0 FIRST ISSUE 10-12-2012

REV. DESCRIPTION DATE

DATE DEPARTMENT NAME SIGNATURE


ISSUED 10-12-2012 IPD Erbizzi L.
CHECKED 10-12-2012 AVV/IPD Sardano R./Volpi G.
APPROVED 10-12-2012 GCPM Casero C.

WEST DELTA ELECTRICITY PRODUCTION


COMPANY
ABU QIR THERMAL POWER PLANT

2 x 650 MW GAS/OIL FIRED UNITS

BOILER PERFORMANCE TEST REPORT


UNIT #6

JOB NO. DOCUMENT NO. REV.


POWER GENERATION ENGINEERING AND
SERVICES COMPANY
0

PROJECT CLIENT

ABU QIR WEST DELTA ELECTRICITY PRODUCTION


THERMAL POWER PLANT - 2 X650 MW COMPANY
JOB NO. DEPARTMENT DOC TYPE

3039 V1-V2 AVV

BOILER PERFORMANCE TEST REPORT


Ansaldo Caldaie S.p.A. reserves all UNIT # 6
rights on this document that can not be
reproduced in any part without its written
consent
DOCUMENT NO. REVISION SHEET OF

30390-A-M1008 0 1 73

Informazioni strettamente riservate di propriet di Ansaldo Caldaie s.p.a. - Da non utilizzare per scopi diversi da quelli per cui sono state
fornite.
Confidential information, property of Ansaldo Caldaie s.p.a. Not to be used for any purpose other than that for which it is supplied.
Titolo Identificativo Rev. Pagina Di
title document no. rev. Page Of
ABU QIR THERMAL POWER PLANT 0 2 73
2 x 650 MW GAS / OIL FIRED UNIT 30390-A-M1008

TABLE OF CONTENTS

1. SCOPE AND OBJECT


2. GENERAL
3. RESULT SUMMARY
3.1 BOILER CAPACITY
3.2 TEMPERATURES AT BOILER BATTERY LIMIT
3.2.1 REHEATER PERFORMANCE EVALUATION
3.3 REHEATER PRESSURE DROP
3.4 MAXIMUM MAIN STEAM PRESSURE DROP
3.5 GUARANTEED EFFICIENCY
3.5.1 EFFICIENCY AT BMCR GAS FIRING
3.6 AUXILIARY CONSUMPTIONS
3.7 A.H. LEAKAGE
3.8 EMISSIONS
3.8.1 GAS FIRING
4. CONCLUSION
5. ATTACHMENT 1: RAW DATA
5.1.1 TEST#1
5.1.2 TEST#2
6. ATTACHMENT 2: FUEL GAS ANALYSIS
6.1.1 TEST #1
6.1.2 TEST #2
7. ATTACHMENT 3: CALCULATION SHEETS
7.1.1 TEST #1
7.1.2 TEST #2
Titolo Identificativo Rev. Pagina Di
title document no. rev. Page Of
ABU QIR THERMAL POWER PLANT 0 3 73
2 x 650 MW GAS / OIL FIRED UNIT 30390-A-M1008

1. Scope and object


Object of this document is to provide a comprehensive report concerning the performance
test results of the steam generating unit 6.

2. General
The performance guarantee test has been carried out with the following time schedule in
accordance with the Boiler performance test procedure 30390-A-M1007 Rev. 03.

Unit Case Fuel Load Date Time start Time end


6 2 GAS 100% MCR* 15/11/2012 10.30 12.00
6 2 GAS 100% MCR* 15/11/2012 12.00 13.30
6 3 GAS BMCR** 17/11/2012 15.45 16.10
6 7 GAS 25% MCR*** 16/11/2012 10.30 12.45
NOTES:
* Test duration has been reduced as per client request
** BMCR test duration has been reduced due to client request
*** Done at 30% according to client request since 25% load would have required the use
of:
- one electrical pump instead of the turbo pump
- level control at one element instead of three

The guarantees have been fulfilled with good margins, except than for auxiliary power
consumption, that is in any case well compensated by the other boiler over performances
(details are reported in the following chapters of the present document).

In particular this report includes:


1. Performance test result summary
2. Data collected during tests
3. Calculation of guaranteed values
4. Post test key observations
Titolo Identificativo Rev. Pagina Di
title document no. rev. Page Of
ABU QIR THERMAL POWER PLANT 0 4 73
2 x 650 MW GAS / OIL FIRED UNIT 30390-A-M1008

3. Result summary
3.1 Boiler capacity
Contract Load
Guarantee Comment Units Guarantee Meas. Comments
Par. No. [Mwe]
Minimum continuous main steam
2.1 Boiler capacity (case 2) 658.2 generating capacity at Turbine kg/s 544.9 545.8
Generator 100% load
Minimum continuous main steam Not a
- Boiler capacity (case 3) 688.0 kg/s 574.3 578.4
generating capacity at BMCR guarantee

During BMCR test there was no limitation in the boiler itself.

Below are shown the thermal loads of case 2 and 3 tests. Both cases show higher thermal
load than design (Boiler Heat Output or BHO).

Design Test Test Electrical


CASE BHO [MW] BHO [MW] Load [MWe]
2 1460.9 1480.7 658.2
3 1517.0 1552.1 688

BMCR load!
Titolo Identificativo Rev. Pagina Di
title document no. rev. Page Of
ABU QIR THERMAL POWER PLANT 0 5 73
2 x 650 MW GAS / OIL FIRED UNIT 30390-A-M1008

3.2 Temperatures at boiler battery limit


Contract Load
Guarantee Comment Units Guarantee Meas.
Par. No. [Mwe]
Minimum average main steam
Temperature at boiler battery
2.2 658.2 temperature when operating at C 541.7 542.1
limit (case2)
100% TG load - Gas firing
Minimum average RH outlet
Temperature at boiler battery
2.3 658.2 temperature when operating at C 567 566.0 *
limit (case2)
100% TG load - Gas firing

* Regarding to RH temperature please consider that Cold Reheater Temperature was


5.2C lower than design

In order to give an idea of the better performance we have converted the credits in
electrical power for MCR test load (gas firing).

For this purpose correction curves from Steam Turbine manufacturer has been used for
evaluating the corresponding kWe credits on ST side:

Gas Firing MCR


Power Credit
Design Test MCR with ST Corr.
Curves
[C] [C] [kWe]
Main steam Temp. out 541.7 542.1 157
Reheater steam Temp. out 567 566 * 1701 *

* See analysis in Par. 3.2.1 for correction on RH outlet temperature based on Cold RH inlet
Temperature, showing the fulfilment of the guaranteed value.
Titolo Identificativo Rev. Pagina Di
title document no. rev. Page Of
ABU QIR THERMAL POWER PLANT 0 6 73
2 x 650 MW GAS / OIL FIRED UNIT 30390-A-M1008

Gas Firing
BMCR *
Design Test BMCR
[C] [C]
Main steam Temp. out 541.8 539
Reheater steam Temp. out 565.8 564
* Steam Temperatures at case 3 were slightly below the guaranteed value, but it has to be
considered that:

Boiler Heat Output was higher than design one (measured 1552.1 MW vs. design
1517.0 MW)
The test duration was reduced, thus it was not possible to reach a stable load with
guaranteed parameters
Titolo Identificativo Rev. Pagina Di
title document no. rev. Page Of
ABU QIR THERMAL POWER PLANT 0 7 73
2 x 650 MW GAS / OIL FIRED UNIT 30390-A-M1008

3.2.1 Reheater performance evaluation


During tests at MCR, boundary conditions of reheater coils were off design; indeed cold
reheater temperature was well below than design.
The following analysis is made to evaluate the enhance of electrical power credit due to
higher RH coils heat absorption.
In order to understand the real credit we have to consider the following RH conditions:
1. Cold reheater flow
2. Cold reheater temperature
3. Overall reheater absorption

The cold reheater flow during test was higher than design:
Design Test
Cold reheater flow [kg/s] 459.53 460.3

Cold reheater temperature during the test was 5.2C lower than design as shown in the
below table:
Design Test
Cold reheater temperature [C] 337.2 332

In the below table is shown the comparison between design and test RH power:
Design Test
Cold reheater temperature [C] 337.2 332.0
Cold reheater pressure [bara] 41.2 38.2
Cold reheater flow [kg/s] 459.5 460.3
Cold reheater enthalpy [kJ/kg] 3058.1 3052.3

Hot reheater temperature [C] 567.0 566.0


Hot reheater pressure [bara] 39.25 36.9
Hot reheater flow [kg/s] 459.53 460.3
Hot reheater enthalpy [kJ/kg] 3599.8 3599.7

Ratio
Reheater power absorbtion [MW] 248.94 251.95 101.2
Titolo Identificativo Rev. Pagina Di
title document no. rev. Page Of
ABU QIR THERMAL POWER PLANT 0 8 73
2 x 650 MW GAS / OIL FIRED UNIT 30390-A-M1008

During tests the heat absorption of RH coils was 1.2% higher than design.
As suggested by ASME PTC 4 paragraph 5.18.13 the temperature of HRH is considered
higher than guaranteed if tested RH heat absorption is higher than design.
In the below table the test HRH temperature has been changed in order to have the same
heat absorption as in design condition.
MCR
Design Corr. Test
Cold reheater temperature [C] 337.2 332.0
Cold reheater pressure [bara] 41.2 38.2
Cold reheater flow [kg/s] 459.5 460.3
Cold reheater enthalpy [kJ/kg] 3058.1 3052.3

Hot reheater temperature [C] 567.0 563.15 566.02 - 563.15 = 2.87


Hot reheater pressure [bara] 39.3 36.9
Hot reheater flow [kg/s] 459.5 460.3
Hot reheater enthalpy [kJ/kg] 3599.8 3593.1

Reheater power absorbtion [MW] 248.94 248.94


563.15C is the temperature of Hot Reheater that should be assumed as guaranteed
Temperature corresponding to the test Cold Reheat Temperature

Test Hot RH T = 566.0 > 563.15, therefore the guarantee has been fulfilled.

Nevertheless the increased flow through the GRF helped to enhance RH power absorption
leading to a HRH steam credit equal to 2.87C.

In order to give an idea of the better overall performance this temperature credit has been
converted into equivalent electrical power credits (kWe) on ST side by the means of
correction curves from Steam Turbine manufacturer:

Power Credit
with ST Corr.
Curves
C [kWe]
HRH temperature credit 2.87 1701
Titolo Identificativo Rev. Pagina Di
title document no. rev. Page Of
ABU QIR THERMAL POWER PLANT 0 9 73
2 x 650 MW GAS / OIL FIRED UNIT 30390-A-M1008

3.3 Reheater pressure drop

Contract Load Meas.


Guarantee Comment Units Guarantee Delta
Par. No. [Mwe] Corrected

Maximum Reheater steam


2.4 658.2 100% TG bar 1.9 0.67 1.23
pressure drop (case 2)

Tests are showing lower RH pressure drop than design. The above value has been
corrected to design condition (mass flow and density).

In order to give an idea of the better overall performance this credit has been converted
into equivalent electrical power credits (kWe) on ST side by the means of correction
curves from Steam Turbine manufacturer:

Power Credit
Design Test MCR with ST Corr.
Curves
[bar] [bar] [kWe]
Reheater pressure drop 1.90 0.67 1660

Please note that this credit itself is big enough to balance the entire over absorption in
auxiliary power, even the uncorrected value (Ref. Par. 3.6).
Titolo Identificativo Rev. Pagina Di
title document no. rev. Page Of
ABU QIR THERMAL POWER PLANT 0 10 73
2 x 650 MW GAS / OIL FIRED UNIT 30390-A-M1008

3.4 Maximum main steam pressure drop

Contract Load Measured


Par. No.
Guarantee Comment Units Guarantee
[Mwe] Corrected
From feedwater inlet terminal
Maximum main steam
- 658.2 point to SH outlet (excluding bar 12 11.62
pressure drop (case 3)
static head) at BMCR

Tests are showing lower main steam pressure drop than design. The above value has
been corrected to design condition (mass flow and density).
Titolo Identificativo Rev. Pagina Di
title document no. rev. Page Of
ABU QIR THERMAL POWER PLANT 0 11 73
2 x 650 MW GAS / OIL FIRED UNIT 30390-A-M1008

3.5 Guaranteed Efficiency

Contract Load Meas.


Guarantee Comment Units Guarantee Meas. Delta
Par. No. [Mwe] Corrected

Efficiency firing gas


2.5 658.2 100% TG % 86.73 87.25 87.26 0.53
(case 2)

MCR load is showing an higher efficiency value.


In order to give an idea of the better overall performance this credit has been converted
into equivalent electrical power credits (kWe) according to plant balance calculations:

Power Credit
Design Test MCR Balance Calc
[%] [%] [kWe]
Efficiency (corrected) 86.73 87.26 3962

Also in this case please note that this credit itself is more than enough for balancing the
entire over absorption in auxiliary power, even the uncorrected value (Ref. Par. 3.6).

Test #1 Test #2
measured measured
[%] [%]
Efficiency 87.25 87.25

The table is showing how the measured value is exactly the same for both the test carried
out. This means in principle that:

Performance test instruments were sufficient in number and well calibrated


The boiler was in real steady state
Boiler control system is well tuned
Titolo Identificativo Rev. Pagina Di
title document no. rev. Page Of
ABU QIR THERMAL POWER PLANT 0 12 73
2 x 650 MW GAS / OIL FIRED UNIT 30390-A-M1008

Test MCR Test MCR


with design with Test
fuel Fuel
[%] [%]
Efficiency (corrected) 87.26 87.26

Please note that, since the test fuel gas analysis was in line with design one, the efficiency
resulting from Design Fuel and that from Test Fuel are exactly the same figure.

3.5.1 Efficiency at BMCR Gas Firing

Even if not guaranteed below is shown the calculation for as tested efficiency at BMCR
firing gas.

Load
Description Comment Units Espected Meas. Delta
[Mwe]

As Tested Efficiency
firing gas at BMCR 688.0 105% TG % 86.69 87.19 0.50
(case 3)
Titolo Identificativo Rev. Pagina Di
title document no. rev. Page Of
ABU QIR THERMAL POWER PLANT 0 13 73
2 x 650 MW GAS / OIL FIRED UNIT 30390-A-M1008

3.6 Auxiliary consumptions


Contract Load Measured
Guarantee Comment Units Guarantee Meas. Delta
Par. No. [Mwe] Corrected

Total auxiliary power


2.9 658.2 100% TG kW 7500 8818 8283 783
consumption (case 2)

Hereafter the auxiliary power consumption break up is reported.


Guarantee Measured
Item Units Delta Test#1 Test#2
Value Value

Forced draft fan motor power - Left kW 3290 3449 159 3455 3444

Forced draft fan motor power - Right kW 3290 3723 433 3728 3718

Recirculating fan motor power - Left kW 410 810 400 812 809

Recirculating fan motor power - Right kW 410 775 365 777 773

Other Auxiliary power absorption kW 100 61 -39 61 61

As shown in above tables the measured power consumption is higher than the guaranteed
value, but we would like to highlight the following aspects.
Agreed correction curves (Ref. Boiler performance test procedure 30390-A-M1007
Rev. 03) reduce the measured value from 8818 kW to 8283 kW due to:
- 54 kW on FD Fans power absorption due to higher heat to steam
- 481 kW on GR Fans power absorption due to lower CRH steam
temperature
Please note that, according to Par. 4, the greater power consumption is more than
balanced by boiler over performances
Titolo Identificativo Rev. Pagina Di
title document no. rev. Page Of
ABU QIR THERMAL POWER PLANT 0 14 73
2 x 650 MW GAS / OIL FIRED UNIT 30390-A-M1008

3.7 A.H. Leakage

Contract Load
Guarantee Comment Units Guarantee Measured
Par. No. [Mwe]
Maximum regenerative air
3.4 658.2 100% TG % 8 6.72
heater leakage (case 2, 10)

The A.H leakage was lower than guaranteed.


Titolo Identificativo Rev. Pagina Di
title document no. rev. Page Of
ABU QIR THERMAL POWER PLANT 0 15 73
2 x 650 MW GAS / OIL FIRED UNIT 30390-A-M1008

3.8 Emissions
3.8.1 Gas firing
Contract Load
Par. No.
Guarantee Comment Units Guarantee Meas.
[Mwe]
3
NOX flue gas emission limits when mg/Nm
221.4 At 25% TG - gas firing 320 213
firing natural gas (case 1) @ 3% O2
3
CO flue gas emission limits when mg/Nm
firing natural gas (case 1)
221.4 At 25% TG - gas firing 250 0
@ 3% O2
3
NOX flue gas emission limits when mg/Nm
658 At 100% TG - gas firing 320 290
firing natural gas (case 4) @ 3% O2
3.7 3
CO flue gas emission limits when mg/Nm
firing natural gas (case 4)
658 At 100% TG - gas firing 250 58
@ 3% O2
3
NOX flue gas emission limits when mg/Nm
688.0 At BMCR TG - gas firing 320 310
firing natural gas (case 5) @ 3% O2
3
CO flue gas emission limits when mg/Nm
firing natural gas (case 5)
688.0 At BMCR TG - gas firing 250 147
@ 3% O2

GAS FIRING
NOx [mg/Nm3 @ 3% O2]

350
GUARANTEED LIMIT
300
NOx [mg/Nm3 @ 3% O2]

250

200
310
150 290
213
100

50

0
25 100 BMCR

Load [%]

NOx emissions at various loads firing Natural Gas


Titolo Identificativo Rev. Pagina Di
title document no. rev. Page Of
ABU QIR THERMAL POWER PLANT 0 16 73
2 x 650 MW GAS / OIL FIRED UNIT 30390-A-M1008

GAS FIRING
CO [mg/Nm3 @ 3% O2]

300

250 GUARANTEED LIMIT


CO [mg/Nm3 @ 3% O2]

200
147
150

100
58
50
0
0
25 100 BMCR

Load [%]

CO emissions at various loads firing Natural Gas

Analysers station
Titolo Identificativo Rev. Pagina Di
title document no. rev. Page Of
ABU QIR THERMAL POWER PLANT 0 17 73
2 x 650 MW GAS / OIL FIRED UNIT 30390-A-M1008

Flue gas sampling at AH inlet

Flue gas sampling detail: mixing bottles at AH outlet


Titolo Identificativo Rev. Pagina Di
title document no. rev. Page Of
ABU QIR THERMAL POWER PLANT 0 18 73
2 x 650 MW GAS / OIL FIRED UNIT 30390-A-M1008

4. Conclusion
The above analysis shows the good behavior of the entire boiler package:

Emission levels are below the guaranteed values


RH pressure drop is much lower than guaranteed
Efficiency is about 0.5% more than guaranteed
Steam temperatures fulfill the design and contractual requirements

As shown above the over-performances of the boiler have been converted in electrical
power credit in order to show with expressive figures the obtained benefit.
This has been done by the means of technical considerations in two ways:

a. RH pressure drop: correction curves from Steam Turbine manufacturer has been
used for evaluating the corresponding kWe credits on ST side
b. Boiler Efficiency: plant balance calculations

Power Credit
Technical
[kWe]
Reheater pressure Drop 1660 a
Efficiency 3962 b
Total 5622

a
Calculated from ST correction curves
b
Calculated from plant balance considerations
Titolo Identificativo Rev. Pagina Di
title document no. rev. Page Of
ABU QIR THERMAL POWER PLANT 0 19 73
2 x 650 MW GAS / OIL FIRED UNIT 30390-A-M1008

Regarding to auxiliary power consumption, by applying the corrections foreseen in Boiler


performance test procedure 30390-A-M1007 Rev. 03 (see details at Par. 3.6):

FDF power absorption due to higher heat to steam


GRF power absorption due to lower Cold Reheater Temperature

The overall under performance is 783 kW, as shown in detail in the below table.

FDF GRF Measured


Guarantee Units Guarantee Measured Delta
correction correction Corrected

Total auxiliary power


kW 7500 8818 - 54 - 481 8283 783
consumption (case 2)

It is clear that the over performances given by the boiler itself are much greater than the
underperformance of Fans (approx. 7 times bigger).

By subtracting the overall credits to the auxiliary power over absorption, the situation is as
reported:
Total power absorption underperformance [kWe] 783 -
Total power credits [kWe] 5662 * =
Total equivalent power over absorption [kWe] - 4879

* Power Credit evaluated on technical considerations

Where the negative sign means that the Fans under performance is much more than
compensated by the good boiler behavior.
Obviously the negative shortfall means a positive result for AC.

In the next page the overall test results are reported.


title
FUNCTIONAL GUARANTEES Titolo

Contract Guarantee Measured Corrected


Par. No.
Guarantee Comment Units Test#1 Test#2
Value value Value
Minimum continuous main steam generating
2.1 Boiler capacity (case 2) kg/s 544.9 545.8 - 546.0 545.7
capacity at Turbine Generator 100% load
Temperature at boiler battery limit Minimum average main steam temperature
2.2 C 541.7 5 542.1 - 541.7 542.4
(case2,10) when operating at 100% TG load
Temperature at boiler battery limit Minimum average RH outlet temperature when See Page
2.3 C 567 5 566.0 565.7 566.3
(case2,10) operating at 100% TG load 10
Maximum Reheater steam pressure drop
2.4 When operating at 100% TG load bar 1.9 0.67 - 0.67 0.67
(case 2)

2.5 Efficiency firing gas (case 2) When operating at 100% TG load % 86.73 87.25 87.26 87.25 87.25

When operating at 100% TG load; Calculation


2 x 650 MW GAS / OIL FIRED UNIT

- Efficiency firing gas (case 2) % 86.73 87.26 87.26 87.26 87.26


ABU QIR THERMAL POWER PLANT

with Gas composition at Test condition

2.6 Total auxiliary power consumption (case 2) When operating at 100% TG load kW 7500 8818 8283 8832 8804

Maximum average superheater spray water


2.7 When operating at 100% TG load kg/s 90 52.9 - 53 53
flow (case 2)

EQUIPMENT GUARANTEES
document no.
Identificativo

Contract Guarantee Measured Corrected


Par. No.
Guarantee Comment Units Test#1 Test#2
Value value Value

3.3 RH spray water flow From 25% of TG to BMCR kg/s 0 0 - 0 0


30390-A-M1008

Maximum regenerative air heater leakage


3.4 100% TG % 8 6.72 - 6.48 6.96
(case 2 and 10)
NOX flue gas emission limits when firing mg/Nm3
From 25% TG to BMCR 320 290 - 289 292
natural gas @ 3% O2
rev.

3.7
Rev.

CO flue gas emission limits when firing mg/Nm3


From 25% TG to BMCR 250 58 - 56 61
natural gas @ 3% O2
Maximum main steam pressure drop (case From feedwater inlet terminal point to SH
Page

bar 12 11.72 -
3) outlet (excluding static head) at BMCR
20
Pagina
Of
Di

73
Titolo Identificativo Rev. Pagina Di
title document no. rev. Page Of
ABU QIR THERMAL POWER PLANT 0 21 73
2 x 650 MW GAS / OIL FIRED UNIT 30390-A-M1008

The sky around Abu Qir is cleaner


Titolo Identificativo Rev. Pagina Di
title document no. rev. Page Of
ABU QIR THERMAL POWER PLANT 0 22 73
2 x 650 MW GAS / OIL FIRED UNIT 30390-A-M1008

5. Attachment 1: Raw data


5.1.1 Test#1
Averaged data computed from 10.30.04 - 15/11/12 to 12.00.11 - 15/11/12

ABU QIR ( PERFORMANCE TEST )

Test n. 1
Tag Description Units Values
Tam 1 humidity relative Ambient relative humidity % 63.3257555
Tam 2 Ambient Temperature Ambient temperature C 23.5432143
Barometric pressure Ambient pressure hPa 1017.92301
Ta 1 Air left upstr. AH Air temperature upstr. AH (A) RTD PT 100 0 - 250C C 34.7990369
Ta 2 Air left upstr. AH Air temperature upstr. AH (A) RTD PT 100 0 - 250C C 34.5400254
Ta 3 Air left upstr. AH Air temperature upstr. AH (A) RTD PT 100 0 - 250C C 34.5641319
Ta 4 Air right upstr. AH Air temperature upstr. AH (B) RTD PT 100 0 - 250C C 34.337742
Ta 5 Air right upstr. AH Air temperature upstr. AH (B) RTD PT 100 0 - 250C C 34.2058969
Ta 6 Air right upstr. AH Air temperature upstr. AH (B) RTD PT 100 0 - 250C C 34.1181459
Tgi 1 left. temp. AH (A) Flue gas temperature upstr. AH (A) Tc K " 0 - 500 C " C 350.577253
Tgi 2 left. temp. AH (A) Flue gas temperature upstr. AH (A) Tc K " 0 - 500 C " C 347.976129
Tgi 3 left. temp. AH (A) Flue gas temperature upstr. AH (A) Tc K " 0 - 500 C " C 352.068962
Tgi 4 left. temp. AH (A) Flue gas temperature upstr. AH (A) Tc K " 0 - 500 C " C 350.501331
Tgi 5 left. temp. AH (A) Flue gas temperature upstr. AH (A) Tc K " 0 - 500 C " C 349.96522
Tgi 6 left. temp. AH (A) Flue gas temperature upstr. AH (A) Tc K " 0 - 500 C " C 349.726257
Tgi 7 left. temp. AH (A) Flue gas temperature upstr. AH (A) Tc K " 0 - 500 C " C 352.145653
Tgi 8 left. temp. AH (A) Flue gas temperature upstr. AH (A) Tc K " 0 - 500 C " C 350.037379
Tgi 9 left. temp. AH (A) Flue gas temperature upstr. AH (A) Tc K " 0 - 500 C " C 349.17428
Tgi 10 left. temp. AH (A) Flue gas temperature upstr. AH (A) Tc K " 0 - 500 C " C 349.815627
Tgi 11 left. temp. AH (A) Flue gas temperature upstr. AH (A) Tc K " 0 - 500 C " C 353.764808
Tgi 12 left. temp. AH (A) Flue gas temperature upstr. AH (A) Tc K " 0 - 500 C " C 352.696675
Tgi 13 left. temp. AH (A) Flue gas temperature upstr. AH (A) Tc K " 0 - 500 C " C 352.099785
Tgi 14 left. temp. AH (A) Flue gas temperature upstr. AH (A) Tc K " 0 - 500 C " C 353.742548
Tgi 15 left. temp. AH (A) Flue gas temperature upstr. AH (A) Tc K " 0 - 500 C " C 354.201497
Tgi 16 left. temp. AH (A) Flue gas temperature upstr. AH (A) Tc K " 0 - 500 C " C 352.780978
Tgi 17 left. temp. AH (A) Flue gas temperature upstr. AH (A) Tc K " 0 - 500 C " C 349.522465
Tgi 18 left. temp. AH (A) Flue gas temperature upstr. AH (A) Tc K " 0 - 500 C " C 349.908703
Tgi 19 left. temp. AH (A) Flue gas temperature upstr. AH (A) Tc K " 0 - 500 C " C 352.095654
Tgi 20 left. temp. AH (A) Flue gas temperature upstr. AH (A) Tc K " 0 - 500 C " C 349.624236
Tgi 21 left. temp. AH (A) Flue gas temperature upstr. AH (A) Tc K " 0 - 500 C " C 353.474431
Tgi 22 left. temp. AH (A) Flue gas temperature upstr. AH (A) Tc K " 0 - 500 C " C 352.571572
Tgi 23 left. temp. AH (A) Flue gas temperature upstr. AH (A) Tc K " 0 - 500 C " C 349.923709
Tgi 24 left. temp. AH (A) Flue gas temperature upstr. AH (A) Tc K " 0 - 500 C " C 350.89111
Tgo 1 left. temp. AH (A) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 107.945133
Tgo 2 left. temp. AH (A) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 112.620634
Tgo 3 left. temp. AH (A) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 114.786176
Tgo 4 left. temp. AH (A) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 117.363322
Tgo 5 left. temp. AH (A) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 102.232044
Tgo 6 left. temp. AH (A) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 108.602201
Tgo 7 left. temp. AH (A) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 107.73806
Tgo 8 left. temp. AH (A) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 116.41556
Tgo 9 left. temp. AH (A) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 102.264469
Tgo 10 left. temp. AH (A) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 107.610182
Tgo 11 left. temp. AH (A) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 111.450771
Tgo 12 left. temp. AH (A) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 115.124259
Tgo 13 left. temp. AH (A) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 101.592016
Tgo 14 left. temp. AH (A) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 107.300924
Tgo 15 left. temp. AH (A) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 111.861764
Tgo 16 left. temp. AH (A) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 117.419192
Tgo 17 left. temp. AH (A) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 98.4005854
Tgo 18 left. temp. AH (A) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 98.040221
Tgo 19 left. temp. AH (A) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 104.89939
Tgo 20 left. temp. AH (A) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 114.464411
Tgo 21 left. temp. AH (A) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 89.1856358
Tgo 22 left. temp. AH (A) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 89.2800445
Tgo 23 left. temp. AH (A) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 100.38429
Tgo 24 left. temp. AH (A) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 107.050341
Tgi 25 right. temp. AH (B) Flue gas temperature upstr. AH (B) Tc K " 0 - 500 C " C 347.114603
Tgi 26 right. temp. AH (B) Flue gas temperature upstr. AH (B) Tc K " 0 - 500 C " C 348.657314
Tgi 27 right. temp. AH (B) Flue gas temperature upstr. AH (B) Tc K " 0 - 500 C " C 349.514774
Tgi 28 right. temp. AH (B) Flue gas temperature upstr. AH (B) Tc K " 0 - 500 C " C 350.654871
Tgi 29 right. temp. AH (B) Flue gas temperature upstr. AH (B) Tc K " 0 - 500 C " C 349.193254
Tgi 30 right. temp. AH (B) Flue gas temperature upstr. AH (B) Tc K " 0 - 500 C " C 351.245817
Tgi 31 right. temp. AH (B) Flue gas temperature upstr. AH (B) Tc K " 0 - 500 C " C 352.15685
Tgi 32 right. temp. AH (B) Flue gas temperature upstr. AH (B) Tc K " 0 - 500 C " C 352.24485
Tgi 33 right. temp. AH (B) Flue gas temperature upstr. AH (B) Tc K " 0 - 500 C " C 354.892902
Tgi 34 right. temp. AH (B) Flue gas temperature upstr. AH (B) Tc K " 0 - 500 C " C 349.775772
Tgi 35 right. temp. AH (B) Flue gas temperature upstr. AH (B) Tc K " 0 - 500 C " C 347.709631
Tgi 36 right. temp. AH (B) Flue gas temperature upstr. AH (B) Tc K " 0 - 500 C " C 353.006984
Tgi 37 right. temp. AH (B) Flue gas temperature upstr. AH (B) Tc K " 0 - 500 C " C 348.708381
Tgi 38 right. temp. AH (B) Flue gas temperature upstr. AH (B) Tc K " 0 - 500 C " C 352.455141
Tgi 39 right. temp. AH (B) Flue gas temperature upstr. AH (B) Tc K " 0 - 500 C " C 350.15083
Tgi 40 right. temp. AH (B) Flue gas temperature upstr. AH (B) Tc K " 0 - 500 C " C 351.257106
Tgi 41 right. temp. AH (B) Flue gas temperature upstr. AH (B) Tc K " 0 - 500 C " C 351.539825
Tgi 42 right. temp. AH (B) Flue gas temperature upstr. AH (B) Tc K " 0 - 500 C " C 350.577085
Tgi 43 right. temp. AH (B) Flue gas temperature upstr. AH (B) Tc K " 0 - 500 C " C 351.046689
Tgi 44 right. temp. AH (B) Flue gas temperature upstr. AH (B) Tc K " 0 - 500 C " C 352.26594
Tgi 45 right. temp. AH (B) Flue gas temperature upstr. AH (B) Tc K " 0 - 500 C " C 353.292288
Tgi 46 right. temp. AH (B) Flue gas temperature upstr. AH (B) Tc K " 0 - 500 C " C 354.628911
Tgi 47 right. temp. AH (B) Flue gas temperature upstr. AH (B) Tc K " 0 - 500 C " C 354.884074
Tgi 48 right. temp. AH (B) Flue gas temperature upstr. AH (B) Tc K " 0 - 500 C " C 349.563307
Tgo 25 right. temp. AH (B) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 106.449305
Tgo 26 right. temp. AH (B) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 107.08506
Tgo 27 right. temp. AH (B) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 109.003712
Tgo 28 right. temp. AH (B) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 111.118268
Tgo 29 right. temp. AH (B) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 99.0030754
Tgo 30 right. temp. AH (B) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 102.345166
Tgo 31 right. temp. AH (B) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 104.032418
Tgo 32 right. temp. AH (B) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 110.875464
Tgo 33 right. temp. AH (B) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 94.7802574
Tgo 34 right. temp. AH (B) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 101.136597
Tgo 35 right. temp. AH (B) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 107.966585
Tgo 36 right. temp. AH (B) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 110.191908
Tgo 37 right. temp. AH (B) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 95.0233754
Tgo 38 right. temp. AH (B) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 102.329649
Tgo 39 right. temp. AH (B) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 108.296066
Tgo 40 right. temp. AH (B) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 110.53678
Tgo 41 right. temp. AH (B) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 93.1916845
Tgo 42 right. temp. AH (B) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 96.4918791
Tgo 43 right. temp. AH (B) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 99.1897727
Tgo 44 right. temp. AH (B) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 109.916808
Tgo 45 right. temp. AH (B) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 85.7962378
Tgo 46 right. temp. AH (B) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 88.5153013
Tgo 47 right. temp. AH (B) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 96.1589511
Tgo 48 right. temp. AH (B) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 103.31191
A1 O2 downstream. AHs Flue gas O2 analysis (downstream. AHs) % 2.20716016
A2 O2 upstream AHs Flue gas O2 analysis (upstream. AHs) % 0.78215707
A3 CO upstream AHs Flue gas CO analysis (upstream AHs) ppm 49.9789835
A4 NO downstr. AHs Flue gas NO analysis (downstream AHs) ppm 158.120536
W01 Feedwater flow at boiler inlet mbar 989.339667
P01 Feedwater pressure at flowmeeter bar 179.616171
T01 TI 103 Feedwater temperature at boiler inlet C 273.223021
P02 PI 100 Feedwater pressure at boiler inlet bar 179.117313
W02 FE 112 Desuperheating water flow to SH (1st stage) mbar 366.391369
W03 FE 122 Desuperheating water flow to SH (2nd stage) mbar 161.16746
P03 PI 112 Desuperheating water press. to SH (1st/2nd stage) bar 200.230337
T02 TE 111 Desuperheating water temperature to SH C 182.216858
W04 FE 153 Desuperheating water flow to RH mbar 0.83388205
P05 PE 153 Desuperheating water pressure to RH bar 37.0174837
T03 TT152 Desuperheating water temperature to RH C 25.0773201
T04 TI 222 SH outlet steam temperature right side Tc K 0-650 C C 541.716213
T05 TI 212 SH outlet steam temperature left side Tc K 0-650 C mbar 541.75277
P06 PI 226 SH outlet steam pressure PT 0-250 bar bar 167.107115
T07 TI 281 Hot reheated steam temperature Tc K 0-650 C C 565.691481
P08 PT 283 Hot reheated steam pressure PT 0-100 bar bar 35.8827139
T06 TI252 Cold reheated steam temperature a HP ST outlet Tc J 0 - 400 C 331.730107
P07 PT 250 Cold reheated steam pressure a HP ST Outlet PT. 0 - 100 bar bar 37.2593087
KF1 F.D.F. MA200 Forced draft fan motor power 1 AP MA200 0 - 4800 KW KW 3454.75707
KF2 F.D.F. MA100 Forced draft fan motor power 1 AP MA100 0 - 4800 KW KW 3728.03547
KG1 R.G.M. MA 200 Recirculating fan motor power 1FU MA200 0 - 1050 KW KW 811.773807
KG2 R.G.M. MA 100 Recirculating fan motor power 1FU MA100 0 - 1050 KW KW 777.237748
Averaged 1Air left temp.upstr.AH C 34.634398
Averaged 2Air right temp.upstr. AH C 34.220595
Averaged 3 Flue gas left Temperature upstr.AH C 351.22026
Averaged 4 Flue gas left Temp. downstr. AH C 106.83465
Averaged 5 Flue gas right Temp. upstr. AH C 351.10572
Averaged 6 Flue gas right Temp. downstr. AH C 102.19776
Company Ansaldo Caldaie
Date
Sign

Company
Date
Sign
Averaged data computed from 10.30.04 - 15/11/12 to 12.00.11 - 15/11/12

FUNCTIONAL GUARANTEES

Contract
Par. No.
Guarantee Comment Units Value Measured

Minimum continuous main steam


2.1 Boiler capacity (case 2) generating capacity at Turbine kg/s 544.9 546.0
Generator 100% load
Minimum average main steam
2.2 Temperature at boiler battery limit (case2,10) temperature when operating at 100% C 541.7 5 541.7
TG load
Minimum average RH outlet
2.3 Temperature at boiler battery limit (case2,10) temperature when operating at 100% C 567 5 565.7
TG load

To be corrected after MHI


2.4 Maximum Reheater steam pressure drop (case 2) When operating at 100% TG load bar 1.9 0.67
calculation on RH flow

2.5 Efficiency firing gas (case 2) When operating at 100% TG load % 86.73 87.25

To be corrected for:
- CRH Temperature
2.6 Total auxiliary power consumption (case 2) When operating at 100% TG load kW 7500 8832
- RH flow
- Boiler Heat Output

Maximum average superheater spray water flow


2.7 When operating at 100% TG load kg/s 90 53
(case 2)

Other aux power cons.


Cooling FAN kW 38.07
AHs kW 22.5

FUNCTIONAL GUARANTEES
Contract
Par. No.
Guarantee Comment Units Value Measured

3.3 RH spray water flow From 25% of TG to BMCR kg/s 0 0

Maximum regenerative air heater leakage (case 2 and


3.4 100% TG % 8 6.48
10)
mg/Nm3 @ 3%
NOX flue gas emission limits when firing natural gas From 25% TG to BMCR 320 289
O2
3.7 3
mg/Nm @ 3%
CO flue gas emission limits when firing natural gas From 25% TG to BMCR 250 56
O2
Titolo Identificativo Rev. Pagina Di
title document no. rev. Page Of
ABU QIR THERMAL POWER PLANT 0 27 73
2 x 650 MW GAS / OIL FIRED UNIT 30390-A-M1008

5.1.2 Test#2
Averaged data computed from 12.00.11 - 15/11/12 to 13.30.25 - 15/11/12

ABU QIR ( PERFORMANCE TEST )

Test n. 2
Tag Description Units Values
Tam 1 humidity relative Ambient relative humidity % 58.9747917
Tam 2 Ambient Temperature Ambient temperature C 24.0989931
Barometric pressure Ambient pressure hPa 1017.32042
Ta 1 Air left upstr. AH Air temperature upstr. AH (A) RTD PT 100 0 - 250C C 35.3343354
Ta 2 Air left upstr. AH Air temperature upstr. AH (A) RTD PT 100 0 - 250C C 35.0771626
Ta 3 Air left upstr. AH Air temperature upstr. AH (A) RTD PT 100 0 - 250C C 35.1001205
Ta 4 Air right upstr. AH Air temperature upstr. AH (B) RTD PT 100 0 - 250C C 34.7203692
Ta 5 Air right upstr. AH Air temperature upstr. AH (B) RTD PT 100 0 - 250C C 34.5320816
Ta 6 Air right upstr. AH Air temperature upstr. AH (B) RTD PT 100 0 - 250C C 34.472911
Tgi 1 left. temp. AH (A) Flue gas temperature upstr. AH (A) Tc K " 0 - 500 C " C 350.554195
Tgi 2 left. temp. AH (A) Flue gas temperature upstr. AH (A) Tc K " 0 - 500 C " C 347.981493
Tgi 3 left. temp. AH (A) Flue gas temperature upstr. AH (A) Tc K " 0 - 500 C " C 352.06034
Tgi 4 left. temp. AH (A) Flue gas temperature upstr. AH (A) Tc K " 0 - 500 C " C 350.521302
Tgi 5 left. temp. AH (A) Flue gas temperature upstr. AH (A) Tc K " 0 - 500 C " C 349.982158
Tgi 6 left. temp. AH (A) Flue gas temperature upstr. AH (A) Tc K " 0 - 500 C " C 349.727747
Tgi 7 left. temp. AH (A) Flue gas temperature upstr. AH (A) Tc K " 0 - 500 C " C 352.116295
Tgi 8 left. temp. AH (A) Flue gas temperature upstr. AH (A) Tc K " 0 - 500 C " C 350.037977
Tgi 9 left. temp. AH (A) Flue gas temperature upstr. AH (A) Tc K " 0 - 500 C " C 349.174178
Tgi 10 left. temp. AH (A) Flue gas temperature upstr. AH (A) Tc K " 0 - 500 C " C 349.805171
Tgi 11 left. temp. AH (A) Flue gas temperature upstr. AH (A) Tc K " 0 - 500 C " C 353.772243
Tgi 12 left. temp. AH (A) Flue gas temperature upstr. AH (A) Tc K " 0 - 500 C " C 352.707791
Tgi 13 left. temp. AH (A) Flue gas temperature upstr. AH (A) Tc K " 0 - 500 C " C 352.172441
Tgi 14 left. temp. AH (A) Flue gas temperature upstr. AH (A) Tc K " 0 - 500 C " C 353.787262
Tgi 15 left. temp. AH (A) Flue gas temperature upstr. AH (A) Tc K " 0 - 500 C " C 354.208697
Tgi 16 left. temp. AH (A) Flue gas temperature upstr. AH (A) Tc K " 0 - 500 C " C 352.798955
Tgi 17 left. temp. AH (A) Flue gas temperature upstr. AH (A) Tc K " 0 - 500 C " C 349.601608
Tgi 18 left. temp. AH (A) Flue gas temperature upstr. AH (A) Tc K " 0 - 500 C " C 349.990971
Tgi 19 left. temp. AH (A) Flue gas temperature upstr. AH (A) Tc K " 0 - 500 C " C 352.063073
Tgi 20 left. temp. AH (A) Flue gas temperature upstr. AH (A) Tc K " 0 - 500 C " C 349.619981
Tgi 21 left. temp. AH (A) Flue gas temperature upstr. AH (A) Tc K " 0 - 500 C " C 353.488443
Tgi 22 left. temp. AH (A) Flue gas temperature upstr. AH (A) Tc K " 0 - 500 C " C 352.590128
Tgi 23 left. temp. AH (A) Flue gas temperature upstr. AH (A) Tc K " 0 - 500 C " C 349.898531
Tgi 24 left. temp. AH (A) Flue gas temperature upstr. AH (A) Tc K " 0 - 500 C " C 350.830531
Tgo 1 left. temp. AH (A) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 108.329419
Tgo 2 left. temp. AH (A) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 113.1735
Tgo 3 left. temp. AH (A) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 115.185839
Tgo 4 left. temp. AH (A) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 117.799289
Tgo 5 left. temp. AH (A) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 102.699331
Tgo 6 left. temp. AH (A) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 109.168686
Tgo 7 left. temp. AH (A) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 108.135579
Tgo 8 left. temp. AH (A) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 116.879186
Tgo 9 left. temp. AH (A) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 102.638502
Tgo 10 left. temp. AH (A) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 107.824907
Tgo 11 left. temp. AH (A) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 111.939863
Tgo 12 left. temp. AH (A) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 115.566982
Tgo 13 left. temp. AH (A) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 101.957681
Tgo 14 left. temp. AH (A) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 107.81698
Tgo 15 left. temp. AH (A) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 112.2147
Tgo 16 left. temp. AH (A) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 117.853022
Tgo 17 left. temp. AH (A) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 98.6784687
Tgo 18 left. temp. AH (A) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 98.6172793
Tgo 19 left. temp. AH (A) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 105.113585
Tgo 20 left. temp. AH (A) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 114.94224
Tgo 21 left. temp. AH (A) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 89.5854269
Tgo 22 left. temp. AH (A) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 89.6551203
Tgo 23 left. temp. AH (A) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 100.746982
Tgo 24 left. temp. AH (A) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 107.519427
Tgi 25 right. temp. AH (B) Flue gas temperature upstr. AH (B) Tc K " 0 - 500 C " C 347.086365
Tgi 26 right. temp. AH (B) Flue gas temperature upstr. AH (B) Tc K " 0 - 500 C " C 348.646398
Tgi 27 right. temp. AH (B) Flue gas temperature upstr. AH (B) Tc K " 0 - 500 C " C 349.53629
Tgi 28 right. temp. AH (B) Flue gas temperature upstr. AH (B) Tc K " 0 - 500 C " C 350.680007
Tgi 29 right. temp. AH (B) Flue gas temperature upstr. AH (B) Tc K " 0 - 500 C " C 349.157627
Tgi 30 right. temp. AH (B) Flue gas temperature upstr. AH (B) Tc K " 0 - 500 C " C 351.199525
Tgi 31 right. temp. AH (B) Flue gas temperature upstr. AH (B) Tc K " 0 - 500 C " C 352.129943
Tgi 32 right. temp. AH (B) Flue gas temperature upstr. AH (B) Tc K " 0 - 500 C " C 352.226509
Tgi 33 right. temp. AH (B) Flue gas temperature upstr. AH (B) Tc K " 0 - 500 C " C 354.937669
Tgi 34 right. temp. AH (B) Flue gas temperature upstr. AH (B) Tc K " 0 - 500 C " C 349.798269
Tgi 35 right. temp. AH (B) Flue gas temperature upstr. AH (B) Tc K " 0 - 500 C " C 347.695062
Tgi 36 right. temp. AH (B) Flue gas temperature upstr. AH (B) Tc K " 0 - 500 C " C 353.016189
Tgi 37 right. temp. AH (B) Flue gas temperature upstr. AH (B) Tc K " 0 - 500 C " C 348.723062
Tgi 38 right. temp. AH (B) Flue gas temperature upstr. AH (B) Tc K " 0 - 500 C " C 352.473538
Tgi 39 right. temp. AH (B) Flue gas temperature upstr. AH (B) Tc K " 0 - 500 C " C 350.163403
Tgi 40 right. temp. AH (B) Flue gas temperature upstr. AH (B) Tc K " 0 - 500 C " C 351.278845
Tgi 41 right. temp. AH (B) Flue gas temperature upstr. AH (B) Tc K " 0 - 500 C " C 351.553503
Tgi 42 right. temp. AH (B) Flue gas temperature upstr. AH (B) Tc K " 0 - 500 C " C 350.604204
Tgi 43 right. temp. AH (B) Flue gas temperature upstr. AH (B) Tc K " 0 - 500 C " C 351.103307
Tgi 44 right. temp. AH (B) Flue gas temperature upstr. AH (B) Tc K " 0 - 500 C " C 352.293872
Tgi 45 right. temp. AH (B) Flue gas temperature upstr. AH (B) Tc K " 0 - 500 C " C 353.292338
Tgi 46 right. temp. AH (B) Flue gas temperature upstr. AH (B) Tc K " 0 - 500 C " C 354.641858
Tgi 47 right. temp. AH (B) Flue gas temperature upstr. AH (B) Tc K " 0 - 500 C " C 354.874879
Tgi 48 right. temp. AH (B) Flue gas temperature upstr. AH (B) Tc K " 0 - 500 C " C 349.55579
Tgo 25 right. temp. AH (B) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 106.857317
Tgo 26 right. temp. AH (B) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 107.384695
Tgo 27 right. temp. AH (B) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 109.199155
Tgo 28 right. temp. AH (B) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 111.326949
Tgo 29 right. temp. AH (B) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 99.4070067
Tgo 30 right. temp. AH (B) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 102.554263
Tgo 31 right. temp. AH (B) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 104.280944
Tgo 32 right. temp. AH (B) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 111.089644
Tgo 33 right. temp. AH (B) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 95.0992823
Tgo 34 right. temp. AH (B) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 101.385386
Tgo 35 right. temp. AH (B) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 108.306077
Tgo 36 right. temp. AH (B) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 110.483297
Tgo 37 right. temp. AH (B) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 95.3536987
Tgo 38 right. temp. AH (B) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 102.627192
Tgo 39 right. temp. AH (B) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 108.613847
Tgo 40 right. temp. AH (B) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 110.828666
Tgo 41 right. temp. AH (B) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 93.5383185
Tgo 42 right. temp. AH (B) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 96.7375977
Tgo 43 right. temp. AH (B) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 99.5844796
Tgo 44 right. temp. AH (B) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 110.16239
Tgo 45 right. temp. AH (B) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 86.1326159
Tgo 46 right. temp. AH (B) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 88.8351476
Tgo 47 right. temp. AH (B) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 96.5207951
Tgo 48 right. temp. AH (B) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 103.59571
A1 O2 downstream. AHs Flue gas O2 analysis (downstream. AHs) % 2.23671389
A2 O2 upstream AHs Flue gas O2 analysis (upstream. AHs) % 0.7092125
A3 CO upstream AHs Flue gas CO analysis (upstream AHs) ppm 54.699375
A4 NO downstr. AHs Flue gas NO analysis (downstream AHs) ppm 160.569618
W01 Feedwater flow at boiler inlet mbar 991.004475
P01 Feedwater pressure at flowmeeter bar 179.732236
T01 TI 103 Feedwater temperature at boiler inlet C 273.165564
P02 PI 100 Feedwater pressure at boiler inlet bar 179.222178
W02 FE 112 Desuperheating water flow to SH (1st stage) mbar 354.434808
W03 FE 122 Desuperheating water flow to SH (2nd stage) mbar 158.814177
P03 PI 112 Desuperheating water press. to SH (1st/2nd stage) bar 200.685923
T02 TE 111 Desuperheating water temperature to SH C 182.199517
W04 FE 153 Desuperheating water flow to RH mbar 0.67422731
P05 PE 153 Desuperheating water pressure to RH bar 36.9466058
T03 TT152 Desuperheating water temperature to RH C 25.383333
T04 TI 222 SH outlet steam temperature right side Tc K 0-650 C C 542.405374
T05 TI 212 SH outlet steam temperature left side Tc K 0-650 C mbar 542.38125
P06 PI 226 SH outlet steam pressure PT 0-250 bar bar 167.18157
T07 TI 281 Hot reheated steam temperature Tc K 0-650 C C 566.34025
P08 PT 283 Hot reheated steam pressure PT 0-100 bar bar 35.8527761
T06 TI252 Cold reheated steam temperature a HP ST outlet Tc J 0 - 400 C 332.313678
P07 PT 250 Cold reheated steam pressure a HP ST Outlet PT. 0 - 100 bar bar 37.2361836
KF1 F.D.F. MA200 Forced draft fan motor power 1 AP MA200 0 - 4800 KW KW 3443.50887
KF2 F.D.F. MA100 Forced draft fan motor power 1 AP MA100 0 - 4800 KW KW 3718.48688
KG1 R.G.M. MA 200 Recirculating fan motor power 1FU MA200 0 - 1050 KW KW 808.72046
KG2 R.G.M. MA 100 Recirculating fan motor power 1FU MA100 0 - 1050 KW KW 773.066386
Averaged 1Air left temp.upstr.AH C 35.17054
Averaged 2Air right temp.upstr. AH C 34.575121
Averaged 3 Flue gas left Temperature upstr.AH C 351.22881
Averaged 4 Flue gas left Temp. downstr. AH C 107.25175
Averaged 5 Flue gas right Temp. upstr. AH C 351.11119
Averaged 6 Flue gas right Temp. downstr. AH C 102.49602
Company Ansaldo Caldaie
Date
Sign

Company
Date
Sign
Averaged data computed from 12.00.11 - 15/11/12 to 13.30.25 - 15/11/12

FUNCTIONAL GUARANTEES - Preliminary values

Contract
Par. No.
Guarantee Comment Units Value Measured

Minimum continuous main steam


2.1 Boiler capacity (case 2) generating capacity at Turbine kg/s 544.9 545.7
Generator 100% load
Minimum average main steam
2.2 Temperature at boiler battery limit (case2,10) temperature when operating at 100% C 541.7 5 542.4
TG load
Minimum average RH outlet
2.3 Temperature at boiler battery limit (case2,10) temperature when operating at 100% C 567 5 566.3
TG load

To be corrected after MHI


2.4 Maximum Reheater steam pressure drop (case 2) When operating at 100% TG load bar 1.9 0.67
calculation on RH flow

2.5 Efficiency firing gas (case 2) When operating at 100% TG load % 86.73 87.25

To be corrected for:
- CRH Temperature
2.6 Total auxiliary power consumption (case 2) When operating at 100% TG load kW 7500 8804
- RH flow
- Boiler Heat Output

Maximum average superheater spray water flow


2.7 When operating at 100% TG load kg/s 90 53
(case 2)

Other aux power cons.


Cooling FAN kW 38.07
AHs kW 22.5

FUNCTIONAL GUARANTEES
Contract
Par. No.
Guarantee Comment Units Value Measured

3.3 RH spray water flow From 25% of TG to BMCR kg/s 0 0

Maximum regenerative air heater leakage (case 2 and


3.4 100% TG % 8 6.96
10)
3
mg/Nm @ 3%
NOX flue gas emission limits when firing natural gas From 25% TG to BMCR 320 292
O2
3.7 3
mg/Nm @ 3%
CO flue gas emission limits when firing natural gas From 25% TG to BMCR 250 61
O2
Titolo Identificativo Rev. Pagina Di
title document no. rev. Page Of
ABU QIR THERMAL POWER PLANT 0 32 73
2 x 650 MW GAS / OIL FIRED UNIT 30390-A-M1008

6. Attachment 2: Fuel gas analysis


Hereafter the natural gas analysis received from:

Intertek Commodities
Cargo Inspection, Analytical Services
Petroleum and carg Services,Laboratory Services
217 Abdel Salam Aref Lauran,Alexandria,Egypt
Tel:
Office : 0020-3-(4590141 / 5850464 / 5824441)
Mobile: 002-0100-1924419
Fax : 0020-3-5831438
www.intertek.com/petroleum/testing/cargo/
www.intertek.com/minerals/
www.intertek.com/government/

6.1.1 Test #1
Titolo Identificativo Rev. Pagina Di
title document no. rev. Page Of
ABU QIR THERMAL POWER PLANT 0 33 73
2 x 650 MW GAS / OIL FIRED UNIT 30390-A-M1008

6.1.2 Test #2

Fuel gas sampling station


Titolo Identificativo Rev. Pagina Di
title document no. rev. Page Of
ABU QIR THERMAL POWER PLANT 0 34 73
2 x 650 MW GAS / OIL FIRED UNIT 30390-A-M1008

7. Attachment 3: Calculation sheets


7.1.1 Test #1
WEST DELTA ELECTRICITY PRODUCTION COMPANY ABU QIR THERMAL POWER PLANT UNITS 6 & 7
2 x 650 MW GAS/OIL FIRED UNITS GUARANTEED EFFICIENCY CALCULATION

Date 15/11/12
Time 10:30-12:00
Test n. 1
Load 100% GAS

INPUT DATA Unit Value Symbol Formula

Reference conditions
Reference air temperature C 25 Tre
Barometric pressure Pa 101792 Pa
Dry-bulb temperature at location 6 C 23.5 Tdb
Wet-bulb temperature at location 6 C 18.7 Twb
Relative humidity at Iocation 6 % 63.33 Rhm
Design entering air temperature C 41 TAEn

Design fuel data


Fuel type - G (G=Gas; O=Oil)
Higher heating value of fuel at constant volume kJ/kg 54995.0 HHVFcv
Higher heating value of fuel at constant pressure kJ/kg 55060.3 HHVF
Percent carbon in fuel % wt. 74.73 MpCF
Percent hydrogen in fuel % wt. 24.71 MpH2F
Nitrogen in fuel % wt. 0.15 MpN2F
Sulfur in fuel % wt. 0.00 MpSF
Oxygen in fuel % wt. 0.41 MpO2F
Percent water in fuel % wt. 0.00 MpH2OF
Percent ash in fuel % wt. 0.00 MpAsF
% 100.0 total

Flue gas data


At Air Heater inlet:
Measured percent O2 in flue gas at boiler inlet, dry basis % vol. dry 0.782 DVpO2En
Measured percent O2 in flue gas at boiler inlet, wet basis % vol. wet 0.64 VpO2En
Percent CO in flue gas, dry basis % vol. dry 0.0050 DVpCOEn
Quantity of NOx as NO % vol. dry 0.0158 DVpNOx

At Air Heater outlet:


Measured percent O2 in flue gas at A.H. outlet, dry basis % vol. dry 2.21 DVpO2Lv
WEST DELTA ELECTRICITY PRODUCTION COMPANY ABU QIR THERMAL POWER PLANT UNITS 6 & 7
2 x 650 MW GAS/OIL FIRED UNITS GUARANTEED EFFICIENCY CALCULATION

Date 15/11/12
Time 10:30-12:00
Test n. 1
Load 100% GAS

INPUT DATA Unit Value Symbol Formula

Measured flows
Mass flow rate of fuel kg/s 30.8 MrF
Additional water per mass fuel kg/s 0 MFrWAd
Mass flow rate of feedwater at boiler inlet kg/s 492.7 MrW24
Mass flow rate of superheated steam at boiler outlet kg/s 546.0 MrSt32
Mass flow rate of cold reheat kg/s 460.5 MrSt33
Mass flow rate of Blow Down kg/s 0.0 MrWbd
Mass flow rate of Sh spray water kg/s 53.3 MrW25
Mass flow rate of Rh spray water kg/s 0 MrW26

Fuel, air & flue gas temperatures


Temperature of fuel at boiler inlet C 26.0 Tfuel
Air heater entering air temperature C 34.4 TAEn
Temperature of wet air at Air Heater outlet C 326.6 TALv
Temperature of wet flue gas at Air Heater inlet C 351.2 TFgEn
Temperature of wet flue gas at A.H. outlet with leakage C 104.5 TFgLv
Temperature of wet flue gas at A.H. outlet without leakage C 107.9 TFgLCr
-> Change TFgLvCr (w/oL) untill 0 = 0.00
Water & steam temperatures
Water temperature at Economizer inlet C 273.2 TW24
Steam temperature at Superheater outlet C 541.7 TSt32
Water temperature at Sh attemperator inlet C 182.2 TW25
Steam temperature at cold Rh C 331.7 TSt33
Steam temperature at Reheater outlet C 565.7 TSt34
Water temperature at Rh attemperator inlet C 182.2 TW26

Water & steam pressures


Water pressure at SH attemperators bar abs. 201.2 PW25
Water pressure at Economizer inlet bar abs. 180.1 PW24
Drum pressure bar abs. 176.93 PSt31
Steam pressure at Superheater outlet bar abs. 168.1 PSt32
Water pressure at RH attemperators bar abs. 201.2 PW26
Cold reheater pressure bar abs. 38.26 PSt33
Hot reheater pressure bar abs. 36.88 PSt34

Auxiliaries absorbed power


Gas recirculating fan kW 1589.0 QX
Efficiency % 0.95 EX
WEST DELTA ELECTRICITY PRODUCTION COMPANY ABU QIR THERMAL POWER PLANT UNITS 6 & 7
2 x 650 MW GAS/OIL FIRED UNITS GUARANTEED EFFICIENCY CALCULATION

Date 15/11/12
Time: 10:30-12:00
Test n. 1
Load 100% GAS

OUTPUT Unit Value Symbol Formula

5.4 Energy balance


Main steam flow kg/s 546.0 MrSt32
Main steam pressure bar 168.1 PSt32
Main steam temperature C 541.7 TSt32
Main steam enthalpy kJ/kg 3407.9 HSt32
Feed water flow kg/s 492.7 MrW24
Feed water pressure bar 180.1 PW24
Feed water temperature C 273.2 TW24
Feed water enthalpy kJ/kg 1198.1 HW24
SH spray water flow kg/s 53.3 MrW25
SH spray water pressure bar 201.2 PW25
SH spray water temperature C 182.2 TW25
SH spray water enthalpy kJ/kg 782.8 HW25
Cold reheat flow kg/s 460.5 MrSt33
Cold reheat pressure bar 38.3 PSt26
Cold reheat temperature C 331.7 TSt33
Cold reheat enthalpy kJ/kg 3051.6 HSt33
Hot reheat flow kg/s 460.5 MrSt34
Hot reheat pressure bar 36.9 PSt34
Hot reheat temperature C 565.7 TSt34
Hot reheat enthalpy kJ/kg 3598.9 HSt34
RH spray water flow kg/s 0.0 MrW26
RH spray water pressure bar 201.2 PW26
RH spray water temperature C 182.2 TW26
RH spray water enthalpy kJ/kg 782.8 HW26

( MrSt32 * HSt32 - ( MrW24 * HW24 + MrW25 *


Total heat output MW 1480.7 QrO HW25 ) + MrSt34 * HSt34 - ( MrSt33 * HSt33 +
MrW26 * HW26 ) ) / 100
CAIRO ELECTRICITY PRODUCTION COMPANY ABU QIR THERMAL POWER PLANT UNITS 6 & 7
2 x 350 MW GAS/OIL FIRED UNITS GUARANTEED EFFICIENCY CALCULATION

Date 15/11/12
Time 10:30-12:00
Test n. 1
Load 100% GAS

A.H. INLET Units Value Symbol Formula

5.8 Fuel properties


Higher heating value of fuel at constant volume kJ/kg 54995.00 HHVFcv
Percent hydrogen in fuel % mass 24.71486254 MpH2F
HH value of fuel at constant pressure kJ/kg 55060.35 HHVF HHVFcv + 2,644 * MpH2F

5.10.2 Unburned carbon calculation


Mass of residue per unit volume at Air Heater outlet g. of residue/m3 0.00 MvRs
Mass flow rate of wet gas at Air Heater outlet kg/s 0 MrFgLv
Density of wet ftue gas at Air Heater outlet kg/m3 0.823 DnFgLv
Mass flow rate of residue at air heater outlet kg/s 0.000 MrRsLv ( MvRs * MrFgLv ) / ( 1000 * DnFgLv )
Mass flow rate of fuel kg/s 30.8 MrF
Mass fraction of residue at Air Heater outlet per mass unit of fuel kg/kg 0.0000 MFrRsLv MrRsLv / MrF
Percent unburned carbon in residue at Air Heater outlet % mass 85 MpCRsLv
Percent of unburned carbon at A.H. outlet per mass unit of fuel % 0.00 MpUbC MFrRsLv * MpCRsLv
Percent carbon in fuel % mass 74.72860258 MpCF
Carbon burned % mass 74.73 MpCb MpUbC - MpCF

5.11.2 Moisture in air (kg/kg dry air)


Barometric pressure psi 14.47 Pa Pa * 14,22 / 100000
Dry-bulb temperature at location 6 F 74.38 Tdbz Tdb * 1,8 + 32
Wet-bulb temperature at location 6 F 65.62 Twbz Twb * 1,8 + 32
C1 - 1.93E-02 -
C2 - 1.29E-03 -
C3 - 1.21E-05 -
C4 - 4.53E-07 -
C5 - 6.84E-11 -
C6 - 2.20E-11 -
C1 + C2 * Twbz + C3 * ( Twbz * 2 ) + C4 * ( Twbz * 3
Saturation pressure of water vapor at wet-bulb temperature psia 3.12E-01 PsWTwb
) + C5 * ( Twbz * 4 ) + C6 * ( Twbz * 5 )
PsWTwb - ( Pa - PsWTwb ) * ( Tdbz - Twbz ) / (
Partial pressure of water vapor in air - 0.267 PpWvA
2830 - 1,44 * Twbz )
Mass fraction of moisture In dry air, mass H20/mass dry air kg/kg dry air 0.012 MFrWDA 0,622 * ( PpWvA / ( Pa - PpWvA ) )
CAIRO ELECTRICITY PRODUCTION COMPANY ABU QIR THERMAL POWER PLANT UNITS 6 & 7
2 x 350 MW GAS/OIL FIRED UNITS GUARANTEED EFFICIENCY CALCULATION

Date 15/11/12
Time 10:30-12:00
Test n. 1
Load 100% GAS

A.H. INLET Units Value Symbol Formula

5.11.3 Theoretical air calculation (corrected)


Carbon burned on a mass percentage basis % mass 74.73 MpCb
Percent hydrogetn in fuet % mass 24.71486254 MpH2F
Sulfur in fuel % mass 0.0 MpSF
Sutfur capture ratio kg/kg 0 MFrSc
Oxygen in fuel % mass 0.411340238 MpO2F
0,1151 * MpCb + 0,343 * MpH2F + 0,0431 * MpSF *
Mass of theoretical air corrected on input from fuel basis kg/kg fuel as fired 17.06 MFrThACr
( 1 + 0,5 * MFrSc ) - 0,0432 * MpO2F
Moles of theoretical air required (corrected) moles/kg as fired fuel 0.5891 MoThACr MFrThACr / 28,963
Theoretical air corrected on input from fuel basis kg/kJ 0.000310 MqThACr MFrThACr / HHVF

5.11.4.1 Percent excess air at Air Heater inlet


Measured percent 02 in flue gas at A.H. inlet, dry basis % volume dry 0.78 MoThACr
Carbon burned on a mass percentage basis % mass 74.73 MpCb
Sutfur capture ratio kg/kg 0 MFrSc
Sulfur in fuel % mass 0 MpSF
Nitrogen In fuel % mass 0.145194639 MpN2F
Moles of dry gas (CO2) from sorbent per mass fuel moles/mass fuel 0 MoCO2Sb
MpCb / 1201 + ( 1 - MFrSc ) * MpSF / 3206,4 +
Moles dry products from fuel (CO2, N2F, and actual SO2 produced) moles/mass fuel 0.062 MoDPc
MpN2F / 2801,3 + MoCO2Sb
100 * ( DVpO2 * ( MoDPc + 0,7905 * MoThACr ) ) / (
Percent excess air at Air Heater inlet % 3.48 XpAEn
MoThACr * ( 20,95 - MoThACr ) )

5.11.4.2 Calculation of DVpO2, DVpCO2, DVpSO2, DVpN2f and DVpN2a on a dry basis (%vol. dry)
Moles dry gas per mass fuel moles/mass fuel 0.55 MoDFg MoDPc + MoThACr * ( 0,7905 + XpAEn / 100 )
Percent 02 in flue gas, dry basis (measured) % volume dry 0.782 DVpO2
Percent of CO2 in flue gas, dry basis % volume dry 11.35 DVpCO2 ( MpCb / 12,01 + 100 * MoCO2Sb ) / MoDFg
Percent of SO2 in flue gas, wet basis % volume dry 0.0000 DVpSO2 MpSF / 32,064 * ( 1 - 0 ) ) / MoDFg
Percent N2 from fuel in flue gas, wet basis % volume dry 0.0095 DVpN2f ( MpN2F / 28,013 ) / MoDFg
Percent nitrogen (atmospheric) in flue gas, dry basis % volume dry 87.86 DVpN2a 100 - DVpO2En - DVpCO2 - DVpSO2 - DVpN2f

100.00 DVpO2 + DVpCO2 + DVpSO2 + DVpN2f + DVpN2a


CAIRO ELECTRICITY PRODUCTION COMPANY ABU QIR THERMAL POWER PLANT UNITS 6 & 7
2 x 350 MW GAS/OIL FIRED UNITS GUARANTEED EFFICIENCY CALCULATION

Date 15/11/12
Time 10:30-12:00
Test n. 1
Load 100% GAS

A.H. INLET Units Value Symbol Formula

5.11.4.4 Calculation of VpO2, VpCO2, VpSO2, VpN2f and VpN2a on a wet basis (%vol. wet)
MoDPc + ( MpH2F / 201,6 ) + MpH2OF / 1801,5 +
MoDPc plus moles H2O frorn fuel, sorbent and any additional moisture moles/mass fuel 0.185 MoWPc
MFrWAd / 18,15
Moles of moisture in air moles/kg air 0 XpAEn 1,608 * MFrWAd
MoWPc + MoThACr * ( 0,7905 + MoWA + XpAEn /
Moles of wet gas per mass fuel moles/mass fuel as fired 0.671 MoFg
100 ) * ( 1+ XpAEn ) )
Percent O2 in flue gas, wet basis % volume wet 0.639 VpO2 ( XpAEn * MoThACr * 0,2095 / MoFg )
Percent of CO2 in flue gas, wet basis % volume wet 9.273 VpCO2 ( MpCb / 12,01 ) / MoFg
Percent of SO2 in flue gas, wet basis % volume wet 0.0000 VpSO2 ( MpSF / 32,064 ) / MoFg
( MpH2F / 2,016 + MpH2OF / 18,015 + MFrWAd /
Percent water in flue gas, wet basis % volume wet 18.27 VpH2O 18,015 + ( 100 + XpAEn ) * MoThACr * XpAEn ) /
MoFg
Percent N2 from fuel in flue gas, wet basis % volume wet 0.008 VpN2f ( MpN2F / 28,013 ) / MoFg
Percent N2 (atmospheric) in flue gas, wet basis % volume wet 71.81 VpN2a 100 - VpO2 - VpCO2 - VpSO2 - VpH2O - VpN2f
VpO2 + VpCO2 + VpSO2 + VpH2O + VpN2f +
100.00
VpN2a
CAIRO ELECTRICITY PRODUCTION COMPANY ABU QIR THERMAL POWER PLANT UNITS 6 & 7
2 x 350 MW GAS/OIL FIRED UNITS GUARANTEED EFFICIENCY CALCULATION

Date 15/11/12
Time 10:30-12:00
Test n. 1
Load 100% GAS

A.H. INLET Units Value Symbol Formula

5.11.5 MqDALv - Dry air at Air Heater inlet


Mass of total dry air at A.H. outlet on input from fueI basis kg/kJ 0.0003206 MqDALv MqThACr * ( 1+ XpAEn / 100 )
Mass of total air corrected on input from fuel basis kg/kg fuel as fired 17.65 MFrDALv MFrThACr * ( 1+ XpAEn / 100 )

5.11.06 MrALv - Wet air at Air Heater inlet (kg/s)


Mass of total wet air at Air Heater outlet on input from fueI basis kg/kJ 0.00032 MqALv ( 1 + MFrWDA ) * MqDALv
Potential energy of combustion available from fuel kW 1695859 QrF MrF * HHVF
Mass flow rate of wet air at A.H. inlet kg/s 550.08 MrALv MqALv * QrF

5.12.00 Flue gas products at Air Heater inlet


5.12.01 Wet gas from fuel at A. H. inlet on fuel input basis
Wet gas from fuel kg/kJ 0.0000182 MqFgF ( 100 - MpAsF - MpUbC ) / ( 100 * HHVF )

5.12.2 Moisture from water in fuel


Moisture from water in fuel kg/kJ 0.000000000 MqWF MpH2OF / ( 100 * HHVF )

5.12.3 Water from combustion of hydrogen in fuel


Water from combustion of hydrogen in fuel kg/kJ 0.0000401 MqWH2F ( 8,937 * MpH2F ) / ( 100 * HHVF )

5.12.6 Water from moisture in air at A. H. inlet


Water from moisture in air kg/kJ 0.00000 MqWALv MFrWDA * MqDALv

5.12.8 Total moisture in flue gas at A.H. inlet on fuel input basis
Total moisture in flue gas at A. H. inlet on fuel input basis kg/kJ 0.000044 MqWFgEn MqWF + MqWH2F + MqWALv

5.12.9 Mass of wet gas at A. H. inlet on input from fuel basis


Mass of wet gas at A. H. inlet on input from fuel basis kg/kJ 0.00034 MqFgEn MqDALv + MqWALv + MqFgF

5.12.10 Dry flue gas weight at A. H. inlet on input from fuel basis
Mass dry gas at A.H. inlet on input from fueI basis kg/kJ 0.00029867 MqDFgEn MqFgEn - MqWFgEn

5.12.11 Moisture in flue gas at A. H. inlet, percent of wet flue gas


Moisture in flue gas at A.H. inlet, percent of wet flue gas % mass 12.80 MpWFgEn 100 * ( MqWFgEn / MqFgEn )
WEST DELTA ELECTRICITY PRODUCTION COMPANY ABU QIR THERMAL POWER PLANT UNITS 6 & 7
2 x 650 MW GAS/OIL FIRED UNITS GUARANTEED EFFICIENCY CALCULATION

Date 15/11/12
Time 10:30-12:00
Test n. 1
Load 100% GAS

A.H. OUTLET Units Value Symbol Formula

5.08.00 Fuel properties


Higher heating value of fuel at constant volume kJ/kg 54995.00 NHVFcv
Percent hydrogen in fuel % mass 24.71486254 MpH2F
HH value of fuel at constant pressure kJ/kg 55060.3 HHVF HHVFcv + 2,644 * MpH2F

5.11.12 Moisture in air (kg/kg dry air)


Barometric pressure psi 14.47 Pa Pa * 14,22 / 100000
Dry-bulb temperature at location 6 F 74.38 Tdbz Tdb * 1,8 + 32
Wet-bulb temperature at location 6 F 65.62 Twbz Twb * 1,8 + 32
C1 1.93E-02 -
C2 1.29E-03 -
C3 1.21E-05 -
C4 4.53E-07 -
C5 6.84E-11 -
C6 2.20E-11 -
C1 + C2 * Twbz + C3 * ( Twbz * 2 ) + C4 * ( Twbz *
Saturation pressure of water vapor at wet-bulb temperature 3.12E-01 PsWTwb
3 ) + C5 * ( Twbz * 4 ) + C6 * ( Twbz * 5 )
PsWTwb - ( Pa - PsWTwb ) * ( Tdbz - Twbz ) / (
Partial pressure of water vapor in air 0.267 PpWvA
2830 - 1,44 * Twbz )
Mass fraction of moisture In dry air, mass H20/mass dry air kg/kg dry air 0.012 MFrWDA 0,622 * ( PpWvA / ( Pa - PpWvA ) )

5.11.3 Theoretical air calculation (corrected)


Carbon burned on a mass percentage basis % mass 74.73 MpCb
Percent hydrogetl in fuet % mass 24.71486254 MpH2F
Sulfur in fuel % mass 0.0 MpSF
Sutfur capture ratio kg/kg 0 MFrSc
Oxygen in fuel % mass 0.41 MpO2F
0,1151 * MpCb + 0,343 * MpH2F + 0,0431 * MpSF *
Mass of theoretical air corrected on input from fuel basis kg/kg fuel as fired 17.06 MFrThACr
( 1 + 0,5 * MFrSc ) - 0,0432 * MpO2F
moles/kg as fired
Moles of theoretical air required (corrected) 0.5891 MoThACr MFrThACr / 28,963
fuel
Theoretical air corrected on input from fuel basis kg/kJ 0.000310 MqThACr MFrThACr / HHVF
WEST DELTA ELECTRICITY PRODUCTION COMPANY ABU QIR THERMAL POWER PLANT UNITS 6 & 7
2 x 650 MW GAS/OIL FIRED UNITS GUARANTEED EFFICIENCY CALCULATION

Date 15/11/12
Time 10:30-12:00
Test n. 1
Load 100% GAS

A.H. OUTLET Units Value Symbol Formula

5.11.4.1 Percent excess air at Air Heater outlet


Measured percent 02 in flue gas at A.H. inlet, dry basis % volume dry 2.21 DVpO2
Carbon burned on a mass percentage basis % mass 74.73 MpCb
Sutfur capture ratio (kg/kg) 0 MFrSc
Sulfur in fuel % mass 0 MpSF
Nitrogen In fuel % mass 0.145194639 MpN2F
Moles of dry gas (CO2) from sorbent per mass fuel moles/mass fuel 0 MoCO2Sb
MpCb / 1201 + ( 1 - MFrSc ) * MpSF / 3206,4 +
Moles dry products from fuel (CO2, N2F, and actual SO2 produced) moles/mass fuel 0.0626 MoDPc
MpN2F / 2801,3 + MoCO2Sb
100 * ( DVpO2 * ( MoDPc + 0,7905 * MoThACr ) ) / (
Percent excess air at Air Heater outlet % 10.56 XpALv
MoThACr * ( 20,95 - MoThACr ) )

5.11.4.2 Calculation of DVpO2, DVpCO2, DVpSO2, DVpN2f


and DVpN2a on a dry basis (%vol. dry)
Moles dry gas per mass fuel moles/mass fuel 0.590 MoDFg MoDPc + MoThACr * ( 0,7905 + XpAEn / 100 )
Percent 02 in flue gas, dry basis (measured) % volume dry 2.207 DVpO2
Percent of CO2 in flue gas, dry basis % volume dry 10.54 DVpCO2 ( MpCb / 12,01 + 100 * MoCO2Sb ) / MoDFg
Percent of SO2 in flue gas, dry basis % volume dry 0.00000 DVpSO2 MpSF / 32,064 * ( 1 - 0 ) ) / MoDFg
Percent N2 from fuel in flue gas, dry basis % volume dry 0.00878 DVpN2f ( MpN2F / 28,013 ) / MoDFg
Percent nitrogen (atmospheric) in flue gas, dry basis % volume dry 87.25 DVpN2a 100 - DVpO2En - DVpCO2 - DVpSO2 - DVpN2f
Flue gas dry composition at air heater outlet: 100.00 DVpO2 + DVpCO2 + DVpSO2 + DVpN2f + DVpN2a
WEST DELTA ELECTRICITY PRODUCTION COMPANY ABU QIR THERMAL POWER PLANT UNITS 6 & 7
2 x 650 MW GAS/OIL FIRED UNITS GUARANTEED EFFICIENCY CALCULATION

Date 15/11/12
Time 10:30-12:00
Test n. 1
Load 100% GAS

A.H. OUTLET Units Value Symbol Formula

5.11.4.4 Calculation of VpO2, VpCO2, VpSO2, VpN2f and


VpN2a on a wet basis (%vol. wet)
MoDPc + ( MpH2F / 201,6 ) + MpH2OF / 1801,5 +
MoDPc plus moles H2O frorn fuel, sorbent and any additional moisture moles/mass fuel 0.185 MoWPc
MFrWAd / 18,15
Moles of moisture in air moles/kg air 0 MoWA 1,608 * MFrWAd
moles/mass fuel as MoWPc + MoThACr * ( 0,7905 + MoWA + XpAEn /
Moles of wet gas per mass fuel 0.713 MoFg
fired 100 ) * ( 1+ XpAEn ) )
Percent O2 in flue gas, wet basis % volume wet 1.828 VpO2 ( XpAEn * MoThACr * 0,2095 / MoFg )
Percent of CO2 in flue gas, wet basis % volume wet 8.726 VpCO2 ( MpCb / 12,01 ) / MoFg
Percent of SO2 in flue gas, wet basis % volume wet 0.0000 VpSO2 ( MpSF / 32,064 ) / MoFg
( MpH2F / 2,016 + MpH2OF / 18,015 + MFrWAd /
Percent water in flue gas, wet basis % volume wet 17.19 VpH2O 18,015 + ( 100 + XpAEn ) * MoThACr * XpAEn ) /
MoFg
Percent N2 from fuel in flue gas, wet basis % volume wet 0.007 VpN2f ( MpN2F / 28,013 ) / MoFg
Percent N2 (atmospheric) in flue gas, wet basis % volume wet 72.25 VpN2a 100 - VpO2 - VpCO2 - VpSO2 - VpH2O - VpN2f
VpO2 + VpCO2 + VpSO2 + VpH2O + VpN2f +
Flue gas wet composition at air heater outlet: 100.00
VpN2a

5.11.05 MqDALv - Dry air at Air Heater outlet


Mass of total dry air at A.H. outlet on input from fueI basis kg/kJ 0.0003426 MqDALv MqThACr * ( 1+ XpAEn / 100 )
Mass of total air corrected on input from fuel basis kg/kg fuel as fired 18.86 MFrDALv MFrThACr * ( 1+ XpAEn / 100 )

5.11.06 MrALv - Wet air at Air Heater outlet (kg/s)


Mass of total wet air at Air Heater outlet on input from fueI basis kg/kJ 0.00035 MqALv ( 1 + MFrWDA ) * MqDALv
Potential energy of combustion available from fuel kW 1695859 QrF MrF * HHVF
Mass flow rate of wet air at A.H. outlet kg/s 587.74 MrALv MqALv * QrF
WEST DELTA ELECTRICITY PRODUCTION COMPANY ABU QIR THERMAL POWER PLANT UNITS 6 & 7
2 x 650 MW GAS/OIL FIRED UNITS GUARANTEED EFFICIENCY CALCULATION

Date 15/11/12
Time 10:30-12:00
Test n. 1
Load 100% GAS

A.H. OUTLET Units Value Symbol Formula

5.12 Flue gas products at Air Heater outlet


5.12.01 Wet gas from fuel at A. H. inlet on fuel input basis

Wet gas from fuel kg/kJ 0.0000182 MqFgF ( 100 - MpAsF - MpUbC ) / ( 100 * HHVF )
5.12.2 Moisture from water in fuel
Moisture from water in fuel kg/kJ 0.000000000 MqWF
MpH2OF / ( 100 * HHVF )
5.12.3 Water from combustion of hydrogen in fuel
Water from combustion of hydrogen in fuel kg/kJ 0.0000401 MqWH2F ( 8,937 * MpH2F ) / ( 100 * HHVF )

5.12.6 Water from moisture in air at Air Heater outlet


Water from moisture in air kg/kJ 0.00000 MqWALv MFrWDA * MqDALv

5.12.8 Total moisture in flue gas at A. H. outlet on fuel input


basis
Total moisture in flue gas at A. H. outlet on fuel input basis kg/kJ 0.000044 MqWFgEn MqWF + MqWH2F + MqWALv

5.12.9 Mass of wet gas at A. H. outlet on input from fuel


basis
Mass of wet gas at A. H. outlet on input from fuel basis kg/kJ 0.0004 MqFgLv MqDALv + MqWALv + MqFgF

5.12.10 Dry flue gas weight at A. H. outlet on input from fuel


basis
Mass dry gas at A.H. outlet on input from fueI basis kg/kJ 0.0003 MqDFgEn MqFgEn - MqWFgEn
WEST DELTA ELECTRICITY PRODUCTION COMPANY ABU QIR THERMAL POWER PLANT UNITS 6 & 7
2 x 650 MW GAS/OIL FIRED UNITS GUARANTEED EFFICIENCY CALCULATION

Date 15/11/12
Time 10:30-12:00
Test n. 1
Load 100% GAS

A.H. OUTLET Units Value Symbol Formula

5.12.11 Moisture in flue gas at A. H. outlet, percent of wet


flue gas
Moisture in flue gas at A.H. outlett, percent of wet flue gas % mass 12.10 MpWFgEn 100 * ( MqWFgEn / MqFgEn )

5.13 Air and flue gas temperature


5.13.1 T Re - Reference temperature
Reference temperature C 25 T Re

5.13.2 Average entering air temperature (C)


Average entering air temperature C 34.4 TMnAEn

5.13.03 TFgLvCr - Corrected Gas Outlet Temperature


Air temperature entering the air heater C 34.4 TAEn
Gas Temperature leaving the air heater C 104.5 TFgLV
Mean specific heat of wet air between TAEn and TFgLv kJ/kg 1.03 MnCpA
Mean specific heat of wet flue gas between TGLv and TFgLvCr kJ/kg 1.37 MnCpFg
Wet gas weight leaving the air heater kg/kJ 0.00036 MqFgLv
Wet gas weight entering the air heater kg/kJ 0.00034 MqFgEn
TFgLV + ( MnCpA / MnCpFg ) * ( MqFgLv / MqFgEn
Corrected Gas Outlet Temperature (Excluding Leakage) C 107.9 TFgLvCr
- 1 ) * ( TFgLV - TAEn )

5.18.2.2 Regenerative air heater corrections


( ( TAEn * ( TFgEn - TFgLv ) + TFgEn * ( TFgLv -
A.H.r temperature correction for entering air temperature C 5.118 TDiTAEn
TAEn ) ) / ( TFgEn - TAEn ) ) - TFgLv
A. H.r temperature correction for entering gas temperature C 0 TDiFgEn
A.H. temperature correction for entering gas mass flow C 0 TDiMrFgEn
A.H. temperature corrected for off design X-ratio C 0 TDiXr
TFgLCr + TDiTAEn + TDiFgEn + TDiMrFgEn +
Exit gas temperature corrected to design conditions C 113.0 TFgLvCrd
TDiXr
WEST DELTA ELECTRICITY PRODUCTION COMPANY ABU QIR THERMAL POWER PLANT UNITS 6 & 7
2 x 650 MW GAS/OIL FIRED UNITS GUARANTEED EFFICIENCY CALCULATION

Date 15/11/12
Time 10:30-12:00
Test n. 1
Load 100% GAS

LOSSES Units Value Symbol Formula

5.14.1 QpLDFg - Loss due to dry gas


Percent 02 in flue gas, dry basis (measured) % mass dry 2.37 MpO2
Percent of CO2 in flue gas, dry basis % mass dry 15.57 MpCO2
Percent of SO2 in flue gas, dry basis % mass dry 0.000 MpSO2
Percent N2 from fuel in flue gas, dry basis % mass dry 0.0083 MpN2f
Percent nitrogen (atmospheric) in flue gas, dry basis % mass dry 82.05 MpN2a
Exit gas temperature corrected to design conditions C 113.04 TFgLvCrd
Enthalpy of dry flue gas leaving, excluding Ieakage kJ/kg 114.46 HDFgLvCr
Enthalpy of dry flue gas at reference temperature kJ/kg 25.13 HDFgLvRef
Loss due to dry gas % 2.67 QpLDFg 100*'MqDFgEn*(HDFgLvCr-HDFgLvRef)

5.14.2 Water from fuel losses (%)


5.14.2.1 QpLH2F - Loss due to water formed from comb. of H2 in fuel
Water from combustion of hydrogen in fuel kg/kJ 0.00004012 MqWH2F
Enthalpy of steam at corr. exit gas temp. TFgLvCrd kJ/kg 2710.20 HStLvCr
Enthalpy of water at reference temperature Btu/lb 45.00 HWRe 9 / 5 * Tre + 32 - 32
Enthalpy of water at reference temperature kJ/kg 104.567 HWRe HWRe * 2,3237
Loss due to water from combustion of H2 in fuel % 10.45 QpLH2F 100 * MqWH2F * ( HStLvCr - HWRe )

5.14.2.3 QpLWF - Loss due to water in a gaseous fuel


Water from H20 in fuel kg/kJ 0.00000 MqWF
Enthalpy of steam at corr. exit gas temp. TFgLvCrd kJ/kg 2710.20 HStLvCr
Enthalpy of water at reference temperature Btu/lb 45.00
Enthalpy of water at reference temperature kJ/kg 104.57 HWRe
Loss due to water in fuel % 0.00000 QpLWF =100*MqWF*(HStLvCr-HWRe)

5.14.3 QpLWA - loss due to moisture in air (%)


Mass fraction of moisture in dry air kg/kg 0.012 MFrWDA
Mass of total dry air at A.H. outlet on input from fueI basis kg/kJ 0.0003206 MqDALv
Enthalpy of water at TFgLvCr kJ/kg 165.31 HWLvCr
Loss due to moisture in air % 0.062 QpLWA 100 * MFrWDA * MqDALv * HWLvCr
WEST DELTA ELECTRICITY PRODUCTION COMPANY ABU QIR THERMAL POWER PLANT UNITS 6 & 7
2 x 650 MW GAS/OIL FIRED UNITS GUARANTEED EFFICIENCY CALCULATION

Date 15/11/12
Time 10:30-12:00
Test n. 1
Load 100% GAS

LOSSES Units Value Symbol Formula

5.14.4.3 QpLCO - Loss due to carbon monoxide (CO) in flue gas (%)
Percent CO in flue gas at A.H. outlet wet basis % vol. dry 0.005 VpCOEn
Moles dry gas per mass fuel moles/kg 0.548 MoDFg
Molecular weight of carbon monoxide, CO kg/mole 28.01 MwCO
Higher heating value of carbon monoxide kJ/kg 10111 HHVCO
Higher heating value of fuel at constant pressure kJ/kg 55060 HHVF
Loss due to carbon monoxide (CO) in flue gas % 0.0141 QpLCO VpCOEn * MoDFg * MwCO * HHVCO / HHVF

5.14.8 QpLNOx - Loss due to the formation of NOx (%)


Heat of formation of NO kJ/kg 89850 HrNOx
Moles dry gas per mass fuel moles/kg 0.55 MoDFg
Quantity of NOx as NO on a dry basis % vol 0.0158 DVpNOx
Higher heating value of fuel at constant pressure kJ/kg 55060 HHVF
Loss due to the formation of NOx (%) % 0.0142 QpLNOx DvpNOx * MoDFg * HrNOx / HHVF

5.14.9 QpLSrc - Loss due to surface radiation and convection (%)


Convection heat transfer coefficient Btu/ft2 h F 0.74 Hcaz MAX ( 0,35 * Vaz ^ ( 4 / 5 ) ; 0.2 * Tdi ^ ( 1 / 3 ) )
2 0,847 + 0,00236 * Tdi + 0,00000294 * Tdi ^ 2 +
Radiation heat transfer coefficient Btu/ft h F 0.97 Hraz
0,00000000137 * Tdi ^ 3
2
Flat project surface area of the casing lagging over insulation ft 104983 Afz Afz m2 * 0,092903
m2 9753 Afz m2 MAX(0.35*E70^(4/5);0.2*E68^(1/3))
Temperature difference F 50 Tdi
Avarage velocity of air near surface ft/sec 1.67 Vaz
m/s 0.51 Vaz * 0,3048006096
Loss due to surface radiation and convection Btu/h 8972494 QrLSrc 0,74 + Hraz * Afz * ( Tdi )
Loss due to surface radiation and convection W 2629569 QrLSrc QrLSrc * 0,29307

5.19.04 Enthalpy of Water Vapor (Btu/lbm)


Coefficient for enthalpy calculation (from 200F to 1000F) C0 -34.1 C0
Coefficient for enthalpy calculation (from 200F to 1000F) C1 0.4408 C1
Coefficient for enthalpy calculation (from 200F to 1000F) C2 2.38E-05 C2
Coefficient for enthalpy calculation (from 200F to 1000F) C3 9.64E-09 C3
Exit gas temperature corrected to design conditions C 113.0396868 TFgLvCrd
Exit gas temperature corrected to design conditions F 235.4714363 TFgLvCrd 9 / 5 * TFgLvCrd + 32
C0 + C1 * TFgLvCrd + C2 * TFgLvCrd ^ 2 + C3 *
Enthalpy of Steam/Water at 1psia Btu/lbm 71.14 HWv
TFgLvCrd ^ 3
Enthalpy of Steam/Water at 1psia kJ/kg 165.31 HWv HWv * 2,3237
WEST DELTA ELECTRICITY PRODUCTION COMPANY ABU QIR THERMAL POWER PLANT UNITS 6 & 7
2 x 650 MW GAS/OIL FIRED UNITS GUARANTEED EFFICIENCY CALCULATION

Date 15/11/12
Time 10:30-12:00
Test n. 1
Load 100% GAS

LOSSES Units Value Symbol Formula

5.19.05 Enthalpy of Steam Water at 1 psia (Btu/lbm)


Coefficient for enthalpy calculation (from 200F to 1000F) C0 1062.2 C0
Coefficient for enthalpy calculation (from 200F to 1000F) C1 0.4329 C1
Coefficient for enthalpy calculation (from 200F to 1000F) C2 3.96E-05 C2
Exit gas temperature corrected to design conditions C 113.0 TFgLvCrd
Exit gas temperature corrected to design conditions F 235.5 TFgLvCrd 9 / 5 * TFgLvCrd + 32
Enthalpy of Steam/Water at 1psia Btu/lbm 1166.33 HWv C0 + C1 * TFgLvCrd + C2 * TFgLvCrd ^ 2
Enthalpy of Steam/Water at 1psia kJ/kg 2710.20 HWv HWv * 2,3237
WEST DELTA ELECTRICITY PRODUCTION COMPANY ABU QIR THERMAL POWER PLANT UNITS 6 & 7
2 x 650 MW GAS/OIL FIRED UNITS GUARANTEED EFFICIENCY CALCULATION

Date 15/11/12
Time 10:30-12:00
Test n. 1
Load 100% GAS

CREDITS Units Value Symbol

5.15.1 QpBDA - Credit due to Entering Dry Air (%)


Mass of total dry air at A.H. inlet on input from fueI basis kg/kJ 0.0003206 MqDALv
Enthalpy of dry air at the average entering air temperature TMnAEn kJ/kg 16.08 HDAEn
Enthalpy of dry air at Tref kJ/kg 0.00 HDATRef
Credit due to Entering Dry Air % 0.52 QpBDA 100 * MqDALv * ( HDAEn - HDATRef 9

5.15.2 QpBWA - Credit due to moist. in entering air (%)


Mass fraction of moisture In dry air, mass H20/mass dry air kg/kg 0.012 MFrWDA
Mass of total dry air at A.H. inlet on input from fueI basis kg/kJ 0.0003426 MqDALv
Enthalpy of water vapor at average entering air temperature TMnAEn kJ/kg 29.8 HWvEn
Average entering air temperature C 41 TMnAEn
Credit due to moisture in entering air % 0.012 QpBWA 100 * MFrWDA * MqDALv * HWvEn

5.19.10 Hk - Enthalpy Coefficients for Abbreviated JANA/NASA Correlation - Dry Air


Entering air temperature F 105.8 T ( T * 1,8 ) + 32
C 41 T
K 314.2 TK ( T * 459,7 ) / 1,8
Reference air temperature C 25 Tref
F 77 Tref ( Tref * 1,8 ) + 32
K 298.2 TrefK ( Tref * 459,7 ) / 1,8
Coefficient for dry air enthalpy calculation (from 255 K to 1000 K) C0 - -1.31E+02 C0
Coefficient for dry air enthalpy calculation (from 255 K to 1000 K) C1 - 4.58E-01 C1
Coefficient for dry air enthalpy calculation (from 255 K to 1000 K) C2 - -1.08E-04 C2
Coefficient for dry air enthalpy calculation (from 255 K to 1000 K) C3 - 1.78E-07 C3
Coefficient for dry air enthalpy calculation (from 255 K to 1000 K) C4 - -9.25E-11 C4
Coefficient for dry air enthalpy calculation (from 255 K to 1000 K) C5 - 1.68E-14 C5
C0 + C1 * TrefK + C2 * ( TrefK * 2 ) + C3 * ( TrefK * 3
Enthalpy of dry air at the reference entering air temperature Btu/lbm 0.00 Hkref
) + C4 * ( TrefK * 4 ) + C5 * ( TrefK * 5 )
kJ/kg 0.00 Hkref Hkref * 2,3237
C0 + C1 * TK + C2 * ( TK * 2 ) + C3 * ( TK * 3 ) + C4
Enthalpy of dry air at the average entering air temperature TMnAEn Btu/lbm 6.92 Hk
* ( TK * 4 ) + C5 * ( TK * 5 )
kJ/kg 16.08 Hk Hk * 2,3237
WEST DELTA ELECTRICITY PRODUCTION COMPANY ABU QIR THERMAL POWER PLANT UNITS 6 & 7
2 x 650 MW GAS/OIL FIRED UNITS GUARANTEED EFFICIENCY CALCULATION

Date 15/11/12
Time 10:30-12:00
Test n. 1
Load 100% GAS

CREDITS Units Value Symbol

5.19.8 HGF - Enthalpy of Natural Gas


Temperature of fuel at boiler inlet C 26 Tfuel
F 78.8 Tfuel ( Tfuel * 1,8 ) + 32
Reference air temperature C 25 Tref
F 77 Tref (Tref * 1,8 ) + 32
Coefficient for natural gas calculation (from 0F to 500F) C0 - -37.2 C0
Coefficient for natural gas calculation (from 0F to 500F) C1 - 0.4693 C1
Coefficient for natural gas calculation (from 0F to 500F) C2 - 1.75E-04 C2
Coefficient for natural gas calculation (from 0F to 500F) C3 - 4.33E-08 C3
Enthalpy of natural gas at the reference air temperature Btu/lbm -0.01 HGFref
C0 + C1 * Tref + C2 * ( Tref * 2 ) + C3 * ( Tref * 3 )
Enthalpy of natural gas at the reference air temperature kJ/kg -0.01 HGFref * 2,3237
Enthalpy of natural gas at boiler inlet Btu/lbm 8.90E-01 HGF
C0 + C1 * Tfuel + C2 * ( Tfuel * 2 ) + C3 * ( Tfuel * 3 )
Enthalpy of natural gas at boiler inlet kJ/kg 2.07E+00 HGF HGF * 2,3237

5.19.04 Enthalpy of Water Vapor (Btu/lbm)


Coefficient for enthalpy calculation (from 200F to 1000F) C0 -34.1 C0
Coefficient for enthalpy calculation (from 200F to 1000F) C1 0.4408 C1
Coefficient for enthalpy calculation (from 200F to 1000F) C2 2.38E-05 C2
Coefficient for enthalpy calculation (from 200F to 1000F) C3 9.64E-09 C3
Average entering air temperature C 41 TMnAEn
Exit gas temperature corrected to design conditions F 105.8 TFgLvCrd 9 / 5 * TMnAEn + 32
C0 + C1 * TFgLvCrd + C2 * ( TFgLvCrd * 2 ) + C3 * (
Enthalpy of Steam/Water at 1psia Btu/lbm 12.81 HWv
TFgLvCrd * 3 )
Enthalpy of Steam/Water at 1psia kJ/kg 29.81 HWv HWv * 2,326
WEST DELTA ELECTRICITY PRODUCTION COMPANY ABU QIR THERMAL POWER PLANT UNITS 6 & 7
2 x 650 MW GAS/OIL FIRED UNITS GUARANTEED EFFICIENCY CALCULATION

Date 15/11/12
Time 10:30-12:00
Test n. 1
Load 100% GAS

CREDITS Units Value Symbol Formula

Losses and Credits calculated on percent input from fuel


LOSSES
Loss due to dry gas 5.14.1 % 2.6680 QpLDFg
Loss due to water formed from combustion of H2 in fuel (%) 5.14.2.1 % 10.4526 QpLH2F
Loss due to water vapor in a gaseous fuel 5.14.2.3 % 0.0000 QpLWF
Loss due to moisture in air 5.14.3 % 0.0619 QpLWA
Loss due to carbon monoxide (CO) in flue gas 5.14.4.3 % 0.0141 QpLCO
Loss due to the formation of NOx 5.14.8 % 0.0142 QpLNOx
Total Losses calculated on percent input from fuel % 13.2108 SmQpL

CREDITS
Credit due to Entering Dry Air 5.15.1 % 0.52 QpBDA
Credit due to moisture in entering air 5.15.2 % 0.0119 QpBWA
Credit due to sensible heat in fuel 5.15.3 % 0.0038 QpBF
Total Credits calculated on percent input from fuel % 0.53 SmQpB

Losses and Credits calculated on percent input from fuel


LOSSES
Loss due to surface radiation and convection kW 2630 QrLSrc

CREDITS
Credit due to electricity driven equipment kW 1509.6 QrBX QX * EX

BOILER EFFICIENCY
(100-
Boiler efficiency % 87.25 EF SmQpL+SmQpB)*((QrO*1000)/(QrO*1000+(QrLSrc)-
(QrBX)))
WEST DELTA ELECTRICITY PRODUCTION COMPANY ABU QIR THERMAL POWER PLANT UNITS 6 & 7
2 x 650 MW GAS/OIL FIRED UNITS GUARANTEED EFFICIENCY CALCULATION

Date 15/11/12
Time 10:30-12:00
Test n. 1
Load 100% GAS

ADDITIONAL BOILER FUNCTIONAL AND EQUIPMENT TESTS Units Value Symbol Formula

RHEATER PRESURE DORP - CASE 2


Rehater flow kg/s 460.46 MrSt33

Cold reheater pressure bara 38.26 PSt33


Cold reheater temperature C 331.73 TSt33
Cold reheater specific volume m3/kg 0.067 vST33

Hot reheater pressure bara 36.88 PSt34


Hot reheater temperature C 565.69 TSt34
Hot reheater specific volume m3/kg 0.103 vST34

RH pressure drop bar 1.38 DPRHtest PSt26 - PSt34


Mean RH steam specific volume m3/kg 0.0849 vST3433 ( vST33 + vST34 ) / 2

Reference RH steam mass flow kg/s 459.530 MrSt33ref


Reference mean RH steam specific volume m3/kg 0.0796 vST3433ref

DPRHtest *( MrSt33ref / MrSt33) ^ 2 * (vST3433ref /


Corrected Total reheater pressure drop 1.29 DPRHcorr
bar vSt3433)
Additional Pressure drop at reference conditions bar 0.62
Final corrected RH pressure drop bar 0.67
Titolo Identificativo Rev. Pagina Di
title document no. rev. Page Of
ABU QIR THERMAL POWER PLANT 0 54 73
2 x 650 MW GAS / OIL FIRED UNIT 30390-A-M1008

7.1.2 Test #2
WEST DELTA ELECTRICITY PRODUCTION COMPANY ABU QIR THERMAL POWER PLANT UNITS 6 & 7
2 x 650 MW GAS/OIL FIRED UNITS GUARANTEED EFFICIENCY CALCULATION

Date 15/11/12
Time 12:00-13:30
Test n. 2
Load 100% GAS

INPUT DATA Unit Value Symbol Formula

Reference conditions
Reference air temperature C 25 Tre
Barometric pressure Pa 101732 Pa
Dry-bulb temperature at location 6 C 24.1 Tdb
Wet-bulb temperature at location 6 C 18.5 Twb
Relative humidity at Iocation 6 % 58.97 Rhm
Design entering air temperature C 41 TAEn

Design fuel data


Fuel type - G (G=Gas; O=Oil)
Higher heating value of fuel at constant volume kJ/kg 54995.0 HHVFcv
Higher heating value of fuel at constant pressure kJ/kg 55060.3 HHVF
Percent carbon in fuel % wt. 74.73 MpCF
Percent hydrogen in fuel % wt. 24.71 MpH2F
Nitrogen in fuel % wt. 0.15 MpN2F
Sulfur in fuel % wt. 0.00 MpSF
Oxygen in fuel % wt. 0.41 MpO2F
Percent water in fuel % wt. 0.00 MpH2OF
Percent ash in fuel % wt. 0.00 MpAsF
% 100.0 total

Flue gas data


At Air Heater inlet:
Measured percent O2 in flue gas at boiler inlet, dry basis % vol. dry 0.709 DVpO2En
Measured percent O2 in flue gas at boiler inlet, wet basis % vol. wet 0.58 VpO2En
Percent CO in flue gas, dry basis % vol. dry 0.0055 DVpCOEn
Quantity of NOx as NO % vol. dry 0.0161 DVpNOx

At Air Heater outlet:


Measured percent O2 in flue gas at A.H. outlet, dry basis % vol. dry 2.24 DVpO2Lv
WEST DELTA ELECTRICITY PRODUCTION COMPANY ABU QIR THERMAL POWER PLANT UNITS 6 & 7
2 x 650 MW GAS/OIL FIRED UNITS GUARANTEED EFFICIENCY CALCULATION

Date 15/11/12
Time 12:00-13:30
Test n. 2
Load 100% GAS

INPUT DATA Unit Value Symbol Formula

Measured flows
Mass flow rate of fuel kg/s 30.8 MrF
Additional water per mass fuel kg/s 0 MFrWAd
Mass flow rate of feedwater at boiler inlet kg/s 493.1 MrW24
Mass flow rate of superheated steam at boiler outlet kg/s 545.7 MrSt32
Mass flow rate of cold reheat kg/s 460.2 MrSt33
Mass flow rate of Blow Down kg/s 0.0 MrWbd
Mass flow rate of Sh spray water kg/s 52.5 MrW25
Mass flow rate of Rh spray water kg/s 0 MrW26

Fuel, air & flue gas temperatures


Temperature of fuel at boiler inlet C 26.0 Tfuel
Air heater entering air temperature C 34.9 TAEn
Temperature of wet air at Air Heater outlet C 326.5 TALv
Temperature of wet flue gas at Air Heater inlet C 351.2 TFgEn
Temperature of wet flue gas at A.H. outlet with leakage C 104.9 TFgLv
Temperature of wet flue gas at A.H. outlet without leakage C 108.5 TFgLCr
-> Change TFgLvCr (w/oL) untill 0 = 0.00
Water & steam temperatures
Water temperature at Economizer inlet C 273.2 TW24
Steam temperature at Superheater outlet C 542.4 TSt32
Water temperature at Sh attemperator inlet C 182.2 TW25
Steam temperature at cold Rh C 332.3 TSt33
Steam temperature at Reheater outlet C 566.3 TSt34
Water temperature at Rh attemperator inlet C 182.2 TW26

Water & steam pressures


Water pressure at SH attemperators bar abs. 201.7 PW25
Water pressure at Economizer inlet bar abs. 180.2 PW24
Drum pressure bar abs. 177.02 PSt31
Steam pressure at Superheater outlet bar abs. 168.2 PSt32
Water pressure at RH attemperators bar abs. 201.7 PW26
Cold reheater pressure bar abs. 38.24 PSt33
Hot reheater pressure bar abs. 36.85 PSt34

Auxiliaries absorbed power


Gas recirculating fan kW 1581.8 QX
Efficiency % 0.95 EX
WEST DELTA ELECTRICITY PRODUCTION COMPANY ABU QIR THERMAL POWER PLANT UNITS 6 & 7
2 x 650 MW GAS/OIL FIRED UNITS GUARANTEED EFFICIENCY CALCULATION

Date 15/11/12
Time: 12:00-13:30
Test n. 2
Load 100% GAS

OUTPUT Unit Value Symbol Formula

5.4 Energy balance


Main steam flow kg/s 545.7 MrSt32
Main steam pressure bar 168.2 PSt32
Main steam temperature C 542.4 TSt32
Main steam enthalpy kJ/kg 3409.7 HSt32
Feed water flow kg/s 493.1 MrW24
Feed water pressure bar 180.2 PW24
Feed water temperature C 273.2 TW24
Feed water enthalpy kJ/kg 1197.8 HW24
SH spray water flow kg/s 52.5 MrW25
SH spray water pressure bar 201.7 PW25
SH spray water temperature C 182.2 TW25
SH spray water enthalpy kJ/kg 782.8 HW25
Cold reheat flow kg/s 460.2 MrSt33
Cold reheat pressure bar 38.2 PSt26
Cold reheat temperature C 332.3 TSt33
Cold reheat enthalpy kJ/kg 3053.1 HSt33
Hot reheat flow kg/s 460.2 MrSt34
Hot reheat pressure bar 36.9 PSt34
Hot reheat temperature C 566.3 TSt34
Hot reheat enthalpy kJ/kg 3600.4 HSt34
RH spray water flow kg/s 0.0 MrW26
RH spray water pressure bar 201.7 PW26
RH spray water temperature C 182.2 TW26
RH spray water enthalpy kJ/kg 782.8 HW26

( MrSt32 * HSt32 - ( MrW24 * HW24 + MrW25 *


Total heat output MW 1480.6 QrO HW25 ) + MrSt34 * HSt34 - ( MrSt33 * HSt33 +
MrW26 * HW26 ) ) / 100
CAIRO ELECTRICITY PRODUCTION COMPANY ABU QIR THERMAL POWER PLANT UNITS 6 & 7
2 x 350 MW GAS/OIL FIRED UNITS GUARANTEED EFFICIENCY CALCULATION

Date 15/11/12
Time 12:00-13:30
Test n. 2
Load 100% GAS

A.H. INLET Units Value Symbol Formula

5.8 Fuel properties


Higher heating value of fuel at constant volume kJ/kg 54995.00 HHVFcv
Percent hydrogen in fuel % mass 24.71486254 MpH2F
HH value of fuel at constant pressure kJ/kg 55060.35 HHVF HHVFcv + 2,644 * MpH2F

5.10.2 Unburned carbon calculation


Mass of residue per unit volume at Air Heater outlet g. of residue/m3 0.00 MvRs
Mass flow rate of wet gas at Air Heater outlet kg/s 0 MrFgLv
Density of wet ftue gas at Air Heater outlet kg/m3 0.823 DnFgLv
Mass flow rate of residue at air heater outlet kg/s 0.000 MrRsLv ( MvRs * MrFgLv ) / ( 1000 * DnFgLv )
Mass flow rate of fuel kg/s 30.8 MrF
Mass fraction of residue at Air Heater outlet per mass unit of fuel kg/kg 0.0000 MFrRsLv MrRsLv / MrF
Percent unburned carbon in residue at Air Heater outlet % mass 85 MpCRsLv
Percent of unburned carbon at A.H. outlet per mass unit of fuel % 0.00 MpUbC MFrRsLv * MpCRsLv
Percent carbon in fuel % mass 74.72860258 MpCF
Carbon burned % mass 74.73 MpCb MpUbC - MpCF

5.11.2 Moisture in air (kg/kg dry air)


Barometric pressure psi 14.47 Pa Pa * 14,22 / 100000
Dry-bulb temperature at location 6 F 75.38 Tdbz Tdb * 1,8 + 32
Wet-bulb temperature at location 6 F 65.33 Twbz Twb * 1,8 + 32
C1 - 1.93E-02 -
C2 - 1.29E-03 -
C3 - 1.21E-05 -
C4 - 4.53E-07 -
C5 - 6.84E-11 -
C6 - 2.20E-11 -
C1 + C2 * Twbz + C3 * ( Twbz * 2 ) + C4 * ( Twbz * 3
Saturation pressure of water vapor at wet-bulb temperature psia 3.09E-01 PsWTwb
) + C5 * ( Twbz * 4 ) + C6 * ( Twbz * 5 )
PsWTwb - ( Pa - PsWTwb ) * ( Tdbz - Twbz ) / (
Partial pressure of water vapor in air - 0.257 PpWvA
2830 - 1,44 * Twbz )
Mass fraction of moisture In dry air, mass H20/mass dry air kg/kg dry air 0.011 MFrWDA 0,622 * ( PpWvA / ( Pa - PpWvA ) )
CAIRO ELECTRICITY PRODUCTION COMPANY ABU QIR THERMAL POWER PLANT UNITS 6 & 7
2 x 350 MW GAS/OIL FIRED UNITS GUARANTEED EFFICIENCY CALCULATION

Date 15/11/12
Time 12:00-13:30
Test n. 2
Load 100% GAS

A.H. INLET Units Value Symbol Formula

5.11.3 Theoretical air calculation (corrected)


Carbon burned on a mass percentage basis % mass 74.73 MpCb
Percent hydrogetn in fuet % mass 24.71486254 MpH2F
Sulfur in fuel % mass 0.0 MpSF
Sutfur capture ratio kg/kg 0 MFrSc
Oxygen in fuel % mass 0.411340238 MpO2F
0,1151 * MpCb + 0,343 * MpH2F + 0,0431 * MpSF *
Mass of theoretical air corrected on input from fuel basis kg/kg fuel as fired 17.06 MFrThACr
( 1 + 0,5 * MFrSc ) - 0,0432 * MpO2F
Moles of theoretical air required (corrected) moles/kg as fired fuel 0.5891 MoThACr MFrThACr / 28,963
Theoretical air corrected on input from fuel basis kg/kJ 0.000310 MqThACr MFrThACr / HHVF

5.11.4.1 Percent excess air at Air Heater inlet


Measured percent 02 in flue gas at A.H. inlet, dry basis % volume dry 0.71 MoThACr
Carbon burned on a mass percentage basis % mass 74.73 MpCb
Sutfur capture ratio kg/kg 0 MFrSc
Sulfur in fuel % mass 0 MpSF
Nitrogen In fuel % mass 0.145194639 MpN2F
Moles of dry gas (CO2) from sorbent per mass fuel moles/mass fuel 0 MoCO2Sb
MpCb / 1201 + ( 1 - MFrSc ) * MpSF / 3206,4 +
Moles dry products from fuel (CO2, N2F, and actual SO2 produced) moles/mass fuel 0.062 MoDPc
MpN2F / 2801,3 + MoCO2Sb
100 * ( DVpO2 * ( MoDPc + 0,7905 * MoThACr ) ) / (
Percent excess air at Air Heater inlet % 3.14 XpAEn
MoThACr * ( 20,95 - MoThACr ) )

5.11.4.2 Calculation of DVpO2, DVpCO2, DVpSO2, DVpN2f and DVpN2a on a dry basis (%vol. dry)
Moles dry gas per mass fuel moles/mass fuel 0.55 MoDFg MoDPc + MoThACr * ( 0,7905 + XpAEn / 100 )
Percent 02 in flue gas, dry basis (measured) % volume dry 0.709 DVpO2
Percent of CO2 in flue gas, dry basis % volume dry 11.39 DVpCO2 ( MpCb / 12,01 + 100 * MoCO2Sb ) / MoDFg
Percent of SO2 in flue gas, wet basis % volume dry 0.0000 DVpSO2 MpSF / 32,064 * ( 1 - 0 ) ) / MoDFg
Percent N2 from fuel in flue gas, wet basis % volume dry 0.0095 DVpN2f ( MpN2F / 28,013 ) / MoDFg
Percent nitrogen (atmospheric) in flue gas, dry basis % volume dry 87.89 DVpN2a 100 - DVpO2En - DVpCO2 - DVpSO2 - DVpN2f

100.00 DVpO2 + DVpCO2 + DVpSO2 + DVpN2f + DVpN2a


CAIRO ELECTRICITY PRODUCTION COMPANY ABU QIR THERMAL POWER PLANT UNITS 6 & 7
2 x 350 MW GAS/OIL FIRED UNITS GUARANTEED EFFICIENCY CALCULATION

Date 15/11/12
Time 12:00-13:30
Test n. 2
Load 100% GAS

A.H. INLET Units Value Symbol Formula

5.11.4.4 Calculation of VpO2, VpCO2, VpSO2, VpN2f and VpN2a on a wet basis (%vol. wet)
MoDPc + ( MpH2F / 201,6 ) + MpH2OF / 1801,5 +
MoDPc plus moles H2O frorn fuel, sorbent and any additional moisture moles/mass fuel 0.185 MoWPc
MFrWAd / 18,15
Moles of moisture in air moles/kg air 0 XpAEn 1,608 * MFrWAd
MoWPc + MoThACr * ( 0,7905 + MoWA + XpAEn /
Moles of wet gas per mass fuel moles/mass fuel as fired 0.669 MoFg
100 ) * ( 1+ XpAEn ) )
Percent O2 in flue gas, wet basis % volume wet 0.579 VpO2 ( XpAEn * MoThACr * 0,2095 / MoFg )
Percent of CO2 in flue gas, wet basis % volume wet 9.301 VpCO2 ( MpCb / 12,01 ) / MoFg
Percent of SO2 in flue gas, wet basis % volume wet 0.0000 VpSO2 ( MpSF / 32,064 ) / MoFg
( MpH2F / 2,016 + MpH2OF / 18,015 + MFrWAd /
Percent water in flue gas, wet basis % volume wet 18.32 VpH2O 18,015 + ( 100 + XpAEn ) * MoThACr * XpAEn ) /
MoFg
Percent N2 from fuel in flue gas, wet basis % volume wet 0.008 VpN2f ( MpN2F / 28,013 ) / MoFg
Percent N2 (atmospheric) in flue gas, wet basis % volume wet 71.79 VpN2a 100 - VpO2 - VpCO2 - VpSO2 - VpH2O - VpN2f
VpO2 + VpCO2 + VpSO2 + VpH2O + VpN2f +
100.00
VpN2a
CAIRO ELECTRICITY PRODUCTION COMPANY ABU QIR THERMAL POWER PLANT UNITS 6 & 7
2 x 350 MW GAS/OIL FIRED UNITS GUARANTEED EFFICIENCY CALCULATION

Date 15/11/12
Time 12:00-13:30
Test n. 2
Load 100% GAS

A.H. INLET Units Value Symbol Formula

5.11.5 MqDALv - Dry air at Air Heater inlet


Mass of total dry air at A.H. outlet on input from fueI basis kg/kJ 0.0003196 MqDALv MqThACr * ( 1+ XpAEn / 100 )
Mass of total air corrected on input from fuel basis kg/kg fuel as fired 17.60 MFrDALv MFrThACr * ( 1+ XpAEn / 100 )

5.11.06 MrALv - Wet air at Air Heater inlet (kg/s)


Mass of total wet air at Air Heater outlet on input from fueI basis kg/kJ 0.00032 MqALv ( 1 + MFrWDA ) * MqDALv
Potential energy of combustion available from fuel kW 1695859 QrF MrF * HHVF
Mass flow rate of wet air at A.H. inlet kg/s 548.07 MrALv MqALv * QrF

5.12.00 Flue gas products at Air Heater inlet


5.12.01 Wet gas from fuel at A. H. inlet on fuel input basis
Wet gas from fuel kg/kJ 0.0000182 MqFgF ( 100 - MpAsF - MpUbC ) / ( 100 * HHVF )

5.12.2 Moisture from water in fuel


Moisture from water in fuel kg/kJ 0.000000000 MqWF MpH2OF / ( 100 * HHVF )

5.12.3 Water from combustion of hydrogen in fuel


Water from combustion of hydrogen in fuel kg/kJ 0.0000401 MqWH2F ( 8,937 * MpH2F ) / ( 100 * HHVF )

5.12.6 Water from moisture in air at A. H. inlet


Water from moisture in air kg/kJ 0.00000 MqWALv MFrWDA * MqDALv

5.12.8 Total moisture in flue gas at A.H. inlet on fuel input basis
Total moisture in flue gas at A. H. inlet on fuel input basis kg/kJ 0.000044 MqWFgEn MqWF + MqWH2F + MqWALv

5.12.9 Mass of wet gas at A. H. inlet on input from fuel basis


Mass of wet gas at A. H. inlet on input from fuel basis kg/kJ 0.00034 MqFgEn MqDALv + MqWALv + MqFgF

5.12.10 Dry flue gas weight at A. H. inlet on input from fuel basis
Mass dry gas at A.H. inlet on input from fueI basis kg/kJ 0.00029763 MqDFgEn MqFgEn - MqWFgEn

5.12.11 Moisture in flue gas at A. H. inlet, percent of wet flue gas


Moisture in flue gas at A.H. inlet, percent of wet flue gas % mass 12.81 MpWFgEn 100 * ( MqWFgEn / MqFgEn )
WEST DELTA ELECTRICITY PRODUCTION COMPANY ABU QIR THERMAL POWER PLANT UNITS 6 & 7
2 x 650 MW GAS/OIL FIRED UNITS GUARANTEED EFFICIENCY CALCULATION

Date 15/11/12
Time 12:00-13:30
Test n. 2
Load 100% GAS

A.H. OUTLET Units Value Symbol Formula

5.08.00 Fuel properties


Higher heating value of fuel at constant volume kJ/kg 54995.00 NHVFcv
Percent hydrogen in fuel % mass 24.71486254 MpH2F
HH value of fuel at constant pressure kJ/kg 55060.3 HHVF HHVFcv + 2,644 * MpH2F

5.11.12 Moisture in air (kg/kg dry air)


Barometric pressure psi 14.47 Pa Pa * 14,22 / 100000
Dry-bulb temperature at location 6 F 75.38 Tdbz Tdb * 1,8 + 32
Wet-bulb temperature at location 6 F 65.33 Twbz Twb * 1,8 + 32
C1 1.93E-02 -
C2 1.29E-03 -
C3 1.21E-05 -
C4 4.53E-07 -
C5 6.84E-11 -
C6 2.20E-11 -
C1 + C2 * Twbz + C3 * ( Twbz * 2 ) + C4 * ( Twbz *
Saturation pressure of water vapor at wet-bulb temperature 3.09E-01 PsWTwb
3 ) + C5 * ( Twbz * 4 ) + C6 * ( Twbz * 5 )
PsWTwb - ( Pa - PsWTwb ) * ( Tdbz - Twbz ) / (
Partial pressure of water vapor in air 0.257 PpWvA
2830 - 1,44 * Twbz )
Mass fraction of moisture In dry air, mass H20/mass dry air kg/kg dry air 0.011 MFrWDA 0,622 * ( PpWvA / ( Pa - PpWvA ) )

5.11.3 Theoretical air calculation (corrected)


Carbon burned on a mass percentage basis % mass 74.73 MpCb
Percent hydrogetl in fuet % mass 24.71486254 MpH2F
Sulfur in fuel % mass 0.0 MpSF
Sutfur capture ratio kg/kg 0 MFrSc
Oxygen in fuel % mass 0.41 MpO2F
0,1151 * MpCb + 0,343 * MpH2F + 0,0431 * MpSF *
Mass of theoretical air corrected on input from fuel basis kg/kg fuel as fired 17.06 MFrThACr
( 1 + 0,5 * MFrSc ) - 0,0432 * MpO2F
moles/kg as fired
Moles of theoretical air required (corrected) 0.5891 MoThACr MFrThACr / 28,963
fuel
Theoretical air corrected on input from fuel basis kg/kJ 0.000310 MqThACr MFrThACr / HHVF
WEST DELTA ELECTRICITY PRODUCTION COMPANY ABU QIR THERMAL POWER PLANT UNITS 6 & 7
2 x 650 MW GAS/OIL FIRED UNITS GUARANTEED EFFICIENCY CALCULATION

Date 15/11/12
Time 12:00-13:30
Test n. 2
Load 100% GAS

A.H. OUTLET Units Value Symbol Formula

5.11.4.1 Percent excess air at Air Heater outlet


Measured percent 02 in flue gas at A.H. inlet, dry basis % volume dry 2.24 DVpO2
Carbon burned on a mass percentage basis % mass 74.73 MpCb
Sutfur capture ratio (kg/kg) 0 MFrSc
Sulfur in fuel % mass 0 MpSF
Nitrogen In fuel % mass 0.145194639 MpN2F
Moles of dry gas (CO2) from sorbent per mass fuel moles/mass fuel 0 MoCO2Sb
MpCb / 1201 + ( 1 - MFrSc ) * MpSF / 3206,4 +
Moles dry products from fuel (CO2, N2F, and actual SO2 produced) moles/mass fuel 0.0626 MoDPc
MpN2F / 2801,3 + MoCO2Sb
100 * ( DVpO2 * ( MoDPc + 0,7905 * MoThACr ) ) / (
Percent excess air at Air Heater outlet % 10.72 XpALv
MoThACr * ( 20,95 - MoThACr ) )

5.11.4.2 Calculation of DVpO2, DVpCO2, DVpSO2, DVpN2f


and DVpN2a on a dry basis (%vol. dry)
Moles dry gas per mass fuel moles/mass fuel 0.591 MoDFg MoDPc + MoThACr * ( 0,7905 + XpAEn / 100 )
Percent 02 in flue gas, dry basis (measured) % volume dry 2.237 DVpO2
Percent of CO2 in flue gas, dry basis % volume dry 10.52 DVpCO2 ( MpCb / 12,01 + 100 * MoCO2Sb ) / MoDFg
Percent of SO2 in flue gas, dry basis % volume dry 0.00000 DVpSO2 MpSF / 32,064 * ( 1 - 0 ) ) / MoDFg
Percent N2 from fuel in flue gas, dry basis % volume dry 0.00876 DVpN2f ( MpN2F / 28,013 ) / MoDFg
Percent nitrogen (atmospheric) in flue gas, dry basis % volume dry 87.23 DVpN2a 100 - DVpO2En - DVpCO2 - DVpSO2 - DVpN2f
Flue gas dry composition at air heater outlet: 100.00 DVpO2 + DVpCO2 + DVpSO2 + DVpN2f + DVpN2a
WEST DELTA ELECTRICITY PRODUCTION COMPANY ABU QIR THERMAL POWER PLANT UNITS 6 & 7
2 x 650 MW GAS/OIL FIRED UNITS GUARANTEED EFFICIENCY CALCULATION

Date 15/11/12
Time 12:00-13:30
Test n. 2
Load 100% GAS

A.H. OUTLET Units Value Symbol Formula

5.11.4.4 Calculation of VpO2, VpCO2, VpSO2, VpN2f and


VpN2a on a wet basis (%vol. wet)
MoDPc + ( MpH2F / 201,6 ) + MpH2OF / 1801,5 +
MoDPc plus moles H2O frorn fuel, sorbent and any additional moisture moles/mass fuel 0.185 MoWPc
MFrWAd / 18,15
Moles of moisture in air moles/kg air 0 MoWA 1,608 * MFrWAd
moles/mass fuel as MoWPc + MoThACr * ( 0,7905 + MoWA + XpAEn /
Moles of wet gas per mass fuel 0.714 MoFg
fired 100 ) * ( 1+ XpAEn ) )
Percent O2 in flue gas, wet basis % volume wet 1.853 VpO2 ( XpAEn * MoThACr * 0,2095 / MoFg )
Percent of CO2 in flue gas, wet basis % volume wet 8.715 VpCO2 ( MpCb / 12,01 ) / MoFg
Percent of SO2 in flue gas, wet basis % volume wet 0.0000 VpSO2 ( MpSF / 32,064 ) / MoFg
( MpH2F / 2,016 + MpH2OF / 18,015 + MFrWAd /
Percent water in flue gas, wet basis % volume wet 17.17 VpH2O 18,015 + ( 100 + XpAEn ) * MoThACr * XpAEn ) /
MoFg
Percent N2 from fuel in flue gas, wet basis % volume wet 0.007 VpN2f ( MpN2F / 28,013 ) / MoFg
Percent N2 (atmospheric) in flue gas, wet basis % volume wet 72.25 VpN2a 100 - VpO2 - VpCO2 - VpSO2 - VpH2O - VpN2f
VpO2 + VpCO2 + VpSO2 + VpH2O + VpN2f +
Flue gas wet composition at air heater outlet: 100.00
VpN2a

5.11.05 MqDALv - Dry air at Air Heater outlet


Mass of total dry air at A.H. outlet on input from fueI basis kg/kJ 0.0003431 MqDALv MqThACr * ( 1+ XpAEn / 100 )
Mass of total air corrected on input from fuel basis kg/kg fuel as fired 18.89 MFrDALv MFrThACr * ( 1+ XpAEn / 100 )

5.11.06 MrALv - Wet air at Air Heater outlet (kg/s)


Mass of total wet air at Air Heater outlet on input from fueI basis kg/kJ 0.00035 MqALv ( 1 + MFrWDA ) * MqDALv
Potential energy of combustion available from fuel kW 1695859 QrF MrF * HHVF
Mass flow rate of wet air at A.H. outlet kg/s 588.33 MrALv MqALv * QrF
WEST DELTA ELECTRICITY PRODUCTION COMPANY ABU QIR THERMAL POWER PLANT UNITS 6 & 7
2 x 650 MW GAS/OIL FIRED UNITS GUARANTEED EFFICIENCY CALCULATION

Date 15/11/12
Time 12:00-13:30
Test n. 2
Load 100% GAS

A.H. OUTLET Units Value Symbol Formula

5.12 Flue gas products at Air Heater outlet


5.12.01 Wet gas from fuel at A. H. inlet on fuel input basis

Wet gas from fuel kg/kJ 0.0000182 MqFgF ( 100 - MpAsF - MpUbC ) / ( 100 * HHVF )
5.12.2 Moisture from water in fuel
Moisture from water in fuel kg/kJ 0.000000000 MqWF
MpH2OF / ( 100 * HHVF )
5.12.3 Water from combustion of hydrogen in fuel
Water from combustion of hydrogen in fuel kg/kJ 0.0000401 MqWH2F ( 8,937 * MpH2F ) / ( 100 * HHVF )

5.12.6 Water from moisture in air at Air Heater outlet


Water from moisture in air kg/kJ 0.00000 MqWALv MFrWDA * MqDALv

5.12.8 Total moisture in flue gas at A. H. outlet on fuel input


basis
Total moisture in flue gas at A. H. outlet on fuel input basis kg/kJ 0.000044 MqWFgEn MqWF + MqWH2F + MqWALv

5.12.9 Mass of wet gas at A. H. outlet on input from fuel


basis
Mass of wet gas at A. H. outlet on input from fuel basis kg/kJ 0.0004 MqFgLv MqDALv + MqWALv + MqFgF

5.12.10 Dry flue gas weight at A. H. outlet on input from fuel


basis
Mass dry gas at A.H. outlet on input from fueI basis kg/kJ 0.0003 MqDFgEn MqFgEn - MqWFgEn
WEST DELTA ELECTRICITY PRODUCTION COMPANY ABU QIR THERMAL POWER PLANT UNITS 6 & 7
2 x 650 MW GAS/OIL FIRED UNITS GUARANTEED EFFICIENCY CALCULATION

Date 15/11/12
Time 12:00-13:30
Test n. 2
Load 100% GAS

A.H. OUTLET Units Value Symbol Formula

5.12.11 Moisture in flue gas at A. H. outlet, percent of wet


flue gas
Moisture in flue gas at A.H. outlett, percent of wet flue gas % mass 12.04 MpWFgEn 100 * ( MqWFgEn / MqFgEn )

5.13 Air and flue gas temperature


5.13.1 T Re - Reference temperature
Reference temperature C 25 T Re

5.13.2 Average entering air temperature (C)


Average entering air temperature C 34.9 TMnAEn

5.13.03 TFgLvCr - Corrected Gas Outlet Temperature


Air temperature entering the air heater C 34.9 TAEn
Gas Temperature leaving the air heater C 104.9 TFgLV
Mean specific heat of wet air between TAEn and TFgLv kJ/kg 1.03 MnCpA
Mean specific heat of wet flue gas between TGLv and TFgLvCr kJ/kg 1.38 MnCpFg
Wet gas weight leaving the air heater kg/kJ 0.00037 MqFgLv
Wet gas weight entering the air heater kg/kJ 0.00034 MqFgEn
TFgLV + ( MnCpA / MnCpFg ) * ( MqFgLv / MqFgEn
Corrected Gas Outlet Temperature (Excluding Leakage) C 108.5 TFgLvCr
- 1 ) * ( TFgLV - TAEn )

5.18.2.2 Regenerative air heater corrections


( ( TAEn * ( TFgEn - TFgLv ) + TFgEn * ( TFgLv -
A.H.r temperature correction for entering air temperature C 4.771 TDiTAEn
TAEn ) ) / ( TFgEn - TAEn ) ) - TFgLv
A. H.r temperature correction for entering gas temperature C 0 TDiFgEn
A.H. temperature correction for entering gas mass flow C 0 TDiMrFgEn
A.H. temperature corrected for off design X-ratio C 0 TDiXr
TFgLCr + TDiTAEn + TDiFgEn + TDiMrFgEn +
Exit gas temperature corrected to design conditions C 113.3 TFgLvCrd
TDiXr
WEST DELTA ELECTRICITY PRODUCTION COMPANY ABU QIR THERMAL POWER PLANT UNITS 6 & 7
2 x 650 MW GAS/OIL FIRED UNITS GUARANTEED EFFICIENCY CALCULATION

Date 15/11/12
Time 12:00-13:30
Test n. 2
Load 100% GAS

LOSSES Units Value Symbol Formula

5.14.1 QpLDFg - Loss due to dry gas


Percent 02 in flue gas, dry basis (measured) % mass dry 2.40 MpO2
Percent of CO2 in flue gas, dry basis % mass dry 15.55 MpCO2
Percent of SO2 in flue gas, dry basis % mass dry 0.000 MpSO2
Percent N2 from fuel in flue gas, dry basis % mass dry 0.0082 MpN2f
Percent nitrogen (atmospheric) in flue gas, dry basis % mass dry 82.04 MpN2a
Exit gas temperature corrected to design conditions C 113.29 TFgLvCrd
Enthalpy of dry flue gas leaving, excluding Ieakage kJ/kg 114.72 HDFgLvCr
Enthalpy of dry flue gas at reference temperature kJ/kg 25.13 HDFgLvRef
Loss due to dry gas % 2.67 QpLDFg 100*'MqDFgEn*(HDFgLvCr-HDFgLvRef)

5.14.2 Water from fuel losses (%)


5.14.2.1 QpLH2F - Loss due to water formed from comb. of H2 in fuel
Water from combustion of hydrogen in fuel kg/kJ 0.00004012 MqWH2F
Enthalpy of steam at corr. exit gas temp. TFgLvCrd kJ/kg 2710.67 HStLvCr
Enthalpy of water at reference temperature Btu/lb 45.00 HWRe 9 / 5 * Tre + 32 - 32
Enthalpy of water at reference temperature kJ/kg 104.567 HWRe HWRe * 2,3237
Loss due to water from combustion of H2 in fuel % 10.45 QpLH2F 100 * MqWH2F * ( HStLvCr - HWRe )

5.14.2.3 QpLWF - Loss due to water in a gaseous fuel


Water from H20 in fuel kg/kJ 0.00000 MqWF
Enthalpy of steam at corr. exit gas temp. TFgLvCrd kJ/kg 2710.67 HStLvCr
Enthalpy of water at reference temperature Btu/lb 45.00
Enthalpy of water at reference temperature kJ/kg 104.57 HWRe
Loss due to water in fuel % 0.00000 QpLWF =100*MqWF*(HStLvCr-HWRe)

5.14.3 QpLWA - loss due to moisture in air (%)


Mass fraction of moisture in dry air kg/kg 0.011 MFrWDA
Mass of total dry air at A.H. outlet on input from fueI basis kg/kJ 0.0003196 MqDALv
Enthalpy of water at TFgLvCr kJ/kg 165.78 HWLvCr
Loss due to moisture in air % 0.060 QpLWA 100 * MFrWDA * MqDALv * HWLvCr
WEST DELTA ELECTRICITY PRODUCTION COMPANY ABU QIR THERMAL POWER PLANT UNITS 6 & 7
2 x 650 MW GAS/OIL FIRED UNITS GUARANTEED EFFICIENCY CALCULATION

Date 15/11/12
Time 12:00-13:30
Test n. 2
Load 100% GAS

LOSSES Units Value Symbol Formula

5.14.4.3 QpLCO - Loss due to carbon monoxide (CO) in flue gas (%)
Percent CO in flue gas at A.H. outlet wet basis % vol. dry 0.005 VpCOEn
Moles dry gas per mass fuel moles/kg 0.546 MoDFg
Molecular weight of carbon monoxide, CO kg/mole 28.01 MwCO
Higher heating value of carbon monoxide kJ/kg 10111 HHVCO
Higher heating value of fuel at constant pressure kJ/kg 55060 HHVF
Loss due to carbon monoxide (CO) in flue gas % 0.0154 QpLCO VpCOEn * MoDFg * MwCO * HHVCO / HHVF

5.14.8 QpLNOx - Loss due to the formation of NOx (%)


Heat of formation of NO kJ/kg 89850 HrNOx
Moles dry gas per mass fuel moles/kg 0.55 MoDFg
Quantity of NOx as NO on a dry basis % vol 0.0161 DVpNOx
Higher heating value of fuel at constant pressure kJ/kg 55060 HHVF
Loss due to the formation of NOx (%) % 0.0143 QpLNOx DvpNOx * MoDFg * HrNOx / HHVF

5.14.9 QpLSrc - Loss due to surface radiation and convection (%)


Convection heat transfer coefficient Btu/ft2 h F 0.74 Hcaz MAX ( 0,35 * Vaz ^ ( 4 / 5 ) ; 0.2 * Tdi ^ ( 1 / 3 ) )
2 0,847 + 0,00236 * Tdi + 0,00000294 * Tdi ^ 2 +
Radiation heat transfer coefficient Btu/ft h F 0.97 Hraz
0,00000000137 * Tdi ^ 3
2
Flat project surface area of the casing lagging over insulation ft 104983 Afz Afz m2 * 0,092903
m2 9753 Afz m2 MAX(0.35*E70^(4/5);0.2*E68^(1/3))
Temperature difference F 50 Tdi
Avarage velocity of air near surface ft/sec 1.67 Vaz
m/s 0.51 Vaz * 0,3048006096
Loss due to surface radiation and convection Btu/h 8972494 QrLSrc 0,74 + Hraz * Afz * ( Tdi )
Loss due to surface radiation and convection W 2629569 QrLSrc QrLSrc * 0,29307

5.19.04 Enthalpy of Water Vapor (Btu/lbm)


Coefficient for enthalpy calculation (from 200F to 1000F) C0 -34.1 C0
Coefficient for enthalpy calculation (from 200F to 1000F) C1 0.4408 C1
Coefficient for enthalpy calculation (from 200F to 1000F) C2 2.38E-05 C2
Coefficient for enthalpy calculation (from 200F to 1000F) C3 9.64E-09 C3
Exit gas temperature corrected to design conditions C 113.2885347 TFgLvCrd
Exit gas temperature corrected to design conditions F 235.9193625 TFgLvCrd 9 / 5 * TFgLvCrd + 32
C0 + C1 * TFgLvCrd + C2 * TFgLvCrd ^ 2 + C3 *
Enthalpy of Steam/Water at 1psia Btu/lbm 71.35 HWv
TFgLvCrd ^ 3
Enthalpy of Steam/Water at 1psia kJ/kg 165.78 HWv HWv * 2,3237
WEST DELTA ELECTRICITY PRODUCTION COMPANY ABU QIR THERMAL POWER PLANT UNITS 6 & 7
2 x 650 MW GAS/OIL FIRED UNITS GUARANTEED EFFICIENCY CALCULATION

Date 15/11/12
Time 12:00-13:30
Test n. 2
Load 100% GAS

LOSSES Units Value Symbol Formula

5.19.05 Enthalpy of Steam Water at 1 psia (Btu/lbm)


Coefficient for enthalpy calculation (from 200F to 1000F) C0 1062.2 C0
Coefficient for enthalpy calculation (from 200F to 1000F) C1 0.4329 C1
Coefficient for enthalpy calculation (from 200F to 1000F) C2 3.96E-05 C2
Exit gas temperature corrected to design conditions C 113.3 TFgLvCrd
Exit gas temperature corrected to design conditions F 235.9 TFgLvCrd 9 / 5 * TFgLvCrd + 32
Enthalpy of Steam/Water at 1psia Btu/lbm 1166.53 HWv C0 + C1 * TFgLvCrd + C2 * TFgLvCrd ^ 2
Enthalpy of Steam/Water at 1psia kJ/kg 2710.67 HWv HWv * 2,3237
WEST DELTA ELECTRICITY PRODUCTION COMPANY ABU QIR THERMAL POWER PLANT UNITS 6 & 7
2 x 650 MW GAS/OIL FIRED UNITS GUARANTEED EFFICIENCY CALCULATION

Date 15/11/12
Time 12:00-13:30
Test n. 2
Load 100% GAS

CREDITS Units Value Symbol

5.15.1 QpBDA - Credit due to Entering Dry Air (%)


Mass of total dry air at A.H. inlet on input from fueI basis kg/kJ 0.0003196 MqDALv
Enthalpy of dry air at the average entering air temperature TMnAEn kJ/kg 16.08 HDAEn
Enthalpy of dry air at Tref kJ/kg 0.00 HDATRef
Credit due to Entering Dry Air % 0.51 QpBDA 100 * MqDALv * ( HDAEn - HDATRef 9

5.15.2 QpBWA - Credit due to moist. in entering air (%)


Mass fraction of moisture In dry air, mass H20/mass dry air kg/kg 0.011 MFrWDA
Mass of total dry air at A.H. inlet on input from fueI basis kg/kJ 0.0003431 MqDALv
Enthalpy of water vapor at average entering air temperature TMnAEn kJ/kg 29.8 HWvEn
Average entering air temperature C 41 TMnAEn
Credit due to moisture in entering air % 0.012 QpBWA 100 * MFrWDA * MqDALv * HWvEn

5.19.10 Hk - Enthalpy Coefficients for Abbreviated JANA/NASA Correlation - Dry Air


Entering air temperature F 105.8 T ( T * 1,8 ) + 32
C 41 T
K 314.2 TK ( T * 459,7 ) / 1,8
Reference air temperature C 25 Tref
F 77 Tref ( Tref * 1,8 ) + 32
K 298.2 TrefK ( Tref * 459,7 ) / 1,8
Coefficient for dry air enthalpy calculation (from 255 K to 1000 K) C0 - -1.31E+02 C0
Coefficient for dry air enthalpy calculation (from 255 K to 1000 K) C1 - 4.58E-01 C1
Coefficient for dry air enthalpy calculation (from 255 K to 1000 K) C2 - -1.08E-04 C2
Coefficient for dry air enthalpy calculation (from 255 K to 1000 K) C3 - 1.78E-07 C3
Coefficient for dry air enthalpy calculation (from 255 K to 1000 K) C4 - -9.25E-11 C4
Coefficient for dry air enthalpy calculation (from 255 K to 1000 K) C5 - 1.68E-14 C5
C0 + C1 * TrefK + C2 * ( TrefK * 2 ) + C3 * ( TrefK * 3
Enthalpy of dry air at the reference entering air temperature Btu/lbm 0.00 Hkref
) + C4 * ( TrefK * 4 ) + C5 * ( TrefK * 5 )
kJ/kg 0.00 Hkref Hkref * 2,3237
C0 + C1 * TK + C2 * ( TK * 2 ) + C3 * ( TK * 3 ) + C4
Enthalpy of dry air at the average entering air temperature TMnAEn Btu/lbm 6.92 Hk
* ( TK * 4 ) + C5 * ( TK * 5 )
kJ/kg 16.08 Hk Hk * 2,3237
WEST DELTA ELECTRICITY PRODUCTION COMPANY ABU QIR THERMAL POWER PLANT UNITS 6 & 7
2 x 650 MW GAS/OIL FIRED UNITS GUARANTEED EFFICIENCY CALCULATION

Date 15/11/12
Time 12:00-13:30
Test n. 2
Load 100% GAS

CREDITS Units Value Symbol

5.19.8 HGF - Enthalpy of Natural Gas


Temperature of fuel at boiler inlet C 26 Tfuel
F 78.8 Tfuel ( Tfuel * 1,8 ) + 32
Reference air temperature C 25 Tref
F 77 Tref (Tref * 1,8 ) + 32
Coefficient for natural gas calculation (from 0F to 500F) C0 - -37.2 C0
Coefficient for natural gas calculation (from 0F to 500F) C1 - 0.4693 C1
Coefficient for natural gas calculation (from 0F to 500F) C2 - 1.75E-04 C2
Coefficient for natural gas calculation (from 0F to 500F) C3 - 4.33E-08 C3
Enthalpy of natural gas at the reference air temperature Btu/lbm -0.01 HGFref
C0 + C1 * Tref + C2 * ( Tref * 2 ) + C3 * ( Tref * 3 )
Enthalpy of natural gas at the reference air temperature kJ/kg -0.01 HGFref * 2,3237
Enthalpy of natural gas at boiler inlet Btu/lbm 8.90E-01 HGF
C0 + C1 * Tfuel + C2 * ( Tfuel * 2 ) + C3 * ( Tfuel * 3 )
Enthalpy of natural gas at boiler inlet kJ/kg 2.07E+00 HGF HGF * 2,3237

5.19.04 Enthalpy of Water Vapor (Btu/lbm)


Coefficient for enthalpy calculation (from 200F to 1000F) C0 -34.1 C0
Coefficient for enthalpy calculation (from 200F to 1000F) C1 0.4408 C1
Coefficient for enthalpy calculation (from 200F to 1000F) C2 2.38E-05 C2
Coefficient for enthalpy calculation (from 200F to 1000F) C3 9.64E-09 C3
Average entering air temperature C 41 TMnAEn
Exit gas temperature corrected to design conditions F 105.8 TFgLvCrd 9 / 5 * TMnAEn + 32
C0 + C1 * TFgLvCrd + C2 * ( TFgLvCrd * 2 ) + C3 * (
Enthalpy of Steam/Water at 1psia Btu/lbm 12.81 HWv
TFgLvCrd * 3 )
Enthalpy of Steam/Water at 1psia kJ/kg 29.81 HWv HWv * 2,326
WEST DELTA ELECTRICITY PRODUCTION COMPANY ABU QIR THERMAL POWER PLANT UNITS 6 & 7
2 x 650 MW GAS/OIL FIRED UNITS GUARANTEED EFFICIENCY CALCULATION

Date 15/11/12
Time 12:00-13:30
Test n. 2
Load 100% GAS

CREDITS Units Value Symbol Formula

Losses and Credits calculated on percent input from fuel


LOSSES
Loss due to dry gas 5.14.1 % 2.6663 QpLDFg
Loss due to water formed from combustion of H2 in fuel (%) 5.14.2.1 % 10.4545 QpLH2F
Loss due to water vapor in a gaseous fuel 5.14.2.3 % 0.0000 QpLWF
Loss due to moisture in air 5.14.3 % 0.0596 QpLWA
Loss due to carbon monoxide (CO) in flue gas 5.14.4.3 % 0.0154 QpLCO
Loss due to the formation of NOx 5.14.8 % 0.0143 QpLNOx
Total Losses calculated on percent input from fuel % 13.2101 SmQpL

CREDITS
Credit due to Entering Dry Air 5.15.1 % 0.51 QpBDA
Credit due to moisture in entering air 5.15.2 % 0.0115 QpBWA
Credit due to sensible heat in fuel 5.15.3 % 0.0038 QpBF
Total Credits calculated on percent input from fuel % 0.53 SmQpB

Losses and Credits calculated on percent input from fuel


LOSSES
Loss due to surface radiation and convection kW 2630 QrLSrc

CREDITS
Credit due to electricity driven equipment kW 1502.7 QrBX QX * EX

BOILER EFFICIENCY
(100-
Boiler efficiency % 87.25 EF SmQpL+SmQpB)*((QrO*1000)/(QrO*1000+(QrLSrc)-
(QrBX)))
WEST DELTA ELECTRICITY PRODUCTION COMPANY ABU QIR THERMAL POWER PLANT UNITS 6 & 7
2 x 650 MW GAS/OIL FIRED UNITS GUARANTEED EFFICIENCY CALCULATION

Date 15/11/12
Time 12:00-13:30
Test n. 2
Load 100% GAS

ADDITIONAL BOILER FUNCTIONAL AND EQUIPMENT TESTS Units Value Symbol Formula

RHEATER PRESURE DORP - CASE 2


Rehater flow kg/s 460.17 MrSt33

Cold reheater pressure bara 38.24 PSt33


Cold reheater temperature C 332.31 TSt33
Cold reheater specific volume m3/kg 0.067 vST33

Hot reheater pressure bara 36.85 PSt34


Hot reheater temperature C 566.34 TSt34
Hot reheater specific volume m3/kg 0.103 vST34

RH pressure drop bar 1.38 DPRHtest PSt26 - PSt34


Mean RH steam specific volume m3/kg 0.0851 vST3433 ( vST33 + vST34 ) / 2

Reference RH steam mass flow kg/s 459.530 MrSt33ref


Reference mean RH steam specific volume m3/kg 0.0796 vST3433ref

DPRHtest *( MrSt33ref / MrSt33) ^ 2 * (vST3433ref /


Corrected Total reheater pressure drop 1.29 DPRHcorr
bar vSt3433)
Additional Pressure drop at reference conditions bar 0.62
Final corrected RH pressure drop bar 0.67