Not considered in practice
Three-core Xc = 22 17.3 Isc3 = 8.7 kA
cable 100 x
100 m 0.08 = 8
95 mm2copper
Three-core Xc = 20 59 18.9 Isc4 = 3.9 kA
cable x 0.08 =
20 m 1.6
10 mm2copper
final circuits

RT : Total resistance. XT: Total reactance. Isc : 3-phase maximum short-circuit current Calculations

made as described in figure G36

Fig. G37: Example of maximum short-circuit current calculations for a LV installation supplied at 400 V (nominal)

from a 1000 kVA MV/LV transformer

Notes

1. ^ Short-circuit MVA: EL Isc where:

EL = phase-to-phase nominal system voltage expressed in kV (r.m.s.)

Isc = 3-phase short-circuit current expressed in kA (r.m.s.)


2. ^ up to 36 kV

3. ^ For 50 Hz systems, but 0.18 m/m length at 60 Hz.

Isc at the receiving end of a feeder as a function of the Isc at its


sending end.
The network shown in Figure G38 typifies a case for the application of Figure G39 , derived by the
method of composition (mentioned in chapter Protection against electric shocks and electric
fires ). These tables give a rapid and sufficiently accurate value of short-circuit current at a point in a
network, knowing:

The value of short-circuit current upstream of the point considered

The length and composition of the circuit between the point at which the short-circuit current
level is known, and the point at which the level is to be determined

It is then sufficient to select a circuit-breaker with an appropriate short-circuit fault rating immediately
above that indicated in the tables.

If more precise values are required, it is possible to make a detailed calculation or to use a software
package, such as Ecodial. In such a case, moreover, the possibility of using the cascading technique
should be considered, in which the use of a current limiting circuit-breaker at the upstream position
would allow all circuit-breakers downstream of the limiter to have a short-circuit current rating much
lower than would otherwise be necessary (See chapter LV switchgear: functions and selection ).

Method

Select the c.s.a. of the conductor in the column for copper conductors (in this example the c.s.a. is
47.5 mm2).

Search along the row corresponding to 47.5 mm2 for the length of conductor equal to that of the
circuit concerned (or the nearest possible on the low side). Descend vertically the column in which
the length is located, and stop at a row in the middle section (of the 3 sections of the Figure)
corresponding to the known fault-current level (or the nearest to it on the high side).

In this case 30 kA is the nearest to 28 kA on the high side. The value of short-circuit current at the
downstream end of the 20 metre circuit is given at the intersection of the vertical column in which the
length is located, and the horizontal row corresponding to the upstream Isc (or nearest to it on the
high side).

This value in the example is seen to be 14.7 kA.


The procedure for aluminium conductors is similar, but the vertical column must be ascended into
the middle section of the table.

In consequence, a DIN-rail-mounted circuit-breaker rated at 63 A and Isc of 25 kA (such as a NG


125N unit) can be used for the 55 A circuit in Figure G38.

A Compact rated at 160 A with an Isc capacity of 25 kA (such as a NS160 unit) can be used to
protect the 160 A circuit.

Fig. G38: Determination of downstream short-circuit current level Isc using Figure G39

Copper 230 V / 400 V

c.s.a.of Length of circuit (in metres)


phase
conductor
s (mm2)

1.5 1.3 1.8 2.6 3. 5.2 7.3 1


6 0
3

2.5 1.1 1.5 2.1 3.0 4.3 6. 8.6 12. 1


1 1 7
2
4 1.2 1.7 2.4 3.4 4.9 6.9 9. 13. 19. 2
7 7 4 7

6 1.8 2.6 3.6 5.2 7.3 10. 1 21 29 4


3 4. 1
6

10 2. 3.0 4.3 6.1 8.6 12.2 17. 2 34 49 6


2 2 4 9

16 1. 2 3. 4.9 6.9 9.7 13. 19.4 27 3 55 78 1


7 . 4 8 9 0
4

25 1 1. 2. 3 5. 7.6 10. 15. 21 30 43 6 86 121 1


. 9 7 . 4 8 2 1 7
3 8 2

35 1 2. 3. 5 7. 10. 15. 21 30 43 60 8 120 170 2


. 7 8 . 5 6 1 5 4
9 3 0

47.5 1 2 3. 5. 7 10 14. 20 29 41 58 82 1 163 231 3


. . 6 1 . .2 4 1 2
8 6 2 5 6

70 2 3 5. 7. 1 15 21 30 43 60 85 120 1 240 340


. . 3 5 0 .1 7
7 8 . 0
7

95 2. 3 5 7. 10 1 20 29 41 58 82 115 163 2 326 461


6 . . 2 .2 4 3
6 1 . 1
5

120 1. 2. 3. 4 6 9. 12 1 26 37 52 73 103 146 206 2 412


6 3 2 . . 1 .9 8 9
6 5 . 1
3
150 1.2 1. 2. 3. 5 7 9. 14 1 28 40 56 79 112 159 224 3 448
8 5 5 . . 9 .0 9 1
0 0 . 7
8

185 1.5 2. 2. 4. 5 8 11 16 2 33 47 66 94 133 187 265 3 529


1 9 2 . . .7 .6 3 7
9 3 4

240 1.8 2. 3. 5. 7 1 4. 21 2 41 58 83 117 165 233 330 4 659


6 7 2 . 0 6 9 6
3 . 6
3

300 2.2 3. 4. 6. 8 1 17 25 3 50 70 99 140 198 280 396 5


1 4 2 . 2 .6 5 6
8 . 1
4

2x120 2.3 3. 4. 6. 9 1 18 26 3 52 73 103 146 206 292 412 5


2 6 5 . 2 .3 7 8
1 . 3
9

2x150 2.5 3. 5. 7. 9 1 20 28 4 56 79 112 159 224 317 448 6


5 0 0 . 4 0 3
9 . 4
0

2x185 2.9 4. 5. 8. 1 1 23 33 4 66 94 133 187 265 375 530 7


2 9 3 1 6 7 4
. . 9
7 6

3x120 3.4 4. 6. 9. 1 1 27 39 5 77 110 155 219 309 438 619


9 9 7 3 9 5
. .
7 4

3x150 3.7 5. 7. 10 1 2 30 42 6 84 119 168 238 336 476 672


3 5 .5 4 1 0
.
9
3x185 4.4 6. 8. 12 1 2 35 50 7 10 141 199 281 398 562
2 8 .5 7 5 0 0
.
6

Isc Isc downstream (in kA)


upstream
(in kA)

100 93 9 87 82 7 7 62 54 4 37 29 22 17. 12. 9.3 6.7 4. 3.5 2.5 1


0 7 0 5 0 6 9 8

90 84 8 79 75 7 6 58 51 4 35 28 22 16. 12. 9.2 6.7 4. 3.5. 2.5 1


2 1 5 3 7 5 8 8

80 75 7 71 68 6 5 54 47 4 34 27 21 16. 12. 9.1 6.6 4. 3.5 2.5 1


4 4 9 0 3 2 8 8

70 66 6 63 61 5 5 49 44 3 32 26 20 15. 12. 8.9 6.6 4. 3.4 2.5 1


5 8 4 8 8 0 8 8

60 57 5 55 53 5 4 44 39 3 29 24 20 15. 11.6 8.7 6.5 4. 3.4 2.5 1


6 1 8 5 2 7 8

50 48 4 46 45 4 4 38 35 3 27 22 18. 14. 11.2 8.5 6.3 4. 3.4 2.4 1


7 3 1 1 3 5 6 7

40 39 3 38 37 3 3 32 30 2 24 20 16. 13. 10. 8.1 6.1 4. 3.3 2.4 1


8 6 4 7 8 5 6 5 7

35 34 3 33 33 3 3 29 27 2 22 18. 15. 12. 10. 7.9 6.0 4. 3.3 2.4 1


4 2 0 4 8 8 9 2 5 7

30 29 2 29 28 2 2 25 24 2 20 17. 14. 12. 9.8 7.6 5.8 4. 3.2 2.4 1


9 7 7 2 3 7 2 4 7

25 25 2 24 24 2 2 22 21 1 17 15. 13. 11.2 9.2 7.3 5.6 4. 3.2 2.3 1


4 3 3 9 .4 5 4 2 7
.
1

20 20 2 19 19 1 1 17 17 1 14 13. 11.8 10. 8.4 6.8 5.3 4. 3.1 2.3 1


0 .4 .2 8 8 .8 .0 6 .9 4 1 1 7
. . .
8 4 1

15 14. 4 14 14 1 1 13 3. 1 11 11.0 9.9 8.7 7.4 6.1 4.9 3. 2.9 2.2 1


8 1. .7 .5 4 4 .7 3 2 .9 8 6
8 . . .
3 1 7

10 9.9 9. 9. 9. 9 9 9. 9. 8 8. 8.0 7.4 6.7 5.9 5.1 4.2 3. 2.7 2.0 1


9 8 8 . . 4 2 . 5 4 5
7 6 9

7 7.0 6. 6. 6. 6 6 6. 6. 6 6. 6.0 5.6 5.2 4.7 4.2 3.6 3. 2.4 1.9 1


9 9 9 . . 7 6 . 2 0 4
9 8 4

5 5.0 5. 5. 4. 4 4 4. 4. 4 4. 4.5 4.3 4.0 3.7 3.4 3.0 2. 2.1 1.7 1


0 0 9 . . 9 8 . 6 5 3
9 9 7

4 4.0 4. 4. 4. 4 3 3. 3. 3 3. 3.6 3.5 3.3 3.1 2.9 2.6 2. 1.9 1.6 1


0 0 0 . . 9 9 . 7 2 2
0 9 8

3 3.0 3. 3. 3. 3 3 2. 2. 2 2. 2.8 2.7 2.6 2.5 2.3 2.1 1. 1.6 1.4 1


0 0 0 . . 9 9 . 9 9 1
0 0 9

2 2.0 2. 2. 2. 2 2 2. 2. 1 1. 1.9 1.9 1.8 1.8 1.7 1.6 1. 1.3 1.1 1


0 0 0 . . 0 0 2 9 4 0
0 0 .
0

1 1.0 1. 1. 1. 1 1 1. 1. 1 1. 1.0 1.0 1.0 0.9 0.9 0.9 0. 0.8 0.7 0


0 0 0 . . 0 0 . 0 8 6
0 0 0

Note: for a 3-phase system having 230 V between phases, divide the above lengths by
Fig. G39: Isc at a point downstream, as a function of a known upstream fault-current value and the length and c.s.a.

of the intervening conductors, in a 230/400 V 3-phase system.

Calculation of minimum levels of short-circuit current.


If a protective device in a circuit is intended only to protect against short-circuit faults, it is essential that it will
operate with certainty at the lowest possible level of short-circuit current that can occur on the circuit

In general, on LV circuits, a single protective device protects against all levels of current, from the
overload threshold through the maximum rated short-circuit current breaking capability of the device.
The protection device should be able to operate in a maximum time to ensure people and circuit
safety, for all short-circuit current or fault current that may occur. To check that behavior, calculation
of minimal short-circuit current or fault current is mandatory.

In addition, in certain cases overload protective devices and separate short-circuit protective devices
are used.

Examples of such arrangements

Figures G40 to G42 show some common arrangements where overload and short-circuit
protections are achieved by separate devices.

Fig. G40: Circuit protected by aM fuses


Fig. G41: Circuit protected by circuit breaker without thermal overload relay

Fig. G42a: Circuit breaker D provides protection against short-circuit faults as far as and including
the load

As shown in Figures G40 and G41, the most common circuits using separate devices control and
protect motors.

Figure G42a constitutes a derogation in the basic protection rules, and is generally used on circuits
of prefabricated bustrunking, lighting rails, etc.

Variable speed drive

Figure G42b shows the functions provided by the variable speed drive, and if necessary some
additional functions provided by devices such as circuit-breaker, thermal relay, RCD.
Protection to be Protection generally Additional protection if not
provided provided by the variable provided by the variable
speed drive speed drive

Cable overload Yes CB / Thermal relay

Motor overload Yes CB / Thermal relay

Downstream short- Yes


circuit

Variable speed drive Yes


overload

Overvoltage Yes

Undervoltage Yes

Loss of phase Yes

Upstream short-circuit Circuit-breaker

(short-circuit tripping)

Internal fault Circuit-breaker

(short-circuit and overload

tripping)

Downstream earth fault (self protection) RCD 300 mA or CB in TN


(indirect contact) earthing system
Direct contact fault RCD 30 mA

Fig. G42b: Protection to be provided for variable speeed drive applications

Conditions to be fulfilled

The protective device must fulfill:

instantaneous trip setting Im < Iscmin for a circuit-breaker


fusion current Ia < Iscmin for a fuse

The protective device must therefore satisfy the two following conditions:

Its breaking capacity must be greater than Isc, the 3-phase short-circuit current at its point of
installation

Elimination of the minimum short-circuit current possible in the circuit, in a time tc compatible
with the thermal constraints of the circuit conductors, where:

(valid for tc < 5 seconds)

where S is the cross section area of the cable, k is a factor depending of the cable conductor
material, the insulation material and initial temperature.

Example: for copper XLPE, initial temperature 90 C, k = 143 (see IEC60364-4-43 434.3.2 table
43A).

Comparison of the tripping or fusing performance curve of protective devices, with the limit curves of
thermal constraint for a conductor shows that this condition is satisfied if:

Isc (min) > Im (instantaneous or short timedelay circuit-breaker trip setting current level),
(see Fig. G43 )

Isc (min) > Ia for protection by fuses. The value of the current Ia corresponds to the crossing
point of the fuse curve and the cable thermal withstand curve (see Fig. G44 and Fig. G45)

Fig. G43: Protection by circuit breaker


Fig. G44: Protection by aM-type fuses

Fig. G45: Protection by gG-type fuses

Practical method of calculating Lmax

In practice this means that the length of circuit downstream of the protective device must not exceed a

calculated maximum length:

The limiting effect of the impedance of long circuit conductors on the value of short-circuit currents
must be checked and the length of a circuit must be restricted accordingly.

The method of calculating the maximum permitted length has already been demonstrated in TN- and
IT- earthed schemes for single and double earth faults, respectively. Two cases are considered
below:

1 - Calculation of Lmax for a 3-phase 3-wire circuit


The minimum short-circuit current will occur when two phase wires are short-circuited at the remote
end of the circuit (see Fig. G46).

Fig. G46: Definition of L for a 3-phase 3-wire circuit

Using the conventional method, the voltage at the point of protection P is assumed to be 80% of
the nominal voltage during a short-circuit fault, so that 0.8 U = Isc Zd, where:

Zd = impedance of the fault loop


Isc = short-circuit current (ph/ph)
U = phase-to-phase nominal voltage

For cables 120 mm2, reactance may be neglected, so that [1]

where:

= resistivity of conductor material at the average temperature during a short-circuit,


Sph = c.s.a. of a phase conductor in mm2
L = length in metres

The condition for the cable protection is Im Isc with Im = magnetic trip current setting of the CB.

This leads to which gives

with U = 400 V

= 0.023 .mm2/m[2] (Cu)

therefore

with Lmax = maximum circuit length in metres

In general, the value of Im is given with +/- 20% tolerance, so Lmax should be calculated for
Im+20% (worst case).
k factor values are provided in the following table, taking into account these 20%, and as a function
of cross-section for Sph > 120 mm2[1]

Cross-section (mm2) 120 150 185 240 300

k (for 400 V) 5800 5040 4830 4640 4460

2 - Calculation of Lmax for a 3-phase 4-wire 230/400 V circuit

The minimum Isc will occur when the short-circuit is between a phase conductor and the neutral at
the end of the circuit.

A calculation similar to that of example 1 above is required, but for a single-phase fault (230V).

If Sn (neutral cross-section) = Sph

Lmax = k Sph / Im with k calculated for 230V, as shown in the table below

Cross-section (mm2) 120 150 185 240 300

k (for 400 V) 3333 2898 2777 2668 2565

If Sn (neutral cross-section) < Sph, then (for cable cross-section 120mm 2)

Tabulated values for Lmax

Figure G47 below gives maximum circuit lengths (Lmax) in metres, for:

3-phase 4-wire 400 V circuits (i.e. with neutral) and

1-phase 2-wire 230 V circuits

protected by general-purpose circuit-breakers.

In other cases, apply correction factors (given in Figure G51) to the lengths obtained.
In general, the value of Im is given with +/- 20% tolerance.

Lmax values below are therefore calculated for Im+20% (worst case).

For the 50 mm2 c.s.a., calculation are based on a 47.5 mm2 real c.s.a.

Operating current level Im of the instantaneous c.s.a. (nominal cross-sectional-area) of conductors (in mm2)
magnetic tripping element (in A)

1.5 2.5 4 6 10 16 25 35 50 70 95 12

50 100 167 26 400


7

63 79 133 21 317
2

80 63 104 16 250 41
7 7

100 50 83 13 200 33
3 3

125 40 67 10 160 26 427


7 7

160 31 52 83 125 20 333


8

200 25 42 67 100 16 267 417


7

250 20 33 53 80 13 213 333 46


3 7

320 16 26 42 63 10 167 260 36 495


4 5
400 13 21 33 50 83 133 208 29 396
2

500 10 17 27 40 67 107 167 23 317


3

560 9 15 24 36 60 95 149 20 283 41


8 7

630 8 13 21 32 53 85 132 18 251 37


5 0

700 7 12 19 29 48 76 119 16 226 33 452


7 3

800 6 10 17 25 42 67 104 14 198 29 396


6 2

875 6 10 15 23 38 61 95 13 181 26 362 45


3 7

1000 5 8 13 20 33 53 83 117 158 23 317 40


3

1120 4 7 12 18 30 48 74 10 141 20 283 35


4 8

1250 4 7 11 16 27 43 67 93 127 18 253 32


7

1600 5 8 13 21 33 52 73 99 14 198 25
6

2000 4 7 10 17 27 42 58 79 117 158 20

2500 5 8 13 21 33 47 63 93 127 16
3200 4 6 10 17 26 36 49 73 99 12

4000 5 8 13 21 29 40 58 79 10

5000 4 7 11 17 23 32 47 63 80

6300 5 8 13 19 25 37 50 63

8000 4 7 10 15 20 29 40 50

10000 5 8 12 16 23 32 40

12500 4 7 9 13 19 25 32

Fig. G47: Maximum circuit lengths in metres for copper conductors (for aluminium, the lengths must be multiplied by

0.62)

Figures G48 to G50 give maximum circuit length (Lmax) in metres for:

3-phase 4-wire 400 V circuits (i.e. with neutral) and

1-phase 2-wire 230 V circuits


protected in both cases by domestic-type circuit-breakers or with circuit-breakers having
similar tripping/current characteristics.

In other cases, apply correction factors to the lengths indicated.

These factors are given in Figure G51.

Circuit-breaker rating (A) c.s.a. (nominal cross-sectional-area) of conductors (in mm2)

1.5 2.5 4 6 10 16 25
6 200 333 533 800

10 120 200 320 480 800

16 75 125 200 300 500 800

20 60 100 160 240 400 640

25 48 80 128 192 320 512 800

32 37 62 100 150 250 400 625

40 30 50 80 120 200 320 500

50 24 40 64 96 160 256 400

63 19 32 51 76 127 203 317

80 15 25 40 60 100 160 250

100 12 20 32 48 80 128 200

125 10 16 26 38 64 102 160

Fig. G48: Maximum length of copper-conductor circuits in metres protected by B-type circuit-breakers

Circuit-breaker rating (A) c.s.a. (nominal cross-sectional-area) of conductors (in mm2)

1.5 2.5 4 6 10 16 25

6 100 167 267 400 667


10 60 100 160 240 400 640

16 37 62 100 150 250 400 625

20 30 50 80 120 200 320 500

25 24 40 64 96 160 256 400

32 18.0 31 50 75 125 200 313

40 15.0 25 40 60 100 160 250

50 12.0 20 32 48 80 128 200

63 9.5 16.0 26 38 64 102 159

80 7.5 12.5 20 30 50 80 125

100 6.0 10.0 16.0 24 40 64 100

125 5.0 8.0 13.0 19.0 32 51 80

Fig. G49: Maximum length of copper-conductor circuits in metres protected by C-type circuit-breakers

Circuit-breaker rating (A) c.s.a. (nominal cross-sectional-area) of conductors (in mm2)

1.5 2.5 4 6 10 16 25

1 429 714

2 214 357 571 857


3 143 238 381 571 952

4 107 179 286 429 714

6 71 119 190 286 476 762

10 43 71 114 171 286 457 714

16 27 45 71 107 179 286 446

20 21 36 57 86 143 229 357

25 17.0 29 46 69 114 183 286

32 13.0 22 36 54 89 143 223

40 11.0 18.0 29 43 71 114 179

50 9.0 14.0 23 34 57 91 143

63 7.0 11.0 18.0 27 45 73 113

80 5.0 9.0 14.0 21 36 57 89

100 4.0 7.0 11.0 17.0 29 46 71

125 3.0 6.0 9.0 14.0 23 37 57

Fig. G50: Maximum length of copper-conductor circuits in metres protected by D-type circuit-breakers

Circuit detail
3-phase 3-wire 400 V circuit or 1-phase 2-wire 400 V circuit (no neutral)

1-phase 2-wire (phase and neutral) 230 V circuit

3-phase 4-wire 230/400 V circuit or 2-phase 3-wire 230/400 V circuit (i.e with neutral) Sph / S neutra

Sph / S neutra

Fig. G51: Correction factor to apply to lengths obtained from Figures G47 to G50

Note: IEC 60898 accepts an upper short-circuit-current tripping range of 10-50 In for type D circuit-
breakers. European standards, and Figure G50 however, are based on a range of 10-20 In, a range
which covers the vast majority of domestic and similar installations.

Examples

Example 1

In a 3-phase 3-wire 400 V installation the protection is provided by a 50 A circuit-breaker type


NS80HMA, the instantaneous short-circuit current trip, is set at 500 A (accuracy of 20%), i.e. in the
worst case would require 500 x 1,2 = 600 A to trip. The cable c.s.a. = 10 mm 2 and the conductor
material is copper.

In Figure G47, the row Im = 500 A crosses the column c.s.a. = 10 mm2 at the value for Lmax of 67
m. The circuit-breaker protects the cable against short-circuit faults, therefore, provided that its
length does not exceed 67 metres.

Example 2

In a 3-phase 3-wire 400 V circuit (without neutral), the protection is provided by a 220 A circuit-
breaker type NSX250N with an instantaneous short-circuit current trip unit type MA set at 2,000 A (
20%), i.e. a worst case of 2,400 A to be certain of tripping. The cable c.s.a. = 120 mm 2 and the
conductor material is copper.

In Figure G47 the row Im = 2,000 A crosses the column c.s.a. = 120 mm2 at the value for Lmax of
200 m. Being a 3-phase 3-wire 400 V circuit (without neutral), a correction factor
from Figure G51 must be applied. This factor is seen to be 1.73.

The circuit-breaker will therefore protect the cable against short-circuit current, provided that its
length does not exceed 200 x 1.73 = 346 metres.
Notes

1. ^ a b For larger c.s.a.s, the resistance calculated for the conductors must be increased to
account for the non-uniform current density in the conductor (due to skin and proximity
effects Suitable values are as follows:

150 mm2: R + 15 %

185 mm2: R + 20 %

240 mm2: R + 25 %

300 mm2: R + 30 %

2. ^ Resistivity for copper EPR/XLPE cables when passing short-circuit current, eg for the max
temperature they can withstand = 90C (cf Figure G35b).

Verification of the withstand capabilities of cables under short-circuit


conditions.
Thermal constraints

When the duration of short-circuit current is brief (several tenths of a second up to five seconds
maximum) all of the heat produced is assumed to remain in the conductor, causing its temperature
to rise. The heating process is said to be adiabatic, an assumption that simplifies the calculation and
gives a pessimistic result, i.e. a higher conductor temperature than that which would actually occur,
since in practice, some heat would leave the conductor and pass into the insulation.

For a period of 5 seconds or less, the relationship I2t = k2S2 characterizes the time in seconds during
which a conductor of c.s.a. S (in mm 2) can be allowed to carry a current I, before its temperature
reaches a level which would damage the surrounding insulation.

The factor k is given in Figure G52 below.

Conductor insulation

PVC 300 mm2 PVC > 300 mm2 EPR XLPE Rubber 60 C
Initial temperature C 70 70 90 60

Final temperature C 160 140 250 200

Material of conductor

Copper 115 103 143 141

Aluminium 76 68 94 93

Fig. G52: Value of the constant k according to table 43A of IEC 60364-4-43

The method of verification consists in checking that the thermal energy I 2t per ohm of conductor
material, allowed to pass by the protecting circuit-breaker (from manufacturers catalogues) is less
than that permitted for the particular conductor (as given in Figure G53 below).

S (mm2) PVC XLPE

Copper Aluminium Copper Aluminium

1.5 0.0297 0.0130 0.0460 0.0199

2.5 0.0826 0.0361 0.1278 0.0552

4 0.2116 0.0924 0.3272 0.1414

6 0.4761 0.2079 0.7362 0.3181

10 1.3225 0.5776 2.0450 0.8836

16 3.3856 1.4786 5.2350 2.2620


25 8.2656 3.6100 12.7806 5.5225

35 16.2006 7.0756 25.0500 10.8241

50[a] 29.839 13.032 46.133 19.936

[a] For 50mm2 cable, the values are calculated for the actual cross-section of 47.5mm2

Fig. G53: Maximum allowable thermal stress for cables I2t (expressed in ampere2 x second x 106)

Example

Is a copper-cored XLPE cable of 4 mm2 c.s.a. adequately protected by a iC60N circuit-breaker?


(see Fig. G53b)

Figure G53 shows that the I2t value for the cable is 0.3272 x 106, while the maximum let-through
value by the circuit-breaker, as given in the manufacturers catalogue, is considerably less ( <
0.1.106 A2s).

The cable is therefore adequately protected by the circuit-breaker up to its full rated breaking
capability.

Electrodynamic constraints

For all type of circuit (conductors or bus-trunking), it is necessary to take electrodynamic effects into
account.

To withstand the electrodynamic constraints, the conductors must be solidly fixed and the connection
must be strongly tightened.

For bus-trunking, rails, etc. it is also necessary to verify that the electrodynamic withstand
performance is satisfactory when carrying short-circuit currents. The peak value of current, limited by
the circuit-breaker or fuse, must be less than the busbar system rating. Tables of coordination
ensuring adequate protection of their products are generally published by the manufacturers and
provide a major advantage of such systems.
Fig. G53b: Example of energy limitation of a MCB for different ratings.

Connection and choice for protective earthing conductor.


Protective (PE) conductors provide the bonding connection between all exposed and extraneous
conductive parts of an installation, to create the main equipotential bonding system. These
conductors conduct fault current due to insulation failure (between a phase conductor and an
exposed conductive part) to the earthed neutral of the source. PE conductors are connected to the
main earthing terminal of the installation.

The main earthing terminal is connected to the earthing electrode (see Chapter E) by the earthing
conductor (grounding electrode conductor in the USA).

PE conductors must be:

Insulated and coloured yellow and green (stripes)

Protected against mechanical and chemical damage


In IT and TN-earthed schemes it is strongly recommended that PE conductors should be installed in
close proximity (i.e. in the same conduits, on the same cable tray, etc.) as the live cables of the
related circuit. This arrangement ensures the minimum possible inductive reactance in the earth-fault
current carrying circuits.

It should be noted that this arrangement is originally provided by bus-trunking.

Connection

PE conductors must:

Not include any means of breaking the continuity of the circuit (such as a switch, removable
links, etc.)

Connect exposed conductive parts individually to the main PE conductor, i.e. in parallel, not
in series, as shown in Figure G54

Have an individual terminal on common earthing bars in distribution boards.

Fig. G54: A poor connection in a series arrangement will leave all downstream appliances
unprotected

TT scheme
The PE conductor need not necessarily be installed in close proximity to the live conductors of the
corresponding circuit, since high values of earth-fault current are not needed to operate the RCD-
type of protection used in TT installations.

IT and TN schemes

The PE or PEN conductor, as previously noted, must be installed as close as possible to the
corresponding live conductors of the circuit and no ferro-magnetic material must be interposed
between them. A PEN conductor must always be connected directly to the earth terminal of an
appliance, with a looped connection from the earth terminal to the neutral terminal of the appliance
(see Fig. G55).

TN-C scheme (the neutral and PE conductor are one and the same, referred to as a PEN
conductor)
The protective function of a PEN conductor has priority, so that all rules governing PE
conductors apply strictly to PEN conductors

TN-C to TN-S transition


The PE conductor for the installation is connected to the PEN terminal or bar
(see Figure G56) generally at the origin of the installation. Downstream of the point of
separation, no PE conductor can be connected to the neutral conductor.

Fig. G55: Direct connection of the PEN conductor to the earth terminal of an appliance

Fig. G56: The TN-C-S scheme

Types of materials
Materials of the kinds mentioned below in Figure G57 can be used for PE conductors, provided that
the conditions mentioned in the last column are satisfied.

Type of protective earthing IT scheme TN scheme TT Conditions to be respected


conductor(PE) scheme

Supplementary In the same cable Strongly Strongly Correct The PE conductor must be
conductor as the phases, or ecommended recommended insulated to the same level as
in the same cable the phases
run

Independent of Possible[a] Possible[a][b] Correct


the phase The PE conductor may
conductors
be bare or insulated[b]

Metallic housing of bus-trunking or of Possible[c] PE possible[c] Correct


other prefabricated prewired ducting[e] PEN possible[h] The electrical
[c] [c]
External sheath of extruded, mineral- Possible PE possible Possible continuity must be assured
insulated conductors (e.g. PEN not
pyrotenax type systems) recommended[b][c] by protection against
[d] [d]
Certain extraneous conductive Possible PE possible Possible deterioration by mechanical,
elements[f] such as:
PEN forbidden chemical and

Steel building structure electrochemical hazards

Machine frames Their conductance

must be adequate
[g]
Water pipes
Metallic cable ways, such as, Possible[d] PE possible[d] Possible
conduits[i]ducts, trunking, trays, PEN not
ladders, and so on recommended[b][d]
Forbidden for use as PE conductors, are: metal conduits[i], gas pipes, hot-water pipes, cable-armouring tapes[i]or wires[i]

[a] In TN and IT schemes, fault clearance is generally achieved by overcurrent devices (fuses or circuit-breakers) so

that the impedance of the fault-current loop must be sufficiently low to assure positive protective device operation.

The surest means of achieving a low loop impedance is to use a supplementary core in the same cable as the circuit

conductors (or taking the same route as the circuit conductors). This solution minimizes the inductive reactance and

therefore the impedance of the loop.

[b] The PEN conductor is a neutral conductor that is also used as a protective earth conductor. This means that a

current may be flowing through it at any time (in the absence of an earth fault). For this reason an insulated conductor

is recommended for PEN operation.

[c] The manufacturer provides the necessary values of R and X components of the impedances (phase/PE,

phase/PEN) to include in the calculation of the earth-fault loop impedance.


[d] Possible, but not recomended, since the impedance of the earth-fault loop cannot be known at the design stage.

Measurements on the completed installation are the only practical means of assuring adequate protection for

persons.

[e] It must allow the connection of other PE conductors. Note: these elements must carry an indivual green/yellow

striped visual indication, 15 to 100 mm long (or the letters PE at less than 15 cm from each extremity).

[f] These elements must be demountable only if other means have been provided to ensure uninterrupted continuity

of protection.

[g] With the agreement of the appropriate water authorities.

[h] In the prefabricated pre-wired trunking and similar elements, the metallic housing may be used as a PEN

conductor, in parallel with the corresponding bar, or other PE conductor in the housing.

[i] Forbidden in some countries only. Universally allowed to be used for supplementary equipotential conductors.

Fig. G57: Choice of protective conductors (PE).

Choice of earthing method implementation.

After consulting applicable regulations, Figure E16 and Figure E17 can be used as an aid in
deciding on divisions and possible galvanic isolation of appropriate sections of a proposed
installation.

Division of source

This technique concerns the use of several transformers instead of employing one high-rated unit. In
this way, a load that is a source of network disturbances (large motors, furnaces, etc.) can be
supplied by its own transformer.

The quality and continuity of supply to the whole installation are thereby improved.

The cost of switchgear is reduced (short-circuit current level is lower).

The cost-effectiveness of separate transformers must be determined on a case by case basis.

Network islands

The creation of galvanically-separated islands by means of LV/LV transformers makes it possible to


optimise the choice of earthing methods to meet specific requirements (see Fig. E18 and Fig. E19).
Fig. E18: TN-S island within an IT system

Fig. E19: IT islands within a TN-S system

Conclusion

The optimisation of the performance of the whole installation governs the choice of earthing system.

Including:

Initial investments, and

Future operational expenditures, hard to assess, that can arise from insufficient reliability,
quality of equipment, safety, continuity of service, etc.
An ideal structure would comprise normal power supply sources, local reserve power supply sources
(see Selection criteria for the TT, TN and IT systems ) and the appropriate earthing arrangements.

Installation and measurements of earth electrodes.

A very effective method of obtaining a low-resistance earth connection is to bury a conductor in the form of a
closed loop in the soil at the bottom of the excavation for building foundations.

The resistance R of such an electrode (in homogeneous soil) is given (approximately) in ohms by:

where

L = length of the buried conductor in metres


= soil resistivity in ohm-metres

The quality of an earth electrode (resistance as low as possible) depends essentially on two factors:

Installation method

Type of soil

Installation methods

Three common types of installation will be discussed:

Buried ring

(see Fig. E20)

This solution is strongly recommended, particularly in the case of a new building.

The electrode should be buried around the perimeter of the excavation made for the foundations. It
is important that the bare conductor be in intimate contact with the soil (and not placed in the gravel
or aggregate hard-core, often forming a base for concrete). At least four (widely-spaced) vertically
arranged conductors from the electrode should be provided for the installation connections and,
where possible, any reinforcing rods in concrete work should be connected to the electrode.
The conductor forming the earth electrode, particularly when it is laid in an excavation for
foundations, must be in the earth, at least 50 cm below the hard-core or aggregate base for the
concrete foundation. Neither the electrode nor the vertical rising conductors to the ground floor,
should ever be in contact with the foundation concrete.

For existing buildings, the electrode conductor should be buried around the outside wall of the
premises to a depth of at least 1 metre. As a general rule, all vertical connections from an electrode
to above-ground level should be insulated for the nominal LV voltage (600-1,000 V).

The conductors may be:

Copper: Bare cable ( 25 mm2) or multiple-strip ( 25 mm2) and ( 2 mm thick)

Aluminium with lead jacket: Cable ( 35 mm2)

Galvanised-steel cable: Bare cable ( 95 mm2) or multiple-strip ( 100 mm2 and 3 mm


thick)

The approximate resistance R of the electrode in ohms:

where

L = length of conductor in metres


= resistivity of the soil in ohm-metres (see Influence of the type of soil )

Fig. E20: Conductor buried below the level of the foundations, i.e. not in the concrete

Earthing rods
(see Fig. E21)

For n rods:

Vertically driven earthing rods are often used for existing buildings, and for improving (i.e. reducing
the resistance of) existing earth electrodes.

The rods may be:

Copper or (more commonly) copper-clad steel. The latter are generally 1 or 2 metres long
and provided with screwed ends and sockets in order to reach considerable depths, if necessary
(for instance, the water-table level in areas of high soil resistivity)

Galvanised[1] steel pipe 25 mm diameter or rod 15 mm diameter, 2 metres long in each


case.

Fig. E21: Earthing rods connected in parallel

It is often necessary to use more than one rod, in which case the spacing between them should
exceed the depth to which they are driven, by a factor of 2 to 3.

The total resistance (in homogeneous soil) is then equal to the resistance of one rod, divided by the
number of rods in question.

The approximate resistance R obtained is: if the distance separating the rods > 4L
where

L = the length of the rod in metres


= resistivity of the soil in ohm-metres (see Influence of the type of soil)
n = the number of rods

Vertical plates

(see Fig. E22)

For a vertical plate electrode:

Rectangular plates, each side of which must be 0.5 metres, are commonly used as earth
electrodes, being buried in a vertical plane such that the centre of the plate is at least 1 metre below
the surface of the soil.

The plates may be:

Copper of 2 mm thickness

Galvanised[1] steel of 3 mm thickness

The resistance R in ohms is given (approximately), by:

where

L = the perimeter of the plate in metres


= resistivity of the soil in ohm-metres (see Influence of the type of soil)
Fig. E22: Vertical plate - 2 mm thickness (Cu)

Influence of the type of soil

Measurements on earth electrodes in similar soils are useful to determine the resistivity value to be applied for
the design of an earth-electrode system

Type of soil Mean value of resistivity in m

Swampy soil, bogs 1 - 30

Silt alluvium 20 - 100

Humus, leaf mould 10 - 150

Peat, turf 5 - 100

Soft clay 50

Marl and compacted clay 100 - 200

Jurassic marl 30 - 40
Clayey sand 50 - 500

Siliceous sand 200 - 300

Stoney ground 1,500 - 3,000

Grass-covered-stoney sub-soil 300 - 500

Chalky soil 100 - 300

Limestone 1,000 - 5,000

Fissured limestone 500 - 1,000

Schist, shale 50 - 300

Mica schist 800

Granite and sandstone 1,500 - 10,000

Modified granite and sandstone 100 - 600

Fig. E23: Resistivity (m) for different types of soil

Type of soil Average value of resistivity in m

Fertile soil, compacted damp fill 50

Arid soil, gravel, uncompacted non-uniform fill 500

Stoney soil, bare, dry sand, fissured rocks 3000


Fig. E24: Average resistivity (m) values for approximate earth-elect

Measurement and constancy of the resistance between an earth electrode and the
earth

The resistance of the electrode/earth interface rarely remains constant

Among the principal factors affecting this resistance are the following:

Humidity of the soil


The seasonal changes in the moisture content of the soil can be significant at depths of up to
2 meters.
At a depth of 1 metre the resistivity and therefore the resistance can vary by a ratio of 1 to 3
between a wet winter and a dry summer in temperate regions

Frost
Frozen earth can increase the resistivity of the soil by several orders of magnitude. This is
one reason for recommending the installation of deep electrodes, in particular in cold
climates

Ageing
The materials used for electrodes will generally deteriorate to some extent for various
reasons, for example:

Chemical reactions (in acidic or alkaline soils)

Galvanic: due to stray DC currents in the earth, for example from electric railways, etc. or
due to dissimilar metals forming primary cells. Different soils acting on sections of the
same conductor can also form cathodic and anodic areas with consequent loss of surface
metal from the latter areas. Unfortunately, the most favourable conditions for low earth-
electrode resistance (i.e. low soil resistivity) are also those in which galvanic currents can
most easily flow.

Oxidation
Brazed and welded joints and connections are the points most sensitive to oxidation.
Thorough cleaning of a newly made joint or connection and wrapping with a suitable
greased-tape binding is a commonly used preventive measure.
Measurement of the earth-electrode resistance

There must always be one or more removable links to isolate an earth electrode so that it can be
tested.

There must always be removable links which allow the earth electrode to be isolated from the
installation, so that periodic tests of the earthing resistance can be carried out. To make such tests,
two auxiliary electrodes are required, each consisting of a vertically driven rod.

Ammeter method (see Fig. E25)

Fig. E25: Measurement of the resistance to earth of the earth electrode of an installation by means
of an ammeter

When the source voltage U is constant (adjusted to be the same value for each test) then:
In order to avoid errors due to stray earth currents (galvanic -DC- or leakage currents from power
and communication networks and so on) the test current should be AC, but at a different frequency
to that of the power system or any of its harmonics. Instruments using hand-driven generators to
make these measurements usually produce an AC voltage at a frequency of between 85 Hz and 135
Hz.

The distances between the electrodes are not critical and may be in different directions from the
electrode being tested, according to site conditions. A number of tests at different spacings and
directions are generally made to cross-check the test results.

Use of a direct-reading earthing-resistance ohmmeter

These instruments use a hand-driven or electronic-type AC generator, together with two auxiliary
electrodes, the spacing of which must be such that the zone of influence of the electrode being
tested should not overlap that of the test electrode (C). The test electrode (C) furthest from the
electrode (X) under test, passes a current through the earth and the electrode under test, while the
second test electrode (P) picks up a voltage. This voltage, measured between (X) and (P), is due to
the test current and is a measure of the contact resistance (of the electrode under test) with earth. It
is clear that the distance (X) to (P) must be carefully chosen to give accurate results. If the distance
(X) to (C) is increased, however, the zones of resistance of electrodes (X) and (C) become more
remote, one from the other, and the curve of potential (voltage) becomes more nearly horizontal
about the point (O).

In practical tests, therefore, the distance (X) to (C) is increased until readings taken with electrode
(P) at three different points, i.e. at (P) and at approximately 5 metres on either side of (P), give
similar values. The distance (X) to (P) is generally about 0.68 of the distance (X) to (C).
[a] the principle of [b] showing the
measurement is based on effect on the
assumed homogeneous soil potential gradient
conditions. Where the zones of when (X) and (C)
influence of electrodes C and X are widely spaced.
overlap, the location of test The location of test
electrode P is difficult to electrode P is not
determine for satisfactory critical and can be
results. easily determined.

Fig. E26: Measurement of the resistance to the mass of earth of electrode (X) using an earth-electrode-testing

ohmmeter

Notes

1. ^ a b Where galvanised conducting materials are used for earth electrodes, sacrificial cathodic
protection anodes may be necessary to avoid rapid corrosion of the electrodes where the
soil is aggressive. Specially prepared magnesium anodes (in a porous sack filled with a
suitable soil) are available for direct connection to the electrodes. In such circumstances, a
specialist should be consulted.
Selection criteria for the TT, TN and IT systems.
Selection does not depend on safety criteria.

The three systems are equivalent in terms of protection of persons if all installation and operating rules are
correctly followed.

The selection criteria for the best system(s) depend on the regulatory requirements, the required continuity of
service, operating conditions and the types of network and loads

In terms of the protection of persons, the three system earthing arrangements (SEA) are equivalent
if all installation and operating rules are correctly followed. Consequently, selection does not depend
on safety criteria.

It is by combining all requirements in terms of regulations, continuity of service, operating conditions


and the types of network and loads that it is possible to determine the best system(s) (see Fig. E16).

Selection is determined by the following factors:

Above all, the applicable regulations which in some cases impose certain types of SEA

Secondly, the decision of the owner if supply is via a private MV/LV transformer (MV
subscription) or the owner has a private energy source (or a separate-winding transformer)

If the owner effectively has a choice, the decision on the SEA is taken following discussions with the
network designer (design office, contractor).

The discussions must cover:

First of all, the operating requirements (the required level of continuity of service) and the
operating conditions (maintenance ensured by electrical personnel or not, in-house personnel or
outsourced, etc.)

Secondly, the particular characteristics of the network and the loads (see Fig. E17 ).

TN- TN- IT1[a] IT2[b] Comments


TT S C

Electrical characteristics

Fault current - -- -- + --
Fault voltage - - - + -

Touch voltage +/- - - + -


-

Protection

Protection of persons against indirect contact + + + + +

Protection of persons with emergency generating sets + - - + -

Protection against fire (with an RCD) + + Not + +


allowed
Overvoltages

Continuous overvoltage + + + - +

Transient overvoltage + - - + -

Overvoltage if transformer - + + + +
breakdown(primary/secondary)

Electromagnetic compatibility

Immunity to nearby lightning strikes - + + + +


Immunity to lightning strikes on MV lines - - - - -

Continuous emission of an electromagnetic field + + - + +

Transient non-equipotentiality of the PE + - - + -

Continuity of service

Interruption for first fault - - - + +

Voltage dip during insulation fault + - - + -

Installation

Special devices - + + - -

Number of earth electrodes - + + -/+ -/+


Number of cables - - + - -

Maintenance

Cost of repairs - -- -- - --

Installation damage + - - ++ -

[a] IT-net when a first fault occurs.

[b] IT-net when a second fault occurs.

Fig. E16: Comparison of system earthing arrangements

Type of network Advised

Very large network with high-quality earth electrodes for exposed conductive parts (10 max.)
Very large network with low-quality earth electrodes for exposed conductive parts (> 30 ) TN

Disturbed area (storms) (e.g. television or radio transmitter) TN

Network with high leakage currents (> 500 mA) TN[d]

Network with outdoor overhead lines TT[e]

Emergency standby generator set IT

Type of loads

Loads sensitive to high fault currents (motors, etc.) IT

Loads with a low insulation level (electric furnaces,welding machines, heating elements, TN[i]
immersion heaters, equipment in large kitchens)

Numerous phase-neutral single-phase loads (mobile, semi-fixed, portable) TT[j]


TN-S

Loads with sizeable risks (hoists, conveyers, etc.) TN[k]

Numerous auxiliaries (machine tools) TN-S


Miscellaneous

Supply via star-star connected power transformer[n] TT

Premises with risk of fire IT[o]

Increase in power level of LV utility subscription, requiring a private substation TT[p]

Installation with frequent modifications TT[q]

Installation where the continuity of earth circuits is uncertain (work sites, old installations) TT[s]

Electronic equipment (computers, PLCs) TN-S

Machine control-monitoring network, PLC sensors and actuators IT[t]

[a] When the SEA is not imposed by regulations, it is selected according to the level of operating characteristics

(continuity of service that is mandatory for safety reasons or desired to enhance productivity, etc.). Whatever the

SEA, the probability of an insulation failure increases with the length of the network. It may be a good idea to break

up the network, which facilitates fault location and makes it possible to implement the system advised above for each

type of application.

[b] The risk of flashover on the surge limiter turns the isolated neutral into an earthed neutral. These risks are high for

regions with frequent thunder storms or installations supplied by overhead lines. If the IT system is selected to ensure

a higher level of continuity of service, the system designer must precisely calculate the tripping conditions for a

second fault.

[c] Risk of RCD nuisance tripping.

[d] Whatever the SEA, the ideal solution is to isolate the disturbing section if it can be easily identified.

[e] Risks of phase-to-earth faults affecting equipotentiality.


[f] Insulation is uncertain due to humidity and conducting dust.

[g] The TN system is not advised due to the risk of damage to the generator in the case of an internal fault. What is

more, when generator sets supply safety equipment, the system must not trip for the first fault.

[h] The phase-to-earth current may be several times higher than In, with the risk of damaging or accelerating the

ageing of motor windings, or of destroying magnetic circuits.

[i] To combine continuity of service and safety, it is necessary and highly advised, whatever the SEA, to separate

these loads from the rest of the installation (transformers with local neutral connection).

[j] When load equipment quality is not a design priority, there is a risk that the insulation resistance will fall rapidly.

The TT system with RCDs is the best means to avoid problems.

[k] The mobility of this type of load causes frequent faults (sliding contact for bonding of exposed conductive parts)

that must be countered. Whatever the SEA, it is advised to supply these circuits using transformers with a local

neutral connection.

[l] Requires the use of transformers with a local TN system to avoid operating risks and nuisance tripping at the first

fault (TT) or a double fault (IT).

[l2] With a double break in the control circuit.

[m] Excessive limitation of the phase-to-neutral current due to the high value of the zero-phase impedance (at least 4

to 5 times the direct impedance). This system must be replaced by a star-delta arrangement.

[n] The high fault currents make the TN system dangerous. The TN-C system is forbidden.

[o] Whatever the system, the RCD must be set to n 500 mA.

[p] An installation supplied with LV energy must use the TT system. Maintaining this SEA means the least amount of

modifications on the existing network (no cables to be run, no protection devices to be modified).

[q] Possible without highly competent maintenance personnel.

[r] This type of installation requires particular attention in maintaining safety. The absence of preventive measures in

the TN system means highly qualified personnel are required to ensure safety over time.

[s] The risks of breaks in conductors (supply, protection) may cause the loss of equipotentiality for exposed

conductive parts. A TT system or a TN-S system with 30 mA RCDs is advised and is often mandatory. The IT system

may be used in very specific cases.

[t] This solution avoids nuisance tripping for unexpected earth leakage.

Fig. E17: Influence of networks and loads on the selection of system earthing arrangements.

Characteristics of TT, TN and IT systems.


TT system

(see Fig. E12)


The TT system:

Technique for the protection of persons: the exposed conductive parts are earthed and residual current
devices (RCDs) are used

Operating technique: interruption for the first insulation fault

Fig. E12: TT system

Note: If the exposed conductive parts are earthed at a number of points, an RCD must be installed
for each set of circuits connected to a given earth electrode.

Main characteristics

Simplest solution to design and install. Used in installations supplied directly by the public LV
distribution network.

Does not require continuous monitoring during operation (a periodic check on the RCDs may
be necessary).

Protection is ensured by special devices, the residual current devices (RCD), which also
prevent the risk of fire when they are set to 500 mA.

Each insulation fault results in an interruption in the supply of power, however the outage is
limited to the faulty circuit by installing the RCDs in series (selective RCDs) or in parallel (circuit
selection).
Loads or parts of the installation which, during normal operation, cause high leakage
currents, require special measures to avoid nuisance tripping, i.e. supply the loads with a
separation transformer or use specific RCDs (see TT system - Protective measures).

TN system

see (Fig. E13 and Fig. E14)

The TN system:

Technique for the protection of persons:

Interconnection and earthing of exposed conductive parts and the neutral are mandatory

Interruption for the first fault using overcurrent protection (circuit-breakers or fuses)

Operating technique: interruption for the first insulation fault

Fig. E13: TN-C system

Fig. E14: TN-S system

Main characteristics
Generally speaking, the TN system:

Requires the installation of earth electrodes at regular intervals throughout the


installation

Requires that the initial check on effective tripping for the first insulation fault be
carried out by calculations during the design stage, followed by mandatory measurements to
confirm tripping during commissioning

Requires that any modification or extension be designed and carried out by a


qualified electrician

May result, in the case of insulation faults, in greater damage to the windings of
rotating machines

May, on premises with a risk of fire, represent a greater danger due to the higher
fault currents

In addition, the TN-C system:

At first glance, would appear to be less expensive (elimination of a device pole and of
a conductor)

Requires the use of fixed and rigid conductors

Is forbidden in certain cases:

Premises with a risk of fire

For computer equipment (presence of harmonic currents in the neutral)

In addition, the TN-S system:

May be used even with flexible conductors and small conduits

Due to the separation of the neutral and the protection conductor, provides a clean
PE (computer systems and premises with special risks)

IT system
(see Fig. E15)

IT system:

Protection technique:

Interconnection and earthing of exposed conductive parts

Indication of the first fault by an insulation monitoring device (IMD)

Interruption for the second fault using overcurrent protection (circuit-breakers or fuses)

Operating technique:

Monitoring of the first insulation fault

Mandatory location and clearing of the fault

Interruption for two simultaneous insulation faults

Fig. E15: IT system

Main characteristics

Solution offering the best continuity of service during operation

Indication of the first insulation fault, followed by mandatory location and clearing, ensures
systematic prevention of supply outages

Generally used in installations supplied by a private MV/LV or LV/LV transformer


Requires maintenance personnel for monitoring and operation

Requires a high level of insulation in the network (implies breaking up the network if it is very
large and the use of circuit-separation transformers to supply loads with high leakage currents)

The check on effective tripping for two simultaneous faults must be carried out by
calculations during the design stage, followed by mandatory measurements during commissioning
on each group of interconnected exposed conductive parts

Protection of the neutral conductor must be ensured as indicated in Protection of the neutral
conductor inside chapter Sizing and protection of conductors.

Definition of standardised earthing schemes.

he different earthing schemes (often referred to as the type of power system or system earthing arrangements)
described characterise the method of earthing the installation downstream of the secondary winding of a MV/LV
transformer and the means used for earthing the exposed conductive-parts of the LV installation supplied from it

The choice of these methods governs the measures necessary for protection against indirect-contact
hazards.

The earthing system qualifies three originally independent choices made by the designer of an
electrical distribution system or installation:

The type of connection of the electrical system (that is generally of the neutral conductor)
and of the exposed parts to earth electrod (s)

A separate protective conductor or protective conductor and neutral conductor being a single
conductor

The use of earth fault protection of overcurrent protective switchgear which clear only
relatively high fault currents or the use of additional relays able to detect and clear small insulation
fault currents to earth

In practice, these choices have been grouped and standardised as explained below.
Each of these choices provides standardised earthing systems with three advantages and
drawbacks:

Connection of the exposed conductive parts of the equipment and of the neutral conductor to
the PE conductor results in equipotentiality and lower overvoltages but increases earth fault
currents

A separate protective conductor is costly even if it has a small cross-sectional area but it is
much more unlikely to be polluted by voltage drops and harmonics, etc. than a neutral conductor
is. Leakage currents are also avoided in extraneous conductive parts

Installation of residual current protective relays or insulation monitoring devices are much
more sensitive and permits in many circumstances to clear faults before heavy damage occurs
(motors, fires, electrocution). The protection offered is in addition independent with respect to
changes in an existing installation

TT system (earthed neutral)

(see Fig. E3)

One point at the supply source is connected directly to earth. All exposed- and extraneous-
conductive-parts are connected to a separate earth electrode at the installation. This electrode may
or may not be electrically independent of the source electrode. The two zones of influence may
overlap without affecting the operation of protective devices.

Fig. E3: TT System

TN systems (exposed conductive parts connected to the neutral)


The source is earthed as for the TT system (above). In the installation, all exposed- and extraneous-
conductive-parts are connected to the neutral conductor. The several versions of TN systems are
shown below.

TN-C system

(see Fig. E4)

The neutral conductor is also used as a protective conductor and is referred to as a PEN
(Protective Earth and Neutral) conductor. This system is not permitted for conductors of less than 10
mm2 or for portable equipment.

The TN-C system requires an effective equipotential environment within the installation with
dispersed earth electrodes spaced as regularly as possible since the PEN conductor is both the
neutral conductor and at the same time carries phase unbalance currents as well as 3 rd order
harmonic currents (and their multiples).

The PEN conductor must therefore be connected to a number of earth electrodes in the installation.

Caution: In the TN-C system, the protective conductor function has priority over the neutral
function. In particular, a PEN conductor must always be connected to the earthing terminal of a load
and a jumper is used to connect this terminal to the neutral terminal.

Fig. E4: TN-C system

TN-S system

(see Fig. E5)


The TN-S system (5 wires) is obligatory for circuits with cross-sectional areas less than 10 mm 2 for
portable equipment.

The protective conductor and the neutral conductor are separate. On underground cable systems
where lead-sheathed cables exist, the protective conductor is generally the lead sheath. The use of
separate PE and N conductors (5 wires) is obligatory for circuits with cross-sectional areas less than
10 mm2 for portable equipment.

Fig. E5: TN-S system

TN-C-S system

(see Fig. E6 and Fig. E7)

The TN-C and TN-S systems can be used in the same installation. In the TN-C-S system, the TN-C
(4 wires) system must never be used downstream of the TN-S (5 wires) system, since any accidental
interruption in the neutral on the upstream part would lead to an interruption in the protective
conductor in the downstream part and therefore a danger.
Fig. E6: TN-C-S system

Fig. E7: Connection of the PEN conductor in the TN-C system

IT system (isolated or impedance-earthed neutral)

IT system (isolated neutral)

No intentional connection is made between the neutral point of the supply source and earth
(see Fig. E8).

Fig. E8: IT system (isolated neutral)

Exposed- and extraneous-conductive-parts of the installation are connected to an earth electrode.


In practice all circuits have a leakage impedance to earth, since no insulation is perfect. In parallel
with this (distributed) resistive leakage path, there is the distributed capacitive current path, the two
paths together constituting the normal leakage impedance to earth (see Fig. E9).

Fig. E9: IT system (isolated neutral)

Example (see Fig. E10)

In a LV 3-phase 3-wire system, 1 km of cable will have a leakage impedance due to C1, C2, C3 and
R1, R2 and R3 equivalent to a neutral earth impedance Zct of 3,000 to 4,000 , without counting the
filtering capacitances of electronic devices.

Fig. E10: Impedance equivalent to leakage impedances in an IT system

IT system (impedance-earthed neutral)

An impedance Zs (in the order of 1,000 to 2,000 ) is connected permanently between the neutral
point of the transformer LV winding and earth (see Fig. E11). All exposed- and extraneous-
conductive-parts are connected to an earth electrode. The reasons for this form of power-source
earthing are to fix the potential of a small network with respect to earth (Zs is small compared to the
leakage impedance) and to reduce the level of overvoltages, such as transmitted surges from the
MV windings, static charges, etc. with respect to earth. It has, however, the effect of slightly
increasing the first-fault current level.

Fig. E11: IT system (impedance-earthed neutral).

Earthing connections.

In a building, the connection of all metal parts of the building and all exposed conductive parts of electrical
equipment to an earth electrode prevents the appearance of dangerously high voltages between any two
simultaneously accessible metal parts

Definitions

National and international standards (IEC 60364) clearly define the various elements of earthing
connections. The following terms are commonly used in industry and in the literature. Bracketed
numbers refer to Figure E1
Fig. E1: An example of a block of flats in which the main earthing terminal (6) provides the main
equipotential connection; the removable link (7) allows an earth-electrode-resistance check

Earth electrode (1): A conductor or group of conductors in intimate contact with, and
providing an electrical connection with Earth (cf details in section 1.6 of Chapter E.)

Earth: The conductive mass of the Earth, whose electric potential at any point is
conventionally taken as zero

Electrically independent earth electrodes: Earth electrodes located at such a distance from
one another that the maximum current likely to flow through one of them does not significantly
affect the potential of the other(s)

Earth electrode resistance: The contact resistance of an earth electrode with the Earth
Earthing conductor (2): A protective conductor connecting the main earthing terminal (6) of
an installation to an earth electrode (1) or to other means of earthing (e.g. TN systems);

Exposed-conductive-part: A conductive part of equipment which can be touched and which is


not a live part, but which may become live under fault conditions

Protective conductor (3): A conductor used for some measures of protection against electric
shock and intended for connecting together any of the following parts:

Exposed-conductive-parts

Extraneous-conductive-parts

The main earthing terminal

Earth electrode(s)

The earthed point of the source or an artificial neutral

Extraneous-conductive-part: A conductive part liable to introduce a potential, generally earth


potential, and not forming part of the electrical installation (4).
For example:

Non-insulated floors or walls, metal framework of buildings

Metal conduits and pipework (not part of the electrical installation) for water, gas, heating,
compressed-air, etc. and metal materials

associated with them

Bonding conductor (5): A protective conductor providing equipotential bonding

Main earthing terminal (6): The terminal or bar provided for the connection of protective
conductors, including equipotential bonding conductors, and conductors for functional earthing, if
any, to the means of earthing.

Connections

The main equipotential bonding system


The bonding is carried out by protective conductors and the aim is to ensure that, in the event of an
incoming extraneous conductor (such as a gas pipe, etc.) being raised to some potential due to a
fault external to the building, no difference of potential can occur between extraneous-conductive-
parts within the installation.

The bonding must be effected as close as possible to the point(s) of entry into the building, and be
connected to the main earthing terminal (6).

However, connections to earth of metallic sheaths of communications cables require the


authorisation of the owners of the cables.

Supplementary equipotential connections

These connections are intended to connect all exposed-conductive-parts and all extraneous-
conductive-parts simultaneously accessible, when correct conditions for protection have not been
met, i.e. the original bonding conductors present an unacceptably high resistance.

Connection of exposed-conductive-parts to the earth electrode(s)

The connection is made by protective conductors with the object of providing a low-resistance path
for fault currents flowing to earth.

Components

(see Fig. E2)

Effective connection of all accessible metal fixtures and all exposed-conductive-parts of electrical
appliances and equipment, is essential for effective protection against electric shocks.

Component parts to consider:

as exposed-conductive-parts as extraneous-conductive-parts

Elements used in building construction


Cableways

Metal or reinforced concrete (RC):


Conduits

Steel-framed structure
Impregnated-paper-insulated lead-covered cable,
armoured or unarmoured Reinforcement rods

Mineral insulated metal-sheathed cable (pyrotenax, Prefabricated RC panels

etc.)
Switchgear Surface finishes:

cradle of withdrawable switchgear Floors and walls in reinforced concrete

Appliances without further

Exposed metal parts of class 1 insulated appliances surface treatment

Tiled surface

Metallic covering:

Metallic wall covering


Non-electrical elements Building services elements other than electrical

metallic fittings associated with cableways (cable Metal pipes, conduits, trunking, etc. for gas,water

trays, cable ladders, etc.) and heating systems, etc.

Metal objects: Related metal components (furnaces,

tanks,reservoirs, radiators)
Close to aerial conductors or to busbars

Metallic fittings in wash rooms, bathrooms, toilets,


In contact with electrical equipment.
etc.

Metallised papers
Component parts not to be considered:
as exposed-conductive-parts as extraneous-conductive-parts

Diverse service channels, ducts, etc.

Wooden-block floors
Conduits made of insulating material

Rubber-covered or linoleum-covered floors


Mouldings in wood or other insulating material

Dry plaster-block partition


Conductors and cables without metallic sheaths
Brick walls

Carpets and wall-to-wall carpeting


Switchgear


Enclosures made of insulating material
Appliances


All appliances having class II insulation regardless of

the type of exterior envelope

Fig. E2: List of exposed-conductive-parts and extraneous-conductive-parts.

Cables and busways.


Distribution and installation methods

(see Fig. E36)

Distribution takes place via cableways that carry single insulated conductors or cables and include a
fixing system and mechanical protection.
Fig. E36: Radial distribution using cables in a hotel

Busbar trunking (busways)

Busways, also referred to as busbar trunking systems, stand out for their ease of installation, flexibility and
number of possible connection points

Busbar trunking is intended to distribute power (from 20 A to 5000 A) and lighting (in this application,
the busbar trunking may play a dual role of supplying electrical power and physically holding the
lights).

Busbar trunking system components

A busbar trunking system comprises a set of conductors protected by an enclosure (see Fig. E37).
Used for the transmission and distribution of electrical power, busbar trunking systems have all the
necessary features for fitting: connectors, straights, angles, fixings, etc. The tap-off points placed at
regular intervals make power available at every point in the installation.

Fig. E37: Busbar trunking system design for distribution of currents from 25 to 4000A

The various types of busbar trunking:

Busbar trunking systems are present at every level in electrical distribution: from the link between
the transformer and the low voltage switch switchboard (MLVS) to the distribution of power sockets
and lighting to offices, or power distribution to workshops.
Fig. E38: Radial distribution using busways

We talk about a distributed network architecture.

There are essentially three categories of busways.

Transformer to MLVS busbar trunking


Installation of the busway may be considered as permanent and will most likely never be
modified. There are no tap-off points.
Frequently used for short runs, it is almost always used for ratings above 1,600 /2,000 A, i.e.
when the use of parallel cables makes installation impossible. Busways are also used
between the MLVS and downstream distribution switchboards.
The characteristics of main-distribution busways authorize operational currents from1,000 to
5,000 A and short-circuit withstands up to 150 kA.

Sub-distribution busbar trunking with low or high tap-off densities


Downstream of main-distribution busbar trunking , two types of applications must be
supplied:

Mid-sized premises (industrial workshops with injection presses and metalwork machines or
large supermarkets with heavy loads).
The short-circuit and current levels can be fairly high (respectively 20 to 70 kA and 100 to
1,000 A)

Small sites (workshops with machine-tools, textile factories with small


machines,supermarkets with small loads). The short-circuit and current levels are lower
(respectively 10 to 40 kA and 40 to 400 A)
Sub-distribution using busbar trunking meets user needs in terms of:

Modifications and upgrades given the high number of tap-off points

Dependability and continuity of service because tap-off units can be connected under
energized conditions in complete safety
The sub-distribution concept is also valid for vertical distribution in the form of 100 to 5,000 A
risers in tall buildings.

Lighting distribution busbar trunking


Lighting circuits can be distributed using two types of busbar trunking according to whether
the lighting fixtures are suspended from the busbar trunking or not.

busbar trunking designed for the suspension of lighting fixtures


These busways supply and support light fixtures (industrial reflectors, discharge lamps, etc.).
They are used in industrial buildings, supermarkets, department stores and warehouses. The
busbar trunkings are very rigid and are designed for one or two 25 A or 40 A circuits. They
have tap-off outlets every 0.5 to 1 m.

busbar trunking not designed for the suspension of lighting fixtures


Similar to prefabricated cable systems, these busways are used to supply all types of lighting
fixtures secured to the building structure. They are used in commercial buildings (offices,
shops, restaurants, hotels, etc.), especially in false ceilings. The busbar trunking is flexible
and designed for one 20 A circuit. It has tap-off outlets every 1.2 m to 3 m.

Busbar trunking systems are suited to the requirements of a large number of buildings.

Industrial buildings: garages, workshops, farm buildings, logistic centers, etc.

Commercial areas: stores, shopping malls, supermarkets, hotels, etc.


Tertiary buildings: offices, schools, hospitals, sports rooms, cruise liners, etc.

Standards

Busbar trunking systems must meet all rules stated in IEC 61439-6.

This defines the manufacturing arrangements to be complied with in the design of busbar trunking
systems (e.g.: temperature rise characteristics, short-circuit withstand, mechanical strength, etc.) as
well as test methods to check them.

The new standard IEC61439-6 describes in particular the design verifications and routine
verifications required to ensure compliance.

By assembling the system components on the site according to the assembly instructions, the
contractor benefits from conformity with the standard.

The advantages of busbar trunking systems

Flexibility

Easy to change configuration (on-site modification to change production line configuration or


extend production areas).

Reusing components (components are kept intact): when an installation is subject to major
modifications, the busbar trunking is easy to dismantle and reuse.

Power availability throughout the installation (possibility of having a tap-off point every
meter).

Wide choice of tap-off units.

Simplicity

Design can be carried out independently from the distribution and layout of current
consumers.

Performances are independent of implementation: the use of cables requires a lot of derating
coefficients.
Clear distribution layout

Reduction of fitting time: the trunking system allows fitting times to be reduced by up to 50%
compared with a traditional cable installation.

Manufacturers guarantee.

Controlled execution times: the trunking system concept guarantees that there are no
unexpected surprises when fitting. The fitting time is clearly known in advance and a quick solution
can be provided to any problems on site with this adaptable and scalable equipment.

Easy to implement: modular components that are easy to handle, simple and quick to
connect.

Dependability

Reliability guaranteed by being factory-built

Fool-proof units

Sequential assembly of straight components and tap-off units making it impossible to make
any mistakes

Continuity of service

The large number of tap-off points makes it easy to supply power to any new current
consumer. Connecting and disconnecting is quick and can be carried out in complete safety even
when energized. These two operations (adding or modifying) take place without having to stop
operations.

Quick and easy fault location since current consumers are near to the line

Maintenance is non existent or greatly reduced

Major contribution to sustainable development

Busbar trunking systems allow circuits to be combined. Compared with a traditional cable
distribution system, consumption of raw materials for insulators is divided by 4 due to the busbar
trunking distributed network concept (see Fig. E39).
Reusable device and all of its components are fully recyclable.

Does not contain PVC and does not generate toxic gases or waste.

Reduction of risks due to exposure to electromagnetic fields.

Fig. E39: Example of a set of 14 x 25A loads distributed along 34 meters (for busway, Canalis KS
250A)

New functional features for Canalis

Busbar trunking systems are getting even better. Among the new features we can mention:

Increased performance with a IP55 protection index and new ratings of 160 A through to
1000 A (Ks).

New lighting offers with pre-cabled lights and new light ducts.

New fixing accessories. Quick fixing system, cable ducts, shared support with VDI (voice,
data, images) circuits.

Busbar trunking systems are perfectly integrated with the environment:

white color to enhance the working environment, naturally integrated in a range of electrical
distribution products.
conformity with European regulations on reducing hazardous materials (RoHS).

Examples of Canalis busbar trunking systems

Fig. E41: Rigid busbar trunking able to support light fittings: Canalis KBA or KBB (25 and 40 A)

Fig. E43: A busway for medium power distribution: Canalis KN (40 up to 160 A)

Fig. E44: A busway for medium power distribution: Canalis KS (100 up to 1000A)
Fig. E45: A busway for high power distribution: Canalis KT (800 up to 5000A).

The architecture design.


The architecture design considered in this document starts at the preliminary design stage
(see Fig. D3 step1). It generally covers the levels of MV/LV main distribution, LV power distribution,
and exceptionally the terminal distribution level. (see Fig. D2).

In buildings all consumers are connected in low voltage. It means that MV distribution consists in:

connection to utility,

distribution to MV/LV substation(s),

MV/LV substation(s) itself.


Fig. D2: Example of single-line diagram

The design of an electrical distribution architecture can be described by a 3-stage process, with
iterative possibilities. This process is based on taking account of the installation characteristics and
criteria to be satisfied.

Internal MV circuits.
Internal MV circuits are dedicated to the supply of the secondary MV/LV substations dispersed in the
installation. They are three typical principles commonly used for this purpose Fig. D11:

Single feeder

Dual feeder

Open ring.
Comparison of these three typical principles of internal distribution is given Fig. D12.

MV circuit configuration

Characteristic to Single feeder Open ring Dual feeder


consider

Site topology Any Single or several Single or several


buildings buildings

Power demand Any > 1250kVA > 2500kVA

Disturbance Long interruption Short interruption Short interruption not


sensitivity acceptable acceptable acceptable

Fig. D12: Comparison of the typical internal circuits.

Number of MV/LV transformers.


For every MV/LV substation, the definition of the number of MV/LV transformers takes into account
the following criteria:
Total power supplied by the substation

Standardization of the rated power to reduce the number of spare transformers

Limit of the rated power. It is recommended to set this limit at 1250 kVA in order to facilitate
the handling and the replacement of the transformers

Scalability of the installation

Need to separate the loads having a high level of sensitivity to the electrical perturbations

Need to dedicate a transformer to the load generating a high level of perturbation such as
voltage dips, harmonics, flicker

Need for partial or total redundancy. When required, two transformers each sized for the full
load and equipped with an automatic change-over are installed

Loads requiring a dedicated neutral system. IT for example to ensure the continuity of
operation in case of phase to earth fault.

LV distribution - centralized or distributed layout.


Layout

Position of the main MV and LV equipment on the site or in the building.

This layout choice is applied to the results of stage 1.

Selection guide

As recommended in IEC60364-8-1 6.3, MV/LV substation location can be determined by using the
barycenter method:

taking into account service conditions: in dedicated premises if the layout in the workshop is
too restrictive (temperature, vibrations, dust, etc.)

Placing heavy equipment (transformers, generators, etc.) close to walls or to main exits for
ease of maintenance.

A layout example is given in the following diagram (Fig. D13):


Fig. D13: The position of the global load barycentre guides the positioning of power sources

Centralized or distributed layout of LV distribution

In centralized layout, each load is connected directly to the power source. (Fig. D14):
Fig. D14: Example of centralized layout with point to point links

In distributed layout, loads are connected to sources via a busway. This type of distribution is well
adapted to supply many loads that are spread out, where easy change is requested or future new
connection (need of flexibility) (Fig. D15):

Fig. D15: Example of distributed layout, with busway

Factors in favour of centralized layout (see summary table in Fig. D16):

Installation flexibility: no,


Load distribution: localized loads (high unit power loads).

Factors in favor of distributed layout:

Installation flexibility: "Implementation" flexibility (moving of workstations, etc),

Load distribution: uniform distribution of low or medium unit power loads

Load distribution

Flexibility (see Installation Localized Intermediate Uniformly


flexibilityfor definition of the loads distribution distributed
flexibility levels) loads loads

No flexibility Centralized Decentralized

Flexibility of design

Implementation flexibility Centralized Decentralized

Operation flexibility

Fig. D16: Recommendations for centralized or distributed layout

Centralized distribution gives greater independence of circuits, reducing the consequences of a


failure from power availability point of view.

The use of decentralized distribution with busway is a way to merge all the circuits in one: it makes it
possible to take into account the diversity factor (ks), which means cost savings on conductor sizing
(See Fig. D17). The choice between centralized and decentralized solutions, according to the
diversity factor, allows to find an economic optimum between investment costs, installation costs and
operating costs.

These two distribution modes are often combined.


Fig. D17: Example of a set of 14 x 25A loads distributed along 34 meters (for busway, Canalis KS
250A).

Presence of LV back-up generators.

LV backup-up generator is the association of an alternator mechanically powered by a thermal


engine.

No electrical power can be delivered until the generator has reached its rated speed. This type of
device is therefore not suitable for an uninterrupted power supply. Depending, if the generator is
sized to supply power to all or only part of the installation, there is either total or partial redundancy.

A back-up generator runs generally disconnected from the network. A source changeover and an
interlocking system is therefore required (see Fig. D18).

The generator back-up time depends on the quantity of available fuel.


Fig. D18: Connection of a back-up generator

The main characteristics to consider for implementing LV back-up generator:

Sensitivity of loads to power interruption (see Voltage Interruption Sensitivity for definition),

Availability of the public distribution network (see Service reliability for the definition),

Other constraints (e.g.: generators compulsory in hospitals or high buildings)

In addition the presence of generators can be decided to reduce the energy bill or due to the
opportunity for co-generation. These two aspects are not taken into account in this guide.

The presence of a back-up generator is essential if the loads cannot be shed (only short interruption
acceptable) or if the utility network availability is low.

Determining the number of back-up generator units is in line with the same criteria as determining
the number of transformers, as well as taking account of economic and availability considerations
(redundancy, start-up reliability, maintenance facility).

Determining the generator apparent power, depends on:

installation power demand of loads to be supplied,


transient constraints that can occur by motors inrush current for example.

Configuration of LV circuits.
Single feeder configuration

Fig. D20

This is the reference configuration and the most simple. A load is connected to one single source.
This configuration provides a minimum level of availability, since there is no redundancy in case of
power source failure.

Fig. D20: Single feeder configuration

Parallel transformers configuration

Fig. D21

The power supply is provided by more than 1 transformer generally connected in parallel to the
same main LV switchboard.

Fig. D21: Parallel transformers configuration


Variant: Normally open coupled transformers

Fig. D22

In order to increase the availability it is possible to split the main LV switchboard into 2 parts, with a
normally open bus-coupler (NO). This configuration may require an Automatic Transfer Switch
between the coupler and transformer incomers.

These 2 configurations are more often used when power demand is greater than 1 MVA.

Fig. D22: Normally open coupled transformers

Main LV switchboard interconnected by a busway

Fig. D23

Transformers are physically distant, and operated in parallel. They are connected by a busway, the
load can always be supplied in the case of failure of one of the sources. The redundancy can be:

Total: each transformer being able to supply all of the installation,

Partial: each transformer only being able to supply part of the installation. In this case, part of
the loads must be disconnected (load-shedding) in the case of one of transformer failure.
Fig. D23: Main LV switchboard interconnected by a busway

LV ring configuration

Fig. D24

This configuration can be considered as an extension of the previous configuration with


interconnection between switchboards. Typically, 4 transformers connected in parallel to the same
MV line, supply a ring using busway. A given load is then supplied by several transformers. This
configuration is well suited to large sites, with high load density (in kVA/m 2). If all of the loads can be
supplied by 3 transformers, there is total redundancy in the case of failure of one of the transformers.
In fact, each busbar can be fed by one or other of its ends. Otherwise, downgraded operation must
be considered (with partial load shedding). This configuration requires special design of the
protection plan in order to ensure discrimination in all of the fault circumstances.

As the previous configuration this type of installation is commonly used in automotive industry or
large site manufacturing industry.
Fig. D24: Ring configuration

Double-ended power supply

Fig. D25

This configuration is implemented in cases where maximum availability is required. The principle
involves having 2 independent power sources, e.g.:

2 transformers supplied by different MV lines,

1 transformer and 1 generator,

1 transformer and 1 UPS.

An automatic transfer switch (ATS) is used to avoid the sources being parallel connected. This
configuration allows preventive and curative maintenance to be carried out on all of the electrical
distribution system upstream without interrupting the power supply.
Fig. D25: Double-ended configuration with automatic transfer switch

Configuration combinations

Fig. D26

An installation can be made up of several sub-asssemblies with different configurations, according to


requirements for the availability of the different types of load. E.g.: generator unit and UPS, choice
by sectors (some sectors supplied by cables and others by busways).

Fig. D26: Example of a configuration combination 1: Single feeder, 2: Main LV switchboard


interconnected by a busway, 3: Double-ended

For the different possible configurations, the most probable and usual set of characteristics is given
in the following table:
Characteristic to be Configuration
considered

Single feeder Parallel transformer or Main LV switchboard LV ring


(fig. D20) transformers connected via a interconnected by a busway
coupler (fig. D21-D22) (fig D24)

Site topology Any Any 1 level 5000 to 25000 m2 1 level 5000 to


m2

Power demand < 2500kVA Any 2500kVA > 2500kVA

Location latitude Any Any Medium or high Medium or high

Load distribution Localized Localized loads Intermediate or uniform load Intermediate or


loads distribution uniform load
distribution

Maintainability Minimal Standard Standard Standard

Disturbances Low sensitivity High sensitivity High sensitivity High sensitivity


sensitivity

Fig. D27: Recommendations for the configuration of LV circuits.

Example: electrical installation in a printworks.


Brief description

Printing of personalized mailshots intended for mail order sales.

Installation characteristics

Characteristic Category

Activity Mechanical
Site topology single storey building 10000m2 (8000m2 dedicated to the process,
2000m2 for ancillary areas)

Layout latitude High

Service reliability Standard

Maintainability Standard

Installation flexibility
No flexibility planned:

HVAC

Process utilities

Office power supply

Possible flexibility:

finishing, putting in envelopes

special machines, installed at a later date

rotary machines (uncertainty at the draft design

stage)
Power demand 3500kVA

Load distribution Intermediate distribution

Power interruptions
sensitivity
Sheddable circuits:

offices (apart from PC power sockets)

air conditioning, office heating

social premises
maintenance premises

long interruptions acceptable:

printing machines

workshop HVAC (hygrometric control

Finishing, envelope filling

Process utilities (compressor, recycling of cooled

water)

No interruptions acceptable:

servers, office PCs


Disturbance sensitivity

Average sensitivity:

motors, lighting

High sensitivity:

IT

No special precaution to be taken due to the connection to the EdF

network (low level of disturbance)

Disturbance capability Non disturbing

Other constraints

Building with lightning classification: lightning surge

arresters installed

Power supply by overhead single feeder line

Technological characteristics
Criteria Category

Service conditions
IP: standard (no dust, no water protection)

IK: standard (use of technical pits, dedicated

premises)

C: standard (temperature regulation)


Required service index 211

Offer availability by country No problem (project carried out in Europe)

Other criteria Not applicable

Architecture assessment criteria

Criteria Category

On-site work time Standard

Environmental impact Minimal: compliance with European standard regulations

Preventive maintenance costs Standard

Power supply availability Tier 1

Step 1: Architecture fundamentals

Choice Main criteria Solution

Connection to upstream Isolated site, 3500 kVA MV single-line service


network

MV Circuits Layout + criticality single feeder


Number of transformers Power > 2500kVA 2 x 2000kVA

Number and distribution of Surface area and power 2 possible solutions: 1 substation or 2 substations
substations distribution

if 1 substations: Normaly open bus-coupler

between MLVS

if 2 substations: Main LV switchboard

interconnected by a busway
MV Generator Site activity No

Fig. D31: Two possible single-line diagrams

Step 2: Architecture details

Choice Main criteria Solution

Layout Service conditions Dedicated premises


LV circuit 2 transformers, requested by Solution from fig.D22 or D23 are possible
configuration the power demand

Centralized or Uniform loads, distributed


distributed layout power, scalability possibilities Decentralized with busbar trunking:

Non-uniform loads, direct link finishing sector, envelope filling

from MLVS
Centralized with cables:

special machines, rotary machines, HVAC,

process utilities, offices (2 switchboards), office air

conditioning, social premises, maintenance


Presence of back- Criticality low No back-up generator
up generator

Network availability: standard

Presence of UPS Criticality UPS unit for IT devices and office workstations

Fig. D32: Detailed single-line diagram (1 substation based on fig.D22)


Fig. D33: Detailed single-line diagram (2 substation based on fig.D24)

Choice of technological solutions

Choice Main criteria Solution

MV/LV substation Service conditions indoor (dedicated premises)

MV switchboard Offer availability by country SM6 (installation in Europe)

Transformers Service conditions cast resin transfo (avoids constraints related to oil)

LV switchboard Service conditions, service index for LV MLVS: Prisma P


switchboards

Sub-distribution: Prisma

Busway Load distribution Canalis KS (fig.D32 or D33)


Canalis KT for main distribution (fig D33)

UPS units Installed power to be supplied, back-up Galaxy PW


time

Power factor correction Reactive power to provide for the minimum


up to the full load without harmonic (see
chapter Power Factor Correction for more
information), presence of harmonics.

MCBs.
Instantaneous Trip Setting.
6, 8, 10, 13, 16, 20, 25, 32, 40, 50, 63, 80, 100 and 125 A.
Instantaneous tripping less than 0.1 sec. for tripping.

B. 3 5 of the rated continuous Suitable for resistive loads,


currents. heaters, lighting etc.
C. 5 10 of the rated continuous Suitable for the reactive loads
currents. motors, general lighting etc.
D. 10 20 of the rated continuous Suitable for high reactive loads
currents. transformers, motors etc.

Permissible I2t (let-through energy) in A2s for circuit-breakers type B with rated
current up to and including 63A.

Permissible I2t (let-through energy) in A2s for circuit-breakers type C with rated
current up to and including 63A.
Cables withstanding capacities.

The application of fault current protective devices to cable protection is


detailed in BS 7671
and is given by:
I2t k2S2
Where:
I2t is the energy let-through value of the protective device
k2S2 is the energy withstand of the cable.

The code allows the breaking capacity of a circuit-breaker to be less than its
associated prospective fault current when back-up protection is employed in
cascading through a suitable upstream protective devices. Back-up protection
consists of an upstream short-circuit protective device (SCPD) that helps a
downstream circuit-breaker to break fault currents greater than its maximum
breaking current. However, where an MCCB, MCB or fuse is the upstream SCPD, and
the downstream SCPD is an MCB, coordination tests can be used to validate that the
I2t of the specific combination will not exceed the I2t value of the downstream MCB
at its maximum breaking capacity.
The I 2t of the upstream SCPD A and downstream MCB B operating together at
20 kA, will be equal to or less than the I 2t of MCB B at 10 kA. The I 2t to be used
in the conductor fault current assessment would be that of MCB B at 10 kA.

MCCBs.
(MCCBs) may have fixed or adjustable protection settings, normally a three position
toggle operating handle giving on-off-tripped indication plus reset function, and a
performance level relative to the incoming supply such that they can be installed at
a point close to the supply transformer.
Ratings: 16A to 1600A (may be upto 3200A), with the short circuit withstanding
capacities upto 100kA in selections.
Rated Short-Time Withstand Current.
Circuit-breakers of Selectivity Category B have a short-time delay (STD)
allowing timegraded
selectivity between circuit-breakers in series.
Icw is the fault current the circuit-breaker will withstand for the maximum
short-time
delay time.
Preferred times are: 0.05, 0.1, 0.25, 0.5 and 1.0 second.

In order to provide protection against electric shock in accordance with the


Wiring, it is necessary to determine the maximum value of Zs that will give
the required disconnection time. This will give the max. length of the circuits
downstream of the device for achieving the protections at around 80% of the
phase to N voltages. No tolerance may be required for the IT trippings,
but a 20% may be considered in the case of instantaneous types.
Calculation Methodology

This calculation is based on IEEE Std 80 (2000), "Guide for safety in AC substation grounding".
There are two main parts to this calculation:

Earthing grid conductor sizing

Touch and step potential calculations

IEEE Std 80 is quite descriptive, detailed and easy to follow, so only an overview will be
presented here and IEEE Std 80 should be consulted for further details (although references
will be given herein).

Prerequisites

The following information is required / desirable before starting the calculation:

A layout of the site

Maximum earth fault current into the earthing grid

Maximum fault clearing time

Ambient (or soil) temperature at the site

Soil resistivity measurements at the site (for touch and step only)

Resistivity of any surface layers intended to be laid (for touch and step only)

Earthing Grid Conductor Sizing

Determining the minimum size of the earthing grid conductors is necessary to ensure
that the earthing grid will be able to withstand the maximum earth fault current. Like a
normal power cable under fault, the earthing grid conductors experience an adiabatic
short circuit temperature rise. However unlike a fault on a normal cable, where the
limiting temperature is that which would cause permanent damage to the cable's
insulation, the temperature limit for earthing grid conductors is the melting point of the
conductor. In other words, during the worst case earth fault, we don't want the
earthing grid conductors to start melting!
The minimum conductor size capable of withstanding the adiabatic temperature rise
associated with an earth fault is given by re-arranging IEEE Std 80 Equation 37:

Where is the minimum cross-sectional area of the earthing grid conductor


(mm2)

is the energy of the maximum earth fault (A2s)

is the maximum allowable (fusing) temperature (C)

is the ambient temperature (C)

is the thermal coefficient of resistivity (C - 1)

is the resistivity of the earthing conductor (.cm)

is

is the thermal capacity of the conductor per unit volume(Jcm - 3C - 1)

The material constants Tm, r, r and TCAP for


common conductor materials can be found in
IEEE Std 80 Table 1. For example. commercial
hard-drawn copper has material constants:

Tm = 1084 C

r = 0.00381 C - 1

r = 1.78 .cm

TCAP = 3.42 Jcm - 3C - 1.

As described in IEEE Std 80 Section 11.3.1.1, there are alternative methods to formulate
this equation, all of which can also be derived from first principles).

There are also additional factors that should be considered (e.g. taking into account
future growth in fault levels), as discussed in IEEE Std 80 Section 11.3.3.
Touch and Step Potential Calculations

When electricity is generated remotely and there are no return paths for earth faults
other than the earth itself, then there is a risk that earth faults can cause dangerous
voltage gradients in the earth around the site of the fault (called ground potential rises).
This means that someone standing near the fault can receive a dangerous electrical
shock due to:

Touch voltages - there is a dangerous potential difference between the earth and a

metallic object that a person is touching

Step voltages - there is a dangerous voltage gradient between the feet of a person

standing on earth

The earthing grid can be used to dissipate fault currents to remote earth and reduce the
voltage gradients in the earth. The touch and step potential calculations are performed in
order to assess whether the earthing grid can dissipate the fault currents so that
dangerous touch and step voltages cannot exist.

Step 1: Soil Resistivity

The resistivity properties of the soil where the earthing grid will be laid is an important
factor in determining the earthing grid's resistance with respect to remote earth. Soils
with lower resistivity lead to lower overall grid resistances and potentially smaller
earthing grid configurations can be designed (i.e. that comply with safe step and touch
potentials).

It is good practice to perform soil resistivity tests on the site. There are a few standard
methods for measuring soil resistivity (e.g. Wenner four-pin method). A good discussion
on the interpretation of soil resistivity test measurements is found in IEEE Std 80 Section
13.4.

Sometimes it isn't possible to conduct soil resistivity tests and an estimate must suffice.
When estimating soil resistivity, it goes without saying that one should err on the side of
caution and select a higher resistivity. IEEE Std 80 Table 8 gives some guidance on range
of soil resistivities based on the general characteristics of the soil (i.e. wet organic soil =
10 .m, moist soil = 100 .m, dry soil = 1,000 .m and bedrock = 10,000 .m).
Step 2: Surface Layer Materials

Applying a thin layer (0.08m - 0.15m) of high resistivity material (such as gravel, blue
metal, crushed rock, etc) over the surface of the ground is commonly used to help
protect against dangerous touch and step voltages. This is because the surface layer
material increases the contact resistance between the soil (i.e. earth) and the feet of a
person standing on it, thereby lowering the current flowing through the person in the
event of a fault.

IEEE Std 80 Table 7 gives typical values for surface layer material resistivity in dry and
wet conditions (e.g. 40mm crushed granite = 4,000 .m (dry) and 1,200 .m (wet)).

The effective resistance of a person's feet (with respect to earth) when standing on a
surface layer is not the same as the surface layer resistance because the layer is not thick
enough to have uniform resistivity in all directions. A surface layer derating factor needs
to be applied in order to compute the effective foot resistance (with respect to earth) in
the presence of a finite thickness of surface layer material. This derating factor can be
approximated by an empirical formula as per IEEE Std 80 Equation 27:

Where is the surface layer


derating factor

is the soil resistivity (.m)

is the resistivity of the surface layer material (.m)

is the thickness of the surface layer (m)

This derating factor will be used later in Step 5 when calculating the maximum allowable
touch and step voltages.

Step 3: Earthing Grid Resistance

A good earthing grid has low resistance (with respect to remote earth) to minimise
ground potential rise (GPR) and consequently avoid dangerous touch and step voltages.
Calculating the earthing grid resistance usually goes hand in hand with earthing grid
design - that is, you design the earthing grid to minimise grid resistance. The earthing
grid resistance mainly depends on the area taken up by the earthing grid, the total length
of buried earthing conductors and the number of earthing rods / electrodes.

IEEE Std 80 offers two alternative options for calculating the earthing grid resistance
(with respect to remote earth) - 1) the simplified method (Section 14.2) and 2) the
Schwarz equations (Section 14.3), both of which are outlined briefly below. IEEE Std 80
also includes methods for reducing soil resistivity (in Section 14.5) and a treatment for
concrete-encased earthing electrodes (in Section 14.6).

Simplified Method

IEEE Std 80 Equation 52 gives the simplified method as modified by Sverak to include the
effect of earthing grid depth:

Where is the earthing grid resistance with respect to remote earth ()

is the soil resistivitiy (.m)

is the total length of buried conductors (m)

is the total area occupied by the earthing grid (m2)

is the depth of the earthing grid (m)

Schwarz Equations

The Schwarz equations are a series of equations that are more accurate in modelling the
effect of earthing rods / electrodes. The equations are found in IEEE Std 80 Equations 53,
54, 55(footnote) and 56, as follows:

Where is the earthing grid resistance with respect to remote earth ()

is the earth resistance of the grid conductors ()


is the earth resistance of the earthing electrodes ()

is the mutual earth resistance between the grid conductors and earthing electrodes
()

And the grid, earthing electrode and mutual earth resistances are:

Where is the soil resistivity (.m)

is the total length of buried grid conductors (m)

is for conductors buried at depth metres and with cross-sectional


radius metres, or simply for grid conductors on the surface

is the total area covered by the grid conductors (m2)

is the length of each earthing electrode (m)

is number of earthing electrodes in area

is the cross-sectional radius of an earthing electrode (m)

and are constant coefficients depending on the geometry of the grid

The coefficient can be approximated by the following:

(1) For depth :

(2) For depth :

(3) For depth :

The coefficient can be approximated by the following:

(1) For depth :

(2) For depth :


(3) For depth :

Where in both

cases, is
the length-to-
width ratio of th
earthing grid.

Step 4:
Maximum Gri
Current

The maximum
grid current is t
worst case eart
fault current tha
would flow via
the earthing gri
back to remote
earth. To
calculate the
maximum grid
current, you
firstly need to
calculate the
worst case
symmetrical
earth fault
current at the
facility that wou
have a return
path through
remote earth (c

this ). This
can be found
from the power
systems studies
or from manual
calculation.
Generally
speaking, the
highest relevan
earth fault level
will be on the
primary side of
the largest
distribution
transformer (i.e
either the
terminals or the
delta windings).

Current Division
Factor

Not all of the


earth fault
current will flow
back through
remote earth. A
portion of the
earth fault
current may ha
local return pat
(e.g. local
generation) or
there could be
alternative retu
paths other tha
remote earth
(e.g. overhead
earth return
cables, buried
pipes and cable
etc). Therefore
current division

factor must
be applied to
account for the
proportion of th
fault current
flowing back
through remote
earth.

Computing the
current division
factor is a task
that is specific t
each project an
the fault locatio
and it may
incorporate som
subjectivity (i.e
"engineeing
judgement"). In
any case, IEEE
Std 80 Section
15.9 has a good
discussion on
calculating the
current division
factor. In the
most
conservative
case, a current
division factor

of can
be applied,
meaning that
100% of earth
fault current
flows back
through remote
earth.

The symmetrica

grid current
calculated by:

Decrement Fact

The symmetrica
current is not th
maximum grid c
because of asym
in short circuits
namely a dc cur
offset. This is ca
by the decreme
factor, which ca
calculated from
Std 80 Equation

Where is t
decrement facto

is the duration of the fault (s)

is the dc time offset constant (see below)


The dc time offs
derived from IE
Equation 74:

Where is th
fault location

is the system frequency (Hz)

The maximum g
calculated by:

Step 5: Touch

One of the goal


protect people a
the event of an
ac electric curre
human body ca
range of 60 to 1
fibrillation and h
duration of an e
the risk of mort
faults are cleare
need to prescrib
touch and step
lethal shocks.

The maximum t
touch scenarios
from IEEE Std S
50kg and 70kg:
Touch voltage li
difference betw
the potential of
during a fault (d

50kg person:

70kg person:

Step voltage lim


surface potentia
distance of 1m
earthed object:

50kg person:

70kg person:

Where

is the step voltage limit (V)

is the surface layer derating factor (as calculated in Step 2)

is the soil resistivity (.m)

is the maximum fault clearing time (s)

The choice of bo
expected weigh
women are exp
to choose 50kg.
Step 6: Groun

Normally, the p
around the site
they are at the
(where the faul
flow of current
gradients in and
difference betw
ground potentia
a maximum po
potentials aroun
fault.

The maximum G

Where

is the maximum grid current found earlier in Step 4 (A)

is the earthing grid resistance found earlier in Step 3 ()


Step 7: Earth

Now we just ne
and step potent
exceed either o
the grid design

However if it do
further analysis
of the maximum
16.5.

Mesh Voltage C

The mesh volta


earthing grid an
Where :: is

is the maximum grid current found earlier in Step 4 (A)

is the geometric spacing factor (see below)

is the irregularity factor (see below)

is the effective buried length of the grid (see below)


Geometric Sp

The geometric s

Where is th

is the depth of buried grid conductors (m)

is the cross-sectional diameter of a grid conductor (m)

is a weighting factor for depth of burial =

is a weighting factor for earth electrodes /rods on the corner mesh

for grids with earth electrodes along the grid perimeter or corners

for grids with no earth electrodes on the corners or on the perimeter

is a geometric factor (see below)


Geometric Fac

The geometric f

With
for square grids, or otherwise

for square and rectangular grids, or otherwise

for square, rectangular and L-shaped grids, or otherwise

Where is th

is the length of grid conductors on the perimeter (m)

is the total area of the grid (m2)

and are the maximum length of the grids in the x and y directions (m)

is the maximum distance between any two points on the grid (m)
Irregularity Fa

The irregularity

Where is the

Effective Buri

The effective bu

For grids wi

Where is th

is the total length of earthing electrodes / rods (m)

For grids wi
Where is th

is the total length of earthing electrodes / rods (m)

is the length of each earthing electrode / rod (m)

and are the maximum length of the grids in the x and y directions (m)
Step Voltage Ca

The maximum a

Where :: is

is the maximum grid current found earlier in Step 4 (A)

is the geometric spacing factor (see below)

is the irregularity factor (as derived above in the mesh voltage calculation)

is the effective buried length of the grid (see below)


Geometric Sp

The geometric s

Where is th

is the depth of buried grid conductors (m)


is a geometric factor (as derived above in the mesh voltage calculation)
Effective Buri

The effective bu

Where is th

is the total length of earthing electrodes / rods (m)


What Now?

Now that the m

, and

then the earthin

If not, however,

Redesign the earthing grid to lower the grid resistance (e.g. more grid conductors,

more earthing electrodes, increasing cross-sectional area of conductors, etc). Once


this is done, re-compute the earthing grid resistance (see Step 3) and re-do the touch
and step potential calculations.

Limit the total earth fault current or create alternative earth fault return paths

Consider soil treatments to lower the resistivity of the soil

Greater use of high resistivity surface layer materials

Worked Ex

In this example
line and a delta

Step 1: Soil

The soil resistiv

Step 2: Surf

A thin 100mm l
Step 3: Eart

Figure 1. Propose

A rectangular e

Length of 90m and a width of 50m

6 parallel rows and 7 parallel columns

Grid conductors will be 120 mm2 and buried at a depth of 600mm

22 earthing rods will be installed on the corners and perimeter of the grid

Each earthing rod will be 3m long

Using the simpl


Step 4: Max

Suppose that th

The X/R ratio at

The decrement

Fianlly, the max

kA

Step 5: Touc

Based on the av

The maximum a
V

The maximum a

Step 6: Gro

The maximum g

The GPR far exc

Step 7: Eart

Mesh Voltage

The component
and is the number of parallel rows and columns respectively (e.g. 6 and 7)
m

m
V.

ntroduction
Number of Earthing Electrode and Earthing Resistance depends on the resistivity of
soil and time for fault current to pass through (1 sec or 3 sec). If we divide the area for
earthing required by the area of one earth plate gives the number of earth pits
required.

There is no general rule to calculate the exact number of earth pits and size of
earthing strip, but discharging of leakage current is certainly dependent on the
cross section area of the material so for any equipment the earth strip size is
calculated on the current to be carried by that strip.

First the leakage current to be carried is calculated and then size of the strip is
determined.

For most of the electrical equipment like transformer, diesel generator set etc., the
general concept is to have 4 number of earth pits. 2 nos for body earthing with 2
separate strips with the pits shorted and 2 nos for Neutral with 2 separate strips with
the pits shorted.

The Size of Neutral Earthing Strip should be capable to carry neutral current of that equipment.
The Size of Body Earthing should be capable to carry half of neutral Current.

For example for 100kVA transformer, the full load current is around 140A.

The strip connected should be capable to carry at least 70A (neutral current) which
means a strip of GI 25x3mm should be enough to carry the current and for body a
strip of 253 will do the needful. Normally we consider the strip size that is generally
used as standards.

However a strip with lesser size which can carry a current of 35A can be used for body
earthing. The reason for using 2 earth pits for each body and neutral and then shorting
them is to serve as back up. If one strip gets corroded and cuts the continuity is
broken and the other leakage current flows through the other run thery by completing
the circuit.

Similarly for panels the no of pits should be 2 nos. The size can be decided on the
main incomer circuit breaker.
For example if main incomer to breaker is 400A, then body earthing for panel can have a strip
size of 256 mm which can easily carry 100A.

Number of earth pits is decided by considering the total fault current to be dissipated
to the ground in case of fault and the current that can be dissipated by each earth pit.
Normally the density of current for GI strip can be roughly 200 amps per square cam.
Based on the length and dia of the pipe used the number of earthing pits can be
finalized.

1. Calculate numbers of pipe earthing


A. Earthing resistance and number of rods for
isolated earth pit
(without buried earthing strip)

The earth resistance of single rod or pipe electrode is calculated as per BS 7430:

R=/23.14xL (loge (8xL/d)-1)


Where:

= Resistivity of soil ( meter),


L = Length of electrode (meter),
D = Diameter of electrode (meter)

Example:
Calculate isolated earthing rod resistance. The earthing rod is 4 meter long and having
12.2mm diameter, soil resistivity 500 meter.

R=500/ (23.144) x (Loge (84/0.0125)-1) =156.19 .

The earth resistance of single rod or pipe electrode is calculated as per IS 3040:

R=100x/23.14xL (loge(4xL/d))
Where:

= Resistivity of soil ( meter),


L = Length of electrode (cm),
D = Diameter of electrode (cm)

Example:
Calculate number of CI earthing pipe of 100mm diameter, 3 meter length. System has
fault current 50KA for 1 sec and soil resistivity is 72.44 -Meters.

Current Density At The Surface of Earth Electrode (As per IS 3043):

Max. allowable current density I = 7.571000/(xt) A/m2


Max. allowable current density = 7.571000/(72.44X1) = 889.419 A/m2
Surface area of one 100mm dia. 3 meter Pipe = 2 x 3.14 x r x L = 2 x 3.14 x 0.05 x3 =
0.942 m2
Max. current dissipated by one Earthing Pipe = Current Density x Surface area of
electrode
Max. current dissipated by one earthing pipe = 889.419x 0.942 = 837.83 A say 838
Amps
Number of earthing pipe required = Fault Current / Max.current dissipated by one
earthing pipe.
Number of earthing pipe required = 50000/838 = 59.66 Say 60 Nos.
Total number of earthing pipe required = 60 Nos.
Resistance of earthing pipe (isolated) R = 100x/23.14xLx(loge (4XL/d))
Resistance of earthing pipe (isolated) R = 10072.44 /23.14x300x(loge (4X300/10)) =
7.99 /Pipe
Overall resistance of 60 no of earthing pipe = 7.99/60 = 0.133 .
Top

B. Earthing resistance and number of rods for


isolated earth pit
(with buried earthing strip)

Resistance of earth strip (R) As per IS 3043:

R=/23.14xLx (loge (2xLxL/wt))


Example:
Calculate GI strip having width of 12mm , length of 2200 meter buried in ground at
depth of 200mm, soil resistivity is 72.44 -meter.

Resistance of earth strip(Re) = 72.44/23.14x2200x(loge (2x2200x2200/.2x.012))


= 0.050
From above calculation overall resistance of 60 no of earthing pipes (Rp) = 0.133 .
And it connected to bury earthing strip. Here net earthing resistance = (RpxRe)/(Rp+Re)
Net eatrthing resistance = (0.1330.05)/(0.133+0.05) = 0.036 .

C. Total earthing resistance and number of electrode


for group
(parallel)

In cases where a single electrode is not sufficient to provide the desired earth
resistance, more than one electrode shall be used. The separation of the electrodes
shall be about 4 m. The combined resistance of parallel electrodes is a complex
function of several factors, such as the number and configuration of electrode the
array.

The total resistance of group of electrodes in different configurations as per BS 7430:

Ra=R (1+a/n) where a=/2X3.14xRxS


Where:

S = Distance between adjustment rod (meter),


= Factor given in table below,
n = Number of electrodes,
= Resistivity of soil ( meter),
R = Resistance of single rod in isolation ()

Factors for parallel electrodes in line (BS 7430)

Number of electrodes (n) Factor ()

2 1.0
3 1.66

4 2.15

5 2.54

6 2.87

7 3.15

3.39
8

9 3.61

10 3.8

For electrodes equally spaced around a hollow square, e.g. around the perimeter of a
building, the equations given above are used with a value of taken from following
table.

For three rods placed in an equilateral triangle, or in an L formation, a value of =


1.66 may be assumed.

Factors for electrodes in a hollow square (BS


7430)

Number of electrodes (n) Factor ()

2 2.71

3 4.51

4 5.48

5 6.13

6 6.63

7 7.03
8 7.36

9 7.65

10 7.9

12 8.3

14 8.6

16 8.9

18 9.2

20 9.4

For Hollow square total number of electrodes (N) = (4n-1).

The rule of thumb is that rods in parallel should be spaced at least twice their length to
utilize the full benefit of the additional rods. If the separation of the electrodes is much
larger than their lengths and only a few electrodes are in parallel, then the resultant
earth resistance can be calculated using the ordinary equation for resistances in
parallel.

In practice, the effective earth resistance will usually be higher than calculation.

Typically, a 4 spike array may provide an improvement 2.5 to 3 times. An 8 spike


array will typically give an improvement of maybe 5 to 6 times.

The Resistance of Original Earthing Rod will be lowered by Total of 40% for Second
Rod, 60% for third Rod,66% for forth rod.

Example:
Calculate Total Earthing Rod Resistance of 200 Number arranges in Parallel having 4
Meter Space of each and if it connects in Hollow Square arrangement. The Earthing
Rod is 4 Meter Long and having 12.2mm Diameter, Soil Resistivity 500 .

First Calculate Single Earthing Rod Resistance:


R = 500/ (23.144) x (Loge (84/0.0125)-1) =136.23 .
Now calculate total resistance of earthing rod of 200 number in parallel
condition:

a = 500/(23.14x136x4) =0.146
Ra (Parallel in Line) =136.23x (1+100.146/200) = 1.67 .

If earthing rod is connected in Hollow square than rod in each side of square is 200 =
(4n-1) so n = 49 No.

Ra (in hollow square) =136.23x (1+9.40.146/200) = 1.61 .

(1) Demand factor (in IEC, Max.Utilization factor (Ku)):

The word demand itself says the meaning of Demand Factor. The ratio of the maximum coincident demand
of a system, or part of a system, to the total connected load of the system.

Demand Factor = Maximum demand / Total connected load

For example, an over sized motor 20 Kw drives a constant 15 Kw load whenever it is ON. The motor
demand factor is then 15/20 =0.75= 75 %.
Demand Factor is express as a percentage (%) or in a ratio (less than 1).

Demand factor is always < =1.

Demand Factor is always change with the time to time or hours to hours of use and it will not constant.
The connected load is always known so it will be easy to calculate the maximum demand if the demand
factor for a certain supply is known at different time intervals and seasons.
The lower the demand factor, the less system capacity required to serve the connected load.

Calculation:

(1) A Residence Consumer has 10 Nos Lamp of 400 W but at the same time It is possible that only 9 Nos of
Bulbs are used at the same time. Here Total Connected load is 1040=400 W. Consumer maximum demand is
940=360 W. Demand Facto of this Load = 360/400 =0.9 or 90%.
(2) One Consumer have 10 lights at 60 Kw each in Kitchen, the load is 60 Kw x 10 = 600 KW. This will be
true only if All lights are Turns ON the same time (Demand factor=100% or 1)
For this Consumer it is observed that only half of the lights being turned ON at a time so we can say that the
demand factor is 0.5 (50%). The estimated load = 600 Kw X 0.5 = 300 Kw.

Use of demand factors:

Feeder conductors should have sufficient Ampere Capacity to carry the load. The Ampere Capacity does not
always be equal to the total of all loads on connected branch-circuits.
This factor must be applied to each individual load, with particular attention to electric motors, which are very
rarely operated at full load.
As per National Electrical Code (NEC) demand factor may be applied to the total load. The demand factor
permits a feeder ampearcity to be less than 100 percent of all the branch-circuit loads connected to it.
Demand factor can be applied to calculate the size of the sub-main which is feeding a Sub panel or a fixed
load like a motor etc. If the panel have total load of 250 kVA , considering a Demand factor of 0.8, we can size the
feeder cable for 250 x 0.8= 200 kVA.
Demand factors for buildings typically range between 50 and 80 % of the connected load.
In an industrial installation this factor may be estimated on an average at 0.75 for motors.
For incandescent-lighting loads, the factor always equals 1.

Demand Factor For Industrial Load

Text Book of Design of Elect. Installation- Jain

Electrical Load Demand Factor

1 No of Motor 1

Up to 10 Nos of Motor 0.75

Up to 20 Nos of Motor 0.65

Up to 30 Nos of Motor 0.6

Up to 40 Nos of Motor 0.5

Up to 50 Nos of Motor 0.4

Demand Factor

Text Book of Design of Elect. Installation- Jain


Utility Demand Factor

Office ,School 0.4

Hospital 0.5

Air Port, Bank, Shops, 0.6

Restaurant, Factory, 0.7

Work Shop, Factory (24Hr Shift) 0.8

Arc Furnace 0.9

Compressor 0.5

Hand tools 0.4

Inductance Furnace 0.8

Demand Factor

Saudi Electricity Company Distribution Standard

Utility Demand Factor


Residential 0.6

Commercial 0.7

Flats 0.7

Hotel 0.75

Mall 0.7

Restaurant 0.7

Office 0.7

School 0.8

Common Area in building 0.8

Public Facility 0.75

Street Light 0.9

Indoor Parking 0.8

Outdoor Parking 0.9

Park / Garden 0.8


Hospital 0.8

Workshops 0.6

Ware House 0.7

Farms 0.9

Fuel Station 0.7

Factories 0.9

Demand Factor

Text Book of Principal of Power System-V.K.Mehta

Utility Demand Factor

Residence Load (<0.25 KW) 1

Residence Load (<0.5 KW) 0.6

Residence Load (>0.1 KW) 0.5

Restaurant 0.7
Theatre 0.6

Hotel 0.5

School 0.55

Small Industry 0.6

Store 0.7

Motor Load (up to 10HP) 0.75

Motor Load (10HP to 20HP) 0.65

Motor Load (20HP to 100HP) 0.55

Motor Load (Above 100HP) 0.50

(2) Diversity factor:

Diversity Factor is ratio of the sum of the individual maximum demands of the various sub circuit of a system
to the maximum demand of the whole system.

Diversity Factor = Sum of Individual Maximum Demands / Maximum Demand of the


System.

Diversity Factor = Installed load / Running load.

The diversity factor is always >= 1.

Diversity Factor is always >1 because sum of individual max. Demands >Max. Demand.
In other terms, Diversity Factor (0 to 100%) is a fraction of Total Load that is particular item contributed to
peak demand. 70% diversity means that the device operates at its nominal or maximum load level 70% of the
time that it is connected and turned ON.
It is expressed as a percentage (%) or a ratio more than 1.
If we use diversity value in % than it should be multiply with Load and if we use in numerical value
(>1) than it should be divided with Load.
Diversity occurs in an operating system because all loads connected to the System are not operating
simultaneously or are not simultaneously operating at their maximum rating. The diversity factor shows that the
whole electrical load does not equal the sum of its parts due to this time Interdependence (i.e. diverseness).
In general terms we can say that diversity factor refers to the percent of time available that a machine. 70%
diversity means that the device operates at its nominal or maximum load level 70% of the time that it is connected
and turned ON.
Consider two Feeders with the same maximum demand but that occur at different intervals of time. When
supplied by the same feeder, the demand on such is less the sum of the two demands. In electrical design, this
condition is known as diversity.
Diversity factor is an extended version of demand factor. It deals with maximum demand of different units at
a time/Maximum demand of the entire system.
Greater the diversity factor, lesser is the cost of generation of power.
Many designers prefer to use unity as the diversity factor in calculations for planning conservatism because
of plant load growth uncertainties. Local experience can justify using a diversity factor larger than unity, and
smaller service entrance conductors and transformer requirements chosen accordingly.
The diversity factor for all other installations will be different, and would be based upon a local evaluation of
the loads to be applied at different moments in time. Assuming it to be 1.0 may, on some occasions, result in a
supply feeder and equipment rating that is rather larger than the local installation warrants, and an over-
investment in cable and equipment to handle the rated load current. It is better to evaluate the pattern of usage of
the loads and calculate an acceptable diversity factor for each particular case.

Calculation:

One Main Feeder have two Sub feeder (Sub Feeder A and Sub Feeder B), Sub Feeder-A have demand at a
time is 35 KW and Sub Feeder-B have demands at a time is 42 KW, but the maximum demand of Main Feeder is
70 KW.
Total individual Maximum Demand =35+42=77 KW.
Maximum Demand of whole System=70 KW
So Diversity factor of The System= 77/70 =1.1
Diversity factor can shoot up above 1.

Use of diversity factor:

The Diversity Factor is applied to each group of loads (e.g. being supplied from a distribution or sub-
distribution board).
Diversity factor is commonly used for a complete a coordination study for a system. This diversity factor is
used to estimate the load of a particular node in the system.
Diversity factor can be used to estimate the total load required for a facility or to size the Transformer
Diversity factors have been developed for main feeders supplying a number of feeders, and typically 1.2 to
1.3 for Residence Consumer and 1.1 to 1.2 for Commercial Load. 1.50 to 2.00 for power and lighting loads.
Note: Reciprocal of the above ratio (will be more than 1) also is used in some other countries.
Diversity factor is mostly used for distribution feeder size and transformer as well as to determine the
maximum peak load and diversity factor is always based on knowing the process. You have to understand what
will be on or off at a given time for different buildings and this will size the feeder. Note for typical buildings
diversity factor is always one. You have to estimate or have a data records to create 24 hours load graph and you
can determine the maximum demand load for node then you can easily determine the feeder and transformer
size.
The diversity factor of a feeder would be the sum of the maximum demands of the individual consumers
divided by the maximum demand of the feeder. In the same manner, it is possible to compute the diversity factor
on a substation, a transmission line or a whole utility system.
The residential load has the highest diversity factor. Industrial loads have low diversity factors usually of 1.4,
street light practically unity and other loads vary between these limits.
Diversity Factor in distribution Network

(Standard Handbook for Electrical Engineers by Fink and Beaty)

General
Elements of System Residential Commercial Large Industrial
Power

Between individual users 2.00 1.46 1.45

Between transformers 1.30 1.30 1.35 1.05

Between feeders 1.15 1.15 1.15 1.05

Between substations 1.10 1.10 1.10 1.10

From users to
transformers 2.00 1.46 1.44

From users to feeder 2.60 1.90 1.95 1.15

From users to substation 3.00 2.18 2.24 1.32

From users to generating


station 3.29 2.40 2.46 1.45

Diversity Factor for Distribution Switchboards


Number of circuits Diversity Factor in % (ks)

Assemblies entirely tested 2 and 3 90%

4 and 5 80%

6 to 9 70%

10 and more 60%

Assemblies partially tested in every case choose 100%

Diversity Factor as per IEC 60439

Circuits Function Diversity Factor in % (ks)

Lighting 90%

Heating and air conditioning 80%

Socket-outlets 70%

Lifts and catering hoist

For the most powerful motor 100%

For the second most powerful motor 75%


For all motors 80%

Diversity Factor for Apartment block

Apartment Diversity Factor in % (ks)

2 To 4 1

5To 19 0.78

10To 14 0.63

15To 19 0.53

20To 24 0.49

25To 29 0.46

30 To 34 0.44

35 To 39 0.42

40To 40 0.41
50 To Above 0.40

Diversity Factor

Text Book of Principal of Power System-V.K.Mehta

Area Residence Ltg Commercial Ltg Ind. Ltg

Between Consumer 3 1.5 1.5

Between Transformer 1.3 1.3 1.3

Between Feeder 1.2 1.2 1.2

Between S.S 1.1 1.1 1.1

(3) Load factor:

The ratio of the Actual Load of equipment to Full load of equipment.

Load Factor=Actual Load / Full Load

It is the ratio of actual kilowatt-Hours used in a given period, divided by the total possible kilowatt -hours that
could have been used in the same period at the peak KW level.
Load Factor = ( energy (kWh per month) ) / ( peak demand (kW) x hours/month )
In other terms Load factor is defined as the ratio of Average load to maximum demand during a given period.
Load Factor= Average Load / Maximum Demand during given Time Period

The Load factor is always <=1.

Load Factor is always less than 1 because maximum demand is always more than average demand.
Load Factor can be calculated for a single day, for a month or for a year.
Load factor in other terms of efficiency.
It is used for determining the overall cost per unit generated.
Higher the load factor is GOOD and it will more Output of Plan, lesser the cost per unit which means an
electricity generator can sell more electricity at a higher spark spread, Fixed costs are spread over more kWh of
output. A power plant may be highly efficient at High load factors.
Low load factor is a BED. A low load factor will use electricity inefficiently relative to what we could be if we
were controlling our peak demand. A power plant may be less efficient at low load factors.
For almost constant loads, the load factor is close to unity.
For Varying Load Factor is closed Zero.
Load Factor is a measure of the effective utilization of the load and distribution equipment, i.e. higher load
factor means better utilization of the transformer, line or cable.
A high load factor means power usage is relatively constant. Low load factor shows that occasionally a high
demand is set. To service that peak, capacity is sitting idle for long periods, thereby imposing higher costs on the
system. Electrical rates are designed so that customers with high load factor are charged less overall per kWh.
Sometimes utility companies will encourage industrial customers to improve their load factors.
Load factor is term that does not appear on your utility bill, but does affect electricity costs. Load
factor indicates how efficiently the customer is using peak demand.
Calculation:
Motor of 20 hp drives a constant 15 hp load whenever it is on.
The motor load factor is then 15/20 = 75%.

Demand Factor & Load Factor

Introduction to Power Requirement for Building J. Paul Guyer,

Utility Demand Factor (%) Load Factor (%)

Communications buildings 60-65 70-75

Telephone exchange building 55-70 20-25

Air passenger terminal building 65-80 28-32

Aircraft fire and rescue station 25-35 13-17

Aircraft line operations building 65-80 24-28

Academic instruction building 40-60 22-26


Applied instruction building 35-65 24-28

Chemistry and Toxicology Laboratory 70-80 22-28

Materials Laboratory 30-35 27-32

Physics Laboratory 70-80 22-28

Electrical and electronics laboratory 20-30 3-7

Cold storage warehouse 70-75 20-25

General warehouse 75-80 23-28

Controlled humidity warehouse 60-65 33-38

Hazardous/flammable storehouse 75-80 20-25

Disposal, salvage, scrap building 35-40 25-20

Hospital 38-42 45-50

Laboratory 32-37 20-25

K-6 schools 75-80 10-15


7-12 schools 65-70 12-17

Churches 65-70 5-25

Post Office 75-80 20-25

Retail store 65-70 25-32

Bank 75-80 20-25

Supermarket 55-60 25-30

Restaurant 45-75 15-25

Auto repair shop 40-60 15-20

Hobby shop, art/crafts 30-40 25-30

Bowling alley 70-75 10-15

Gymnasium 70-75 20-45

Skating rink 70-75 10-15

Indoor swimming pool 55-60 25-50

Theatres 45-55 8-13


Library 75-80 30-35

Golf clubhouse 75-80 15-20

Museum 75-80 30-35

(4) Coincidence factor (in IEC, Factor of simultaneity (ks)):

The reciprocal of diversity factor is coincidence factor


The coincidence factor is the ratio of the maximum demand of a system, or part under consideration, to the
sum of the individual maximum demands of the subdivisions

Coincidence factor = Maximum demand / Sum of individual maximum demands

Expressed as a percentage (%) or a ratio less than 1.

The Confidence Factor is always <=1.

Usually Confidence Factor will decrease as the number of connected customers increases.
The factor ks is applied to each group of loads (e.g. distribution or sub-distribution board).
The determination of these factors is the responsibility of the designer, since it requires a detailed knowledge
of the installation and the conditions in which the individual circuits are to be exploited. For this reason, it is not
possible to give precise values for general application.

(5) Maximum demand:

The maximum demand of an installation is the maximum rate of consumption expressed in amperes, kW or
kVA. It is generally taken as the average rate of consumption over a period of time. Example the 15-minute
maximum kW demand for the week was 150 kW. Maximum demand does not include motor starting currents or
other transient effects. Fault currents and overload currents are also excluded. Maximum demand in KW is
relevant only for metering/tariff purposes.
Maximum demand (often referred to as MD) is the largest current normally carried by circuits, switches and
protective devices. It does not include the levels of current flowing under overload or short circuit conditions.
Maximum Demand is a greatest of all demands that occur during a specific time
The major disadvantage of allocating load using the diversity factors is that most utilities will not have a table
of diversity factors and sometime it is not viable to determine accurate Diversity Factor. In this situation Maximum
Demand is very helpful to calculate size of Feeder or TC.
The kVA rating of all distribution transformers is always known for a feeder. The metered readings can be
taken to each transformer based upon the transformer rating. An allocation factor (AF) can be calculate.
Allocation Factor= Metered Demand (KVA) / Total KVA.
Equipment Demand= AF x Total KVA of Equipments
Calculation:
Actual Loading or Size of TC-1 and TC-2.
Total Load on TC-1 =10+11+12+08= 41 KW.
Maximum Diversity Demand of TC-1= 41 / 1.1 = 37.3 KW.
Total Load on TC-2 =4+3+12+02= 21 KW.
Maximum Diversity Demand of TC-2= 21 / 1.2 = 17.5 KW.
Total Load= 37.3 + 17.5 =54.8 KW.
Allocating Factor (AF)= M.D / Total Load
Allocating Factor (AF)= 0.27.
Actual Load on TC-1=0.2737.3 = 1.20 KW.
Actual Load on TC-2=0.2717.5 = 4.8 KW.
Assessment of maximum demand is very easy for Resistive Load , For example, the maximum demand of a
240 V single-phase 8 kW shower heater can be calculated by dividing the power (8 kW) by the voltage (240 V) to
give a current of 33.3 A. This calculation assumes a power factor of unity, which is a reasonable assumption for
such a purely resistive load.
Lighting circuits pose a special problem when determining MD. Discharge lamps are particularly difficult to
assess, and current cannot be calculated simply by dividing lamp power by supply voltage. The reasons for this
are Control gear losses result in additional current, the power factor is usually less than unity so current is greater,
and Chokes and other control gear usually distort the waveform of the current so that it contains harmonics which
are additional to the fundamental supply current.
So long as the power factor of a discharge lighting circuit is not less than 0.85, the current demand for the
circuit can be calculated from:
current (A) = (lamp power x 1.8) / supply voltage (V)

For example, the steady state current demand of a 240 V circuit supplying ten 65 W fluorescent lamps would
be: I = 10X65X1.8A / 240 = 4.88A
Switches for circuits feeding discharge lamps must be rated at twice the current they are required to carry,
unless they have been specially constructed to withstand the severe arcing resulting from the switching of such
inductive and capacitive loads.

Where to use Demand and Diversity factor:

There is generally confusion between Demand factor and Diversity factor. Demand factors should be
ideally applied to individual loads and diversity factor to a group of loads.
When you talk about diversity, there are naturally more than one or many loads involved.
Demand factor can be applied to calculate the size of the sub-main, which is feeding a Sub panel or a fixed
load like a motor etc, individual Load.
Demand factors are more conservative and are used by NEC for service and feeder sizing.
If the Sub panel have total load is 250 kVA , considering a Demand factor of 0.8, we can size the feeder
cable for 250 x 0.8= 200 kVA.
The Diversity Factor is applied to each group of loads (e.g. being supplied from a distribution or sub-
distribution board), size the Transformer.
Demand factors and diversity factors are used in design. For example, the sum of the connected loads
supplied by a feeder is multiplied by the demand factor to determine the load for which the feeder must be sized.
This load is termed the maximum demand of the feeder. The sum of the maximum demand loads for a number of
sub feeders divided by the diversity factor for the sub feeders will give the maximum demand load to be supplied
by the feeder from which the sub feeders are derived.

Calculate Size of Electrical Switchgear by Demand & Diversity


Factor:

The estimated electrical demand for all feeders served directly from the service entrance is calculated by
multiplying the total connected loads by their demand factors and then adding all of these together. This sum is
divided by the diversity factor (frequently assumed to be unity) to calculate the service entrance
demand which is used to determine ampacity requirements for the service entrance conductors.
When used Diversity and Demand Factor in an electrical design it should be applied as follows, the sum of
the connected loads supplied by a feeder-circuit can be multiplied by the demand factor to determine the load
used to size the components of the system.
The sum of the maximum demand loads for two or more feeders is divided by the diversity factor for the
feeders to derive the maximum demand load.
Example-1: Calculate Size of Transformer having following details:

Feeder Breaker-1 Demand Load= Feeder Breaker-1xDemand Factor.


Feeder Breaker-1 Demand Load=20000.7=1400 KVA
Feeder Breaker-2 Demand Load= Feeder Breaker-2xDemand Factor.
Feeder Breaker-2 Demand Load=15000.6=900 KVA
Feeder Breaker-3 Demand Load= Feeder Breaker-3xDemand Factor.
Feeder Breaker-2 Demand Load=10000.5=500 KVA
Total Feeder Breaker Demand=1400+900+500=2800KVA
Transformer Demand Load= Total Feeder Breaker Demand / Diversity Factor.
Transformer Demand Load=2800/1.1 =2545 KVA
If we Calculated Total Load on Transformer without any Demand & Diversity=2000+1500+1000=4500KVA.
But after Calculating Demand & Diversity Factor Total Load on Transformer =2545 KVA
Example-2: Calculate Size of Main Feeder of Main Transformer having following Details:
Sum of Maximum Demand of Customer on TC-1 =10 KWx0.65 =6.5 KW
Sum of Maximum Demand of Customer on TC-2 =20 KWx0.75 =15 KW
Sum of Maximum Demand of Customer on TC-3 =30 KWx0.65 =19.5 KW
As Diversity of Consumer Connected on TC-1 is 1.5 so,
Maximum Demand on TC-1 =6.5 KW/1.5 = 4 KW.
As Diversity of Consumer Connected on TC-2 is 1.1 so,
Maximum Demand on TC-2 =15 KW/1.1 = 14 KW
As Diversity of Consumer Connected on TC-3 is 1.5 so,
Maximum Demand on TC-3 =19.5 KW/1.5 = 13 KW.
Individual Maximum Demand on Main Transformer =04+14+13= 31 KW.
Maximum Demand on Main Feeder =04+14+13 / 1.3 =24 KW

Significance of Load Factor and Diversity Factor

Load factor and diversity factor play an important part in the cost of the supply of electrical energy. Higher
the values of load factor and diversity factors, lower will be the overall cost per unit generated.
The capital cost of the power station depends upon the capacity of the power station. Lower the maximum
demand of the power station, the lower is the capacity required and therefore lower is the capital cost of the
plant. With a given number of consumers the higher the diversity factor of their loads, the smaller will be the
capacity of the plant required and consequently the fixed charges due to capital investment will be much reduced.
Similarly higher load factor means more average load or more number of units generated for a given
maximum demand and therefore overall cost per unit of electrical energy generated is reduced due to distribution
of standing charges which are proportional to maximum demand and independent of number of units generated.
Thus the suppliers should always try to improve the load factor as well as diversity factor by inducing the
consumers to use the electrical energy during off peak hours and they may be charged at lower rates for such
schemes.

Main-Tie-Main.
Load Configuration.
Both Bus#1 & Bus#2 are supplying normal loads that mean interruption for PT1 or PT2 is accepted for fault located
between M2-PT2 and main supply.
No critical load (instantaneous interruption is not allowed) connected on Bus #1 and Bus #2. It shall be supplied
from UPS.
Load on Bus #1 has a standby load on Bus#2 or vice versa, so if the bus #2 fail, load on bus #1 is operated.
Basic Operation.
This diagram may be useful for our discussion. The basic M1-T-M2 configuration is shown. During normal
operation M1 & M2 breakers are closed and tie breaker T is opened. Supply coming from PT-1 and PT-2.
This drawing indicate when M2 open, T and M1 CBs are closed (abnormal condition). This condition is done for
maintenance purpose for equipment located between M2 to upstream (main source). Load transfer from
bus #2 to bus #1 can be carried out without interruption done by ATS scheme.
If fault located on bus #2 to tie breaker T or bus #1 to tie breaker T, load transfer is prohibited by ATS
scheme. But for fault located from M2 to upstream load transfer is allowed with deenergizing bus #2 loads
first, then tie-breaker T closed by ATS scheme. Loads may be in service after this tranfer, if the loads is set
in auto position.
We cannot maintain the supply on fault bus (e.g. bus #2 or bus #1) before correction is made.
A redundant bus tie or switch isolator acting as maintenance bypass to ATS operation.
Based on discussion above, I do not know, where we have to install those equipment to maintain supply
for fault on respectively bus.
Normally Closed Tie Breaker Operation.
It is possible to operate tie breaker in closed position, but we have to consider a short-circuit level on that
bus. By calculation (Short-circuit study), a fault on bus #1 or bus #2 the magnitude become double. So, we
have to ensure the equipment s.c. rating (buse, breakers, feeder loads, feeder breakers, and etc) meet the
requirements for tie-in in closed position.
Note:
Temporary closing three breakers for maintenance purpose is allowed within 3 cycles to 1 (one) second is
accepted.
Relay application.
1). Bus differential for bus#1 and bus #2 may be applied (we apply on 4.16 kV systems).
2). Directional relay may be applied on incoming breaker M1 & M2 if the NC for tie breaker T is applied.
3). Restrictive earth fault is applied for transformer with low resistance grounding.
4). Please consider to provide better coordination for instantaneous relay between incoming breaker and
load breakers as well as ground fault protection.
5). Syncheck relay is required for synchronising bus # & bus #2 before closing tie breaker T. We provide
permissive closed for ATS schecme. ATS can only be operated if the upstream system is in synchronising
condition (Generating buses are in remote but located closed to each other).
Conclusions.
1). We cannot maintain load on bus faulted before repairing is made.
2). I do not know the location for instaling redudant bus tie breaker or isolator to prevent faulted bus total
failure.
3). Comprehensive study shall be caried out to operate tie breaker in NC. Especially in selecting electrical
equipment and relay coordination.
4). Pay more attention on safety aspect in establishing the ATS scheme.
http://www.sayedsaad.com/substation/index_SF6circuitbreaker.html.

Basic electrical design of a PLC panel (Wiring diagrams).

Building the PLC panel


It is uncommon for engineers to build their own PLC panel designs (but not impossible
of course). For example, once the electrical designs are complete, they must be built
by an electrician. Therefore, it is your responsibility to effectively communicate your
design intentions to the electricians through drawings. In some factories, the
electricians also enter the ladder logic and do debugging .

This article discusses the design issues in implementation that must be considered by
the designer.

Electrical wiring diagrams of a PLC panel


In an industrial setting a PLC is not simply plugged into a wall socket. The electrical
design for each machine must include at least the following components.

1. Transformers to step down AC supply voltages to lower levels


2. Power contacts to manually enable/disable power to the machine with e-stop
buttons
3. Terminals to connect devices
4. Fuses or circuit breakers will cause power to fail if too much current is drawn
5. Grounding to provide a path for current to flow when there is an electrical fault
6. Enclosure to protect the equipment, and users from accidental contact
A control system of a PLC panel will normally use AC and DC power at different voltage
levels. Control cabinets are often supplied with single phase AC at 220/440/550V, or two
phase AC at 220/440V AC, or three phase AC at 330/550V.

This power must be dropped down to a lower voltage level for the controls and DC
power supplies. 110Vac is common in North America, and 220 V AC Is common in
Europe and the Commonwealth countries. It is also common for a control cabinet to
supply a higher voltage to other equipment, such as motors.
Motor controller example
An example of a wiring diagram for a motor controller is shown in Figure 1. Note
that symbols are discussed in detail later).

Dashed lines indicate a single purchased component. This system uses 3 phase AC
power (L1, L2 and L3) connected to the terminals. The three phases are then
connected to a power interrupter. Next, all three phases are supplied to a motor starter
that contains three contacts, M, and three thermal overload relays (breakers).
Figure 1 A Motor Controller Schematic

The contacts, M, will be controlled by the coil, M. The output of the motor starter goes
to a three phase AC motor. Power is supplied by connecting a step down
transformer to the control electronics by connecting to phases L2 and L3. The lower
voltage is then used to supply power to the left and right rails of the ladder below. The
neutral rail is also grounded.

The logic consists of two push buttons:


Start push button is normally open, so that if something fails the motor cannot be
started.
Stop push button is normally closed, so that if a wire or connection fails the system
halts safely.

The system controls the motor starter coil M, and uses a spare contact on the
starter, M, to seal in the motor starter.

The diagram also shows numbering for the wires in the device. This is essential for
industrial control systems that may contain hundreds or thousands of wires. These
numbering schemes are often particular to each facility, but there are tools to help
make wire labels that will appear in the final controls cabinet.

Figure 2 A
Physical Layout for the Control Cabinet
Once the electrical design is complete, a layout for the controls cabinet is developed, as
shown in Figure 2. The physical dimensions of the devices must be considered, and adequate
space is needed to run wires between components.

In the cabinet the AC power would enter at the terminal block, and be connected to the main
breaker.

It would then be connected to the contactors and overload relays that constitute the
motor starter. Two of the phases are also connected to the transformer to power the
logic. The start and stop buttons are at the left of the box (note: normally these are
mounted elsewhere, and a separate layout drawing would be needed).

The final layout in the cabinet might look like the one shown in Figure 1.
Figure 3 Final PLC Panel Wiring
When being built the system will follow certain standards that may be company policy,
or legal requirements. This often includes items such as;

Hold downs the will secure the wire so they dont move
Labels wire labels help troubleshooting
Strain reliefs these will hold the wire so that it will not be pulled out of screw
terminals
Grounding grounding wires may be needed on each metal piece for safety

A photograph of an industrial controls cabinet is shown in Figure 4:

Figure 4
An industrial control cabinet with wire runs, terminal strip, buttons on PLC panel
front, etc.

When including a PLC in the ladder diagram still remains. But, it does tend to become
more complex. Figure 5 below shows a schematic diagram for a PLC based motor
control system, similar to the previous motor control example.
This figure shows the E-stop wired to cutoff power to all of the devices in the circuit,
including the PLC. All critical safety functions should be hardwired this way.

Figure 5 An Electrical Schematic with a PLC.

Measurement of NPE loop resistance in TN, TT and IT systems.

NPE loop resistance


Up-to-date test instruments, with built in modern electronics, can measure loop
resistance even between the neutral N and protection PE conductors in spite of
possible high currents in the neutral conductor. The current, which is driven by phase
voltages through different linear and non-linear loads, causes voltage drops of
extremely irregular (non sine wave) shape.

The voltage drops interfere with the test voltage and thereby disturb the measurement.
Internal test voltage (approx. 40V, AC, <15 mA) is used, as there is no mains voltage
between neutral and protection conductors.

Important advantage of this measurement against Fault Loop test (LPE) is, that the RCD
does definitly not trip during the measurement, this is due to the low test current.

Used test instrument Eurotest 61557 uses special (patented) measurement principle
to filter the test signal and therefore assures correct measurement results.

What can we deduce from the measurement?


The following conclusions can be reached on the basis of the measurement
result:

1. Type of used protection conductor connection (TN, TT or IT-system)


2. Earth Resistance value for TT-system
3. In case of TT or TN-system, the result is quite similar to the Fault Loop

Resistance value, this is why the test instrument can also calculate the Fault
Loop Prospective Short circuit current.

Generally about the measurement principle


As there is no mains voltage between the N and PE terminals which could be used as
a test voltage the instrument must generate an internal one. This voltage may
be either DC or AC. Used instrument uses AC test voltage, measurement is
done following the U-I method according to the figure below.
Fi
gure 1 NPE loop resistance measurement principle

Result = Ut / It = RN-PE
Where:

Ut Test voltage measured by the V-meter.


It Test current measured by the A-meter.
RN-PE Resistance of N-PE loop.

1. Measurement of NPE loop resistance in TN-


system
The test instrument measures the resistance of the neutral and the
protection conductors from the power transformer to the measurement site (the loop
is marked with a bold line on upper figure).

The test result in this case is quite low (maximum a couple of ohms), showing that
a TN-system is involved.
Figure 2
Resistance measurement between neutral and protection conductor in TN-system

Result 1 = RN + RPE

Result 2 = Ipsc = 230V 1,06 / (RN + RPE)


Where:

RN Resistance of neutral conductor (marked with bold line)


RPE Resistance of protection conductor (marked with bold dotted line)
Ipsc Prospective short circuit current of fault loop

2. Measurement of NPE loop resistance in TT-


system
The test instrument measures the resistance in the following
loop Neutral conductor from power transformer to measurement site (mains outlet),
protection conductor from the mains outlet to earth electrode and then back to the
power transformer via soil and the transformers earthing system (the loop is marked
with a bold line on the figure 3 below).

The test result in this case is quite high (in excess of ten ohms), showing that a TT-
system is involved.
Figure 3
Resistance measurement between the neutral and the protection conductor in a TT-
system

Result 1 = RN + RPE + RE + RO

Result 2 = Ipsc = 230V 1,06 / (RN + RPE + RE + RO)

As it could be presumed, that resistance R E is much higher than the sum of all
other resistances, the following can be noted:

Result 1 RE

Result 2 = Ipsc = 230V 1,06 / RE


Where:

RN Resistance of neutral conductor from power transformer to measurement site


(mains outlet)
RPE Resistance of protection conductor from the mains outlet to earthing electrode
RE Earth resistance of protection earth electrode
RO Earth resistance of transformers earthing system
Ipsc Prospective short circuit fault loop current

3. Measurement of NPE loop resistance in IT-


system
As can be seen from the Figure 4, there is no hard wired connection between the
neutral and protection conductor in an IT-system. The test result is therefore very
high (it can even be out of display range), showing that an IT-system is involved.

Figure 4
Resistance measurement between neutral and protection conductor in IT-system
Attention! A high test result in itself is not sufficient evidence that an IT-system is involved
(it could be just an interrupted protection conductor in a TN or TT-system).

Detailed calculation of currents and power according to the type of load.

Calculation of currents & power


Currents and power analysis are key factors in any design or redesign of an
installation they will enable the source(s) to be sized according to the purpose of the
installation, the intended use of the circuits and the receivers to be supplied.

The current consumed Ia corresponds to the nominal current consumed by a receiver


independently of the utilisation factor and the coincidence factor, but taking into
account the aspects of efficiency ( factor), displacement factor or phase shift (cos )
for motors or other inductive or capacitive loads.

For non-linear (or distorting) loads, the quadratic sum of the fundamental current and the
harmonic currents must be calculated in order to obtain the actual rms current.

Lets break the calculation of the power into few parts, so we can easily follow:

1. Purely resistive load


The current consumed Ia of a purely resistive load is calculated by simply applying
the formulas. For single phase:
and for the three-phase:

But beware, very few loads are totally resistive. Incandescent lighting is losing ground to
solutions that offer higher performance levels, but which are on the other hand less pure
from an electrical viewpoint.

Go back to currents and power calculations

2. Non-distorting load that is not purely resistive


The nominal power (Pn) of a motor corresponds to the mechanical power available on
its shaft. The actual power consumed (Pa) corresponds to the active power carried
by the line.

This is dependent on the efficiency of the motor:

The current consumed (Ia) is given by the following formulae. For single-phase:

and for the three-phase:


Where:

Ia rms current consumed (in A)


Pn nominal power (in W; this is the useful power)
U voltage between phases in three-phase, and between phase and neutral in single-
phase (in V)
efficiency
cos displacement factor.

3. Calculation of the current consumed by several


receivers
The example described below shows that the current and power calculations must
be carried out in accordance with precise mathematical rules in order to clearly
distinguish the different components.

Example of asynchronous motors


A group of circuits consists of two three-phase asynchronous motors M 1 and
M2 connected to the same panel (mains supply: 400V AC 50 hz). The nominal power
of the motors are respectively: Pn1 = 22 kW and Pn2 = 37 kW.

The displacement factors are cos 1 = 0.92 for M1 and cos2 = 0.72 for M2 the efficiencies are
1 = 0.91 and 2 = 0.93 respectively.

Calculation of the power consumed:


The reactive power can in this case be calculated by determining the value of tan
from cos. the relationship with the tangent is given by the formula:

Calculation of the reactive power:

Calculation of the apparent power:

Calculation of the total current consumption for M1, M2, M1 + M2 and the
corresponding power factor:
The active power (in W) and the reactive power (in VAr) can be added together algebraically,
while the apparent power and currents can only be added together geometrically.

Go back to currents and power calculations

Presentation of the results


All power analyses must show, as in the table below, at least for each group of:

Active power circuits which corresponds (to the nearest efficiency) to the energy
supplied,
Reactive power so that the compensation devices (capacitors) can be sized,
Apparent power so that the power of the source can be determined and
Current consumed so that the trunking and protection devices can be calculated.
M1 M2 M1 + M2 (Total t)

Active power: P [kW] Pa1 = 24.18 Pa2 = 39.78 Pt = 63.96

Reactive power: Q [kVAR] Q1 = 10.30 Q2 = 38.35 Qt = 48.65

Apparent power: S [kVA] S1 = 26.28 S2 = 55.26 St = 80.36

Current consumed: Ia [A] Ia1 = 38 Ia2 = 80 Iat = 116

cos 0.92 0.72 0.80

Go back to currents and power calculations


4. Overloads on conductors according to the total
harmonic distortion
The current circulating in each phase is equal to the quadratic sum of the
fundamental current (referred to as 1st harmonic order) and all the harmonic
currents (of the following orders):

The THDi (Total Harmonic Distortion) expresses the ratio between the share of all the
harmonic currents and the total current as a percentage.

I1 being the rms value of the fundamental and in In the rms value of the nth order
harmonic. The principle is to apply a current reduction factor that can be calculated
based on the THDi.

For a permissible THDi value of 33%, the current must thus in theory be reduced in
each phase by a factor K:
If the factor is not applied, the current will then be increased by:

This remains acceptable and explains why the standard does not recommend any
derating or oversizing of cross-sections up to 33% THDi.

Above 33%. the standard recommends an increase in the current IB which results in
necessary oversizing of the neutral conductor.

Reduction of the current or oversizing of multi-core cables may also be necessary for
the phase conductors. It should be noted that the standard recommends a
reduction factor of 0.84. which in fact corresponds to a pessimistic THDi of 65%.

Related to the neutral conductor, it is considered that if all the harmonics are 3rd order
and its multiples, they will be added together and the current due to the harmonics in
the neutral will then be IN = 3 Iph, which can be expressed using an equivalent
notation, THDn = 3 THDi.

Devices whose load is said to be non-linear do not consume a current that is a reflection
of the voltage applied. This leads to unnecessary power consumption: the distorting power
that generates an additional current, the consequences of which must not be overlooked.

But this current is never expressed directly because it involves a fairly complex
mathematical calculation, the fourier transform, to ascertain its relative overall part (THDi:
total harmonic distortion) or the value order by order: ih 2, ih3, ih4, ih5,..ihn.

With no precise measurements, it is difficult to know exactly the current level that
corresponds to each harmonic order. It is therefore preferable to simply increase the
cross-section of the neutral conductor as a precaution, since it is known that the main
3rd order harmonics and their multiples are added together in the neutral. and to adapt
the protection of this conductor.
Standard IEC 60364 indicates the increasing factors to be applied to the cross-section

of the neutral conductor according the percentage of 3rd order harmonics.

In principle, the neutral must be the same cross-section as the phase conductor in all
single-phase circuits. In three-phase circuits with a cross-section greater than 16
mm2 [25 mm2 aluminium]. The cross-section of the neutral can be reduced to cross-
section/2.

However this reduction is not permitted if:

The loads are not virtually balanced


The total 3rd order harmonic currents are greater than 15%

If this total is greater than 33%, the cross-section of the active conductors of multi-core
cables is chosen by increasing the current In by a fixed multiplication factor of 1.65.
For single-core cables, only the cross-section of the neutral is increased.

In practice, the increase of the current Ia in the neutral is compensated by an increase


of its cross-section. When the neutral is loaded, a reduction factor of 0.86 is applied to the
permissible current of cables with 3 or 1 conductors.

The current reduction factor KN or rather its inverse which will be used to oversize
the neutral conductor will then be:

With a total 3rd order harmonic distortion of 65%, the current of the phase
conductors must be increased by 119% and that in the neutral conductor by 163%.
If the THDi were to reach 100%, 1/KN would theoretically reach 2.12. This value
would be impossible to reach as it would mean that the harmonic had totally replaced
the fundamental.

The theoretical overcurrent limit for the neutral in relation to the phases is:
These calculations demonstrate that the harmonic currents above all must not be ignored both
in terms of hidden power consumption and in terms of sizing the conductors which may
be overloaded. The relative complexity of the calculations leads to the use of generic derating
values which normally cover most cases, just as software is used elsewhere.

Go back to currents and power calculations

Example of following the standards for defining a


protection device with neutral overloaded by harmonics
For a 3P+N circuit, intended for 170 A, with TNS system, with total 3rd order harmonic
distortion of more than 33%. When sizing the phase cables, the reduction factor of
0.84 (loaded neutral, see above) must be included.

This requires a minimum cross-section of 70 mm2 per phase. The neutral conductor

must be sized to withstand a current of 1.45 170 A = 247 A, i.e. a cross-section

of 95 mm2.

A circuit breaker must therefore be chosen that is capable of withstanding the current
that may cross the neutral:

In device IB neutral In = 250 A


But the device must be set according to the current that may flow in the phases:

Ir IB phases Ir 170 A (and < 206 A, limit of the cable)


A 250 A unprotected interrupted neutral circuit breaker, set to 0.7 is therefore suitable for
this application.

Go back to currents and power calculations


5. Distorting load that is not purely resistive
The current consumed (Ia) is given by the following formulae:

where:

Ia rms current consumed (in A)


Pn nominal power (in W; this is the useful power)
U voltage between phases in three-phase, and between phase and neutral in single-
phase (in V)
efficiency
PF power factor

Go back to currents and power calculations

Example of a fluorescent luminaire and electronic ballast


The nominal active power consumed by the luminaire is 9 W, and the measured
apparent power is 16 VA. The measured displacement factor is cos = 0.845 and the
power factor PF = 0.56.

The measured current consumed Ia is 0.07 A. As cos and the power factor are
different, it is not possible to calculate the value of the tan or that of the reactive
power Q (VAR) for the receiver in question.

The measured cos and power Q which would be calculated can only be calculated for the
reactive power part connected with the sinusoidal component of the signal, in fact the current
of the fundamental at 50Hz: 0.045 A measured in this case.

The powers relative to this linear and sinusoidal part of the load can be calculated as
follows

S = 230 0.045 = 10.3 VA


P = S cos = 10.3 0.85 = 8.7 W
Q = 5.5 VAR which is confirmed by the calculation of the power triangles Q2 = P2 S2
or by the tan:
Q = P tan = 8.7 0.63 = 5.5 VAR
Therefore not all the apparent power consumed is linear as there is a significant difference
between the measured total apparent power S (16 VA) and the calculated theoretical
sinusoidal power (10.3 VA).

It can also be seen that the sinusoidal active power of the device 8.7 W is very similar
to the measured total active power 9 W. It can therefore be deduced that a large part
of power S (16 10.3 = 5.7 VA) is consumed without producing any active power. The
fluorescent luminaire and electronic ballast in the example consumes unproductive
power in the form of harmonic currents.

The total harmonic distortion is easy to calculate and represents expressed as a rate.

The spectral decomposition of the signal carried out on this luminaire shows that
the main harmonic is 3rd order (34 mA) but that all the following odd-order
harmonics are present and decaying. The main purpose of the above example is to
demonstrate that active power information (in W) only for a non-linear receiver is very
inadequate.

The cos has no real relevance or meaning as it is only applicable to the fundamental
signal. Only the apparent power and power factor (PF or ?\.,) information can really quantify
and qualify the power that must be supplied by the source.

In the example given, it can be seen that an active power of approximately 9 W


corresponds to a consumed power of 16 VA.

Many modern devices (light bulbs, computer equipment, domestic appliances and
electronic equipment) have this particular feature of consuming non-linear currents.
For domestic use, where only the power in W is billed (sic), the power savings shown
for these products is attractive. In practice, the currents consumed are higher than it
seems and the energy distributor is supplying wasted energy.

In large commercial or industrial installations the situation is different. A poor

power factor results in consumption of reactive power that is billed. Compensation of


non-linear loads thus becomes meaningful and useful here, but also at the design

stage when it prevents oversizing of the energy sources, which it must be

remembered supply VA (volt-amperes) and not W (watts).

Important: Unlike linear loads (page 29), for non-linear loads the active powers (in W)
can be added together algebraically, the apparent powers must only be added
together geometrically, and likewise the currents which must be the same order.

The reactive powers Q must not be added together except to as certain the relative
part of the power associated with the sinusoidal fundamental signal and the part
connected with the harmonic signals.

Go back to currents and power calculations

Reference // Power balance and choice of power supply solutions by Legrand.

Pick Up Current | Current Setting | Plug Setting Multiplier and Time Setting
Multiplier of Relay.
Pick Up Current of Relay
In all electrical relays, the moving contacts are not free to move. All the
contacts remain in their respective normal position by some force applied on
them continuously. This force is called controlling force of the relay. This
controlling force may be gravitational force, may be spring force, may be
magnetic force.

The force applied on the relays moving parts for changing the normal
position of the contacts, is called deflecting force. This deflecting force is
always in opposition of controlling force and presents always in the relay.
Although the deflecting force always presents in the relay directly connected
to live line, but as the magnitude of this force is less than controlling force in
normal condition, the relay does not operate. If the actuating current in the
relay coil increases gradually, the deflecting force in electro mechanical relay,
is also increased. Once, the deflecting force crosses the controlling force, the
moving parts of the relay initiate to move to change the position of the
contacts in the relay. The current for which the relay initiates it operation is
called pick up current of relay.

Current Setting of Relay


The minimum pick up value of the deflecting force of an electrical relay is
constant. Again the deflecting force of the coil is proportional to its number
of turns and current flowing through the coil.

Now, if we can change the number of active turns of any coil, the required
current to reach at minimum pick value of the deflecting force, in the coil
also changes. That means if active turns of the relay coil is reduced, then
proportionately more current is required to produce desired relay actuating
force. Similarly if active turns of the relay coil is increased, then
proportionately reduced current is required to produce same desired
deflecting force. Practically same model relays may be used in different
systems. As per these systems requirement the pick up current of relay is
adjusted. This is known as current setting of relay. This is achieved by
providing required number of tapping in the coil. These taps are brought out
to a plug bridge. The number of active turns in the coil can be changed by
inserting plug in different points in the bridge. The current setting of
relay is expressed in percentage ratio of relay pick up current to rated
secondary current of CT.

That means, For


example, suppose, you want that, an over current relay should operate when
the system current just crosses 125% of rated current. If the relay is rated
with 1 A, the normal pick up current of the relay is 1 A and it should be
equal to secondary rated current of current transformer connected to the
relay. Then, the relay will be operated when the current of CT secondary
becomes more than or equal 1.25 A. As per definition,

The current setting is sometimes


referred as current plug setting. The current setting of over current relay is
generally ranged from 50 % to 200 %, in steps of 25 %. For earth fault relay
it is from 10% to 70% in steps of 10%.

Plug Setting Multiplier of Relay

Plug setting multiplier of relay is referred as ratio of fault current in the


relay to its pick up current.
Suppose we have
connected on protection CT of ratio 200/1 A and current setting is 150%.
Hence, pick up current of the relay is, 1 150 % = 1.5 A Now, suppose fault
current in the CT primary is 1000 A. Hence, fault current in the CT secondary
i.e. in the relay coil is, 1000 1/200 = 5A Therefore PSM of the relay is, 5 /
1.5 =3.33

Time Setting Multiplier of Relay

The operating time of an electrical relay mainly depends upon two factors :
1. How long distance to be traveled by the moving parts of the relay for
closing relay contacts and
2. How fast the moving parts of the relay cover this distance.
So far adjusting relay operating time, both of the factors to be adjusted. The
adjustment of travelling distance of an electromechanical relay is commonly
known as time setting. This adjustment is commonly known as time setting
multiplier of relay. The time setting dial is calibrated from 0 to 1 in steps
0.05 sec. But by adjusting only time setting multiplier, we can not set the
actual time of operation of an electrical relay. As we already said, the time of
operation also depends upon the speed of operation. The speed of moving
parts of relay depends upon the force due to current in the relay coil. Hence,
it is clear that, speed of operation of an electrical relay depends upon the
level of fault current. In other words, time of operation of relay depends
upon plug setting multiplier. The relation between time of operation and plug
setting multiplier is plotted on a graph paper and this is known as time /
PSM graph. From this graph one can determine, the total time taken by the
moving parts of an electromechanical relay, to complete its total travelling
distance for different PSM. In time setting multiplier, this total travelling
distance is divided and calibrated from 0 to 1 in steps of 0.05. So when time
setting is 0.1, the moving parts of the relay has to travel only 0.1 times of
the total travelling distance, to close the contact of the relay. So, if we get
total operating time of the relay for a particular PSM from time / PSM graph
and if we multiply that time with the time setting multiplier, we will get,
actual time of operation of relay for said PSM and TSM. For getting clear
idea, let us have a practical example. Say a relay has time setting 0.1 and
you have to calculate actual time of operation for PSM 10. From time / PSM
graph of the relay as shown below, we can see the total operating time of
the relay is 3 seconds. That means, the moving parts of the relay take total
3 seconds to travel 100 % travelling distance. As the time setting multiplier
is 0.1 here, actually the moving parts of the relay have to travel only 0.1
100% or 10% of the total travel distance, to close the relay contacts. Hence,
actual operating time of the relay is 3 0.1 = 0.3 sec. i.e. 10% of 3 sec.

Time vs PSM Curve of Relay

This is relation curve between operating time and plug setting multiplier of
an electrical relay. The x-axis or horizontal axis of the Time / PSM graph
represents, PSM and Y-axis or vertical axis represents time of operation of
the relay. The time of operation represents in this graph is that, which
required to operate the relay when time setting multiplier set at 1. From the
Time / PSM curve of a typical relay shown below, it is seen that, if PSM is 10,
the time of operation of relay is 3 sec. That means, the relay will take 3
seconds to complete its operation, with time setting 1. It is also seen from
the curve that, for lower value of plug setting multiplier, i.e. for lower value
of fault current, the time of operation of the relay is inversely proportional to
the fault current. But when PSM becomes more than 20, the operating time
of relay becomes almost constant. This feature is necessary in order to
ensure discrimination on very heavy fault current flowing through sound
feeders.

Calculation of Relay Operation Time

For calculating actual relay operating time, we need to know these following
operation.
1. Current setting.
2. Fault current level.
3. Ratio of current transformer.
4. Time / PSM curve.
5. Time setting.
Step-1 From CT ratio, we first see the rated secondary current of CT. Say
the CT ratio is 100 / 1 A, i.e. secondary current of CT is 1 A. Step-2 From
current setting we calculate the trick current of the relay. Say current setting
of the relay is 150 % therefore pick up current of the relay is 1 150% =
1.5 A. Step-3 Now we have to calculate PSM for the specified faulty current
level. For that, we have to first divide primary faulty current by CT ratio to
get relay faulty current. Say the faulty current level is 1500 A, in the CT
primary, hence secondary equivalent of faulty current is 1500/(100/1) = 15
A Step-4 Now, after
calculating PSM, we have to find out the total time of operation of the relay
from Time / PSM curve. From the curve, say we found the time of operation
of relay is 3 second for PSM = 10. Step-5 Finally that operating time of relay
would be multiplied with time setting multiplier, in order to get actual time of
operation of relay. Hence say time setting of the relay is 0.1. Therefore
actual time of operation of the relay for PSM 10, is 3 0.1 = 0.3 sec or 300
ms.

Working Principle of Over Current Relay

In an over current relay, there would be essentially a current coil. When


normal current flows through this coil, the magnetic effect generated by the
coil is not sufficient to move the moving element of the relay, as in this
condition the restraining force is greater than deflecting force. But when the
current through the coil increased, the magnetic effect increases, and after
certain level of current, the deflecting force generated by the magnetic effect
of the coil, crosses the restraining force, as a result, the moving element
starts moving to change the contact position in the relay.
Types of Over Current Relay
Depending upon time of operation, there are various types of Over Current
relays, such as,
1. Instantaneous over current relay.
2. Definite time over current relay.
3. Inverse time over current relay.
Inverse time over current relay or simply inverse OC relay is again
subdivided as inverse definite minimum time (IDMT), very inverse
time, extremely inverse time over current relay or OC relay.
Instantaneous Over Current Relay
Construction and working principle of instantaneous over current
relay quite simple.
Here generally a magnetic core is wound by current coil. A piece of iron is so
fitted by hinge support and restraining spring in the relay, that when there is
not sufficient current in the coil, the NO contacts remain open. When current
in the coil crosses a present value, the attractive force becomes sufficient to
pull the iron piece towards the magnetic core and consequently the no
contacts are closed.
The preset value of current in the relay coil is referred as pick up setting
current. This relay is referred as instantaneous over current relay, as
ideally, the relay operates as soon as the current in the coil gets higher than
pick up setting current. There is no intentional time delay applied. But there
is always an inherent time delay which can not be avoided practically. In
practice the operating time of an instantaneous relay is of the order of a few
milliseconds. Fig.

Definite Time Over Current Relay

This relay is created by applying intentional time delay after crossing pick up
value of the current. A definite time over current relay can be adjusted
to issue a trip output at definite amount of time after it picks up. Thus, it has
a time setting adjustment and pick up adjustment.

Inverse Time Over Current Relay

Inverse time is a natural character of any induction type rotating device. This
means the speed of rotation of rotating art of the device is faster if input
current is increased. In other words, time of operation inversely varies with
input current. This natural characteristic of electromechanical induction disc
relay in very suitable for over current protection. This is because, in this
relay, if fault is more severe, it would be cleared more faster. Although time
inverse characteristic is inherent to electromechanical induction disc relay,
but the same characteristic can be achieved in microprocessor based relay
also by proper programming.

Inverse Definite Minimum Time Over Current Relay or IDMT O/C Relay

Ideal inverse time characteristics can not be achieved, in an over current


relay. As the current in the system increases, the secondary current of
the current transformer is increased proportionally. The secondary current is
fed to the relay current coil. But when the CT becomes saturated, there
would not be further proportional increase of CT secondary current with
increased system current.

From this phenomenon it is clear that from trick value to certain range of
faulty level, an inverse time relay shows exact inverse characteristic. But
after this level of fault, the CT becomes saturated and relay current does not
increase further with increasing faulty level of the system. As the relay
current is not increased further, there would not be any further reduction in
time of operation in the relay. This time is referred as minimum time of
operation. Hence, the characteristic is inverse in the initial part, which tends
to a definite minimum operating time as the current becomes very high.
That is why the relay is referred as inverse definite minimum time over
current relay or simply IDMT relay.

Motor Protection Relay for High Voltage Induction Motor.


Above 90% of motors used in an industry are induction motors, because
they are cheap, robust & easy to maintain. For higher HP (>250HP) motors
we prefer high voltage, because it will reduce operating current and the size
of the motor.

Why we require protection of motors?

To understand this we need to know the cost associated with the failure of
motor, i.e.
Loss of production (Cost of production)
Replacement of motor (Replacement cost)
Cost of repair
Cost of man hours due to this emergency
The basic function of a protective relay is to identify the fault and
isolate it from the healthy part of the system. This will improve the
reliability of power system. For protection of motor, we have to identify
the various causes of failure and to address the same. The various causes of
failure are as below.
Thermal stress on winding
Single phasing
Earth fault
Short circuit
Locked rotor
Number of hot starts
Bearing failure
Thermal Stress on Winding If a motor runs continuously more
than its rated capacity then this will over heat the winding and insulation.
Subsequently deteriorate the winding insulation resulting in failure of
motor. If the voltage is less than the designed value then also it will over
heat the winding at rated load and fail the motor.
Single Phasing Loss of one phase supplied to the motor (in case
of 3-phase motor) leads to single phasing. If we start the motor on load,
then the motor will fail due to unbalance.
Earth Fault If any part of winding comes in contact with the ground
then we can say the motor is earthed. If we start the motor then it will
lead to failure of motor.
Short Circuit If there is a contact between two phases of a three
phase winding or between the turns of a phase, then this will termed as
short circuit.
Locked Rotor If the driven equipment is in jammed condition or the
motor shaft is jam, then this is known as locked rotor. If we start the
motor then it will fail.
Number of Hot Start Each motor is designed to withstand a certain
number of hot starts. Consider a motor is in running condition, if we stop
the motor & immediately start the same, then this is called as hot start.
Depending upon the thermal curve of a motor we have to give certain
time to bring down the temperature of winding.
Bearing Failure If bearing fails then rubbing of rotor on stator will
occur, resulting physical damage of insulation and winding. The bearing
failure can be avoided by monitoring the bearing temperature. Bearing
temperature detector (BTD) is used for monitoring and tripping of motor
in case of abnormality.
All motor protection relays operate on the basis of current taken by the
motor. Motor protection relay is used for high voltage area having the
following features
Thermal overload protection
Short circuit protection
Single phasing protection
Earth fault protection
Locked rotor protection
Number of start protection
For setting of the relay we require the CT ratio & full load current of the
motor. The setting of different element is listed below
Thermal over Load Element - To set this element we have to
identify the % of Full load current on which the motor is running
continuously. Thermal setting = (Full load current x % of Full load) / CT
ratio.
Short circuit Element - The range available for this element is 1 to 5
times of starting current. Time delay is also available. We normally set at
2 times of I starting with a time delay of 0.1 second.
Single Phasing Element - This element will operate, if there is an
unbalance in current of three phases. It is also called as unbalance
protection. The element is set for 1/3rd of starting current. If it tripped
during starting, then the parameter will changed to 1/2 of starting
current.
Earth Fault Protection - This element measures the neutral current
of star connected CT secondary. The range available for this element is
0.02 to 2 times of CT primary current. Time delay is also available. We
normally set at 0.1 times of CT primary current with a time delay of 0.2
seconds. If tripped during starting of motor, then the time setting can be
raised to 0.5 sec.
Locked rotor protection - The range available for this element is 1
to 5 times of full load current. Time delay is also available. We normally
set at 2 times of FLC. The time delay will be more than the starting time
of the motor. "Starting time means the time require by the motor to reach
its full speed."
Number of hot start protection - Here we will provide the number
of start allowed in specified time duration. By this we will limit the number
of hot start given to the motor.
The schematic diagram to connect a motor protection relay is as below

Modern digital motor protection relays are having some extra features, i.e.
protection against no load running of a motor and thermal protection. In
case of no load running, the relay senses the motor current. If it is less than
the specified value then it will trip the motor. We can also connect the
temperature probe to the relay, which will monitor the bearing and winding
temperature and trip the motor if it exceeds the specified value.
Feeder Protection Relays.

Distance Protection Relay

One of the important protections in Power System Protection is Feeder


Protection. Different types of relays were used for feeder protection
like electromagnetic type relays, static type relays etc. But now a day we are
using Numerical relays for all protections. The benefits of Numerical relays
are,
1. Accurate tripping,
2. Less tolerance,
3. Fault events and counter storage
4. Display of fault parameters on screen
(Fault parameters means current, voltage, resistance and reactance values
during fault and fault distance, Numerical relays can store thousands of
tripping events). The main inputs needed for distance protection
is Voltage and Current from corresponding feeder PT and CT.

According to site condition we will set certain impedance values in relay


settings (i.e., R and X values) for fault detection. Relay will monitor Current
& Voltage in the feeder line (PT and CT secondary), and from these values,
the relay will calculate Impedance value Z. i.e., Z=V/I. In normal load
condition the impedance values on line will be high. But when fault comes on
the feeder line, the impedance will decrease and becomes less than the
impedance setting in the relay, then the distance relay will trip with in 40 ms
in zone 1 (different zones are there and that will be explained later) and
isolate power equipments from fault. I.e., during fault, relay will trip and
shows the fault parameters like fault current, voltage, reactance, resistance
and fault distance on relay screen. Suppose if the fault is on 25km, then
relay will show Fault Distance (FD) = 25km, and thus it becomes easy to
identify the location where there is fault. For Distance protection now a day
Quadrilateral characteristics is used. We already discussed that for fault
identification we have to set different parameters in relay. i.e.,

1. Forward and Backward Resistance (RF, RB),


2. Forward and backward Reactance (XF, XB),
3. RCA (Relay Characteristics Angle) and
4. Line Impedance per km.
These parameters are used for making Quadrilateral characteristics. Suppose
if RCA=70 and we are using parallelogram characteristics (Quadrilateral),
we can plot the graph by setting Forward Resistance (RF) value in positive X
axis, Backward Resistance (RB) in negative X axis, Forward Reactance (XF)
value in positive Y axis, and Backward Reactance (XB) in negative Y axis.

And plot parallelogram with a slope of RCA angle. Thus we will get a
parallelogram graph and the protection zone is inside the parallelogram.
Means during fault the impedance will reach inside the parallelogram then
the relay will trip. In graph there are 4 quadrants of operation

1. First quadrant (R and X values + ve) If the load is inductive and


the fault is in forward direction from Relay, then the relay will trip in this
quadrant values.
2. Second quadrant (R ve and X + ve) If the load is capacitive and
the fault is in reverse direction from Relay, then the relay will trip in this
quadrant values.
3. Third quadrant (R ve and X - ve) If the load is inductive and the
fault is in reverse direction from Relay, then the relay will trip in this
quadrant values.
4. Fourth quadrant (R + ve and X - ve) If the load is capacitive and
the fault is in forward direction from Relay, then the relay will trip in this
quadrant values.
Different Zones of operation, fault distance calculation and other feeder
protection relays etc. will be explained in next article... Remark: A model of
quadrilateral characteristics is shown below.

Types of Electrical Protection Relays or Protective Relays.

Definition of Protective Relay

A relay is automatic device which senses an abnormal condition of electrical


circuit and closes its contacts. These contacts in turns close and complete
the circuit breaker trip coil circuit hence make the circuit breaker tripped for
disconnecting the faulty portion of the electrical circuit from rest of the
healthy circuit. Now lets have a discussion on some terms related to
protective relay. Pickup Level of Actuating Signal: The value of actuating
quantity (voltage or current) which is on threshold above which the relay
initiates to be operated. If the value of actuating quantity is increased, the
electromagnetic effect of the relay coil is increased and above a certain level
of actuating quantity the moving mechanism of the relay just starts to move.

Reset Level: The value of current or voltage below which a relay opens its
contacts and comes in original position. Operating Time of Relay: Just
after exceeding pickup level of actuating quantity the moving mechanism
(for example rotating disc) of relay starts moving and it ultimately close the
relay contacts at the end of its journey. The time which elapses between the
instant when actuating quantity exceeds the pickup value to the instant
when the relay contacts close. Reset Time of Relay: The time which
elapses between the instant when the actuating quantity becomes less than
the reset value to the instant when the relay contacts returns to its normal
position. Reach of Relay: A distance relay operates whenever the distance
seen by the relay is less than the pre-specified impedance. The actuating
impedance in the relay is the function of distance in a distance protection
relay. This impedance or corresponding distance is called reach of the relay.
Power system protection relays can be categorized into different types of
relays.

Types of Relays

Types of protection relays are mainly based on their characteristic, logic, on


actuating parameter and operation mechanism. Based on operation
mechanism protection relay can be categorized as electromagnetic relay,
static relay and mechanical relay. Actually relay is nothing but a combination
of one or more open or closed contacts. These all or some specific contacts
the relay change their state when actuating parameters are applied to the
relay. That means open contacts become closed and closed contacts become
open. In electromagnetic relay these closing and opening of relay contacts
are done by electromagnetic action of a solenoid. In mechanical relay these
closing and opening of relay contacts are done by mechanical displacement
of different gear level system. In static relay it is mainly done
by semiconductor switches like thyristor. In digital relay on and off state can
be referred as 1 and 0 state. Based on Characteristic the protection relay
can be categorized as-
1. Definite time relays
2. Inverse time relays with definite minimum time(IDMT)
3. Instantaneous relays.
4. IDMT with inst.
5. Stepped characteristic.
6. Programmed switches.
7. Voltage restraint over current relay.

Based on of logic the protection relay can be categorized as-

1. Differential.
2. Unbalance.
3. Neutral displacement.
4. Directional.
5. Restricted earth fault.
6. Over fluxing.
7. Distance schemes.
8. Bus bar protection.
9. Reverse power relays.
10. Loss of excitation.
11. Negative phase sequence relays etc.
Based on actuating parameter the protection relay can be categorized as-
1. Current relays.
2. Voltage relays.
3. Frequency relays.
4. Power relays etc.
Based on application the protection relay can be categorized as-
1. Primary relay.
2. Backup relay.
Primary relay or primary protection relay is the first line of power system
protection whereas backup relay is operated only when primary relay fails to
be operated during fault. Hence backup relay is slower in action than
primary relay. Any relay may fail to be operated due to any of the following
reasons,
1. The protective relay itself is defective.
2. DC Trip voltage supply to the relay is unavailable.
3. Trip lead from relay panel to circuit breaker is disconnected.
4. Trip coil in the circuit breaker is disconnected or defective.
5. Current or voltage signals from CT or PT respectively is unavailable.
As because backup relay operates only when primary relay fails, backup
protection relay should not have anything common with primary protection
relay. Some examples of Mechanical Relay are-
1. Thermal
o OT trip (Oil Temperature Trip)
o WT trip (Winding Temperature Trip)
o Bearing temp trip etc.
2. Float type
o Buchholz
o OSR
o PRV
o Water level Controls etc.
3. Pressure switches.
4. Mechanical interlocks.
5. Pole discrepancy relay.
List Different Protective Relays are used for Different Power System
Equipment Protection
Now lets have a look on which different protective relays are used in
different power system equipment protection schemes.

Relays for Transmission & Distribution Lines Protection

Lines to be
SL Relays to be used
protected

400 KV Main-I: Non switched or Numerical Distance Scheme


1
Transmission Line Main-II: Non switched or Numerical Distance Scheme

Main-I : Non switched distance scheme (Fed from Bus


PTs)
220 KV
2 Main-II: Switched distance scheme (Fed from line CVTs)
Transmission Line
With a changeover facility from bus PT to line CVT and
vice-versa.

Main Protection : Switched distance scheme (fed from bus


PT).
132 KV
3 Backup Protection: 3 Nos. directional IDMT O/L Relays
Transmission Line
and
1 No. Directional IDMT E/L relay.

4 33 KV lines Non-directional IDMT 3 O/L and 1 E/L relays.

5 11 KV lines Non-directional IDMT 2 O/L and 1 E/L relays.

Relays for Transformer Protection

Voltage Ratio
and Common
SL Relays on HV Side Relays on LV Side
Capacity of Relays
Transformer

1 11/132 KV 3 nos Non-Directional -- Differential


Generator O/L Relay Relay or
Transformer 1 no Non-Directional Overall
E/L Relay differential
Relay
Overflux
Relay
Buchholz
Relay
and/or standby E/F +
OLTC
REF Relay
Buchholz
Relay
PRV Relay
OT Trip Relay
WT Trip Relay

Differential
Relay or
Overall
differential
Relay
13.8/220 KV 3 nos Non-Directional
Overflux
15.75/220 KV O/L Relay
Relay
18/400 KV 1 no Non-Directional
2 -- Buchholz
21/400 KV E/L Relay
Relay
Generator and/or standby E/F +
OLTC
Transformer REF Relay
Buchholz
Relay
PRV Relay
OT Trip Relay
WT Trip Relay

Differential
Relay
Overflux
3 nos Non-Directional Relay
O/L Relay Buchholz
220 /6.6KV 3 nos Non-
1 no Non-Directional Relay
3 Station Directional O/L
E/L Relay OLTC
Transformer Relay
and/or standby E/F + Buchholz
REF Relay Relay
PRV Relay
OT Trip Relay
WT Trip Relay
Differential
Relay
Overflux
Relay
Buchholz
3 nos Non-
Gen-volt/6.6KV 3 nos Non-Directional Relay
4 Directional O/L
UAT O/L Relay OLTC
Relay
Buchholz
Relay
PRV Relay
OT Trip Relay
WT Trip Relay

Buchholz
Relay
OLTC
132/33/11KV 3 nos O/L Relay 2 nos O/L Relays Buchholz
5
upto 8 MVA 1 no E/L Relay 1 no E/L Relay Relay
PRV Relay
OT Trip Relay
WT Trip Relay

Differential
Relay
Buchholz
Relay
132/33/11KV 3 nos O/L Relay
3 nos O/L Relay OLTC
6 above 8 MVA & 1 no Directional E/L
1 no E/L Relay Buchholz
below 31.5 MVA Relay
Relay
PRV Relay
OT Trip Relay
WT Trip Relay

7 132/33KV, 31.5 3 nos O/L Relay 3 nos O/L Relay Differential


MVA & above 1 no Directional E/L 1 no E/L Relay Relay
Relay Overflux
Relay
Buchholz
Relay
OLTC
Buchholz
Relay
PRV Relay
OT Trip Relay
WT Trip Relay

Differential
Relay
Overflux
Relay
220/33 KV,
Buchholz
31.5MVA & 3 nos O/L Relay 3 nos O/L Relay
Relay
8 50MVA 1 no Directional E/L 1 no Directional E/L
OLTC
220/132KV, 100 Relay Relay
Buchholz
MVA
Relay
PRV Relay
OT Trip Relay
WT Trip Relay

Differential
Relay
Overflux
3 nos Directional O/L Relay
Relay 3 nos Directional Buchholz
(with dir.highset) O/L Relay Relay
400/220KV 1 no Directional E/L (with dir.highset) OLTC
9
315MVA relay. 1 no Directional E/L Buchholz
Restricted E/F relay relay. Relay
3 nos Directional O/L Restricted E/F relay PRV Relay
Relay for action OT Trip Relay
WT Trip Relay
Over Load
(Alarm) Relay

Points to be remembered in respect of protection of transformers


1. No Buchholz relay for transformers below 500 KVA capacity.
2. Transformers up to 1500 KVA shall have only Horn gap protection.
3. Transformers above 1500 KVA and upto 8000 KVA of 33/11KV ratio
shall have one group control breaker on HV side and individual LV
breakers if there is more than one transformer.
4. Transformers above 8000 KVA shall have individual HV and LV circuit
breakers.
5. The relays indicate above shall be provided on HV and LV.
6. LAs to be provided on HV and LV for transformers of all capacities and
voltage class.
7. OLTC out of step protection is to be provided where master follower
scheme is in operation.
8. Fans failure and pumps failure alarms to be connected.
9. Alarms for O.T., W.T., Buchholz (Main tank AND OLTC) should be
connected.
Equivalent Circuit of Transformer referred to Primary and Secondary.

Equivalent Circuit of Transformer

Equivalent impedance of transformer is essential to be calculated because


the electrical power transformer is an electrical power system equipment for
estimating different parameters of electrical power system which may be
required to calculate total internal impedance of an electrical power
transformer, viewing from primary side or secondary side as per
requirement. This calculation requires equivalent circuit of transformer
referred to primary or equivalent circuit of transformer referred to
secondary sides respectively. Percentage impedance is also very essential
parameter of transformer. Special attention is to be given to this parameter
during installing a transformer in an existing electrical power system.
Percentage impedance of different power transformers should be properly
matched during parallel operation of power transformers. The percentage
impedance can be derived from equivalent impedance of transformer so,
it can be said that equivalent circuit of transformer is also required
during calculation of % impedance.

Equivalent Circuit of Transformer Referred to Primary

For drawing equivalent circuit of transformer referred to primary, first


we have to establish general equivalent circuit of transformer then, we
will modify it for referring from primary side. For doing this, first we need to
recall the complete vector diagram of a transformer which is shown in the
figure below. Let us
consider the transformation ratio be,

In the figure above, the applied voltage to the primary is V1 and voltage
across the primary winding is E1. Total current supplied to primary is I1. So
the voltage V1 applied to the primary is partly dropped by I1Z1 or I1R1 +
j.I1X1 before it appears across primary winding. The voltage appeared across
winding is countered by primary induced emf E1. So voltage equation of this
portion of the transformer can be written as,
The equivalent circuit for that equation can be drawn as below,

From the vector diagram above,


it is found that the total primary current I1 has two components, one is no -
load component Io and the other is load component I2. As this
primary current has two components or branches, so there must be a
parallel path with primary winding of transformer. This parallel path of
current is known as excitation branch of equivalent circuit of transformer.
The resistive and reactive branches of the excitation circuit can be
represented as

The load component


I2 flows through the primary winding of transformer and
induced voltage across the winding is E1 as shown in the figure right. This
induced voltage E1transforms to secondary and it is E2 and load component
of primary current I2 is transformed to secondary as secondary current I2.
Current of secondary is I2. So the voltage E2 across secondary winding is
partly dropped by I2Z2 or I2R2 + j.I2X2 before it appears across load. The
load voltage is V2.
The complete equivalent circuit of transformer is shown below.

Now if we
see the voltage drop in secondary from primary side, then it would be K
times greater and would be written as K.Z2.I2. Again I2.N1 = I2.N2

Therefore,

From above equation, secondary impedance of transformer referred to


primary is,

So, the complete equivalent circuit of transformer referred to primary is


shown in the figure below,

Approximate Equivalent Circuit of Transformer


Since Io is very small compared to I1, it is less than 5% of full load primary
current, Iochanges the voltage drop insignificantly. Hence, it is good
approximation to ignore the excitation circuit in approximate equivalent
circuit of transformer. The winding resistance and reactance being in series
can now be combined into equivalent resistance and reactance of
transformer, referred to any particular side. In this case it is side 1 or
primary side.

Equivalent Circuit of Transformer Referred to Secondary

In similar way, approximate equivalent circuit of transformer referred to


secondary can be drawn. Where equivalent impedance of
transformer referred to secondary, can be derived as.
Knee Point Voltage of Current Transformer PS Class.

Current Transformer PS Class

Before understanding Knee Point Voltage of Current


Transformer and current transformer PS class we should recall the
terms instrument security factor of CT and accuracy limit factor.

Instrument Security Factor or ISF of Current Transformer

Instrument security factor is the ratio of instrument limit


primary current to the rated primary current. Instrument limit current of a
metering current transformer is the maximum value of primary current
beyond which current transformer core becomes saturated. Instrument
security factor of CT is the significant factor for choosing the metering
instruments which to be connected to the secondary of the CT. Security or
Safety of the measuring unit is better, if ISF is low. If we go through the
example below it would be clear to us.

Suppose one current transformer has rating 100/1 A and ISF is 1.5 and
another current transformer has same rating with ISF 2. That means, in first
CT, the metering core would be saturated at 1.5 100 or 150 A, whereas is
second CT, core will be saturated at 2 100 or 200 A. That means whatever
may be the primary current of both CTs, secondary current will not increase
further after 150 and 200 A of primary current of the CTs respectively. Hence
maximum secondary current of the CTs would be 1.5 and 2.0 A.

As the maximum current can flow through the instrument connected to the
first CT is 1.5 A which is less than the maximum value of current can flow
through the instrument connected to the second CT i.e. 2 A. Hence security
or safety of the instruments of first CT is better than later.

Another significance of ISF is during huge electrical fault, the short circuit
current, flows through primary of the CT does not affect destructively,
the measuring instrument attached to it as because, the secondary current
of the CT will not rise above the value of rated secondary current multiplied
by ISF.

Accuracy Limit Factor or ALF of Current Transformer

For protection current transformer, the ratio of accuracy limit primary current
to the rated primary current. First we will explain, what is rated accuracy
limit primary current?.

Broadly, this is the maximum value of primary current, beyond which core of
the protection CT or simply protection core of of a CT starts saturated. The
value of rated accuracy limit primary current is always many times more
than the value of instrument limit primary current. Actually CT transforms
the fault current of the electrical power system for operation of
the protection relays connected to the secondary of that CT. If the core of
the CT becomes saturated at lower value of primary current, as in the case
of metering CT, the system fault will not reflect properly to the secondary,
which may cause, the relays remain inoperative even the fault level of the
system is large enough. That is why the core of the protection CT is made
such a way that saturation level of that core must be high enough. But still
there is a limit as because, it is impossible to make one magnetic core with
infinitely high saturation level and secondly most important reason is that
although the protection care should have high saturation level but that must
be limited up to certain level otherwise total transformation of primary
current during huge fault may badly damage the protection relays. So it is
clear from above explanation, rated accuracy limit primary current, should
not be so less, that it will not at all help the relays to be operated on the
other hand this value must not be so high that it can damage the relays.

So, accuracy limit factor or ALF should not have the value nearer to unit
and at the same time it should not be as high as 100. The standard values of
ALF as per IS-2705 are 5, 10, 15, 20 and 30.

Knee Point Voltage of Current Transformer

This is the significance of saturation level of a CT core mainly used for


protection purposes. The sinusoidal voltage of rated frequency applied to the
secondary terminals of current transformer, with other winding being open
circuited, which when increased by 10% cause the exiting current to
increase 50%. The CT core is made of CRGO steel. It has its won saturation
level. The EMF induced in the CT secondary windings is
E2 = 4.44fT2
Where, f is the system frequency, is the maximum magnetic flux in Wb.
T2 is the number of turns of the secondary winding. The flux in the core, is
produced by excitation current Ie. We have a non-liner relationship between
excitation current and magnetizing flux. After certain value of excitation
current, flux will not further increase so rapidly with increase in excitation
current. This non-liner relation curve is also called B - H curve. Again from
the equation above, it is found that, secondary voltage of acurrent
transformer is directly proportional to flux . Hence one typical curve can be
drawn from this relation between secondary voltage and excitation current
as shown below. It is clear from the curve that, linear relation between V
and Ie is maintained from point A and K. The point A is known as ankle
point and point K is known as Knee Point.

In differential and restricted earth fault (REF) protection scheme, accuracy


class and ALF of the CT may not ensure the reliability of the operation. It is
desired that, differential and REF relays should not be operated when fault
occurs outside the protected transformer. When any fault occurs outside the
differential protection zone, the faulty current flows through the CTs of both
sides of electrical power transformer. The both LV and HV CTs have
magnetizing characteristics. Beyond the knee point, for slight increase in
secondary emf a large increasing in excitation current is required. So after
this knee point excitation current of both current transformers will be
extremely high, which may cause mismatch between secondary current of
LV & HV current transformers. This phenomena may cause unexpected
tripping of power transformer. So the magnetizing characteristics of both LV
& HV sides CTs, should be same that means they have same knee point
voltage Vk as well as same excitation current I eat Vk/2. It can be again said
that, if both knee point voltage of current transformer and magnetizing
characteristic of CTs of both sides of power transformer differ, there must be
a mismatch in high excitation currents of the CTs during fault which
ultimately causes the unbalancing between secondary current of both groups
of CTs and transformer trips.

So for choosing CT for differential protection of transformer, one should


consider current transformer PS class rather its convectional protection
class. PS stands for protection special which is defined by knee point
voltage of current transformer Vk and excitation current Ie at Vk/2.

Why CT Secondary Should Not Be Kept Open?

The electrical power system load current always flows through current
transformer primary; irrespective of whether the current transformer is open
circuited or connected to burden at its secondary.

If CT secondary is open circuited,


all the primary current will behave as excitation current, which ultimately
produce huge voltage. Every current transformer has its won non-linear
magnetizing curve, because of which secondary open circuit voltage should
be limited by saturation of the core. If one can measure the rms voltage
across the secondary terminals, he or she will get the value which may not
appear to be dangerous. As the CT primary current is sinusoidal in nature, it
zero 100 times per second.(As frequency of the current is 50 Hz). The rate
of change of flux at every current zero is not limited by saturation and is
high indeed. This develops extremely high peaks or pulses of voltage. This
high peaks of voltage may not be measured by conventional voltmeter. But
these high peaks of induced voltage may breakdown the CT insulation, and
may case accident to personnel. The actual open-circuit voltage peak is
difficult to measure accurately because of its very short peaks. That is why
CT secondary should not be kept open.

Theory of Transformer

We have discussed about the theory of ideal transformer for better


understanding of actual elementary theory of transformer. Now we will go
through the practical aspects one by one of an electrical power
transformer and try to draw vector diagram of transformer in every step.
As we said that, in an ideal transformer; there are no core losses in
transformer i.e. loss free core of transformer. But in practical transformer,
there are hysteresis and eddy current losses in transformer core.

Theory of Transformer on No-Load

Theory of Transformer On No-load, and Having No Winding Resistance and


No Leakage Reactance of Transformer

Let us consider one electrical transformer with only core losses, which
means, it has only core losses but no copper loss and no leakage reactance
of transformer. When an alternating source is applied in the primary, the
source will supply the current for magnetizing the core of transformer.

But this current is not the actual magnetizing current, it is little bit greater
than actual magnetizing current. Actually, total current supplied from the
source has two components, one is magnetizing current which is merely
utilized for magnetizing the core and other component of the source current
is consumed for compensating the core losses in transformer. Because of this
core loss component, the source current in transformer on no-
load condition supplied from the source as source current is not exactly at
90 lags of supply voltage, but it lags behind an angle is less than 90. If
total current supplied from source is I o, it will have one component in phase
with supply voltage V1 and this component of the current I w is core loss
component. This component is taken in phase with source voltage, because
it is associated with active or working losses in transformer. Other
component of the source current is denoted as I . This component produces
the alternating magnetic flux in the core, so it is watt-less; means it is
reactive part of the transformer source current. Hence I will be in
quadrature with V1 and in phase with alternating flux .

Hence, total primary current in transformer on no-load condition can be


represented as

Now you have seen how simple is to explain the theory of transformer in
no-load.

Theory of Transformer on Load

Theory of Transformer On Load But Having No Winding Resistance and


Leakage Reactance
Now we will examine the behavior of above said transformer on load, that
means load is connected to the secondary terminals. Consider, transformer
having core loss but no copper loss and leakage reactance. Whenever load is
connected to the secondary winding, load current will start to flow through
the load as well as secondary winding. This load current solely depends upon
the characteristics of the load and also upon secondary voltage of
the transformer. This current is called secondary current or load current,
here it is denoted as I2. As I2 is flowing through the secondary, a self mmf in
secondary winding will be produced. Here it is N2I2, where, N2 is the number
of turns of the secondary winding of transformer.

This mmf or magneto


motive force in the secondary winding produces flux 2. This 2 will oppose
the main magnetizing flux and momentarily weakens the main flux and tries
to reduce primary self induced emf E1. If E1 falls down below the primary
source voltage V1, there will be an extra current flowing from source to
primary winding. This extra primary current I2 produces extra flux in the
core which will neutralize the secondary counter flux 2. Hence the main
magnetizing flux of core, remains unchanged irrespective of load.
So total current, this transformer draws from source can be divided into two
components, first one is utilized for magnetizing the core and compensating
the core loss i.e. Io. It is no-load component of the primary current. Second
one is utilized for compensating the counter flux of the secondary winding. It
is known as load component of the primary current. Hence total no load
primary current I1 of a electrical power transformer having no
winding resistance and leakage reactance can be represented as follows

Where, 2 is the angle between Secondary Voltage and Secondary Current of


transformer. Now we will proceed one further step toward more practical
aspect of a transformer.

Theory of Transformer On Load, With Resistive Winding, But No Leakage


Reactance

Now, consider the winding resistance of transformer but no leakage


reactance. So far we have discussed about the transformer which has ideal
windings, means winding with no resistance and leakage reactance, but now
we will consider one transformer which has internal resistance in the winding
but no leakage reactance. As the windings are resistive, there would be
a voltage drop in the windings.
We have proved earlier
that, total primary current from the source on load is I1. The voltage drop in
the primary winding with resistance, R1 is R1I1. Obviously, induced emf
across primary winding E1, is not exactly equal to source voltage V1. E1 is
less than V1 by voltage drop I1R1.

Again in the case of secondary, the voltage induced across the secondary
winding, E2 does not totally appear across the load since it also drops by an
amount I2R2, where R2 is the secondary winding resistance and I2 is
secondary current or load current. Similarly, voltage equation of the
secondary side of the transformer will be

Theory of Transformer On Load, With Resistance As Well As Leakage


Reactance in Transformer Windings

Now we will consider the condition, when there is leakage reactance of


transformer as well as winding resistance of transformer.
Let leakage reactances
of primary and secondary windings of the transformer are X1 and
X2respectively. Hence total impedance of primary and secondary winding of
transformer with resistance R1 and R2 respectively, can be represented as,

We have already established the voltage equation of a transformer on


load, with only resistances in the windings, where voltage drops in the
windings occur only due to resistive voltage drop. But when we consider
leakage reactances of transformer windings, voltage drop occurs in the
winding not only because of resistance, it is because of impedance of
transformer windings. Hence, actual voltage equation of a transformer can
easily be determined by just replacing resistances R1 & R2 in the previously
established voltage equations by Z1 and Z2.

Therefore, the voltage equations are,


Resistance drops are in the direction of current vector but, reactive drop will
be perpendicular to the current vector as shown in the above vector
diagram of transformer.
Small and Large Motor Protection Scheme.
The abnormalities in motor or motor faults may appear due to mainly two
reasons -
1. Conditions imposed by the external power supply network,
2. Internal faults, either in the motor or in the driven plant.
Unbalanced supply voltages, under-voltage, reversed phase sequence and
loss of synchronism (in the case of synchronous motor) come under former
category. The later category includes bearing failures, stator winding faults,
motor earth faults and overload etc.

The degree of motor protection system depends on the costs and


applications of the electrical motor.

Small Motor Protection Scheme

Generally motors up to 30 hp are considered in small category. The small


motor protection in this case is arranged by HRC fuse, bimetallic relay and
under voltage relay - all assembled into the motor contractor - starter itself.
Most common cause of motor burn outs on LV fuse protected system is due
to single phasing. This single phasing may remain undetected even if the
motors are protected by conventional bimetallic relay. It can not be detected
by a set of voltage relays connected across the lines. Since, even when one
phase is dead, the motor maintains substantial back emf on its faulty phase
terminal and hence voltage across the voltage relay is prevented from
dropping - off. The difficulties of detecting single phasing can be overcome
by employing a set of three current operated relays as shown in the small
motor protection circuit given below. The current operated relays are very
simple instantaneous relays. There are mainly two parts in this relay one is a
current coil and other is one or more normally open contacts (NO Contacts).
The NO contacts are operated by the mmf of the current coil. This relay is
connected in series with each phase of the supply and backup by HRC fuse.
When the electrical motor starts and runs the supply current passes through
the current coil of the protective relay. The mmf of the current coil makes
the NO contacts closed. If suddenly a single phasing occurs the
corresponding current through the current coil will falls and the contacts of
the corresponding relay will become to its normal open position. The NO
contacts of the all three relays are connected in series to hold - in the motor
contractor. So if any one relay contact opens, results to release of motor
contractor and hence motor will stop running.

Large Motor Protection

Large motor specially induction motors require protection against-


1. Motor bearing failure,
2. Motor over heating,
3. Motor winding failure,
4. Reverse motor rotation.

Motor Bearing Failure


Ball and roller bearings are used for the motor up to 500 hp and beyond this
size sleeve bearings are used. failure of ball or roller bearing usually causes
the motor to a standstill very quickly. Due to sudden mechanical jamming in
motor bearing, the input current of the motor becomes very high. Current
operated protection, attached to the input of the motor can not serve
satisfactorily. Since this motor protection system has to be set to override
the high motor starting current. The difficulty can be over come by providing
thermal over load relay. As the starting current of the motor is high but
exists only during starting so for that current the there will be no over
heating effect. But over current due mechanical jamming exists for longer
time hence there will be a over heating effect. So stalling motor protection
can be offered by the thermal overload relay. Stalling protection can also be
provided by separate definite time over current relay which is operated only
after a certain predefined time if over current persists beyond that period. In
the case of sleeve bearing, a temperature sensing device embedded in the
bearing itself. This scheme of motor protection is more reliable and sensitive
to motor bearing failure since the thermal withstand limit of the motor is
quite higher than that of bearing. If we allow the bearing over heating and
wait for motor thermal relay to trip, the bearing may be permanently
damaged. The temperature sensing device embedded in the bearing stops
the motor if the bearing temperature rises beyond its predefined limit.

Motor Over Heating

The main reason of motor over heating that means over heating of motor
winding is due to either of mechanical over loading, reduced supply voltage,
unbalanced supply voltage and single phasing. The over heating may cause
deterioration of insulation life of motor hence it must be avoided by
providing proper motor protection scheme. To avoid over heating, the motor
should be isolated in 40 to 50 minutes even in the event of small overloads
of the order of 10 %. The protective relay should take into account the
detrimental heating effects on the motor rotor due to negative sequence
currents in the stator arising out of unbalance in supply voltage. The motor
should also be protected by instantaneous motor protection relay against
single phasing such as a stall on loss of one phase when running at full load
or attempting to start with only two of three phases alive.

Motor Winding Failure

The motor protection relay should should have instantaneous trip


elements to detect motor winding failure such as phase to phase and
phase to earth faults. Preferably phase to phase fault unit should be
energized from positive phase sequence component of the motor current and
another instantaneous unit connected in the residual circuit of the current
transformers be used for earth faults protection.

Reverse Motor Rotation

Specially in the case of conveyor belt, the reverse motor rotation must be
avoided. The reverse rotation during starting can be caused due to
inadvertent reversing of supply phases. A comprehensive motor protection
relay with an instantaneous negative sequence unit will satisfy this
requirement. If such relay has not been provided, a watt-meter type relay
can be employed. NB: However, we have to provide some additional
motor protection system for synchronous motor which is discussed
in details in synchronous motor protection topic.
Motor Thermal Overload Protection.
For understanding motor thermal overload protection in induction
motor we can discuss the operating principle of three phase induction motor.
There is one cylindrical stator and a three phase winding is symmetrically
distributed in the inner periphery of the stator. Due to such symmetrical
distribution, when three phase power supply is applied to the stator winding,
a rotating magnetic field is produced. This field rotates at synchronous
speed. The rotor is created in induction motor mainly by numbers solid
copper bars which are shorted at both ends in such a manner that they form
a cylinder cage like structure. This is why this motor is also referred as
squirrel cage induction motor. Anyway let's come to the basic point of three
phase induction motor - which will help us to understand clearly
about motor thermal overload protection.As the rotating magnetic
flux cuts each of the bar conductor of rotor, there will be an induced
circulating current flowing through the bar conductors. At starting the rotor
is stand still and stator field is rotating at synchronous speed, the relative
motion between rotating field and rotor is maximum.

Hence, the rate of cuts of flux with rotor bars is maximum, the induced
current is maximum at this condition. But as the cause of induced current is,
this relative speed, the rotor will try to reduce this relative speed and hence
it will start rotating in the direction of rotating magnetic field to catch the
synchronous speed. As soon as the rotor will come to the synchronous speed
this relative speed between rotor and rotating magnetic field becomes zero,
hence there will not be any further flux cutting and consequently there will
not be any induced current in the rotor bars. As the induced current
becomes zero, there will not be any further need of maintaining zero relative
speed between rotor and rotating magnetic field hence rotor speed falls. As
soon as the rotor speed falls the relative speed between rotor and rotating
magnetic field again acquires a non zero value which again causes induced
current in the rotor bars then rotor will again try to achieve the synchronous
speed and this will continue till the motor is switch on. Due to this
phenomenon the rotor will never achieve the synchronous speed as well as it
will never stop running during normal operation. The difference between the
synchronous speed with rotor speed in respect of synchronous speed, is
termed as slip of induction motor.

The slip in a normally running induction motor typically varies from 1 % to 3


% depending upon the loading condition of the motor. Now we will try to
draw speed current characteristics of induction motor lets have an

example of large boiler fan. In the


characteristic Y axis is taken as time in second, X axis is taken as % of
stator current. When rotor is stand still that is at starting condition, the slip
is maximum hence the induced current in the rotor is maximum and due to
transformation action, stator will also draw a heavy current from the supply
and it would be around 600 % of the rated full load stator current. As the
rotor is being accelerated the slip is reduced, consequently the rotor current
hence stator current falls to around 500 % of the full load rated current
within 12 seconds when the rotor speed attains 80 % of synchronous speed.
After that the stator current falls rapidly to the rated value as the rotor
reaches its normal speed.
Now we will discuss about thermal over loading of electrical motor or
over heating problem of electric motor and the necessity of motor thermal
overload protection. Whenever we think about the overheating of a motor,
the first thing strikes in our mind is over loading. Due to mechanical over
loading of the motor draws higher current from the supply which leads to
excessive over heating of the motor. The motor can also be excessively over
heated if the rotor is mechanically locked i.e. becomes stationary by any
external mechanical force. In this situation the motor will draw excessively
high current from the supply which also leads to thermal over loading of
electrical motor or excessive over heating problem. Another cause of
overheating is low supply voltage. As the power id drawn by the motor from
the supply depends upon the loading condition of the motor, for lower supply
voltage, motor will draw higher current from mains to maintain required
torque. Single phasing also causes thermal over loading of motor. When
one phase of the supply is out of service, the remaining two phases draw
higher current to maintain required load torque and this leads to overheating
of the motor. Unbalance condition between three phases of supply also
causes over heating of the motor winding, as because unbalance system
results to negative sequence current in the stator winding. Again, due to
sudden loss and reestablish of supply voltage may cause excessive heating
of the motor. Since due to sudden loss of supply voltage, the motor is de-
accelerated and due to sudden reestablishment of voltage the motor is
accelerated to achieve its rated speed and hence for that motor draws higher
current form the supply. As the thermal over loading or over heating of the
motor may lead to insulation failure and damage of winding, hence for
proper motor thermal overload protection, the motor should be
protected against the following conditions

1. Mechanical over loading,


2. Stalling of motor shaft,
3. Low supply voltage,
4. Single phasing of supply mains,
5. Unbalancing of supply mains,
6. Sudden Loss and rebuilding of supply voltage.
The most basic protection scheme of the motor is thermal over load
protection which primarily covers the protection of all the above mentioned
condition. To understand the basic principle of thermal over load protection
lets examine the schematic diagram of basic motor control scheme.
In the
figure above, when START push is closed, the starter coil is energized
through the transformer. As the starter coil is energized, normally open (NO)
contacts 5 are closed hence motor gets supply voltage at its terminal and it
starts rotating. This start coil also closes contact 4 which makes the starter
coil energized even the START push button contact is released from its close
position. To stop the motor there are several normally closed (NC) contacts
in series with the starter coil as shown in the figure. One of them is STOP
push button contact. If the STOP push button is pressed, this button contact
opens and breaks the continuity of the starter coil circuit consequently
makes the starter coil de-energized. Hence the contact 5 and 4 come back to
their normally open position. Then, in absence of voltage at motor terminals
it will ultimately stop running. Similarly any of the other NC contacts (1, 2 &
3) connected in series with starter coil if open; it will also stop the motor.
These NC contacts are electrically coupled with various protection relays to
stop operation of the motor in different abnormal conditions. Lets look at
the thermal over load relay and its function in motor thermal overload
protection. The secondary of the CTs in series with motor supply circuit, are
connected with a bimetallic strip of the thermal over load relay (49). As
shown in the figure below, when current through the secondary of any of the
CTs, crosses its predetermined values for a predetermined time, the bi-
metallic strip is over heated and it deforms which ultimately causes to
operate the relay 49. As soon as the relay 49 is operated, the NC contacts 1
and 2 are opened which de-energizes the starter coil and hence stop the
motor. An
other thing we have to remember during providing motor thermal overload
protection. Actually every motor does have some predetermined overload
tolerance value. That means every motor may run beyond its rated load for
a specific allowable period depending on its loading condition. How long a
motor can run safely for a particular load is specified by the manufacturer.
The relation between different loads on motor and corresponding allowable
periods for running the same in safe condition is referred as thermal limit
curve of the motor. Lets look at the curve of a particular motor, given below.
Here Y axis or
vertical axis represents the allowable time in seconds and X axis or
horizontal axis represents percentage of overload. Here it is clear from the
curve that, motor can run safely without any damage due to overheating for
prolonged period at 100 % of the rated load. It can run safely 1000 seconds
at 200 % of normal rated load. It can run safely 100 seconds at 300 % of
normal rated load. It can run safely 15 seconds at 600 % of normal rated
load. The upper portion of the curve represents the normal running condition
of the rotor and the lower most portion represents the mechanical locked
condition of the rotor. Now the operating time Vs actuating current curve of
the chosen thermal over load relay should be situated below the thermal
limit curve of the motor for satisfactory and safe operation. Lets have a
discussion on more details-
Remember the
characteristics of starting current of the motor During start up of the
induction motor, the stator current goes beyond 600 % of normal rated
current but it stays up to 10 to 12 seconds after that stator current suddenly
falls to normal rated value. So if the thermal overload relay is operated
before that 10 to 12 seconds for the current 600 % of normal rated then the
motor cannot be started. Hence, it can be concluded that the operating time
Vs actuating current curve of the chosen thermal over load relay should be
situated below the thermal limit curve of the motor but above the starting
current characteristics curve of the motor. Probable position of the thermal
current relay characteristics is bounded by these two said curves as shown in
the graph by highlighted area.

Another thing has to be remembered during choosing of thermal overload


relay. This relay is not an instantaneous relay. It has a minimum delay in
operation as the bimetallic strip required a minimum time to be heated up
and deformed for maximum value of operating current. From the graph it is
found that the thermal relay will be operated after 25 to 30 seconds if either
the rotor is suddenly mechanically blocked or motor is fail to start. At this
situation the motor will draw a huge current from the supply. If the motor is
not isolated sooner, severer damage may occur.
This
problem is overcome by providing time over current relay with high pickup.
The time current characteristics of these over current relays are so chosen
that for lower value of over load, the relay will not operate since thermal
overload relay will be actuated before it. But for higher value of overload and
for blocked rotor condition time over load relay will be operated instead of
thermal relay because former will actuate much before the latter. Hence both
the bimetallic over load relay and time over current relay are provided for
complete motor thermal overload protection. There is one main
disadvantage of bimetallic thermal over load relay, as the rate of heating and
cooling of bi-metal is affected by ambient temperature, the performance of
the relay may differ for different ambient temperatures. This problem can be
overcome by using RTD or resistance temperature detector. The bigger and
more sophisticated motors are protected against thermal over load more
accurately by using RTD. In stator slots, RTDs are placed along with stator
winding. Resistance of the RTD changes with changing temperature and this
changed resistive value is sensed by a Wheatstone bridge circuit. This motor
thermal overload protection scheme is very simple. RTD of stator is used as
one arm of balanced Wheatstone bridge. The amount of current through the
relay 49 depends upon the degree of unbalancing of the bridge. As the
temperature of the stator winding is increased, the electrical resistance of
the detector increases which disturbs the balanced condition of the bridge.
As a result current start flowing through the relay 49 and the relay will be
actuated after a predetermined value of this unbalanced current and
ultimately starter contact will open to stop the supply to the motor.

Electrical Fault Calculation | Positive Negative Zero Sequence Impedance.


Before applying proper electrical protection system, it is necessary to have
through knowledge of the conditions of electrical power system during faults.
The knowledge of electrical fault condition is required to deploy proper
different protective relays in different locations of electrical power system.
Information regarding values of maximum and minimum fault
currents, voltages under those faults in magnitude and phase relation with
respect to the currents at different parts of power system, to be gathered for
proper application of protection relay system in those different parts of the
electrical power system. Collecting the information from different parameters
of the system is generally known as electrical fault calculation.

Fault calculation broadly means calculation of fault current in any electrical


power system. There are mainly three steps for calculating faults in a
system.

1. Choice of impedance rotations.


2. Reduction of complicated electrical power system network to single
equivalent impedance.
3. Electrical fault currents and voltages calculation by using symmetrical
component theory.

Impedance Notation of Electrical Power System

If we look at any electrical power system, we will find, these are several
voltage levels. For example, suppose a typical power system where electrical
power is generated at 6.6 kV then that 132 kV power is transmitted to
terminal substation where it is stepped down to 33 kV and 11 kV levels and
this 11 kV level may further step down to 0.4kv. Hence from this example it
is clear that a same power system network may have different voltage
levels. So calculation of fault at any location of the said system becomes
much difficult and complicated it try to calculate impedance of different parts
of the system according to their voltage level. This difficulty can be avoided
if we calculate impedance of different part of the system in reference to a
single base value. This technique is called impedance notation of power
system. In other wards, before electrical fault calculation, the system
parameters, must be referred to base quantities and represented as uniform
system of impedance in either ohmic, percentage, or per unit values.
Electrical power and voltage are generally taken as base quantities. In three
phase system, three phase power in MVA or KVA is taken as base power and
line to line voltage in KV is taken as base voltage. The base impedance of
the system can be calculated from these base power and base voltage, as

follows, Per unit is an impedance value of any system is


nothing but the radio of actual impedance of the system to the base

impedance value. Percentage impedance value can be


calculated by multiplying 100 with per unit value. Again it
is sometimes required to convert per unit values referred to new base
values for simplifying different electrical fault calculations. In that case,

The choice of impedance notation depends upon the complicity of the


system. Generally base voltage of a system is so chosen that it requires
minimum number of transfers. Suppose, one system as a large number of
132 KV over head lines, few numbers of 33 KV lines and very few number of
11 KV lines. The base voltage of the system can be chosen either as 132 KV
or 33 KV or 11 KV, but here the best base voltages 132 KV, because it
requires minimum number of transfer during fault calculation.

Network Reduction
After choosing the correct impedance notation, the next step is to reduce
network to a single impedance. For this first we have to convert the
impedance of all generators, lines, cables, transformer to a common base
value. Then we prepare a schematic diagram of electrical power system
showing the impedance referred to same base value of all those generators,
lines, cables and transformers. The network then reduced to a common
equivalent single impedance by using star/delta transformations. Separate
impedance diagrams should be prepared for positive, negative and zero
sequence networks. There phase faults are unique since they are balanced
i.e. symmetrical in three phase, and can be calculated from the single phase
positive sequence impedance diagram. Therefore three phase fault current

is obtained by, Where, I f is the total three phase fault current, v is


the phase to neutral voltage z 1 is the total positive sequence impedance of
the system; assuming that in the calculation, impedance are represented in
ohms on a voltage base.

Symmetrical Component Analysis

The above fault calculation is made on assumption of three phase balanced


system. The calculation is made for one phase only as the current and
voltage conditions are same in all three phases. When actual faults occur in
electrical power system, such as phase to earth fault, phase to phase fault
and double phase to earth fault, the system becomes unbalanced means,
the conditions of voltages and currents in all phases are no longer
symmetrical. Such faults are solved by symmetrical component analysis.
Generally three phase vector diagram may be replaced by three sets of
balanced vectors. One has opposite or negative phase rotation, second has
positive phase rotation and last one is co-phasal. That means these vectors
sets are described as negative, positive and zero sequence, respectively.
The equation between phase and sequence quantities are,

Therefore,

Where all quantities are referred to the reference


phase r. Similarly a set of equations can be written for sequence currents
also. From, voltage and current equations, one can easily determine the
sequence impedance of the system. The development of symmetrical
component analysis depends upon the fact that in balanced system of
impedance, sequence currents can give rise only to voltage drops of the
same sequence. Once the sequence networks are available, these can be
converted to single equivalent impedance. Let us consider Z1, Z2 and Z0 are
the impedance of the system to the flow of positive, negative and zero
sequence current respectively. For earth fault

Phase to phase faults Double phase to earth

faults Three phase faults


If fault current in any particular branch of the network is required, the same
can be calculated after combining the sequence components flowing in that
branch. This involves the distribution of sequence components currents as
determined by solving the above equations, in their respective network
according to their relative impedance. Voltages it any point of the network
can also be determine once the sequence component currents and sequence
impedance of each branch are known.
Sequence Impedance

Positive Sequence Impedance

The impedance offered by the system to the flow of positive sequence


current is called positive sequence impedance.

Negative Sequence Impedance

The impedance offered by the system to the flow of negative sequence


current is called negative sequence impedance.
Zero Sequence Impedance

The impedance offered by the system to the flow of zero sequence current is
known as zero sequence impedance. In previous fault calculation, Z1,
Z2 and Z0 are positive, negative and zero sequence impedance respectively.
The sequence impedance varies with the type of power system
components under consideration:-
1. In static and balanced power system components like transformer and
lines, the sequence impedance offered by the system are the same for
positive and negative sequence currents. In other words, the positive
sequence impedance and negative sequence impedance are same
for transformers and power lines.
2. But in case of rotating machines the positive and negative
sequence impedance are different.
3. The assignment of zero sequence impedance values is a more
complex one. This is because the three zero sequence current at any point
in a electrical power system, being in phase, do not sum to zero but must
return through the neutral and /or earth. In three phase transformer and
machine fluxes due to zero sequence components do not sum to zero in
the yoke or field system. The impedance very widely depending upon the
physical arrangement of the magnetic circuits and winding.
1. The reactance of transmission lines of zero sequence currents
can be about 3 to 5 times the positive sequence current, the lighter
value being for lines without earth wires. This is because the spacing
between the go and return(i.e. neutral and/or earth) is so much
greater than for positive and negative sequence currents which return
(balance) within the three phase conductor groups.
2. The zero sequence reactance of a machine is compounded of
leakage and winding reactance, and a small component due to winding
balance (depends on winding tritch).
3. The zero sequence reactance of transformers depends both on
winding connections and upon construction of core.

External and Internal Faults in Transformer.

External Faults in Power Transformer

External Short - Circuit of Power Transformer

The short - circuit may occurs in two or three phases of electrical


power system. The level of fault current is always high enough. It depends
upon the voltage which has been short - circuited and upon the impedance
of the circuit up to the fault point. The copper loss of the fault feeding
transformer is abruptly increased. This increasing copper loss causes internal
heating in the transformer. Large fault current also produces severe
mechanical stresses in the transformer. The maximum mechanical stresses
occurs during first cycle of symmetrical fault current.

High Voltage Disturbance in Power Transformer

High voltage disturbance in power transformer are of two kinds,


1. Transient Surge Voltage
2. Power Frequency Over Voltage
Transient Surge Voltage
High voltage and high frequency surge may arise in the power system due to
any of the following causes,
Arcing ground if neutral point is isolated.
Switching operation of different electrical equipment.
Atmospheric Lightening Impulse.
Whatever may be the causes of surge voltage, it is after all a traveling wave
having high and steep wave form and also having high frequency. This wave
travels in the electrical power system network, upon reaching in the power
transformer, it causes breakdown the insulation between turns adjacent to
line terminal, which may create short circuit between turns.
Power Frequency Over Voltage
There may be always a chance of system over voltage due to sudden
disconnection of large load. Although the amplitude of this voltage is higher
than its normal level but frequency is same as it was in normal condition.
Over voltage in the system causes an increase in stress on the insulation of
transformer. As we know that, voltage V = 4.44.f.T V , increased
voltage causes proportionate increase in the working flux. This therefore
causes, increased in iron loss and dis - proportionately large increase in
magnetizing current. The increase flux is diverted from the transformer core
to other steel structural parts of the transformer. Core bolts which normally
carry little flux, may be subjected to a large component of flux diverted from
saturated region of the core alongside. Under such condition, the bolt may
be rapidly heated up and destroys their own insulation as well as winding
insulation.
Under Frequency Effect in Power Transformer
As, voltage V = 4.44.f.T V .f as the number of turns in the winding is
fixed. Therefore, V/f From, this equation it is clear that if frequency
reduces in a system, the flux in the core increases, the effect are more or
less similar to that of the over voltage.

Internal Faults in Power Transformer

The principle faults which occurs inside a power transformer are categorized
as,
1. Insulation breakdown between winding and earth
2. Insulation breakdown in between different phases
3. Insulation breakdown in between adjacent turns i.e. inter - turn fault
4. Transformer core fault

Internal Earth Faults in Power Transformer

Internal Earth Faults in a Star Connected Winding with Neutral Point Earthed
through an Impedance
In this case the fault current is dependent on the value of earthing
impedance and is also proportional to the distance of the fault point from
neutral point as the voltage at the point depends upon, the number of
winding turns come under across neutral and fault point. If the distance
between fault point and neutral point is more, the number of turns come
under this distance is also more, hence voltage across the neutral point and
fault point is high which causes higher fault current. So, in few words it can
be said that, the value of fault current depends on the value of earthing
impedance as well as the distance between the faulty point and neutral
point. The fault current also depends up on leakage reactance of the portion
of the winding across the fault point and neutral. But compared to the
earthing impedance,it is very low and it is obviously ignored as it comes in
series with comparatively much higher earthing impedance.
Internal Earth Faults in a Star Connected Winding with Neutral Point Solidly
Earthed
In this case, earthing impedance is ideally zero. The fault current is
dependent up on leakage reactance of the portion of winding comes across
faulty point and neutral point of transformer. The fault current is also
dependent on the distance between neutral point and fault point in the
transformer. As said in previous case the voltage across these two points
depends upon the number of winding turn comes across faulty point and
neutral point. So in star connected winding with neutral point solidly
earthed, the fault current depends upon two main factors, first the leakage
reactance of the winding comes across faulty point and neutral point and
secondly the distance between faulty point and neutral point. But the
leakage reactance of the winding varies in complex manner with position of
the fault in the winding. It is seen that the reactance decreases very rapidly
for fault point approaching the neutral and hence the fault current is highest
for the fault near the neutral end. So at this point, the voltage available for
fault current is low and at the same time the reactance opposes the fault
current is also low, hence the value of fault current is high enough. Again at
fault point away from the neutral point, the voltage available for fault current
is high but at the same time reactance offered by the winding portion
between fault point and neutral point is high. It can be noticed that the fault
current stays a very high level throughout the winding. In other word, the
fault current maintain a very high magnitude irrelevant to the position of the
fault on winding.

Internal Phase to Phase Faults in Power Transformer

Phase to phase fault in the transformer are rare. If such a fault does occur, it
will give rise to substantial current to operate instantaneous over current
relay on the primary side as well as the differential relay.

Inter Turns Fault in Power Transformer

Power Transformer connected with electrical extra high voltage transmission


system, is very likely to be subjected to high magnitude, steep fronted and
high frequency impulse voltage due to lightening surge on the transmission
line. The voltage stresses between winding turns become so large, it can not
sustain the stress and causing insulation failure between inter - turns in
some points. Also LV winding is stressed because of the transferred surge
voltage. Very large number of Power Transformer failure arise from fault
between turns. Inter turn fault may also be occurred due to mechanical
forces between turns originated by external short circuit.

Core Fault in Power Transformer

In any portion of the core lamination is damaged, or lamination of the core is


bridged by any conducting material causes sufficient eddy current to flow,
hence, this part of the core becomes over heated. Some times, insulation of
bolts (Used for tightening the core lamination together) fails which also
permits sufficient eddy current to flow through the bolt and causing over
heating. These insulation failure in lamination and core bolts causes severe
local heating. Although these local heating, causes additional core loss but
can not create any noticeable change in input and output current in the
transformer, hence these faults can not be detected by normal electrical
protection scheme. This is desirable to detect the local over heating
condition of the transformer core before any major fault occurs. Excessive
over heating leads to breakdown of transformer insulating oil with evolution
of gases. These gases are accumulated in Buchholz relay and actuating
Buchholz Alarm.
Backup Protection of Transformer | Over Current and Earth Fault.
Over Current and Earth Fault Protection of Transformer
Backup protection of electrical transformer is simple Over Current
and Earth Fault protection applied against external short circuit and
excessive over loads. These over current and earth Fault relays may be of
Inverse Definite Minimum Time (IDMT) or Definite Time type relays.
Generally IDMT relays are connected to the in-feed side of the transformer.
The over current relays can not distinguish between external short circuit,
over load and internal faults of the transformer. For any of the above
fault, backup protection i.e. over current and earth fault
protection connected to in-feed side of the transformer will operate.

Backup protection is although generally installed at in feed side of the


transformer, but it should trip both the primary and secondary circuit

breakers of the transformer. Over


Current and Earth Fault protection relays may be also provided in load side
of the transformer too, but it should not inter trip the primary side circuit
breaker like the case of backup protection at in-feed side. The operation is
governed primarily by current and time settings and the characteristic curve
of the relay. To permit use of over load capacity of the transformer and co-
ordination with other similar relays at about 125 to 150 % of full load
current of the transformer but below the minimum short circuit current.

Backup protection of transformer has four elements, three over current


relays connected each in each phase and one earth fault relay connected to
the common point of three over current relays as shown in the figure. The
normal range of current settings available on IDMT over current relays is 50
% to 200 % and on earth fault relay 20 to 80 %.

Another range of setting on earth fault relay is also available and may be
selected where the earth fault current is restricted due to insertion of
impedance in the neutral grounding. In the case of transformer winding with
neutral earthed, unrestricted earth fault protection is obtained by connecting
an ordinary earth fault relay across a neutral current transformer. The
unrestricted over current and earth fault relays should have proper time lag
to co-ordinate with the protective relays of other circuit to avoid
indiscriminate tripping.
Transformer Protection and Transformer Fault.
There are different kinds of transformers such as two winding or three
winding electrical power transformers, auto transformer, regulating
transformers, earthing transformers, rectifier transformers etc. Different
transformers demand different schemes of transformer
protection depending upon their importance, winding connections, earthing
methods and mode of operation etc.It is common practice to
provide Buchholz relay protection to all 0.5 MVA and above transformers.
While for all small size distribution transformers, only high voltage fuses are
used as main protective device. For all larger rated and important
distribution transformers, over current protection along with restricted earth
fault protectionis applied. Differential protection should be provided in
the transformers rated above 5 MVA.

Depending upon the normal service condition, nature of transformer faults,


degree of sustained over load, scheme of tap changing, and many other
factors, the suitable transformer protection schemes are chosen.

Nature of Transformer Faults

Although an electrical power transformer is a static device, but internal


stresses arising from abnormal system conditions, must be taken into
consideration. A transformer generally suffers from following types of
transformer fault-
1. Over current due to overloads and external short circuits,
2. Terminal faults,
3. Winding faults,
4. Incipient faults.
All the above mentioned transformer faults cause mechanical and thermal
stresses inside the transformer winding and its connecting terminals.
Thermal stresses lead to overheating which ultimately affect the insulation
system of transformer. Deterioration of insulation leads to winding faults.
Some time failure of transformer cooling system, leads to overheating of
transformer. So the transformer protection schemes are very much required.

The short circuit current of an electrical transformer is normally limited by its


reactance and for low reactance, the value of short circuit current may be
excessively high. The duration of external short circuits which a transformer
can sustain without damage as given in BSS 171:1936.

Transformer % reactance Permitted fault duration in seconds

4% 2

5% 3

6% 4

7 % and over 5

The general winding faults in transformer are either earth faults or inter-
turns faults. Phase to phase winding faults in a transformer is rare. The
phase faults in an electrical transformer may be occurred due to bushing
flash over and faults in tap changer equipment. Whatever may be the faults,
the transformer must be isolated instantly during fault otherwise major
breakdown may occur in the electrical power system. Incipient faults are
internal faults which constitute no immediate hazard. But it these faults are
over looked and not taken care of, these may lead to major faults. The faults
in this group are mainly inter-lamination short circuit due to insulation failure
between core lamination, lowering the oil level due to oil leakage, blockage
of oil flow paths. All these faults lead to overheating. So transformer
protection scheme is required for incipient transformer faults also. The earth
fault, very nearer to neutral point of transformer star winding may also be
considered as an incipient fault. Influence of winding connections and
earthing on earth fault current magnitude. There are mainly two conditions
for earth fault current to flow during winding to earth faults,
1. A current exists for the current to flow into and out of the winding.
2. Ampere-turns balance is maintained between the windings.
The value of winding earth fault current depends upon position of the fault
on the winding, method of winding connection and method of earthing. The
star point of the windings may be earthed either solidly or via a resistor. On
delta side of the transformer the system is earthed through an earthing
transformer. Grounding or earthing transformer provides low impedance path
to the zero sequence current and high impedance to the positive and
negative sequence currents.

Star Winding with Neutral Resistance Earthed


In this case the neutral point of the transformer is earthed via a resistor and
the value of impedance of it, is much higher than that of winding impedance
of the transformer. That means the value of transformer winding impedance
is negligible compared to impedance of earthing resistor. The value of earth
current is, therefore, proportional to the position of the fault in the winding.
As the fault current in the primary winding of the transformer is proportional
to the ratio of the short circuited secondary turns to the total turns on the
primary winding, the primary fault current will be proportional to the square
of the percentage of winding short circuited. The variation of fault current
both in the primary and secondary winding is shown below.
Star Winding with Neutral Solidly Earthed
In this case the earth fault current magnitude is limited solely by the winding
impedance and the fault is no longer proportional to the position of the fault.
The reason for this non linearity is unbalanced flux linkage.
Protection of Lines or Feeder.
As the length of electrical power transmission line is generally long enough
and it runs through open atmosphere, the probability of occurring fault in
electrical power transmission line is much higher than that of electrical
power transformers and alternators. That is why a transmission line requires
much more protective schemes than a transformer and an
alternator.Protection of line should have some special features, such as-
1. During fault, the only circuit breaker closest to the fault point should
be tripped.
2. If the circuit breaker closest the faulty point, fails to trip the circuit
breaker just next to this breaker will trip as back up.
3. The operating time of relay associated with protection of line should be
as minimum as possible in order to prevent unnecessary tripping of circuit
breakers associated with other healthy parts of power system.
These above mentioned requirements cause protection of transmission
line much different from protection of transformer and other equipment of
power systems. The main three methods of transmission line
protection are -

1. Time graded over current protection.


2. Differential protection.
3. Distance protection.

Time Graded Over Current Protection

This may also be referred simply as over-current protection of electrical


power transmission line. Let' discuss different schemes of time graded over
current protection.

Protection of Radial Feeder

In radial feeder, the power flows in one direction only, that is from source to
load. This type of feeders can easily protected by using either definite time
relays or inverse time relays.
Line Protection by Definite Time Relay
This protection scheme is very simple. Here total line is divided into different
sections and each section is provided with definite time relay. The relay
nearest to the end of the line has minimum time setting while time setting of
other relays successively increased, towards the source. For example,
suppose there is a source at point A, in the figure below
At point D the circuit breaker CB-3 is installed with definite time of relay
operation 0.5 sec. Successively, at point C an other circuit breaker CB-2 is
installed with definite time of relay operation 1 sec. The next circuit breaker
CB-1 is installed at point B which is nearest of the point A. At point B, the
relay is set at time of operation 1.5 sec.

Now, assume a fault occurs at point F. Due to this fault, the faulty current
flow through all the current transformers or CTs connected in the line. But as
the time of operation of relay at point D is minimum the CB-3, associated
with this relay will trip first to isolate the faulty zone from rest part of the
line. In case due to any reason, CB-3 fails to trip, then next higher timed
relay will operate the associated CB to trip. In this case, CB-2 will trip. If CB-
2 also fails to trip, then next circuit breaker i.e. CB-1 will trip to isolate
major portion of the line.

Advantages of Definite Time Line Protection


The main advantage of this scheme is simplicity. The second major
advantage is, during fault, only nearest CB towards the source from fault
point will operate to isolate the specific position of the line.
Disadvantage of Definite Time Line Protection
If the number of sections in the line is quite large, the time setting of relay
nearest to the source, would be very long. So during any fault nearer to the
source will take much time to be isolated. This may cause severe destructive
effect on the system.
Over Current Line Protection by Inverse Relay

The drawback as we discussed just in definite time over current protection


of transmission line, can easily be overcome by using inverse time relays. In
inverse relay the time of operation is inversely proportional to fault current.

In the above figure, overall time setting of relay at point D is minimum and
successively this time setting is increased for the relays associated with the
points towards the point A. In case of any fault at point F will obviously trip
CB-3 at point D. In failure of opening CB-3, CB-2 will be operated as overall
time setting is higher in relay at point C. Although, the time setting of relay
nearest to the source is maximum but still it will trip in shorter period, if
major fault occurs near the source, as the time of operation of relay is
inversely proportional to faulty current.

Over Current Protection of Parallel Feeders

For maintaining stability of the system it is required to feed a load from


source by two or more than two feeders in parallel. If fault occurs in any of
the feeders, only that faulty feeder should be isolated from the system in
order to maintain continuity of supply from source to load. This requirement
makes the protection of parallel feeders little bit more complex than simple
non direction over current protection of line as in the case of radial feeders.
The protection of parallel feeder requires to use directional relays and to
grade the time setting of relay for selective tripping.
There are two feeders connected in parallel from source to load. Both of the
feeders have non-directional over current relay at source end. These relays
should be inverse time relay. Also both of the feeders have directional relay
or reverse power relay at their load end. The reverse power relays used here
should be instantaneous type. That means these relays should be operated
as soon as flow of power in the feeder is reversed. The normal direction of
power from source to load. Now, suppose a fault occurs at point F, say the
fault current is If. This fault will get two parallel paths from source, one
through circuit breaker A only and other via CB-B, feeder-2, CB-Q, load bus
and CB-P. This is clearly shown in figure below, where IA and IB are current of
fault shared by feeder-1 and feeder-2 respectively.
As per Kirchoff's current law, IA + IB = If.

Now, IA is flowing through CB-A, IB is flowing through CB-P. As the direction


of flow of CB-P is reversed it will trip instantly. But CB-Q will not trip as flow
of current (power) in this circuit breaker is not reversed. As soon as CB-P is
tripped, the fault current IB stops flowing through feeder and hence there is
no question of further operating of inverse time over current relay. I A still
continues to flow even CB-P is tripped. Then because of over current I A, CB-
A will trip. In this way the faulty feeder is isolated from system.

Differential Pilot Wire Protection

This is simply a differential protection scheme applied to feeders. Several


differential schemes are applied for protection of line but Mess Price Voltage
balance system and Translay Scheme are most popularly used.
Merz Price Balance System
The working principle of Merz Price Balance system is quite simple. In this
scheme of line protection, identical CT is connected to each of the both ends
of the line. The polarity of the CTs are same. The secondary of these current
transformer and operating coil of two instantaneous relays are formed a
closed loop as shown in the figure below. In the loop pilot wire is used to
connect both CT secondary and both relay coil as shown.
Now, from the figure it is quite clear that when the system is under normal
condition, there would not be any current flowing through the loop. As the
secondary current of one CT will cancel out secondary current of other CT.
Now, if any fault occurs in the portion of the line between these two CTs, the
secondary current of one CT will no longer equal and opposite of secondary
current of other CT. Hence there would be a resultant circulating current in
the loop. Due this circulating current, the coil of both relays will close the
trip circuit of associate circuit breaker. Hence, the faulty line will be isolated
from both ends.
Busbar Protection | Busbar Differential Protection Scheme.
In early days only conventional over current relays were used for busbar
protection. But it is desired that fault in any feeder
or transformer connected to the busbar should not disturb busbar system. In
viewing of this time setting of busbar protection relays are made lengthy. So
when faults occurs on busbar itself, it takes much time to isolate the bus
from source which may came much damage in the bus system.In recent
days, the second zone distance protection relays on incoming feeder, with
operating time of 0.3 to 0.5 seconds have been applied for busbar
protection. But this scheme has also a main disadvantage. This scheme of
protection can not discriminate the faulty section of the busbar. Now
days, electrical power system deals with huge amount of power. Hence any
interruption in total bus system causes big loss to the company. So it
becomes essential to isolate only faulty section of busbar during bus fault.
Another drawback of second zone distance protection scheme is that,
sometime the clearing time is not short enough to ensure the system
stability. To overcome the above mentioned difficulties, differential busbar
protection scheme with an operating time less than 0.1 sec., is commonly
applied to many SHT bus systems.

Differential Busbar Protection

Current Differential Protection

The scheme of busbar protection, involves, Kirchoffs current law, which


states that, total current entering an electrical node is exactly equal to total
current leaving the node. Hence, total current entering into a bus section is
equal to total current leaving the bus section.

The principle of differential busbar protection is very simple. Here,


secondaries of CTs are connected parallel. That means, S1 terminals of all
CTs connected together and forms a bus wire. Similarly S 2 terminals of all
CTs connected together to form another bus wire. A tripping relay is
connected across these two bus wires.

Here, in the figure above we assume that at normal condition feed, A, B, C,


D, E and F carries current IA, IB, IC, ID, IE and IF. Now, according to Kirchoffs
current law,
Essentially all the CTs used for differential busbar protection are of same
current ratio. Hence, the summation of all secondary currents must also be
equal to zero. Now, say current through the relay connected in parallel with
all CT secondaries, is iR, and iA, iB, iC, iD, iE and iF are secondary currents.
Now, let us apply KCL at node X. As per KCL at node X,

So, it is clear that under normal condition there is no current flows through
the busbar protection tripping relay. This relay is generally referred as
Relay 87. Now, say fault is occurred at any of the feeders, outside the
protected zone. In that case, the faulty current will pass through primary of
the CT of that feeder. This fault current is contributed by all other feeders
connected to the bus. So, contributed part of fault current flows through the
corresponding CT of respective feeder. Hence at that faulty condition, if we
apply KCL at node K, we will still get, iR = 0.
That means, at external faulty condition, there is no current flows through
relay 87. Now consider a situation when fault is occurred on the bus itself.

At this condition, also the faulty current is contributed by all feeders


connected to the bus. Hence, at this condition, sum of all contributed fault
current is equal to total faulty current. Now, at faulty path there is no CT. (in
external fault, both fault current and contributed current to the fault by
different feeder get CT in their path of flowing).

The sum of all secondary currents is no longer zero. It is equal to secondary


equivalent of faulty current. Now, if we apply KCL at the nodes, we will get a
non zero value of iR. So at this condition current starts flowing through 87
relay and it makes trip the circuit breakercorresponding to all the feeders
connected to this section of the busbar. As all the incoming and outgoing
feeders, connected to this section of bus are tripped, the bus becomes dead.
This differential busbar protection scheme is also referred as current
differential protection of busbar.

Differential Protection of Sectionalized Bus

During explaining working principle of current differential protection of


busbar, we have shown a simple non sectionalized busbar. But in moderate
high voltage system electrical bus sectionalized in than one sections to
increase stability of the system. It is done because, fault in one section of
bus should not disturb other section of the system. Hence during bus fault,
total bus would be interrupted.

Let us draw and discuss about protection of busbar with two sections.

Here, bus section A or zone A is bounded by CT 1, CT2 and CT3 where CT1 and
CT2 are feeder CTs and CT3 is bus CT. Similarly bus section B or zone B is
bounded by CT4, CT5 and CT6where CT4 is bus CT, CT5 and CT6 are feeder CT.
Therefore, zone A and B are overlapped to ensure that, there is no zone left
behind this busbar protection scheme. ASI terminals of CT1, 2 and 3 are
connected together to form secondary bus ASI BSI terminals of CT 4, 5 and 6
are connected together to form secondary bus BSI. S 2 terminals of all CTs
are connected together to form a common bus S 2. Now, busbar protection
relay 87A for zone A is connected across bus ASI and S 2. Relay 87B for zone
B is connected across bus BSI and S 2. This section busbar differential
protection scheme operates in some manner simple current differential
protection of busbar. That is, any fault in zone A, with trip only CB 1, CB2and
bus CB. Any fault in zone B, will trip only CB 5, CB6 and bus CB. Hence, fault in
any section of bus will isolate only that portion from live system. In current
differential protection of busbar, if CT secondary circuits, or bus wires is open
the relay may be operated to isolate the bus from live system. But this is not
desirable.

DC Circuit of Differential Busbar Protection


A typical DC circuit for busbar differential protection scheme is given

below. Here, CSSA and


CSSB are two selector switch which are used to put into service, the busbar
protection system for zone A and zone B respectively. If CSSA is in IN
position, protection scheme for zone A is in service. If CSSB is in IN
position, protection for zone B is in service. Generally both of the switches
are in IN position in normal operating condition. Here, relay coil of 96A and
96B are in series with differential busbar protection relay contact 87A-1 and
87B-1 respectively. 96A relay is multi contacts relay. Each circuit breaker in
zone A is connected with individual contact of 96A. Similarly, 96B is multi
contacts relay and each circuit breaker in zone-B is connected with individual
contacts of 96B. Although here we use only one tripping relay per protected
zone, but this is better to use one individual tripping relay per feeder. In this
scheme one protective relay is provided per feeder circuit breaker, whereas
two tripping relays one for zone A and other for zone B are provided to bus
section or bus coupler circuit breaker. On an interval fault in zone A or bus
section A, the respective bus protection relay 87A, be energized whereas
during internal fault in zone B, the respective relay 87B will be energized. As
soon as relay coil of 87A or 87B is energized respective no. contact 87A-1 or
87B-1 is closed.Hence, the tripping relay 96 will trip the breakers connected
to the faulty zone. To indicate whether zone A or B busbar protection
operated, relay 30 is used. For example, if relay 87A is operated,
corresponding No contact 87A-2 is closed which energized relay 30A. Then
the No contact 30A-1 of relay 30A is closed to energized alarm relay 74.
Supervision relay 95 of respective zone is also energized during internal
fault, but it has a time delay of 3 second. So, it reset as soon as the fault is
cleared and therefore does not pick up zone bus wire shorting relay 95x
which in turn shorts out the bus wires. An alarm contact is also given to this
auxiliary 95x relay to indicate which CT is open circuited. No volt relay 80 is
provided in both trip and non-trip section of the DC circuit of differential
busbar protection system to indicate any discontinuity of D. C. supply.

Voltage Differential Protection of Busbar

The current differential scheme is sensitive only when the CTs do not get
saturated and maintain same current ratio, phase angle error under
maximum faulty condition. This is usually not 80, particularly, in the case of
an external fault on one of the feeders. The CT on the faulty feeder may be
saturated by total current and consequently it will have very large errors.
Due to this large error, the summation of secondary current of all CTs in a
particular zone may not be zero. So there may be a high chance of tripping
of all circuit breakers associated with this protection zone even in the case of
an external large fault. To prevent this maloperation of current
differential busbar protection, the 87 relays are provided with high pick up
current and enough time delay. The greatest troublesome cause of current
transformer saturation is the transient dc component of the short circuit
current. This difficulties can be overcome by using air core CTs. This current
transformer is also called linear coupler. As the core of the CT does not use
iron the secondary characteristic of these CTs, is straight line. In voltage
differential busbar protection the CTs of all incoming and outgoing feeders
are connected in series instead of connecting them in parallel.

The secondaries of all CTs and differential relay form a closed loop. If
polarity of all CTs are properly matched, the sum of voltage across all CT
secondaries is zero. Hence there would be no resultant voltage appears
across the differential relay. When a buss fault occurs, sum of the all CT
secondary voltage is no longer zero. Hence, there would be current circulate
in the loop due to the resultant voltage. As this loop current also flows
through the differential relay, the relay is operated to trip all the circuit
beaker associated with protected bus zone. Except when ground fault
current is severally limited by neutral impedance there is usually no
selectivity problem when such a problem exists, it is solved by use of an
additional more sensitive relaying equipment including a supervising
protective relay.
Protection of Capacitor Bank.
Like other electrical equipments, shunt capacitor may also be subjected to
internal and external electrical faults. Hence this equipment is also to be
protected from internal and external faults. There are numbers of schemes
available for protection of capacitor bank, but during applying any of the
schemes, we should remember the initial investment on that capacitor for
economical point of view. We should compare the initial investment in the
capacitor and the cost of the protection applying on it. There are mainly 3
types of protection arrangement are applied to a capacitor bank.
1. Element Fuse.
2. Unit. Fuse.
3. Bank Protection.

Element Fuses

Manufacturers of capacitor unit commonly provide inbuilt fuse in each


element of the unit. In this case, if any fault occurs in any element itself, it is
automatically disconnected from rest of the unit. In this case, the unit still
serves its purpose, but with smaller output. In smaller rated capacitor bank
only these inbuilt protection scheme is applied to avoid the expenditure of
other special protective equipments.

Unit Fuse

The unit fuse protection is generally provided to limit the duration of arc
inside a faulty capacitor unit. As the arc duration is limited, there is less
chance of major mechanical deformation and huge production of gas in the
faulty unit, and hence the neighborhood units of the bank are saved. If each
unit of a capacitor bank is individually protected against fuse, then in case of
failure of one unit, the capacitor bank can still be running without
interruption before removing and replacing the faulty unit. Another major
advantage of providing fuse protection to each unit of the bank is that, it
indicates the exact location of the faulty unit. But during choosing the size of
the fuse for this purpose, it should be taken into consideration that the fuse
element must withstand the excessive loading due to harmonics in the
system. In the view of that the current rating of the fuse element for this
purpose is taken as 65 % above the full load current. Whenever the
individual unit of capacitor bank is protected by fuse, it is necessary to
provide discharge resistance in each of the units.

Bank Protection

Although in general fuse protection is provided with each of the capacitor


units, but when a capacitor unit is under fault and the associated fuse
element is blown out, the voltage stress increases to the other capacitor
units connected in series in same row. Generally, each capacitor unit is
designed for withstanding 110% of its normal rated voltage. If any other
capacitor unit further becomes out of service, in the same row where
previously one unit is damaged, the voltage stress upon other healthy units
of that row will increase further and easily crosses the limit of maximum
allowable, voltage of these units. Hence it is always desirable to replace
damaged capacitor unit from the bank as soon as possible to avoid excess
voltage stress on the other healthy units. Hence, there must be some
indicating arrangement to identify the exact faulty unit. As soon as the faulty
unit is identified in a bank, the bank should be removed from the service for
replacing the faulty unit. There are several methods of sensing unbalance
voltage caused by failure of capacitor unit. The figure below is showing the
most common arrangement of capacitor bank protection. Here, the
capacitor bank is connected in star formation. Primary of a potential
transformer is connected across each phase. The secondary of all
three potential transformers are connected in series to form an open delta
and a voltage sensitive relay is connected across this open delta. In exact
balanced condition there must not be any voltage appears across the voltage
sensitive relay because summation of balanced 3 phase voltages is zero. But
when there would be any voltage unbalancing due to failure of capacitor
unit, the resultant voltage will appear across the relay and the relay will be
actuated for providing an alarm and trip signals.

The voltage sensitive relay can be so adjusted that up to a certain voltage


unbalancing only alarm contacts would be closed and for certain higher
voltage level the trip contacts along with alarm contacts would be closed.
The potential transformer connected across the capacitors of each phase
also serves for discharging of the bank after being switched off.
In another scheme, the
capacitors in each phase are divided into two equal parts connected in
series. Discharge coil is connected across each of the parts as shown in the
figure. In between the secondary of discharge coil and the sensitive voltage
unbalance the relay an auxiliary transformer is connected which serves to
regulate the voltage difference between secondary voltages of discharge coil
under normal conditions.
Here the capacitor
bank is connected in star and the neutral point is connected to the ground
through a potential transformer. A voltage sensitive relay is connected across
the secondary of the potential transformer. As soon as there is any
unbalance between the phases, the resultant voltage will appear across the
potential transformer and hence the voltage sensitive relay will be actuated
beyond a preset value.
Here, the capacitor bank of each phase is divided into two equal parts
connected in parallel and the star points of both parts are interconnected
through a current transformer. The secondary of the current transformer are
connected across a current sensitive relay. In case any misbalancing occurs
between the two parts of the bank, there would be a unbalance current
flowing through the current transformer and hence the current sensitive
relay will actuate. In this scheme for discharging the bank after switching
off, discharge coil may be connected across the capacitors in each phase.
In another scheme of
protection of capacitor bank, the star point of a three phase capacitor bank
is connected to the ground through a current transformer and a current
sensitive relay is connected across the secondary of the current transformer.
As soon as there is any unbalancing between the phases of capacitor bank,
there must be a current flowing to the ground through the current
transformer and hence the current sensitive relay will be actuated to trip
the circuit breaker associated with the capacitor bank.
Basic electrical design of a PLC panel (Wiring diagrams).

Building the PLC panel


It is uncommon for engineers to build their own PLC panel designs (but not impossible
of course). For example, once the electrical designs are complete, they must be built
by an electrician. Therefore, it is your responsibility to effectively communicate your
design intentions to the electricians through drawings. In some factories, the
electricians also enter the ladder logic and do debugging .

This article discusses the design issues in implementation that must be considered by
the designer.

Electrical wiring diagrams of a PLC panel


In an industrial setting a PLC is not simply plugged into a wall socket. The electrical
design for each machine must include at least the following components.

1. Transformers to step down AC supply voltages to lower levels


2. Power contacts to manually enable/disable power to the machine with e-stop
buttons
3. Terminals to connect devices
4. Fuses or circuit breakers will cause power to fail if too much current is drawn
5. Grounding to provide a path for current to flow when there is an electrical fault
6. Enclosure to protect the equipment, and users from accidental contact
A control system of a PLC panel will normally use AC and DC power at different voltage
levels. Control cabinets are often supplied with single phase AC at 220/440/550V, or two
phase AC at 220/440V AC, or three phase AC at 330/550V.

This power must be dropped down to a lower voltage level for the controls and DC
power supplies. 110Vac is common in North America, and 220 V AC Is common in
Europe and the Commonwealth countries. It is also common for a control cabinet to
supply a higher voltage to other equipment, such as motors.

Motor controller example


An example of a wiring diagram for a motor controller is shown in Figure 1. Note
that symbols are discussed in detail later).

Dashed lines indicate a single purchased component. This system uses 3 phase AC
power (L1, L2 and L3) connected to the terminals. The three phases are then
connected to a power interrupter. Next, all three phases are supplied to a motor starter
that contains three contacts, M, and three thermal overload relays (breakers).
Figure 1 A Motor Controller Schematic

The contacts, M, will be controlled by the coil, M. The output of the motor starter goes
to a three phase AC motor. Power is supplied by connecting a step down
transformer to the control electronics by connecting to phases L2 and L3. The lower
voltage is then used to supply power to the left and right rails of the ladder below. The
neutral rail is also grounded.

The logic consists of two push buttons:


Start push button is normally open, so that if something fails the motor cannot be
started.
Stop push button is normally closed, so that if a wire or connection fails the system
halts safely.

The system controls the motor starter coil M, and uses a spare contact on the
starter, M, to seal in the motor starter.

The diagram also shows numbering for the wires in the device. This is essential for
industrial control systems that may contain hundreds or thousands of wires. These
numbering schemes are often particular to each facility, but there are tools to help
make wire labels that will appear in the final controls cabinet.

Figure 2 A
Physical Layout for the Control Cabinet
Once the electrical design is complete, a layout for the controls cabinet is developed, as
shown in Figure 2. The physical dimensions of the devices must be considered, and adequate
space is needed to run wires between components.

In the cabinet the AC power would enter at the terminal block, and be connected to the main
breaker.

It would then be connected to the contactors and overload relays that constitute the
motor starter. Two of the phases are also connected to the transformer to power the
logic. The start and stop buttons are at the left of the box (note: normally these are
mounted elsewhere, and a separate layout drawing would be needed).

The final layout in the cabinet might look like the one shown in Figure 1.
Figure 3 Final PLC Panel Wiring
When being built the system will follow certain standards that may be company policy,
or legal requirements. This often includes items such as;

Hold downs the will secure the wire so they dont move
Labels wire labels help troubleshooting
Strain reliefs these will hold the wire so that it will not be pulled out of screw
terminals
Grounding grounding wires may be needed on each metal piece for safety

A photograph of an industrial controls cabinet is shown in Figure 4:

Figure 4
An industrial control cabinet with wire runs, terminal strip, buttons on PLC panel
front, etc.

When including a PLC in the ladder diagram still remains. But, it does tend to become
more complex. Figure 5 below shows a schematic diagram for a PLC based motor
control system, similar to the previous motor control example.
This figure shows the E-stop wired to cutoff power to all of the devices in the circuit,
including the PLC. All critical safety functions should be hardwired this way.

Figure 5 An Electrical
Schematic with a PLC.
Electrical Distribution Architecture In Water Treatment Plants.

Water treatment plants

For both drinking water and wastewater treatment, 4 different sizes of plants have
been distinguished. The size of plants can be expressed in quantity of treated water
per day, or in corresponding number of inhabitants.

Four different types of (waste) water treatment plants have been distinguished,
depending on destination and size:

T1 Autonomous water treatment plant // See single-line diagram


T2 Small water or wastewater treatment plant // See single line diagram
T3 Medium sized water or wastewater treatment plant
See single line diagrams //
Double-radial architecture and
Open medium voltage loop
T4 Large water or wastewater treatment plant
See single line diagrams //
Radial-double feed
Open medium voltage loop
Characteristics T1 T2 T3 T4

m3/day 1K-5K 5K-50K 50K-200K 200K-1000K


(drinking water or waste water)

Inhabitants 1K-10K 10K-100K 100K-500K 500K-1000K


Power demand 25-125 kVA 125-1250 kVA 1.25-5 MVA 5-25 MVA

Electrical Distribution

Guidance is given for the selection of Electrical Distribution architecture in water


treatment plants. This includes the selection between different possible configurations
of MV and LV circuits and the implementation of back-up power sources.

The most relevant characteristics of the electrical installation are taken into

account, such as typology, power demand, sensitivity to power interruptions,

Connection to the utility network


MV circuit configuration
Configurations of LV circuits
Backup generators
Presence of uninterruptible power supply (UPS) .

Commissioning tests of protection relays at site (before set to work).

Installation of protection relays

Installation of protection relays at site creates a number of possibilities for errors in


the implementation of the scheme to occur. Even if the scheme has been
thoroughly tested in the factory, wiring to the CTs and VTs on site may be incorrectly
carried out, or the CTs/VTs may have been incorrectly installed.

The impact of such errors may range from simply being a nuisance (tripping occurs
repeatedly on energisation, requiring investigation to locate and correct the errors) through
to failure to trip under fault conditions, leading to major equipment damage, disruption to
supplies and potential hazards to personnel.

The strategies available to remove these risks are many, but all involve some kind
of testing at site. Commissioning tests at site are therefore invariably performed
before protection equipment is set to work. The aims of commissioning tests are:

1. To ensure that the equipment has not been damaged during transit or installation
2. To ensure that the installation work has been carried out correctly
3. To prove the correct functioning of the protection scheme as a whole
The tests carried out will normally vary according to the protection scheme

involved, the relay technology used, and the policy of the client. In many cases, the

tests actually conducted are determined at the time of commissioning by mutual

agreement between the clients representative and the commissioning team.

The following tests are invariably carried out, since the protection scheme will
not function correctly if faults exist.

Wiring diagram check, using circuit diagrams showing all the reference numbers of the
interconnecting wiring
General inspection of the equipment, checking all connections, wires on relays
terminals, labels on terminal boards, etc.
Insulation resistance measurement of all circuits [details]
Perform relay self-test procedure and external communications checks on
digital/numerical relays [details]
Test main current transformers
Polarity check
Magnetisation Curve
Test main voltage transformers
Polarity check
Ratio check
Phasing check
Check that protection relay alarm/trip settings have been entered correctly [details]
Tripping and alarm circuit checks to prove correct functioning
In addition, the following checks may be carried out, depending on the factors noted
above (not covered in this technical article):
Secondary injection test on each relay to prove operation at one or more setting values
Primary injection tests on each relay to prove stability for external faults and to
determine the effective current setting for internal faults (essential for some types of
electromechanical relays)
Testing of protection scheme logic

Insulation resistance tests

All the deliberate earth connections on the wiring to be tested should first be removed,
for example earthing links on current transformers, voltage transformers and
DC supplies. Some insulation testers generate impulses with peak voltages
exceeding 5kV. In these instances any electronic equipment should be disconnected
while the external wiring insulation is checked.
The insulation resistance should be measured to earth and between electrically

separate circuits. The readings are recorded and compared with subsequent routine

tests to check for any deterioration of the insulation.

The insulation resistance measured depends on the amount of wiring involved, its

grade, and the site humidity. Generally, if the test is restricted to one cubicle, a reading

of several hundred megohms should be obtained. If long lengths of site wiring are

involved, the reading could be only a few megohms.

Protection relay self-test procedure

Digital and numerical relays will have a self-test procedure that is detailed in the
appropriate relay manual. These tests should be followed to determine if the relay is
operating correctly.

This will normally involve checking of the relay watchdog circuit, exercising all

digital inputs and outputs and checking that the relay analogue inputs are within

calibration by applying a test current or voltage.

For these tests, the relay outputs are normally disconnected from the remainder of the
protection scheme, as it is a test carried out to prove correct relay, rather than
scheme, operation.
To shorten
testing and commissioning times of SIPROTEC relays, extensive test and diagnostic
functions are available to the user in DIGSI 5

Unit protection schemes involve relays that need to communicate with each
other. This leads to additional testing requirements. The communications path
between the relays is tested using suitable equipment to ensure that the path is
complete and that the received signal strength is within specification. Numerical relays
may be fitted with loopback test facilities that enable either part of or the entire
communications link to be tested from one end.

After completion of these tests, it is usual to enter the relay settings required. This
can be done manually via the relay front panel controls, or using a portable PC and
suitable software.

Whichever, method is used, a check by a second person that the correct settings have
been used is desirable, and the settings recorded. Programmable scheme logic that is
required is also entered at this stage.
SIPRO
TEC relay wiring test editor for monitoring and testing of binary inputs, binary
outputs and LED (click to expand)

Go back to Commissioning tests

Current transformer tests

The following tests are normally carried out prior to energisation of the main circuits :
checking of polarity and current transformer magnetisation curve.
Polarity checks.

Each current transformer should be individually tested to verify that the primary and
secondary polarity markings are correct (see Figure 1).

The ammeter connected to the secondary of the current transformer should be a


robust moving coil, permanent magnet, centre-zero type. A low voltage battery is used,
via a single-pole push-button switch, to energise the primary winding. On closing the
push-button, the DC ammeter, A, should give a positive flick and on opening, a
negative flick.

Figure 1 Current
transformer polarity check

Go back to Commissioning tests

Checking of magnetisation curve

Several points should be checked on each current transformer magnetisation


curve. This can be done by energising the secondary winding from the local mains
supply through a variable auto-transformer while the primary circuit remains open. See
Figure 2.

The characteristic is measured at suitable intervals of applied voltage, until the magnetising
current is seen to rise very rapidly for a small increase in voltage. This indicates the
approximate knee-point or saturation flux level of the current transformer.
The magnetising current should then be recorded at similar voltage intervals as it is
reduced to zero.

Figure 2 Testing current transformer magnetising curve

Care must be taken that the test equipment is suitably rated. The short-time
current rating must be in excess of the CT secondary current rating, to allow for
measurement of the saturation current. This will be in excess of the CT secondary
current rating. As the magnetising current will not be sinusoidal, a moving iron or
dynamometer type ammeter should be used.

It is often found that current transformers with secondary ratings of 1A or less have a knee-
point voltage higher than the local mains supply. In these cases, a step-up interposing
transformer must be used to obtain the necessary voltage to check the magnetisation curve.

Go back to Commissioning tests

Voltage transformer tests


Voltage transformers require testing for polarity, ratio and phasing.

Polarity check of voltage transformer

The voltage transformer polarity can be checked using the method for CT polarity
tests. Care must be taken to connect the battery supply to the primary winding, with
the polarity ammeter connected to the secondary winding. If the voltage transformer is
of the capacitor type, then the polarity of the transformer at the bottom of the capacitor
stack should be checked.

Go back to Commissioning tests

Ratio check of VT

This check can be carried out when the main circuit is first made live. The voltage
transformer secondary voltage is compared with the secondary voltage shown on the
nameplate.

Na
mplate of a single phase voltage transformer (photo credit: emadrlc.blogspot.com)
Go back to Commissioning tests

Phasing check of VT

The secondary connections for a three-phase voltage transformer or a bank of three


single-phase voltage transformers must be carefully checked for phasing. With the
main circuit alive, the phase rotation is checked using a phase rotation meter
connected across the three phases, as shown in Figure 3 below.

Provided an existing proven VT is available on the same primary system, and that
secondary earthing is employed, all that is now necessary to prove correct phasing is
a voltage check between, say, both A phase secondary outputs. There should be
nominally little or no voltage if the phasing is correct.

However, this test does not detect if the phase sequence is correct, but the phases are
displaced by 120o from their correct position, i.e. phase A occupies the position of phase C or
phase B in Figure 3.

This can be checked by removing the fuses from phases B and C (say) and measuring
the phase-earth voltages on the secondary of the VT. If the phasing is correct, only
phase A should be healthy, phases B and C should have only a small residual voltage.
Figure 3
Voltage transformer phasing check

Correct phasing should be further substantiated when carrying out on load tests
on any phase-angle sensitive relays, at the relay terminals. Load current in a known
phase CT secondary should be compared with the associated phase to neutral VT
secondary voltage.
The phase angle between them should be measured, and should relate to the

power factor of the system load.

If the three-phase voltage transformer has a broken-delta tertiary winding, then a


check should be made of the voltage across the two connections from the broken
delta VN and VL, as shown in Figure 3 above. With the rated balanced three- phase
supply voltage applied to the voltage transformer primary windings, the broken-delta
voltage should be below 5V with the rated burden connected.

Go back to Commissioning tests

Protection relay setting checks (alarm and trip settings)

At some point during commissioning, the alarm and trip settings of the relay
elements involved will require to be entered and/or checked. Where the complete
scheme is engineered and supplied by a single contractor, the settings may already
have been entered prior to despatch from the factory, and hence this need not be
repeated.

The method of entering settings varies according to the relay technology used.
For electromechanical and static relays , manual entry of the settings for each relay
element is required. This method can also be used for digital/numerical relays.

However, the amount of data to be entered is much greater, and therefore it is usual to use
appropriate software, normally supplied by the manufacturer, for this purpose. The
software also makes the essential task of making a record of the data entered much easier.

The maximum allowable step potential is 5,664V, which exceeds the step
voltage calculated above and the earthing system passes the step potential
criteria. Having passed both touch and step potential criteria, we can
conclude that the earthing system is safe. Once the data has been entered, it
should be checked for compliance with the recommended settings as calculated from
the protection setting study. Where appropriate software is used for data entry, the
checks can be considered complete if the data is checked prior to download of the
settings to the relay.

Otherwise, a check may required subsequent to data entry by inspection and


recording of the relay settings, or it may be considered adequate to do this at the time
of data entry. The recorded settings form an essential part of the commissioning
documentation provided to the client.

FAULT CURRENT COMPUTATION USING SEQUENCE NETWORKS


In this section we shall demonstrate the use of sequence networks in the calculation of fault currents
using sequence network through some examples.
Example 8.4

Consider the network shown in Fig. 8.10. The system parameters are given below

Generator G : 50 MVA, 20 kV, X" = X1 = X2 = 20%, X0 = 7.5%

Motor M : 40 MVA, 20 kV, X" = X1 = X2 = 20%, X0 = 10%, Xn = 5%

Transformer T1 : 50 MVA, 20 kV /110 kVY, X = 10%

Transformer T2 : 50 MVA, 20 kV /110 kVY, X = 10%

Transmission line: X1 = X2 = 24.2 , X0 = 60.5

We shall find the fault current for when a (a) 1LG, (b) LL and (c) 2LG fault occurs at bus-2.

Fig. 8.10 Radial power system of Example 8.4.

Let us choose a base in the circuit of the generator. Then the per unit impedances of the generator are:

The per unit impedances of the two transformers are

The MVA base of the motor is 40, while the base MVA of the total circuit is 50. Therefore the per unit
impedances of the motor are

For the transmission line

Therefore
Example 8.5

Let us now assume that a 2LG fault has occurred in bus-4 instead of the one in bus-2. Therefore

Also we have

Hence

per unit

Also

per unit

per unit

Therefore the fault currents flowing in the line are

We shall now compute the currents contributed by the generator and the motor to the fault. Let us
denote the current flowing to the fault from the generator side by Ig , while that flowing from the motor
by Im . Then from Fig. 8.11 using the current divider principle, the positive sequence currents contributed
by the two buses are

per unit
per unit

Similarly from Fig. 8.12, the negative sequence currents are given as

per unit

per unit

Finally notice from Fig. 8.13 that the zero sequence current flowing from the generator to the fault is 0.
Then we have

per unit

Therefore the fault currents flowing from the generator side are

and those flowing from the motor are

It can be easily verified that adding Ig and Im we get If given above.

In the above two examples we have neglected the phase shifts of the Y/ transformers. However
according to the American standard, the positive sequence components of the high tension side lead
those of the low tension side by 30 , while the negative sequence behavior is reverse of the positive
sequence behavior. Usually the high tension side of a Y/ transformer is Y-connected. Therefore as we
have seen in Fig. 7.16, the positive sequence component of Y side leads the positive sequence
component of the side by 30 while the negative sequence component of Y side lags that of the side
by 30 . We shall now use this principle to compute the fault current for an unsymmetrical fault.
Let us do some more examples.

Example 8.6

Let us consider the same system as given in Example 8.5. Since the phase shift does not alter the zero
sequence, the circuit of Fig. 8.13 remains unchanged. The positive and the negative sequence circuits
must however include the respective phase shifts. These circuits are redrawn as shown in Figs. 8.14 and
8.15.

Note from Figs. 8.14 and 8.15 that we have dropped the 3 vis--vis that of Fig. 7.16. This is because
the per unit impedances remain unchanged when referred to the either high tension or low tension side of
an ideal transformer. Therefore the per unit impedances will also not be altered.

Fig. 8.14 Positive sequence network of the power system of Fig. 8.10 including transformer
phase shift.

Fig. 8.15 Negative sequence network of the power system of Fig. 8.10 including transformer
phase shift.

Since the zero sequence remains unaltered, these currents will not change from those computed in
Example 8.6. Thus

and per unit

Now the positive sequence fault current from the generator Iga1 , being on the Y-side of the Y/
transformer will lead I ma1 by 30 . Therefore

per unit
per unit
Finally the negative sequence current I ga2 will lag I ma2 by 30 . Hence we have

per unit

per unit
Therefore

Also the fault currents flowing from the motor remain unaltered. Also note that the currents flowing into the
fault remain unchanged. This implies that the phase shift of the Y/ transformers does not affect the fault
currents.

Example 8.7
Let us consider the same power system as given in Example 1.2, the sequence diagrams of which are
given in Figs. 7.18 to 7.20. With respect to Fig. 7.17, let us define the system parameters as:

Generator G1 : 200 MVA, 20 kV, X" = 20%, X0 = 10%

Generator G2 : 300 MVA, 18 kV, X" = 20%, X0 = 10%

Generator G3 : 300 MVA, 20 kV, X " = 25%, X0 = 15%

Transformer T1 : 300 MVA, 220Y/22 kV, X = 10%

Transformer T2 : Three single-phase units each rated 100 MVA, 130Y/25 kV, X = 10%

Transformer T3 : 300 MVA, 220/22 kV, X = 10%

Line B-C : X1 = X2 = 75 , X0 = 100

Line C-D : X1 = X2 = 75 , X0 = 100

Line C-F : X1 = X2 = 50 , X0 = 75

Let us choose the circuit of Generator 3 as the base, the base MVA for the circuit is 300. The base
voltages are then same as those shown in Fig. 1.23. Per unit reactances are then computed as shown
below.

Generator G1 :
, X0 = 0.15
Generator G2 :
, X0 = 0.0656

Generator G3 : , X0 = 0.15

Transformer T1 :

Transformer T2 :

Transformer T3 :

Line B-C :
,

Line C-D :
,

Line C-F :
,

Neglecting the phase shifts of Y/ connected transformers and assuming that the system is unloaded, we
shall find the fault current for a 1LG fault at bus-1 (point C of Fig. 7.17).
From Figs. 7.18 and 7.19, we can obtain the positive and negative sequence Thevenin impedance at
point C as (verify)

X1 = X2 = j 0.2723 per unit

Similarly from Fig. 7.20, the Thevenin equivalent of the zero sequence impedance is

X0 = j 0.4369 per unit

Therefore from (8.7) we get

per unit

Then the fault current is Ifa = 3 Ifa0 = 3.0565 per unit.

Double- Line -to Ground Fault


The faulted segment for a 2LG fault is shown in Fig. 8.7 where it is assumed that the fault has occurred at
node k of the network. In this the phases b and c got shorted through the impedance Zf to the ground.
Since the system is unloaded before the occurrence of the fault we have the same condition as (8.8) for

(8.17)

the phase-a current. Therefore

Fig. 8.7 Representation of 2LG fault.

Also voltages of phases b and c are given by


(8.18)

(8.19)

Therefore

We thus get the following two equations from (8.19)

(8.20)
(8.21)

Substituting (8.18) and (8.20) in (8.21) and rearranging we get

(8.22)

Also since I fa = 0 we have

(8.23)

(8.24)

The Thevenin equivalent circuit for 2LG fault is shown in Fig. 8.8. From this figure we get

The zero and negative sequence currents can be obtained using the current divider principle as
(8.25)

(8.26)

Fig. 8.8 Thevenin equivalent of a 2LG fault.

Example 8.3
Let us consider the same generator as given in Examples 8.1 and 8.2. Let us assume that the generator
is operating without any load when a bolted 2LG fault occurs in phases b and c. The equivalent circuit for
this fault is shown in Fig. 8.9. From this figure we can write
Fig. 8.9 Equivalent circuit of the generator in Fig. 8.4 for a 2LG fault in phases b and c.

Combining the above three equations we can write the following vector-matrix form

Solving the above equation we get

Hence

We can also obtain the above values using (8.24)-(8.26). Note from Example 8.1 that

Then
Now the sequence components of the voltages are

Also note from Fig. 8.9 that

and Vb = Vc = 0. Therefore

which are the same as obtained before.

Line-to-Line Fault
The faulted segment for an L-L fault is shown in Fig. 8.5 where it is assumed that the fault has occurred at
node k of the network. In this the phases b and c got shorted through the impedance Zf . Since the system
is unloaded before the occurrence of the fault we have

(8.8)

Fig. 8.5 Representation of L-L fault.

Also since phases b and c are shorted we have


(8.9)

(8.10)

Therefore from (8.8) and (8.9) we have

We can then summarize from (8.10)

(8.11)

Therefore no zero sequence current is injected into the network at bus k and hence the zero sequence
remains a dead network for an L-L fault. The positive and negative sequence currents are negative of
each other.

Now from Fig. 8.5 we get the following expression for the voltage at the faulted point

(8.12)

(8.13)

Again

Moreover since I fa0 = I fb0 = 0 and I fa1 = - I fb2 , we can write


(8.14)

Therefore combining (8.12) - (8.14) we get

(8.15)

Equations (8.12) and (8.15) indicate that the positive and negative sequence networks are in parallel. The
sequence network is then as shown in Fig. 8.6. From this network we get

(8.16)

Fig. 8.6 Thevenin equivalent of an LL fault.

Example 8.2

Let us consider the same generator as given in Example 8.1. Assume that the generator is unloaded
when a bolted ( Zf = 0) short circuit occurs between phases b and c. Then we get from (8.9) I fb = - I fc .
Also since the generator is unloaded, we have I fa = 0. Therefore from (7.34) we get

Also since V bn = V cn , we can combine the above two equations to get

Then
We can also obtain the above equation from (8.16) as

Also since the neutral current I n is zero, we can write V a = 1.0 and

Hence the sequence components of the line voltages are

Also note that

which are the same as obtained before.

Single-Line-to-Ground Fault
Let a 1LG fault has occurred at node k of a network. The faulted segment is then as shown in Fig. 8.2
where it is assumed that phase-a has touched the ground through an impedance Zf . Since the system is
unloaded before the occurrence of the fault we have

(8.1)
Fig. 8.2 Representation of 1LG fault.

Also the phase-a voltage at the fault point is given by

(8.2)

(8.3)

From (8.1) we can write

Solving (8.3) we get

(8.4)

This implies that the three sequence currents are in series for the 1LG fault. Let us denote the zero,
positive and negative sequence Thevenin impedance at the faulted point
as Z kk0 , Z kk1 and Z kk2respectively. Also since the Thevenin voltage at the faulted phase is Vf we get three

(8.5)

sequence circuits that are similar to the ones shown in Fig. 7.7. We can then write

Then from (8.4) and (8.5) we can write

(8.6)

Again since
We get from (8.6)

(8.7)

The Thevenin equivalent of the sequence network is shown in Fig. 8.3.

Fig. 8.3 Thevenin equivalent of a 1LG fault.

Example 8.1
A three-phase Y-connected synchronous generator is running unloaded with rated voltage when a 1LG
fault occurs at its terminals. The generator is rated 20 kV, 220 MVA, with subsynchronous reactance of
0.2 per unit. Assume that the subtransient mutual reactance between the windings is 0.025 per unit. The
neutral of the generator is grounded through a 0.05 per unit reactance. The equivalent circuit of the
generator is shown in Fig. 8.4. We have to find out the negative and zero sequence reactances.

Fig. 8.4 Unloaded generator of Example 8.1.


Since the generator is unloaded the internal emfs are

Since no current flows in phases b and c, once the fault occurs, we have from Fig. 8.4

Then we also have

From Fig. 8.4 and (7.34) we get

Therefore

From (7.38) we can write Z1 = j ( Ls + Ms ) = j 0.225. Then from Fig. 7.7 we have

Also note from (8.4) that

Therefore from Fig. 7.7 we get


Comparing the above two values with (7.37) and (7.39) we find that Z 0 indeed is equal to j ( Ls - 2 Ms )
and Z2 is equal to j ( Ls + Ms ). Note that we can also calculate the fault current from (8.7) as

Introduction
The sequence circuits and the sequence networks developed in the previous chapter will now be used
for finding out fault current during unsymmetrical faults.

Three Types of Faults

Calculation of fault currents

Let us make the following assumptions:

The power system is balanced before the fault occurs such that of the three sequence networks
only the positive sequence network is active. Also as the fault occurs, the sequence networks are
connected only through the fault location.

The fault current is negligible such that the pre-fault positive sequence voltages are same at all
nodes and at the fault location.

All the network resistances and line charging capacitances are negligible.

All loads are passive except the rotating loads which are represented by synchronous machines.
Based on the assumptions stated above, the faulted network will be as shown in Fig. 8.1 where the
voltage at the faulted point will be denoted by Vf and current in the three faulted phases
are Ifa , I fb and I fc .

We shall now discuss how the three sequence networks are connected when the three types of faults
discussed above occur.

Fig. 8.1 Representation of a faulted segment.

Вам также может понравиться