Вы находитесь на странице: 1из 2

Instructions

MT / MTZ / NTZ Compressors


1" : 80 Nm
1"1/4 : 90 Nm
1"3/4 : 110 Nm

15 Nm
15 Nm
HM12-50
HM8-40

C
Model Supply Voltage
C S Number
S R Maximum current
Serial Starting current
Number
Housing
R
Service
Pressure

Lubricant

Never operate compressors without terminal cover fitted

1 PSC 1 CSR 3
230 V 230 V
Start Relay
C
C
Thermostat Thermostat 5
IOL
IOL
2

A+C S R A+C 1 S R
BF

15 k -1 w

MT MTZ MTZ MTZ NTZ


Operating limits
R22 R407C R134a R404A / R507A
High side pressure range bar (g) 10,9 - 27,7 12,5 - 29,4 7,9 - 22,6 13,2 - 27,7 13,2 - 27,7
Low side pressure range bar (g) 1,0 - 7,0 1,4 - 6,6 0,6 - 4,7 1,0 - 7,2 0,1 - 3,3
Discharge temperature must be kept lower than 130C

Installation and servicing of the compressor by qualified personnel only. Follow these instructions and sound refrigeration engineering
practice relating to installation, commissioning, maintenance and service.

The compressor must only be The compressor is delivered under Under all circumstances, the The compressor must be handled
used for its designed purpose(s) and nitrogen gas pressure (between 0.3 EN378 (or other applicable local safety with caution in the vertical posi-
within its scope of application (refer and 0.7 bar) and hence cannot be regulation) requirements must be tion (maximum offset from the
to operating limits). connected as is; refer to the as- fulfilled. vertical : 15)
Consult Application guidelines and da- sembly section for further details.
tasheet available from cc.danfoss.com

1 FRCC.EI.002.A1.02 Danfoss Commercial Compressors 04/08


Instructions
1 - Introduction to the compressor while it is under vacuum as side as far as possible from the compressor.
this may cause internal damage. The compressor must be operating during this
These instructions pertain to the Maneurop MT, process.
MTZ & NTZ compressors used for refrigeration 7 Electrical connections Do not overcharge the system.
systems. They provide necessary information re- Never release refrigerant to the atmosphere.
garding safety and proper usage of this product. Switch off and isolate the main power supply. Before leaving the installation site, carry out
See overleaf for wiring details. a general installation inspection regarding
2 Handling and storage The compressor is protected against excess cleanliness, noise and leak detection.
current and temperature by an internal over- Record type and amount of refrigerant charge
Handle the compressor with care. Use the load protector. Follow local regulations regar- as well as operating conditions as a reference
dedicated handles in the packaging. Use the ding power line protection. The compressor for future inspections.
compressor lifting lug and use appropriate and must be connected to earth.
safe lifting equipment. All electrical components must be selected as per 12 - Maintenance
Store and transport the compressor in an local standards and compressor requirements.
upright position. Internal pressure and surface temperature
Store the compressor between -35C and 8 Filling the system are dangerous and may cause permanent injury.
50C. Maintenance operators and installers require
Dont expose the compressor and the packa- Keep the compressor switched off. appropriate skills and tools. Tubing temperature
ging to rain or corrosive atmosphere. Fill the refrigerant in liquid phase into the may exceed 100C and can cause severe burns.
condenser or liquid receiver. The charge must
3 Safety measures before assembly be as close as possible to the nominal system Ensure that periodic service inspections to
charge to avoid low pressure operation and ex- ensure system reliability and as required by local
Never use the compressor in a flammable at- cessive superheat. regulations are performed.
mosphere. Keep the refrigerant charge below 2.5 kg per
compressor cylinder if possible. Above this To prevent system related compressor problems,
The compressor ambient temperature may not limit; protect the compressor against liquid following periodic maintenance is recommended:
exceed 50C during off-cycle. flood-back with a pump-down cycle or suction Verify that safety devices are operational and
Mount the compressor on a horizontal flat sur- line accumulator. properly set.
face with less than 3 slope. Never leave the filling cylinder connected to Ensure that the system is leak tight.
Verify that the power supply corresponds to the circuit to avoid overfilling. Check the compressor current draw.
the compressor motor characteristics (see Confirm that the system is operating in a way
nameplate). 9 Verification before commissioning consistent with previous maintenance records
When installing MTZ or NTZ, use equipment and ambient conditions.
specifically reserved for HFC refrigerants which Use safety devices such as safety pressure Check that all electrical connections are still
was never used for CFC refrigerants. switch and mechanical relief valve in compliance adequately fastened.
Use clean and dehydrated refrigeration-grade with both generally and locally applicable regu- Keep the compressor clean and verify the ab-
copper tubes and silver alloy brazing material. lations and safety standards. Ensure that they are sence of rust and oxidation on the compressor
Use clean and dehydrated system components. operational and properly set. shell, tubes and electrical connections.
The piping connected to the compressor must be
flexible in 3 dimensions to dampen vibrations. Check that the settings of high-pressure swit- 13 - Warranty
ches and relief valves dont exceed the maximum
4 - Assembly service pressure of any system component. Always transmit the model number and serial
number with any claim filed regarding this pro-
Slowly release the nitrogen holding charge A low-pressure switch is recommended to duct.
through the schrader port. avoid vacuum operation. Minimum setting 0.1
Remove the gaskets when brazing rotolock bar. The product warranty may be void in following
connectors. Verify that all electrical connections are pro- cases:
Always use new gaskets for assembly. perly fastened and in compliance with local Absence of nameplate.
Connect the compressor to the system as soon regulations. External modifications; in particular, drilling,
as possible to avoid oil contamination from When a crankcase heater is required, it must be welding, broken feet and shock marks.
ambient moisture. energized at least 12 hours before initial start- Compressor opened or returned unsealed.
Avoid material entering into the system while up and start-up after prolonged shutdown. Rust, water or leak detection dye inside the
cutting tubes. Never drill holes where burrs compressor.
cannot be removed. 10 Start-up Use of a refrigerant or lubricant not approved
Braze with great care using state-of-the-art by Danfoss.
technique and vent piping with nitrogen gas All service valves must be in the open posi- Any deviation from recommended instructions
flow. tion. pertaining to installation, application or main-
Connect the required safety and control de- Balance the HP/LP pressure. tenance.
vices. When the schrader port is used for this, Energize the compressor. It must start promptly. Use in mobile applications.
remove the internal valve. If it does not, switch it off immediately. Possible Use in explosive atmospheric environment.
single phase miswiring can cause burn-out No model number or serial number transmitted
5 Leak detection within seconds. with the warranty claim.
If the compressor does not start, check wiring
Never pressurize the circuit with oxygen or dry conformity and voltage on terminals. 14 Disposal
air. This could cause fire or explosion. If the internal overload protector trips out, it
must cool down to 60C to reset. Depending Danfoss recommends that compressors
Do not use dye for leak detection. on ambient temperature, this may take up to and compressor oil should be recycled by
Perform a leak detection test on the complete several hours. a suitable company.
system.
The low side test pressure must not exceed 25 11 Check with running compressor
bar.
When a leak is discovered, repair the leak and Check current draw and voltage.
repeat the leak detection. Check suction superheat to reduce risk of
slugging.
6 Vacuum dehydration When a sight glass is provided observe the oil
level at start and during operation to confirm
Never use the compressor to evacuate the that the oil level remains visible.
system. Respect the operating limits as printed overleaf.
Connect a vacuum pump to both the LP & HP Check all tubes for abnormal vibration. Move-
sides. ments in excess of 1.5 mm require corrective
Evacuate the system to a pressure of 500 m measures such as tube brackets.
Hg (0.67 mbar) absolute. When needed, additional refrigerant in the
Do not use a megohmmeter nor apply power liquid phase may be added in the low-pressure

2 FRCC.EI.002.A1.02 Danfoss Commercial Compressors 04/08

Вам также может понравиться