PROJECT CLIENT
30390-A-M1008 0 1 73
Informazioni strettamente riservate di propriet di Ansaldo Caldaie s.p.a. - Da non utilizzare per scopi diversi da quelli per cui sono state
fornite.
Confidential information, property of Ansaldo Caldaie s.p.a. Not to be used for any purpose other than that for which it is supplied.
Titolo Identificativo Rev. Pagina Di
title document no. rev. Page Of
ABU QIR THERMAL POWER PLANT 0 2 73
2 x 650 MW GAS / OIL FIRED UNIT 30390-A-M1008
TABLE OF CONTENTS
2. General
The performance guarantee test has been carried out with the following time schedule in
accordance with the Boiler performance test procedure 30390-A-M1007 Rev. 03.
The guarantees have been fulfilled with good margins, except than for auxiliary power
consumption, that is in any case well compensated by the other boiler over performances
(details are reported in the following chapters of the present document).
3. Result summary
3.1 Boiler capacity
Contract Load
Guarantee Comment Units Guarantee Meas. Comments
Par. No. [Mwe]
Minimum continuous main steam
2.1 Boiler capacity (case 2) 658.2 generating capacity at Turbine kg/s 544.9 545.8
Generator 100% load
Minimum continuous main steam Not a
- Boiler capacity (case 3) 688.0 kg/s 574.3 578.4
generating capacity at BMCR guarantee
Below are shown the thermal loads of case 2 and 3 tests. Both cases show higher thermal
load than design (Boiler Heat Output or BHO).
BMCR load!
Titolo Identificativo Rev. Pagina Di
title document no. rev. Page Of
ABU QIR THERMAL POWER PLANT 0 5 73
2 x 650 MW GAS / OIL FIRED UNIT 30390-A-M1008
In order to give an idea of the better performance we have converted the credits in
electrical power for MCR test load (gas firing).
For this purpose correction curves from Steam Turbine manufacturer has been used for
evaluating the corresponding kWe credits on ST side:
* See analysis in Par. 3.2.1 for correction on RH outlet temperature based on Cold RH inlet
Temperature, showing the fulfilment of the guaranteed value.
Titolo Identificativo Rev. Pagina Di
title document no. rev. Page Of
ABU QIR THERMAL POWER PLANT 0 6 73
2 x 650 MW GAS / OIL FIRED UNIT 30390-A-M1008
Gas Firing
BMCR *
Design Test BMCR
[C] [C]
Main steam Temp. out 541.8 539
Reheater steam Temp. out 565.8 564
* Steam Temperatures at case 3 were slightly below the guaranteed value, but it has to be
considered that:
Boiler Heat Output was higher than design one (measured 1552.1 MW vs. design
1517.0 MW)
The test duration was reduced, thus it was not possible to reach a stable load with
guaranteed parameters
Titolo Identificativo Rev. Pagina Di
title document no. rev. Page Of
ABU QIR THERMAL POWER PLANT 0 7 73
2 x 650 MW GAS / OIL FIRED UNIT 30390-A-M1008
The cold reheater flow during test was higher than design:
Design Test
Cold reheater flow [kg/s] 459.53 460.3
Cold reheater temperature during the test was 5.2C lower than design as shown in the
below table:
Design Test
Cold reheater temperature [C] 337.2 332
In the below table is shown the comparison between design and test RH power:
Design Test
Cold reheater temperature [C] 337.2 332.0
Cold reheater pressure [bara] 41.2 38.2
Cold reheater flow [kg/s] 459.5 460.3
Cold reheater enthalpy [kJ/kg] 3058.1 3052.3
Ratio
Reheater power absorbtion [MW] 248.94 251.95 101.2
Titolo Identificativo Rev. Pagina Di
title document no. rev. Page Of
ABU QIR THERMAL POWER PLANT 0 8 73
2 x 650 MW GAS / OIL FIRED UNIT 30390-A-M1008
During tests the heat absorption of RH coils was 1.2% higher than design.
As suggested by ASME PTC 4 paragraph 5.18.13 the temperature of HRH is considered
higher than guaranteed if tested RH heat absorption is higher than design.
In the below table the test HRH temperature has been changed in order to have the same
heat absorption as in design condition.
MCR
Design Corr. Test
Cold reheater temperature [C] 337.2 332.0
Cold reheater pressure [bara] 41.2 38.2
Cold reheater flow [kg/s] 459.5 460.3
Cold reheater enthalpy [kJ/kg] 3058.1 3052.3
Test Hot RH T = 566.0 > 563.15, therefore the guarantee has been fulfilled.
Nevertheless the increased flow through the GRF helped to enhance RH power absorption
leading to a HRH steam credit equal to 2.87C.
In order to give an idea of the better overall performance this temperature credit has been
converted into equivalent electrical power credits (kWe) on ST side by the means of
correction curves from Steam Turbine manufacturer:
Power Credit
with ST Corr.
Curves
C [kWe]
HRH temperature credit 2.87 1701
Titolo Identificativo Rev. Pagina Di
title document no. rev. Page Of
ABU QIR THERMAL POWER PLANT 0 9 73
2 x 650 MW GAS / OIL FIRED UNIT 30390-A-M1008
Tests are showing lower RH pressure drop than design. The above value has been
corrected to design condition (mass flow and density).
In order to give an idea of the better overall performance this credit has been converted
into equivalent electrical power credits (kWe) on ST side by the means of correction
curves from Steam Turbine manufacturer:
Power Credit
Design Test MCR with ST Corr.
Curves
[bar] [bar] [kWe]
Reheater pressure drop 1.90 0.67 1660
Please note that this credit itself is big enough to balance the entire over absorption in
auxiliary power, even the uncorrected value (Ref. Par. 3.6).
Titolo Identificativo Rev. Pagina Di
title document no. rev. Page Of
ABU QIR THERMAL POWER PLANT 0 10 73
2 x 650 MW GAS / OIL FIRED UNIT 30390-A-M1008
Tests are showing lower main steam pressure drop than design. The above value has
been corrected to design condition (mass flow and density).
Titolo Identificativo Rev. Pagina Di
title document no. rev. Page Of
ABU QIR THERMAL POWER PLANT 0 11 73
2 x 650 MW GAS / OIL FIRED UNIT 30390-A-M1008
Power Credit
Design Test MCR Balance Calc
[%] [%] [kWe]
Efficiency (corrected) 86.73 87.26 3962
Also in this case please note that this credit itself is more than enough for balancing the
entire over absorption in auxiliary power, even the uncorrected value (Ref. Par. 3.6).
Test #1 Test #2
measured measured
[%] [%]
Efficiency 87.25 87.25
The table is showing how the measured value is exactly the same for both the test carried
out. This means in principle that:
Please note that, since the test fuel gas analysis was in line with design one, the efficiency
resulting from Design Fuel and that from Test Fuel are exactly the same figure.
Even if not guaranteed below is shown the calculation for as tested efficiency at BMCR
firing gas.
Load
Description Comment Units Espected Meas. Delta
[Mwe]
As Tested Efficiency
firing gas at BMCR 688.0 105% TG % 86.69 87.19 0.50
(case 3)
Titolo Identificativo Rev. Pagina Di
title document no. rev. Page Of
ABU QIR THERMAL POWER PLANT 0 13 73
2 x 650 MW GAS / OIL FIRED UNIT 30390-A-M1008
Forced draft fan motor power - Left kW 3290 3449 159 3455 3444
Forced draft fan motor power - Right kW 3290 3723 433 3728 3718
Recirculating fan motor power - Left kW 410 810 400 812 809
Recirculating fan motor power - Right kW 410 775 365 777 773
As shown in above tables the measured power consumption is higher than the guaranteed
value, but we would like to highlight the following aspects.
Agreed correction curves (Ref. Boiler performance test procedure 30390-A-M1007
Rev. 03) reduce the measured value from 8818 kW to 8283 kW due to:
- 54 kW on FD Fans power absorption due to higher heat to steam
- 481 kW on GR Fans power absorption due to lower CRH steam
temperature
Please note that, according to Par. 4, the greater power consumption is more than
balanced by boiler over performances
Titolo Identificativo Rev. Pagina Di
title document no. rev. Page Of
ABU QIR THERMAL POWER PLANT 0 14 73
2 x 650 MW GAS / OIL FIRED UNIT 30390-A-M1008
Contract Load
Guarantee Comment Units Guarantee Measured
Par. No. [Mwe]
Maximum regenerative air
3.4 658.2 100% TG % 8 6.72
heater leakage (case 2, 10)
3.8 Emissions
3.8.1 Gas firing
Contract Load
Par. No.
Guarantee Comment Units Guarantee Meas.
[Mwe]
3
NOX flue gas emission limits when mg/Nm
221.4 At 25% TG - gas firing 320 213
firing natural gas (case 1) @ 3% O2
3
CO flue gas emission limits when mg/Nm
firing natural gas (case 1)
221.4 At 25% TG - gas firing 250 0
@ 3% O2
3
NOX flue gas emission limits when mg/Nm
658 At 100% TG - gas firing 320 290
firing natural gas (case 4) @ 3% O2
3.7 3
CO flue gas emission limits when mg/Nm
firing natural gas (case 4)
658 At 100% TG - gas firing 250 58
@ 3% O2
3
NOX flue gas emission limits when mg/Nm
688.0 At BMCR TG - gas firing 320 310
firing natural gas (case 5) @ 3% O2
3
CO flue gas emission limits when mg/Nm
firing natural gas (case 5)
688.0 At BMCR TG - gas firing 250 147
@ 3% O2
GAS FIRING
NOx [mg/Nm3 @ 3% O2]
350
GUARANTEED LIMIT
300
NOx [mg/Nm3 @ 3% O2]
250
200
310
150 290
213
100
50
0
25 100 BMCR
Load [%]
GAS FIRING
CO [mg/Nm3 @ 3% O2]
300
200
147
150
100
58
50
0
0
25 100 BMCR
Load [%]
Analysers station
Titolo Identificativo Rev. Pagina Di
title document no. rev. Page Of
ABU QIR THERMAL POWER PLANT 0 17 73
2 x 650 MW GAS / OIL FIRED UNIT 30390-A-M1008
4. Conclusion
The above analysis shows the good behavior of the entire boiler package:
As shown above the over-performances of the boiler have been converted in electrical
power credit in order to show with expressive figures the obtained benefit.
This has been done by the means of technical considerations in two ways:
a. RH pressure drop: correction curves from Steam Turbine manufacturer has been
used for evaluating the corresponding kWe credits on ST side
b. Boiler Efficiency: plant balance calculations
Power Credit
Technical
[kWe]
Reheater pressure Drop 1660 a
Efficiency 3962 b
Total 5622
a
Calculated from ST correction curves
b
Calculated from plant balance considerations
Titolo Identificativo Rev. Pagina Di
title document no. rev. Page Of
ABU QIR THERMAL POWER PLANT 0 19 73
2 x 650 MW GAS / OIL FIRED UNIT 30390-A-M1008
The overall under performance is 783 kW, as shown in detail in the below table.
It is clear that the over performances given by the boiler itself are much greater than the
underperformance of Fans (approx. 7 times bigger).
By subtracting the overall credits to the auxiliary power over absorption, the situation is as
reported:
Total power absorption underperformance [kWe] 783 -
Total power credits [kWe] 5662 * =
Total equivalent power over absorption [kWe] - 4879
Where the negative sign means that the Fans under performance is much more than
compensated by the good boiler behavior.
Obviously the negative shortfall means a positive result for AC.
2.5 Efficiency firing gas (case 2) When operating at 100% TG load % 86.73 87.25 87.26 87.25 87.25
2.6 Total auxiliary power consumption (case 2) When operating at 100% TG load kW 7500 8818 8283 8832 8804
EQUIPMENT GUARANTEES
document no.
Identificativo
3.7
Rev.
bar 12 11.72 -
3) outlet (excluding static head) at BMCR
20
Pagina
Of
Di
73
Titolo Identificativo Rev. Pagina Di
title document no. rev. Page Of
ABU QIR THERMAL POWER PLANT 0 21 73
2 x 650 MW GAS / OIL FIRED UNIT 30390-A-M1008
Test n. 1
Tag Description Units Values
Tam 1 humidity relative Ambient relative humidity % 63.3257555
Tam 2 Ambient Temperature Ambient temperature C 23.5432143
Barometric pressure Ambient pressure hPa 1017.92301
Ta 1 Air left upstr. AH Air temperature upstr. AH (A) RTD PT 100 0 - 250C C 34.7990369
Ta 2 Air left upstr. AH Air temperature upstr. AH (A) RTD PT 100 0 - 250C C 34.5400254
Ta 3 Air left upstr. AH Air temperature upstr. AH (A) RTD PT 100 0 - 250C C 34.5641319
Ta 4 Air right upstr. AH Air temperature upstr. AH (B) RTD PT 100 0 - 250C C 34.337742
Ta 5 Air right upstr. AH Air temperature upstr. AH (B) RTD PT 100 0 - 250C C 34.2058969
Ta 6 Air right upstr. AH Air temperature upstr. AH (B) RTD PT 100 0 - 250C C 34.1181459
Tgi 1 left. temp. AH (A) Flue gas temperature upstr. AH (A) Tc K " 0 - 500 C " C 350.577253
Tgi 2 left. temp. AH (A) Flue gas temperature upstr. AH (A) Tc K " 0 - 500 C " C 347.976129
Tgi 3 left. temp. AH (A) Flue gas temperature upstr. AH (A) Tc K " 0 - 500 C " C 352.068962
Tgi 4 left. temp. AH (A) Flue gas temperature upstr. AH (A) Tc K " 0 - 500 C " C 350.501331
Tgi 5 left. temp. AH (A) Flue gas temperature upstr. AH (A) Tc K " 0 - 500 C " C 349.96522
Tgi 6 left. temp. AH (A) Flue gas temperature upstr. AH (A) Tc K " 0 - 500 C " C 349.726257
Tgi 7 left. temp. AH (A) Flue gas temperature upstr. AH (A) Tc K " 0 - 500 C " C 352.145653
Tgi 8 left. temp. AH (A) Flue gas temperature upstr. AH (A) Tc K " 0 - 500 C " C 350.037379
Tgi 9 left. temp. AH (A) Flue gas temperature upstr. AH (A) Tc K " 0 - 500 C " C 349.17428
Tgi 10 left. temp. AH (A) Flue gas temperature upstr. AH (A) Tc K " 0 - 500 C " C 349.815627
Tgi 11 left. temp. AH (A) Flue gas temperature upstr. AH (A) Tc K " 0 - 500 C " C 353.764808
Tgi 12 left. temp. AH (A) Flue gas temperature upstr. AH (A) Tc K " 0 - 500 C " C 352.696675
Tgi 13 left. temp. AH (A) Flue gas temperature upstr. AH (A) Tc K " 0 - 500 C " C 352.099785
Tgi 14 left. temp. AH (A) Flue gas temperature upstr. AH (A) Tc K " 0 - 500 C " C 353.742548
Tgi 15 left. temp. AH (A) Flue gas temperature upstr. AH (A) Tc K " 0 - 500 C " C 354.201497
Tgi 16 left. temp. AH (A) Flue gas temperature upstr. AH (A) Tc K " 0 - 500 C " C 352.780978
Tgi 17 left. temp. AH (A) Flue gas temperature upstr. AH (A) Tc K " 0 - 500 C " C 349.522465
Tgi 18 left. temp. AH (A) Flue gas temperature upstr. AH (A) Tc K " 0 - 500 C " C 349.908703
Tgi 19 left. temp. AH (A) Flue gas temperature upstr. AH (A) Tc K " 0 - 500 C " C 352.095654
Tgi 20 left. temp. AH (A) Flue gas temperature upstr. AH (A) Tc K " 0 - 500 C " C 349.624236
Tgi 21 left. temp. AH (A) Flue gas temperature upstr. AH (A) Tc K " 0 - 500 C " C 353.474431
Tgi 22 left. temp. AH (A) Flue gas temperature upstr. AH (A) Tc K " 0 - 500 C " C 352.571572
Tgi 23 left. temp. AH (A) Flue gas temperature upstr. AH (A) Tc K " 0 - 500 C " C 349.923709
Tgi 24 left. temp. AH (A) Flue gas temperature upstr. AH (A) Tc K " 0 - 500 C " C 350.89111
Tgo 1 left. temp. AH (A) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 107.945133
Tgo 2 left. temp. AH (A) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 112.620634
Tgo 3 left. temp. AH (A) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 114.786176
Tgo 4 left. temp. AH (A) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 117.363322
Tgo 5 left. temp. AH (A) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 102.232044
Tgo 6 left. temp. AH (A) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 108.602201
Tgo 7 left. temp. AH (A) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 107.73806
Tgo 8 left. temp. AH (A) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 116.41556
Tgo 9 left. temp. AH (A) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 102.264469
Tgo 10 left. temp. AH (A) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 107.610182
Tgo 11 left. temp. AH (A) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 111.450771
Tgo 12 left. temp. AH (A) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 115.124259
Tgo 13 left. temp. AH (A) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 101.592016
Tgo 14 left. temp. AH (A) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 107.300924
Tgo 15 left. temp. AH (A) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 111.861764
Tgo 16 left. temp. AH (A) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 117.419192
Tgo 17 left. temp. AH (A) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 98.4005854
Tgo 18 left. temp. AH (A) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 98.040221
Tgo 19 left. temp. AH (A) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 104.89939
Tgo 20 left. temp. AH (A) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 114.464411
Tgo 21 left. temp. AH (A) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 89.1856358
Tgo 22 left. temp. AH (A) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 89.2800445
Tgo 23 left. temp. AH (A) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 100.38429
Tgo 24 left. temp. AH (A) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 107.050341
Tgi 25 right. temp. AH (B) Flue gas temperature upstr. AH (B) Tc K " 0 - 500 C " C 347.114603
Tgi 26 right. temp. AH (B) Flue gas temperature upstr. AH (B) Tc K " 0 - 500 C " C 348.657314
Tgi 27 right. temp. AH (B) Flue gas temperature upstr. AH (B) Tc K " 0 - 500 C " C 349.514774
Tgi 28 right. temp. AH (B) Flue gas temperature upstr. AH (B) Tc K " 0 - 500 C " C 350.654871
Tgi 29 right. temp. AH (B) Flue gas temperature upstr. AH (B) Tc K " 0 - 500 C " C 349.193254
Tgi 30 right. temp. AH (B) Flue gas temperature upstr. AH (B) Tc K " 0 - 500 C " C 351.245817
Tgi 31 right. temp. AH (B) Flue gas temperature upstr. AH (B) Tc K " 0 - 500 C " C 352.15685
Tgi 32 right. temp. AH (B) Flue gas temperature upstr. AH (B) Tc K " 0 - 500 C " C 352.24485
Tgi 33 right. temp. AH (B) Flue gas temperature upstr. AH (B) Tc K " 0 - 500 C " C 354.892902
Tgi 34 right. temp. AH (B) Flue gas temperature upstr. AH (B) Tc K " 0 - 500 C " C 349.775772
Tgi 35 right. temp. AH (B) Flue gas temperature upstr. AH (B) Tc K " 0 - 500 C " C 347.709631
Tgi 36 right. temp. AH (B) Flue gas temperature upstr. AH (B) Tc K " 0 - 500 C " C 353.006984
Tgi 37 right. temp. AH (B) Flue gas temperature upstr. AH (B) Tc K " 0 - 500 C " C 348.708381
Tgi 38 right. temp. AH (B) Flue gas temperature upstr. AH (B) Tc K " 0 - 500 C " C 352.455141
Tgi 39 right. temp. AH (B) Flue gas temperature upstr. AH (B) Tc K " 0 - 500 C " C 350.15083
Tgi 40 right. temp. AH (B) Flue gas temperature upstr. AH (B) Tc K " 0 - 500 C " C 351.257106
Tgi 41 right. temp. AH (B) Flue gas temperature upstr. AH (B) Tc K " 0 - 500 C " C 351.539825
Tgi 42 right. temp. AH (B) Flue gas temperature upstr. AH (B) Tc K " 0 - 500 C " C 350.577085
Tgi 43 right. temp. AH (B) Flue gas temperature upstr. AH (B) Tc K " 0 - 500 C " C 351.046689
Tgi 44 right. temp. AH (B) Flue gas temperature upstr. AH (B) Tc K " 0 - 500 C " C 352.26594
Tgi 45 right. temp. AH (B) Flue gas temperature upstr. AH (B) Tc K " 0 - 500 C " C 353.292288
Tgi 46 right. temp. AH (B) Flue gas temperature upstr. AH (B) Tc K " 0 - 500 C " C 354.628911
Tgi 47 right. temp. AH (B) Flue gas temperature upstr. AH (B) Tc K " 0 - 500 C " C 354.884074
Tgi 48 right. temp. AH (B) Flue gas temperature upstr. AH (B) Tc K " 0 - 500 C " C 349.563307
Tgo 25 right. temp. AH (B) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 106.449305
Tgo 26 right. temp. AH (B) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 107.08506
Tgo 27 right. temp. AH (B) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 109.003712
Tgo 28 right. temp. AH (B) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 111.118268
Tgo 29 right. temp. AH (B) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 99.0030754
Tgo 30 right. temp. AH (B) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 102.345166
Tgo 31 right. temp. AH (B) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 104.032418
Tgo 32 right. temp. AH (B) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 110.875464
Tgo 33 right. temp. AH (B) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 94.7802574
Tgo 34 right. temp. AH (B) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 101.136597
Tgo 35 right. temp. AH (B) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 107.966585
Tgo 36 right. temp. AH (B) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 110.191908
Tgo 37 right. temp. AH (B) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 95.0233754
Tgo 38 right. temp. AH (B) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 102.329649
Tgo 39 right. temp. AH (B) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 108.296066
Tgo 40 right. temp. AH (B) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 110.53678
Tgo 41 right. temp. AH (B) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 93.1916845
Tgo 42 right. temp. AH (B) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 96.4918791
Tgo 43 right. temp. AH (B) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 99.1897727
Tgo 44 right. temp. AH (B) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 109.916808
Tgo 45 right. temp. AH (B) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 85.7962378
Tgo 46 right. temp. AH (B) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 88.5153013
Tgo 47 right. temp. AH (B) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 96.1589511
Tgo 48 right. temp. AH (B) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 103.31191
A1 O2 downstream. AHs Flue gas O2 analysis (downstream. AHs) % 2.20716016
A2 O2 upstream AHs Flue gas O2 analysis (upstream. AHs) % 0.78215707
A3 CO upstream AHs Flue gas CO analysis (upstream AHs) ppm 49.9789835
A4 NO downstr. AHs Flue gas NO analysis (downstream AHs) ppm 158.120536
W01 Feedwater flow at boiler inlet mbar 989.339667
P01 Feedwater pressure at flowmeeter bar 179.616171
T01 TI 103 Feedwater temperature at boiler inlet C 273.223021
P02 PI 100 Feedwater pressure at boiler inlet bar 179.117313
W02 FE 112 Desuperheating water flow to SH (1st stage) mbar 366.391369
W03 FE 122 Desuperheating water flow to SH (2nd stage) mbar 161.16746
P03 PI 112 Desuperheating water press. to SH (1st/2nd stage) bar 200.230337
T02 TE 111 Desuperheating water temperature to SH C 182.216858
W04 FE 153 Desuperheating water flow to RH mbar 0.83388205
P05 PE 153 Desuperheating water pressure to RH bar 37.0174837
T03 TT152 Desuperheating water temperature to RH C 25.0773201
T04 TI 222 SH outlet steam temperature right side Tc K 0-650 C C 541.716213
T05 TI 212 SH outlet steam temperature left side Tc K 0-650 C mbar 541.75277
P06 PI 226 SH outlet steam pressure PT 0-250 bar bar 167.107115
T07 TI 281 Hot reheated steam temperature Tc K 0-650 C C 565.691481
P08 PT 283 Hot reheated steam pressure PT 0-100 bar bar 35.8827139
T06 TI252 Cold reheated steam temperature a HP ST outlet Tc J 0 - 400 C 331.730107
P07 PT 250 Cold reheated steam pressure a HP ST Outlet PT. 0 - 100 bar bar 37.2593087
KF1 F.D.F. MA200 Forced draft fan motor power 1 AP MA200 0 - 4800 KW KW 3454.75707
KF2 F.D.F. MA100 Forced draft fan motor power 1 AP MA100 0 - 4800 KW KW 3728.03547
KG1 R.G.M. MA 200 Recirculating fan motor power 1FU MA200 0 - 1050 KW KW 811.773807
KG2 R.G.M. MA 100 Recirculating fan motor power 1FU MA100 0 - 1050 KW KW 777.237748
Averaged 1Air left temp.upstr.AH C 34.634398
Averaged 2Air right temp.upstr. AH C 34.220595
Averaged 3 Flue gas left Temperature upstr.AH C 351.22026
Averaged 4 Flue gas left Temp. downstr. AH C 106.83465
Averaged 5 Flue gas right Temp. upstr. AH C 351.10572
Averaged 6 Flue gas right Temp. downstr. AH C 102.19776
Company Ansaldo Caldaie
Date
Sign
Company
Date
Sign
Averaged data computed from 10.30.04 - 15/11/12 to 12.00.11 - 15/11/12
FUNCTIONAL GUARANTEES
Contract
Par. No.
Guarantee Comment Units Value Measured
2.5 Efficiency firing gas (case 2) When operating at 100% TG load % 86.73 87.25
To be corrected for:
- CRH Temperature
2.6 Total auxiliary power consumption (case 2) When operating at 100% TG load kW 7500 8832
- RH flow
- Boiler Heat Output
FUNCTIONAL GUARANTEES
Contract
Par. No.
Guarantee Comment Units Value Measured
5.1.2 Test#2
Averaged data computed from 12.00.11 - 15/11/12 to 13.30.25 - 15/11/12
Test n. 2
Tag Description Units Values
Tam 1 humidity relative Ambient relative humidity % 58.9747917
Tam 2 Ambient Temperature Ambient temperature C 24.0989931
Barometric pressure Ambient pressure hPa 1017.32042
Ta 1 Air left upstr. AH Air temperature upstr. AH (A) RTD PT 100 0 - 250C C 35.3343354
Ta 2 Air left upstr. AH Air temperature upstr. AH (A) RTD PT 100 0 - 250C C 35.0771626
Ta 3 Air left upstr. AH Air temperature upstr. AH (A) RTD PT 100 0 - 250C C 35.1001205
Ta 4 Air right upstr. AH Air temperature upstr. AH (B) RTD PT 100 0 - 250C C 34.7203692
Ta 5 Air right upstr. AH Air temperature upstr. AH (B) RTD PT 100 0 - 250C C 34.5320816
Ta 6 Air right upstr. AH Air temperature upstr. AH (B) RTD PT 100 0 - 250C C 34.472911
Tgi 1 left. temp. AH (A) Flue gas temperature upstr. AH (A) Tc K " 0 - 500 C " C 350.554195
Tgi 2 left. temp. AH (A) Flue gas temperature upstr. AH (A) Tc K " 0 - 500 C " C 347.981493
Tgi 3 left. temp. AH (A) Flue gas temperature upstr. AH (A) Tc K " 0 - 500 C " C 352.06034
Tgi 4 left. temp. AH (A) Flue gas temperature upstr. AH (A) Tc K " 0 - 500 C " C 350.521302
Tgi 5 left. temp. AH (A) Flue gas temperature upstr. AH (A) Tc K " 0 - 500 C " C 349.982158
Tgi 6 left. temp. AH (A) Flue gas temperature upstr. AH (A) Tc K " 0 - 500 C " C 349.727747
Tgi 7 left. temp. AH (A) Flue gas temperature upstr. AH (A) Tc K " 0 - 500 C " C 352.116295
Tgi 8 left. temp. AH (A) Flue gas temperature upstr. AH (A) Tc K " 0 - 500 C " C 350.037977
Tgi 9 left. temp. AH (A) Flue gas temperature upstr. AH (A) Tc K " 0 - 500 C " C 349.174178
Tgi 10 left. temp. AH (A) Flue gas temperature upstr. AH (A) Tc K " 0 - 500 C " C 349.805171
Tgi 11 left. temp. AH (A) Flue gas temperature upstr. AH (A) Tc K " 0 - 500 C " C 353.772243
Tgi 12 left. temp. AH (A) Flue gas temperature upstr. AH (A) Tc K " 0 - 500 C " C 352.707791
Tgi 13 left. temp. AH (A) Flue gas temperature upstr. AH (A) Tc K " 0 - 500 C " C 352.172441
Tgi 14 left. temp. AH (A) Flue gas temperature upstr. AH (A) Tc K " 0 - 500 C " C 353.787262
Tgi 15 left. temp. AH (A) Flue gas temperature upstr. AH (A) Tc K " 0 - 500 C " C 354.208697
Tgi 16 left. temp. AH (A) Flue gas temperature upstr. AH (A) Tc K " 0 - 500 C " C 352.798955
Tgi 17 left. temp. AH (A) Flue gas temperature upstr. AH (A) Tc K " 0 - 500 C " C 349.601608
Tgi 18 left. temp. AH (A) Flue gas temperature upstr. AH (A) Tc K " 0 - 500 C " C 349.990971
Tgi 19 left. temp. AH (A) Flue gas temperature upstr. AH (A) Tc K " 0 - 500 C " C 352.063073
Tgi 20 left. temp. AH (A) Flue gas temperature upstr. AH (A) Tc K " 0 - 500 C " C 349.619981
Tgi 21 left. temp. AH (A) Flue gas temperature upstr. AH (A) Tc K " 0 - 500 C " C 353.488443
Tgi 22 left. temp. AH (A) Flue gas temperature upstr. AH (A) Tc K " 0 - 500 C " C 352.590128
Tgi 23 left. temp. AH (A) Flue gas temperature upstr. AH (A) Tc K " 0 - 500 C " C 349.898531
Tgi 24 left. temp. AH (A) Flue gas temperature upstr. AH (A) Tc K " 0 - 500 C " C 350.830531
Tgo 1 left. temp. AH (A) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 108.329419
Tgo 2 left. temp. AH (A) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 113.1735
Tgo 3 left. temp. AH (A) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 115.185839
Tgo 4 left. temp. AH (A) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 117.799289
Tgo 5 left. temp. AH (A) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 102.699331
Tgo 6 left. temp. AH (A) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 109.168686
Tgo 7 left. temp. AH (A) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 108.135579
Tgo 8 left. temp. AH (A) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 116.879186
Tgo 9 left. temp. AH (A) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 102.638502
Tgo 10 left. temp. AH (A) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 107.824907
Tgo 11 left. temp. AH (A) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 111.939863
Tgo 12 left. temp. AH (A) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 115.566982
Tgo 13 left. temp. AH (A) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 101.957681
Tgo 14 left. temp. AH (A) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 107.81698
Tgo 15 left. temp. AH (A) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 112.2147
Tgo 16 left. temp. AH (A) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 117.853022
Tgo 17 left. temp. AH (A) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 98.6784687
Tgo 18 left. temp. AH (A) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 98.6172793
Tgo 19 left. temp. AH (A) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 105.113585
Tgo 20 left. temp. AH (A) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 114.94224
Tgo 21 left. temp. AH (A) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 89.5854269
Tgo 22 left. temp. AH (A) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 89.6551203
Tgo 23 left. temp. AH (A) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 100.746982
Tgo 24 left. temp. AH (A) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 107.519427
Tgi 25 right. temp. AH (B) Flue gas temperature upstr. AH (B) Tc K " 0 - 500 C " C 347.086365
Tgi 26 right. temp. AH (B) Flue gas temperature upstr. AH (B) Tc K " 0 - 500 C " C 348.646398
Tgi 27 right. temp. AH (B) Flue gas temperature upstr. AH (B) Tc K " 0 - 500 C " C 349.53629
Tgi 28 right. temp. AH (B) Flue gas temperature upstr. AH (B) Tc K " 0 - 500 C " C 350.680007
Tgi 29 right. temp. AH (B) Flue gas temperature upstr. AH (B) Tc K " 0 - 500 C " C 349.157627
Tgi 30 right. temp. AH (B) Flue gas temperature upstr. AH (B) Tc K " 0 - 500 C " C 351.199525
Tgi 31 right. temp. AH (B) Flue gas temperature upstr. AH (B) Tc K " 0 - 500 C " C 352.129943
Tgi 32 right. temp. AH (B) Flue gas temperature upstr. AH (B) Tc K " 0 - 500 C " C 352.226509
Tgi 33 right. temp. AH (B) Flue gas temperature upstr. AH (B) Tc K " 0 - 500 C " C 354.937669
Tgi 34 right. temp. AH (B) Flue gas temperature upstr. AH (B) Tc K " 0 - 500 C " C 349.798269
Tgi 35 right. temp. AH (B) Flue gas temperature upstr. AH (B) Tc K " 0 - 500 C " C 347.695062
Tgi 36 right. temp. AH (B) Flue gas temperature upstr. AH (B) Tc K " 0 - 500 C " C 353.016189
Tgi 37 right. temp. AH (B) Flue gas temperature upstr. AH (B) Tc K " 0 - 500 C " C 348.723062
Tgi 38 right. temp. AH (B) Flue gas temperature upstr. AH (B) Tc K " 0 - 500 C " C 352.473538
Tgi 39 right. temp. AH (B) Flue gas temperature upstr. AH (B) Tc K " 0 - 500 C " C 350.163403
Tgi 40 right. temp. AH (B) Flue gas temperature upstr. AH (B) Tc K " 0 - 500 C " C 351.278845
Tgi 41 right. temp. AH (B) Flue gas temperature upstr. AH (B) Tc K " 0 - 500 C " C 351.553503
Tgi 42 right. temp. AH (B) Flue gas temperature upstr. AH (B) Tc K " 0 - 500 C " C 350.604204
Tgi 43 right. temp. AH (B) Flue gas temperature upstr. AH (B) Tc K " 0 - 500 C " C 351.103307
Tgi 44 right. temp. AH (B) Flue gas temperature upstr. AH (B) Tc K " 0 - 500 C " C 352.293872
Tgi 45 right. temp. AH (B) Flue gas temperature upstr. AH (B) Tc K " 0 - 500 C " C 353.292338
Tgi 46 right. temp. AH (B) Flue gas temperature upstr. AH (B) Tc K " 0 - 500 C " C 354.641858
Tgi 47 right. temp. AH (B) Flue gas temperature upstr. AH (B) Tc K " 0 - 500 C " C 354.874879
Tgi 48 right. temp. AH (B) Flue gas temperature upstr. AH (B) Tc K " 0 - 500 C " C 349.55579
Tgo 25 right. temp. AH (B) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 106.857317
Tgo 26 right. temp. AH (B) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 107.384695
Tgo 27 right. temp. AH (B) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 109.199155
Tgo 28 right. temp. AH (B) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 111.326949
Tgo 29 right. temp. AH (B) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 99.4070067
Tgo 30 right. temp. AH (B) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 102.554263
Tgo 31 right. temp. AH (B) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 104.280944
Tgo 32 right. temp. AH (B) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 111.089644
Tgo 33 right. temp. AH (B) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 95.0992823
Tgo 34 right. temp. AH (B) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 101.385386
Tgo 35 right. temp. AH (B) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 108.306077
Tgo 36 right. temp. AH (B) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 110.483297
Tgo 37 right. temp. AH (B) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 95.3536987
Tgo 38 right. temp. AH (B) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 102.627192
Tgo 39 right. temp. AH (B) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 108.613847
Tgo 40 right. temp. AH (B) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 110.828666
Tgo 41 right. temp. AH (B) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 93.5383185
Tgo 42 right. temp. AH (B) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 96.7375977
Tgo 43 right. temp. AH (B) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 99.5844796
Tgo 44 right. temp. AH (B) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 110.16239
Tgo 45 right. temp. AH (B) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 86.1326159
Tgo 46 right. temp. AH (B) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 88.8351476
Tgo 47 right. temp. AH (B) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 96.5207951
Tgo 48 right. temp. AH (B) Flue gas temperature downstr. AH RTD PT 100 " 0 - 250C" C 103.59571
A1 O2 downstream. AHs Flue gas O2 analysis (downstream. AHs) % 2.23671389
A2 O2 upstream AHs Flue gas O2 analysis (upstream. AHs) % 0.7092125
A3 CO upstream AHs Flue gas CO analysis (upstream AHs) ppm 54.699375
A4 NO downstr. AHs Flue gas NO analysis (downstream AHs) ppm 160.569618
W01 Feedwater flow at boiler inlet mbar 991.004475
P01 Feedwater pressure at flowmeeter bar 179.732236
T01 TI 103 Feedwater temperature at boiler inlet C 273.165564
P02 PI 100 Feedwater pressure at boiler inlet bar 179.222178
W02 FE 112 Desuperheating water flow to SH (1st stage) mbar 354.434808
W03 FE 122 Desuperheating water flow to SH (2nd stage) mbar 158.814177
P03 PI 112 Desuperheating water press. to SH (1st/2nd stage) bar 200.685923
T02 TE 111 Desuperheating water temperature to SH C 182.199517
W04 FE 153 Desuperheating water flow to RH mbar 0.67422731
P05 PE 153 Desuperheating water pressure to RH bar 36.9466058
T03 TT152 Desuperheating water temperature to RH C 25.383333
T04 TI 222 SH outlet steam temperature right side Tc K 0-650 C C 542.405374
T05 TI 212 SH outlet steam temperature left side Tc K 0-650 C mbar 542.38125
P06 PI 226 SH outlet steam pressure PT 0-250 bar bar 167.18157
T07 TI 281 Hot reheated steam temperature Tc K 0-650 C C 566.34025
P08 PT 283 Hot reheated steam pressure PT 0-100 bar bar 35.8527761
T06 TI252 Cold reheated steam temperature a HP ST outlet Tc J 0 - 400 C 332.313678
P07 PT 250 Cold reheated steam pressure a HP ST Outlet PT. 0 - 100 bar bar 37.2361836
KF1 F.D.F. MA200 Forced draft fan motor power 1 AP MA200 0 - 4800 KW KW 3443.50887
KF2 F.D.F. MA100 Forced draft fan motor power 1 AP MA100 0 - 4800 KW KW 3718.48688
KG1 R.G.M. MA 200 Recirculating fan motor power 1FU MA200 0 - 1050 KW KW 808.72046
KG2 R.G.M. MA 100 Recirculating fan motor power 1FU MA100 0 - 1050 KW KW 773.066386
Averaged 1Air left temp.upstr.AH C 35.17054
Averaged 2Air right temp.upstr. AH C 34.575121
Averaged 3 Flue gas left Temperature upstr.AH C 351.22881
Averaged 4 Flue gas left Temp. downstr. AH C 107.25175
Averaged 5 Flue gas right Temp. upstr. AH C 351.11119
Averaged 6 Flue gas right Temp. downstr. AH C 102.49602
Company Ansaldo Caldaie
Date
Sign
Company
Date
Sign
Averaged data computed from 12.00.11 - 15/11/12 to 13.30.25 - 15/11/12
Contract
Par. No.
Guarantee Comment Units Value Measured
2.5 Efficiency firing gas (case 2) When operating at 100% TG load % 86.73 87.25
To be corrected for:
- CRH Temperature
2.6 Total auxiliary power consumption (case 2) When operating at 100% TG load kW 7500 8804
- RH flow
- Boiler Heat Output
FUNCTIONAL GUARANTEES
Contract
Par. No.
Guarantee Comment Units Value Measured
Intertek Commodities
Cargo Inspection, Analytical Services
Petroleum and carg Services,Laboratory Services
217 Abdel Salam Aref Lauran,Alexandria,Egypt
Tel:
Office : 0020-3-(4590141 / 5850464 / 5824441)
Mobile: 002-0100-1924419
Fax : 0020-3-5831438
www.intertek.com/petroleum/testing/cargo/
www.intertek.com/minerals/
www.intertek.com/government/
6.1.1 Test #1
Titolo Identificativo Rev. Pagina Di
title document no. rev. Page Of
ABU QIR THERMAL POWER PLANT 0 33 73
2 x 650 MW GAS / OIL FIRED UNIT 30390-A-M1008
6.1.2 Test #2
Date 15/11/12
Time 10:30-12:00
Test n. 1
Load 100% GAS
Reference conditions
Reference air temperature C 25 Tre
Barometric pressure Pa 101792 Pa
Dry-bulb temperature at location 6 C 23.5 Tdb
Wet-bulb temperature at location 6 C 18.7 Twb
Relative humidity at Iocation 6 % 63.33 Rhm
Design entering air temperature C 41 TAEn
Date 15/11/12
Time 10:30-12:00
Test n. 1
Load 100% GAS
Measured flows
Mass flow rate of fuel kg/s 30.8 MrF
Additional water per mass fuel kg/s 0 MFrWAd
Mass flow rate of feedwater at boiler inlet kg/s 492.7 MrW24
Mass flow rate of superheated steam at boiler outlet kg/s 546.0 MrSt32
Mass flow rate of cold reheat kg/s 460.5 MrSt33
Mass flow rate of Blow Down kg/s 0.0 MrWbd
Mass flow rate of Sh spray water kg/s 53.3 MrW25
Mass flow rate of Rh spray water kg/s 0 MrW26
Date 15/11/12
Time: 10:30-12:00
Test n. 1
Load 100% GAS
Date 15/11/12
Time 10:30-12:00
Test n. 1
Load 100% GAS
Date 15/11/12
Time 10:30-12:00
Test n. 1
Load 100% GAS
5.11.4.2 Calculation of DVpO2, DVpCO2, DVpSO2, DVpN2f and DVpN2a on a dry basis (%vol. dry)
Moles dry gas per mass fuel moles/mass fuel 0.55 MoDFg MoDPc + MoThACr * ( 0,7905 + XpAEn / 100 )
Percent 02 in flue gas, dry basis (measured) % volume dry 0.782 DVpO2
Percent of CO2 in flue gas, dry basis % volume dry 11.35 DVpCO2 ( MpCb / 12,01 + 100 * MoCO2Sb ) / MoDFg
Percent of SO2 in flue gas, wet basis % volume dry 0.0000 DVpSO2 MpSF / 32,064 * ( 1 - 0 ) ) / MoDFg
Percent N2 from fuel in flue gas, wet basis % volume dry 0.0095 DVpN2f ( MpN2F / 28,013 ) / MoDFg
Percent nitrogen (atmospheric) in flue gas, dry basis % volume dry 87.86 DVpN2a 100 - DVpO2En - DVpCO2 - DVpSO2 - DVpN2f
Date 15/11/12
Time 10:30-12:00
Test n. 1
Load 100% GAS
5.11.4.4 Calculation of VpO2, VpCO2, VpSO2, VpN2f and VpN2a on a wet basis (%vol. wet)
MoDPc + ( MpH2F / 201,6 ) + MpH2OF / 1801,5 +
MoDPc plus moles H2O frorn fuel, sorbent and any additional moisture moles/mass fuel 0.185 MoWPc
MFrWAd / 18,15
Moles of moisture in air moles/kg air 0 XpAEn 1,608 * MFrWAd
MoWPc + MoThACr * ( 0,7905 + MoWA + XpAEn /
Moles of wet gas per mass fuel moles/mass fuel as fired 0.671 MoFg
100 ) * ( 1+ XpAEn ) )
Percent O2 in flue gas, wet basis % volume wet 0.639 VpO2 ( XpAEn * MoThACr * 0,2095 / MoFg )
Percent of CO2 in flue gas, wet basis % volume wet 9.273 VpCO2 ( MpCb / 12,01 ) / MoFg
Percent of SO2 in flue gas, wet basis % volume wet 0.0000 VpSO2 ( MpSF / 32,064 ) / MoFg
( MpH2F / 2,016 + MpH2OF / 18,015 + MFrWAd /
Percent water in flue gas, wet basis % volume wet 18.27 VpH2O 18,015 + ( 100 + XpAEn ) * MoThACr * XpAEn ) /
MoFg
Percent N2 from fuel in flue gas, wet basis % volume wet 0.008 VpN2f ( MpN2F / 28,013 ) / MoFg
Percent N2 (atmospheric) in flue gas, wet basis % volume wet 71.81 VpN2a 100 - VpO2 - VpCO2 - VpSO2 - VpH2O - VpN2f
VpO2 + VpCO2 + VpSO2 + VpH2O + VpN2f +
100.00
VpN2a
CAIRO ELECTRICITY PRODUCTION COMPANY ABU QIR THERMAL POWER PLANT UNITS 6 & 7
2 x 350 MW GAS/OIL FIRED UNITS GUARANTEED EFFICIENCY CALCULATION
Date 15/11/12
Time 10:30-12:00
Test n. 1
Load 100% GAS
5.12.8 Total moisture in flue gas at A.H. inlet on fuel input basis
Total moisture in flue gas at A. H. inlet on fuel input basis kg/kJ 0.000044 MqWFgEn MqWF + MqWH2F + MqWALv
5.12.10 Dry flue gas weight at A. H. inlet on input from fuel basis
Mass dry gas at A.H. inlet on input from fueI basis kg/kJ 0.00029867 MqDFgEn MqFgEn - MqWFgEn
Date 15/11/12
Time 10:30-12:00
Test n. 1
Load 100% GAS
Date 15/11/12
Time 10:30-12:00
Test n. 1
Load 100% GAS
Date 15/11/12
Time 10:30-12:00
Test n. 1
Load 100% GAS
Date 15/11/12
Time 10:30-12:00
Test n. 1
Load 100% GAS
Wet gas from fuel kg/kJ 0.0000182 MqFgF ( 100 - MpAsF - MpUbC ) / ( 100 * HHVF )
5.12.2 Moisture from water in fuel
Moisture from water in fuel kg/kJ 0.000000000 MqWF
MpH2OF / ( 100 * HHVF )
5.12.3 Water from combustion of hydrogen in fuel
Water from combustion of hydrogen in fuel kg/kJ 0.0000401 MqWH2F ( 8,937 * MpH2F ) / ( 100 * HHVF )
Date 15/11/12
Time 10:30-12:00
Test n. 1
Load 100% GAS
Date 15/11/12
Time 10:30-12:00
Test n. 1
Load 100% GAS
Date 15/11/12
Time 10:30-12:00
Test n. 1
Load 100% GAS
5.14.4.3 QpLCO - Loss due to carbon monoxide (CO) in flue gas (%)
Percent CO in flue gas at A.H. outlet wet basis % vol. dry 0.005 VpCOEn
Moles dry gas per mass fuel moles/kg 0.548 MoDFg
Molecular weight of carbon monoxide, CO kg/mole 28.01 MwCO
Higher heating value of carbon monoxide kJ/kg 10111 HHVCO
Higher heating value of fuel at constant pressure kJ/kg 55060 HHVF
Loss due to carbon monoxide (CO) in flue gas % 0.0141 QpLCO VpCOEn * MoDFg * MwCO * HHVCO / HHVF
Date 15/11/12
Time 10:30-12:00
Test n. 1
Load 100% GAS
Date 15/11/12
Time 10:30-12:00
Test n. 1
Load 100% GAS
Date 15/11/12
Time 10:30-12:00
Test n. 1
Load 100% GAS
Date 15/11/12
Time 10:30-12:00
Test n. 1
Load 100% GAS
CREDITS
Credit due to Entering Dry Air 5.15.1 % 0.52 QpBDA
Credit due to moisture in entering air 5.15.2 % 0.0119 QpBWA
Credit due to sensible heat in fuel 5.15.3 % 0.0038 QpBF
Total Credits calculated on percent input from fuel % 0.53 SmQpB
CREDITS
Credit due to electricity driven equipment kW 1509.6 QrBX QX * EX
BOILER EFFICIENCY
(100-
Boiler efficiency % 87.25 EF SmQpL+SmQpB)*((QrO*1000)/(QrO*1000+(QrLSrc)-
(QrBX)))
WEST DELTA ELECTRICITY PRODUCTION COMPANY ABU QIR THERMAL POWER PLANT UNITS 6 & 7
2 x 650 MW GAS/OIL FIRED UNITS GUARANTEED EFFICIENCY CALCULATION
Date 15/11/12
Time 10:30-12:00
Test n. 1
Load 100% GAS
ADDITIONAL BOILER FUNCTIONAL AND EQUIPMENT TESTS Units Value Symbol Formula
7.1.2 Test #2
WEST DELTA ELECTRICITY PRODUCTION COMPANY ABU QIR THERMAL POWER PLANT UNITS 6 & 7
2 x 650 MW GAS/OIL FIRED UNITS GUARANTEED EFFICIENCY CALCULATION
Date 15/11/12
Time 12:00-13:30
Test n. 2
Load 100% GAS
Reference conditions
Reference air temperature C 25 Tre
Barometric pressure Pa 101732 Pa
Dry-bulb temperature at location 6 C 24.1 Tdb
Wet-bulb temperature at location 6 C 18.5 Twb
Relative humidity at Iocation 6 % 58.97 Rhm
Design entering air temperature C 41 TAEn
Date 15/11/12
Time 12:00-13:30
Test n. 2
Load 100% GAS
Measured flows
Mass flow rate of fuel kg/s 30.8 MrF
Additional water per mass fuel kg/s 0 MFrWAd
Mass flow rate of feedwater at boiler inlet kg/s 493.1 MrW24
Mass flow rate of superheated steam at boiler outlet kg/s 545.7 MrSt32
Mass flow rate of cold reheat kg/s 460.2 MrSt33
Mass flow rate of Blow Down kg/s 0.0 MrWbd
Mass flow rate of Sh spray water kg/s 52.5 MrW25
Mass flow rate of Rh spray water kg/s 0 MrW26
Date 15/11/12
Time: 12:00-13:30
Test n. 2
Load 100% GAS
Date 15/11/12
Time 12:00-13:30
Test n. 2
Load 100% GAS
Date 15/11/12
Time 12:00-13:30
Test n. 2
Load 100% GAS
5.11.4.2 Calculation of DVpO2, DVpCO2, DVpSO2, DVpN2f and DVpN2a on a dry basis (%vol. dry)
Moles dry gas per mass fuel moles/mass fuel 0.55 MoDFg MoDPc + MoThACr * ( 0,7905 + XpAEn / 100 )
Percent 02 in flue gas, dry basis (measured) % volume dry 0.709 DVpO2
Percent of CO2 in flue gas, dry basis % volume dry 11.39 DVpCO2 ( MpCb / 12,01 + 100 * MoCO2Sb ) / MoDFg
Percent of SO2 in flue gas, wet basis % volume dry 0.0000 DVpSO2 MpSF / 32,064 * ( 1 - 0 ) ) / MoDFg
Percent N2 from fuel in flue gas, wet basis % volume dry 0.0095 DVpN2f ( MpN2F / 28,013 ) / MoDFg
Percent nitrogen (atmospheric) in flue gas, dry basis % volume dry 87.89 DVpN2a 100 - DVpO2En - DVpCO2 - DVpSO2 - DVpN2f
Date 15/11/12
Time 12:00-13:30
Test n. 2
Load 100% GAS
5.11.4.4 Calculation of VpO2, VpCO2, VpSO2, VpN2f and VpN2a on a wet basis (%vol. wet)
MoDPc + ( MpH2F / 201,6 ) + MpH2OF / 1801,5 +
MoDPc plus moles H2O frorn fuel, sorbent and any additional moisture moles/mass fuel 0.185 MoWPc
MFrWAd / 18,15
Moles of moisture in air moles/kg air 0 XpAEn 1,608 * MFrWAd
MoWPc + MoThACr * ( 0,7905 + MoWA + XpAEn /
Moles of wet gas per mass fuel moles/mass fuel as fired 0.669 MoFg
100 ) * ( 1+ XpAEn ) )
Percent O2 in flue gas, wet basis % volume wet 0.579 VpO2 ( XpAEn * MoThACr * 0,2095 / MoFg )
Percent of CO2 in flue gas, wet basis % volume wet 9.301 VpCO2 ( MpCb / 12,01 ) / MoFg
Percent of SO2 in flue gas, wet basis % volume wet 0.0000 VpSO2 ( MpSF / 32,064 ) / MoFg
( MpH2F / 2,016 + MpH2OF / 18,015 + MFrWAd /
Percent water in flue gas, wet basis % volume wet 18.32 VpH2O 18,015 + ( 100 + XpAEn ) * MoThACr * XpAEn ) /
MoFg
Percent N2 from fuel in flue gas, wet basis % volume wet 0.008 VpN2f ( MpN2F / 28,013 ) / MoFg
Percent N2 (atmospheric) in flue gas, wet basis % volume wet 71.79 VpN2a 100 - VpO2 - VpCO2 - VpSO2 - VpH2O - VpN2f
VpO2 + VpCO2 + VpSO2 + VpH2O + VpN2f +
100.00
VpN2a
CAIRO ELECTRICITY PRODUCTION COMPANY ABU QIR THERMAL POWER PLANT UNITS 6 & 7
2 x 350 MW GAS/OIL FIRED UNITS GUARANTEED EFFICIENCY CALCULATION
Date 15/11/12
Time 12:00-13:30
Test n. 2
Load 100% GAS
5.12.8 Total moisture in flue gas at A.H. inlet on fuel input basis
Total moisture in flue gas at A. H. inlet on fuel input basis kg/kJ 0.000044 MqWFgEn MqWF + MqWH2F + MqWALv
5.12.10 Dry flue gas weight at A. H. inlet on input from fuel basis
Mass dry gas at A.H. inlet on input from fueI basis kg/kJ 0.00029763 MqDFgEn MqFgEn - MqWFgEn
Date 15/11/12
Time 12:00-13:30
Test n. 2
Load 100% GAS
Date 15/11/12
Time 12:00-13:30
Test n. 2
Load 100% GAS
Date 15/11/12
Time 12:00-13:30
Test n. 2
Load 100% GAS
Date 15/11/12
Time 12:00-13:30
Test n. 2
Load 100% GAS
Wet gas from fuel kg/kJ 0.0000182 MqFgF ( 100 - MpAsF - MpUbC ) / ( 100 * HHVF )
5.12.2 Moisture from water in fuel
Moisture from water in fuel kg/kJ 0.000000000 MqWF
MpH2OF / ( 100 * HHVF )
5.12.3 Water from combustion of hydrogen in fuel
Water from combustion of hydrogen in fuel kg/kJ 0.0000401 MqWH2F ( 8,937 * MpH2F ) / ( 100 * HHVF )
Date 15/11/12
Time 12:00-13:30
Test n. 2
Load 100% GAS
Date 15/11/12
Time 12:00-13:30
Test n. 2
Load 100% GAS
Date 15/11/12
Time 12:00-13:30
Test n. 2
Load 100% GAS
5.14.4.3 QpLCO - Loss due to carbon monoxide (CO) in flue gas (%)
Percent CO in flue gas at A.H. outlet wet basis % vol. dry 0.005 VpCOEn
Moles dry gas per mass fuel moles/kg 0.546 MoDFg
Molecular weight of carbon monoxide, CO kg/mole 28.01 MwCO
Higher heating value of carbon monoxide kJ/kg 10111 HHVCO
Higher heating value of fuel at constant pressure kJ/kg 55060 HHVF
Loss due to carbon monoxide (CO) in flue gas % 0.0154 QpLCO VpCOEn * MoDFg * MwCO * HHVCO / HHVF
Date 15/11/12
Time 12:00-13:30
Test n. 2
Load 100% GAS
Date 15/11/12
Time 12:00-13:30
Test n. 2
Load 100% GAS
Date 15/11/12
Time 12:00-13:30
Test n. 2
Load 100% GAS
Date 15/11/12
Time 12:00-13:30
Test n. 2
Load 100% GAS
CREDITS
Credit due to Entering Dry Air 5.15.1 % 0.51 QpBDA
Credit due to moisture in entering air 5.15.2 % 0.0115 QpBWA
Credit due to sensible heat in fuel 5.15.3 % 0.0038 QpBF
Total Credits calculated on percent input from fuel % 0.53 SmQpB
CREDITS
Credit due to electricity driven equipment kW 1502.7 QrBX QX * EX
BOILER EFFICIENCY
(100-
Boiler efficiency % 87.25 EF SmQpL+SmQpB)*((QrO*1000)/(QrO*1000+(QrLSrc)-
(QrBX)))
WEST DELTA ELECTRICITY PRODUCTION COMPANY ABU QIR THERMAL POWER PLANT UNITS 6 & 7
2 x 650 MW GAS/OIL FIRED UNITS GUARANTEED EFFICIENCY CALCULATION
Date 15/11/12
Time 12:00-13:30
Test n. 2
Load 100% GAS
ADDITIONAL BOILER FUNCTIONAL AND EQUIPMENT TESTS Units Value Symbol Formula