Вы находитесь на странице: 1из 2

RHM International

TEL. +1 888 495 0008 E-MAIL INFO@RHMINTL.COM WWW.RHMINTL.COM

Onsite Power Transformer PD Measuring System


Through its RIF Bushings Built-In Sensing

RHM International can now offer its customers the ability to detect and measure in the field PD activity
in their operating transformers. This proprietary measurement system can only be used when RHM
International RIF bushings equipped with the Smart Measurement Terminal (SMT) are installed on the
transformer. A portable recording and display unit is then used to collect information.

Channel 3-7 Channels (Synchronous sampling)


Signal detecting sensitivity -80dB
PD signal sensitivity 5pC
Successive sampling or scheduled sampling
Working approach
(Upper computer configuration)
Working temperature -40C to 70C
Working humidity 0% to 95% (Non-condensing)
Power supply Battery
Battery life 12 h
Transmission method WIFI or RJ45 twisted pair cable

Benefits:
An easy way of checking for PD activity while a transformer is in-service
Reliable data acquisition
Low interference sensitivity
Provides PD localization by using the different bushings
A straightforward chain of measure: A large C2 capacitance integrated in the RIF bushing at
production time and brought out to a SMT is used to measure the transformers discharge. The portable
PD device collects and processes the high frequency discharge signals from the SMT. Diagnostic software
developed for the RHM measurement system provides the analysis and display.

RIF Bushing with SMT

Alternative Signal Collection Scheme


You can elect to order one RIF bushing with a permanent hard wire connection from the SMT to the
transformer control box as only one SMT PD sensor is required to detect PD activity in a transformer.
This scheme allows the customer to periodically check his transformer for PD activity from the
transformer control box with the transformer remaining in-service. If PD is detected and the customer
wants to pinpoint the area of the PD activity (and provided other RIF bushings with a SMT have being
installed) signals from other RIF bushing SMT PD sensors can be inputted to the portable PD detection
device. This however requires taking the transformer out of service to connect the additional test leads.

(1) LVN bushing equipped with SMT PD


sensor
(2) LV bushings equipped with SMT PD
sensor
(3) Transformer control cabinet
(4) RHM Internationals portable PD
measurement device
(5) Permanent hard wire connection from
bushing SMT to transformer control
cabinet
(6) Test lead connections from other RIF
bushing SMT PD sensors to portable PD
detection device
CONTACT US

Contact Us
RHM International Tel: +1 888 495 0008
280 Clark Road Fax: +1 617 608 0274
Brookline, MA 02445
USA
RHM International considers all inquiries worldwide
US

For any inquiries about the products and their availability, please call or email us at: info@rhmintl.com