Академический Документы
Профессиональный Документы
Культура Документы
1 Introduction Contents
1 Introduction ...................................................... 1
The electro-mechanical power meter has been
1.1 Specification ...................................................... 2
gradually replaced by the electronic meter.
2 MKM34Z128 microcontroller series ............... 3
Modern electronic meters have a number of 3 Basic theory ..................................................... 4
advantages over their electro-mechanical 3.1 Active energy ..................................................... 4
predecessors. Their mechanical construction is 3.2 Reactive energy ................................................. 4
more cost-effective due to the fact that there are 3.3 Active power ...................................................... 5
no moving parts. In addition, electronic meters 3.4 Reactive power .................................................. 5
have a one percent accuracy, or even better, in 3.5 RMS current and voltage .................................. 5
the dynamic range of power measurement of 3.6 Apparent Power ................................................. 6
1000:1, whereas electro-mechanical meters have 3.7 Power factor ...................................................... 6
a two percent accuracy in the dynamic range of 4 Hardware design .............................................. 6
80:1. The higher the accuracy and dynamic 4.1 Power supply ..................................................... 7
range of the measurement, the more precise the 4.2 Digital circuits ................................................... 8
4.3 Analog circuits ................................................ 12
energy bills.
5 Software design ............................................. 14
This design reference manual describes a 5.1 Block diagram ................................................. 14
solution for a one-phase electronic power meter 5.2 Software tasks ................................................. 15
based on the MKM34Z128CLL5 5.3 Performance .................................................... 19
microcontroller. This microcontroller is part of 6 Application set-up.......................................... 21
the Freescale Kinetis-M microcontroller family. 7 FreeMASTER visualization ........................... 22
8 Accuracy and performance .......................... 24
The Kinetis-M microcontrollers address
8.1 Room temperature accuracy testing ............. 25
accuracy needs by providing a high- 8.2 Extended temperature accuracy testing ....... 26
performance analog front-end (24-bit AFE) 8.3 EMC testing ..................................................... 27
combined with an embedded Programmable 9 Summary......................................................... 28
Gain Amplifier (PGA). Besides high- 10 References...................................................... 30
performance analog peripherals, these new 11 Revision history ............................................. 31
devices integrate memories, input-output ports,
digital blocks, and a variety of communication
options. Moreover, the ARM Cortex-M0+ core,
with support for 32-bit math, enables fast
execution of metering algorithms.
1.1 Specification
As already indicated, the Kinetis-M one-phase power meter reference design is ready for use in a real
application. More precisely, its metrology portion has undergone thorough laboratory testing using the
test equipment ELMA8303 [1]. Thanks to intensive testing, an accurate 24-bit AFE, and continual
algorithm improvements, the one-phase power meter calculates active and reactive energies more
accurately and over a higher dynamic range than required by common standards. All information,
including accuracies, operating conditions, and optional features, are summarized in the following table:
Table 1-1. Kinetis-M one-phase power meter specification
Type of meter One-phase residential
Type of measurement 4-Quadrant
Metering algorithm Filter-based
Precision (accuracy) IEC50470-3 class C, 0.5% (for active and reactive energy)
Voltage range 90265 VRMS
Current Range 0120 A (5 A is nominal current, peak current is up to 152 A)
Frequency range 4753 Hz
500, 1000, 2000, 5000, 10000, 20000, 50000 (default), 100000, 200000,
Meter constant (imp/kWh, imp/kVArh) 500000, 1000000, 2000000, 4000000 and 6000000. Note, that pulse
numbers above 50000 are applicable only for low-current measurement.
Functionality V, A, kW, kVAr, kVA, kWh (import/export), kVARh (lead/lag), Hz, time, date
Voltage sensor Voltage divider
Current sensor Shunt resistor down to 120
Energy output pulse interface Two red LEDs (active and reactive energy)
3 Basic theory
The critical task for a digital processing engine or a microcontroller in an electricity metering application
is the accurate computation of the active energy, reactive energy, active power, reactive power, apparent
power, RMS voltage, and RMS current. The active and reactive energies are sometimes referred to as the
billing quantities. The remaining quantities are calculated for informative purposes, and they are referred
as non-billing. Further follows a description of billing and non-billing metering quantities and calculation
formulas.
Eq. 3-1
Eq. 3-3
Eq. 3-4
Eq. 3-5
Eq. 3-6
Eq. 3-7
For sinusoidal waveforms with no higher harmonics, the apparent power can also be calculated using the
power triangle method, as a vector sum of the active power (P) and reactive power (Q) components.
Eq. 3-8
Due to better accuracy, we preferably use Eq. 3-7 to calculate the apparent power of any general
waveforms with higher harmonics. In purely sinusoidal systems with no higher harmonics, both Eq. 3-7
and Eq. 3-8 will provide the same results.
Eq. 3-9
where angle is the phase angle between the current and voltage waveforms in the sinusoidal
system.
Circuits containing purely resistive heating elements (filament lamps, cooking stoves, and so forth) have
a power factor of one. Circuits containing inductive or capacitive elements (electric motors, solenoid
valves, lamp ballasts, and others) often have a power factor below one.
The Kinetis-M one-phase power meter reference design uses a filter-based metering algorithm [2]. This
particular algorithm calculates the billing and non-billing quantities according to formulas given in this
section. Thanks to using digital filters, the algorithm requires only instantaneous voltage and current
samples to be provided at constant sampling intervals. After slight modification of the application
software, it is also possible to use FFT based algorithms [3], [8].
4 Hardware design
This section describes the power meter electronics. The power meter electronics are divided into three
parts:
Power supply
Digital circuits
Analog signal conditioning circuits
Eq. 4-1
The resistor values R23=45.3 k and R24=23.7 k were chosen to produce a regulated output voltage of
3.6 V. The following supply voltages are all derived from the regulated output voltage (VPWR):
VDD digital voltage for the microcontroller and digital circuits,
VDDA analog voltage for the microcontrollers 24-bit SD ADC and 1.2 V VREF,
SAR_VDDA analog voltage for the microcontrollers 16-bit SAR ADC.
2
1
3
A
VOUT VPWR
1
2
GND
L201 820uH U8
JP3
1
1 2 1 5 2
5
6
7
8
1
1
2
LNK302DN 2 L1 1uH
S10K250E2 1 2
HDR 1X1 GND
+ C220 + C221 D205 C219 C23 C24 C25 C26 10UF 10UF
2
DNP R219 3 4
4.7uF 4.7uF ES1JL C11 C10 C9
1.6K EN ADJ
JP4 JP2 JP1 JP5 100UF 10UF 10UF 10UF 10UF
HDR 1X1 HDR 1X1 HDR 1X1 HDR 1X1 1uF 1uF 1uF
A
GND GND
SPX3819M5-L
GND GND
GND GND GND GND GND GND GND GND GND GND
GND
1
NOTE
The digital and analog voltages VDD, VDDA and SAR_VDDA are lower
by a voltage drop on the diode D6 (0.35 V) than the regulated output
voltage VPWR.
D1
R216
WP7104LSRD
KVARH_LED 390.0 C A
VDD
D3
R204
HSMS-C170
USER_LED 2.0K C A
VDD
The user LED (D3) is driven by software through output pin PTH7. It blinks when the power meter
enters the calibration mode, and turns solid after the power meter is calibrated and is operating normally.
/PULSE_OUT
J1
1
2
HDR 1X2
1 4
VPWR Pulse
output
SCI0_RX R9 1.0K
1
C6 Q1
OP506B
2200PF
2
GND GND
D4
SCI0_TX R10 680 A C
TSAL4400
GND
VPWR
1 4
D201
R3 4.7K A C
A
MMSD4148T1G J202
R8
C3 1 2
1.0K
D200 RXD 3 4 RTS
SFH6106-4
2.2uF MMSD4148T1G TXD 5 6
U3
DTR 7 8
C
HDR_2X5
Max. 19200 Bd
D202
4 1 C A
MMSD4148T1G
GND
12
11 NC_12
NC_11
VDD
C5 0.1UF 1 10 MMA_XOUT
BY P XOUT
GND 2 9 MMA_Y OUT
VDD Y OUT
I2C0_SDA 3 8 MMA_ZOUT
SDA ZOUT
MMA_EN 4 7
EN GND GND
GND
SCL
R6 4.7K
5
6
MMA8491Q
R5 4.7K
I2C0_SCL
C4
0.1UF
GND GND
8
U2
C2
0.1UF
4 W25X10CLSN
GND GND
8
U1
SPI0_MOSI 5
SI VCC
R1 10K 1
CS
3 2 SPI0_MISO
WP SO
7
HOLD
SPI0_SCK 6
SCK VSS
EEPROM_SS
CAT25040VE
C1 4
0.1UF
GND GND
J200 VPWR
1 2 C201 0.1UF
3 4 GND
5 6 SCI3_TX
7 8 SCI3_RX R202 R201
RF_RST 9 10 4.7K 4.7K
SCI3_RTS 11 12
SCI3_CTS 13 14
15 16
I2C1_SDA
I2C1_SCL
RF_IO 17 18 RF_CTRL
19 20
GND
CON_2X10
NOTE
Both the UMI and RF MC1323x-IPB interfaces are designed to supply the
external communication modules from the regulated output voltage
VPWR. Therefore, use only communication modules with a supply
voltage of 3.6 V and a continuous current of up to 60 mA.
C16
J7
0.1UF
RES_OUT 1
RES_INP 2
GND
HDR 1X2
R20 22 DNP
SDADM0
C17
0.1UF
GND
C14
R21
390
0.015 UF
GND GND
SDADM2
C15
R18
390
0.015 UF
GND
1
Vishay Beyschlags MELF0204 resistors maximum operating voltage is 200 V. The maximum power dissipation is 0.25 W
for a temperature range of up to 70 C.
R220 1.6M
GND
R221 4.7M
VBAT
Status information on whether the power meter is connected or disconnected from the mains is critical
for transitioning between the power meter operating modes. The presence of a mains AC voltage is
signaled by the logic signal PWR_MSR that is derived from the regulated output voltage (VPWR). If the
power meter is connected to the mains (VPWR=3.6 V), the PWR_MSR will transition to 3.15 V and the
software will read this signal from the PTC5 pin as logic 1. On the other hand, a power meter
disconnected from the mains will be read by the microcontroller device as logic 0.
R222 47K
VPWR
R223 330K
GND
C223 0.1UF
PWR_MSR
5 Software design
This section describes the software application of the Kinetis-M one-phase power meter reference
design. The software application consists of measurement, calculation, calibration, user interface, and
communication tasks.
Communications and
Pulse Output Generation
FreeMASTER Segment LCD
Controller Driver
HMI
IR interface UART0 Peripheral Crossbar Isolated open-
(IEC1107) Driver (XBAR) Driver collector output
GPIO & PORT
Drivers
FreeMASTER Quad Timer (TMR) Peripheral Crossbar kWh and kVARh
Protocol Library Driver (XBAR) Driver LEDs
SPI1
Driver
Data Processing Analog Measurements and Energy Calculations
(executes periodically)
Filter Based Phase Voltage and
Analogue Front-End
Metering Algorithm Current Signal
(AFE) Driver
Library Conditioning Circuit
Clock Management Calculation Billing Quantities
(executes periodically)
Independent Real
Time Clock (IRTC)
Driver
32.768 kHz External Calculation Non-billing Auxiliary Measurements Battery Voltage
Crystal Quantities Conditioning Circuit
Phase-Locked Loop (executes periodically) Analog-to-Digital
(PLL) Driver Converter (ADC)
Driver
Supply Voltage
HMI Control / Interaction Task
Conditioning Circuit
(execute periodically)
Advanced Tampering
Device Initialization and Security
Communication Tasks
I2C0 (event triggered execution) Watchdog (WDOG) Voltage Reference
Driver Driver (VREF) Driver
MMA8491Q 3-axis
digital accelerometer Parameter Management
Tasks Low Leakage
GPIO & PORT System Integration
(event triggered execution) Wakeup (LLWU)
Drivers Module (SIM) Driver
Driver
Power Management
System Mode Power Management
Non-volatile Memory SPI0 Driver
Controller (SMC) Controller (PMC) SPI1 Driver
(NVM) Driver
Driver Driver
All tasks executed by the Kinetis-M one-phase power meter software are briefly explained in the
following subsections.
Eq. 5-1
Eq. 5-2
Eq. 5-3
where , are calibration gains, is the calculated phase shift caused by parasitic
inductance of the shunt resistor, and , , , are quantities measured by the non-
calibrated meter.
Eq. 5-4
Eq. 5-5
5.2.4 Calculations
The execution of the calculation task is carried out periodically every 833.3 s. The calculation task
scales the samples using calibration offsets and calibration gains obtained during the calibration phase:
Eq. 5-6
Eq. 5-7
where , are measured samples, , and are
calibration parameters.
The scaled samples are then used by the metering algorithm.
NOTE
We found experimentally that increasing the calculation update rate
beyond 1200 Hz doesnt improve the accuracy of the measurement and
calculations.
5.3 Performance
Table 5-2 shows the memory requirements of the Kinetis-M one-phase power meter software
application2.
Table 5-2. Memory requirements
Flash size RAM size
Function Description
[KB] [KB]
The software application reserves the 4.0 KB RAM for the FreeMASTER recorder. If the recorder is not
required, or a fewer number of variables will be recorded, you may reduce the size of this buffer by
modifying the FMSTR_REC_BUFF_SIZE constant (refer to the freemaster_cfg.h header file, line 72).
2
Application compiled using the IAR Embedded Workbench for ARM (version 6.50.6) with full optimization for execution
speed.
NOTE
The filter-based metering algorithm configuration tool estimates the
minimum system clock frequency for the ARM Cortex-M0+ core to
calculate billing and non-billing quantities with an update rate of 1200 Hz
to approximately 8.4 MHz. As shown in the following figure, by slowing
down the update rate of the non-billing calculations from 1200 to 600 Hz
and further by reducing the Hilbert-filter length from 49 to 39-taps, the
required performance will even decrease by 32.14% to 5.7 MHz.
Figure 5-3. Minimum system clock requirements for the filter-based metering algorithm
Re-active
energy LED
(red)
Built-in optical readout
interface: 4800/8-N-1
User button
Tamper
button 1 (hidden)
User LED
(red)
Tamper
button 2 (hidden)
Terminal
cover
PHASE
Mains 120/230V
(50Hz) NEUTRAL NEUTRAL
External load up to
PHASE 80A or 120 A
Among the main capabilities of the power meter, is registering the active and reactive energy consumed
by an external load. After connecting the power meter to the mains, or when you press the user button,
the power meter transitions from the power-down mode to either the normal mode or standby mode,
respectively. In normal and standby modes, the LCD is turned on and shows the last quantity. The user
can list through the menus and display other quantities by pressing the user button. All configuration and
informative quantities accessible through the LCD are summarized in the following table:
Table 6-1. Quantities shown on the LCD
Value Units Format OBIS code
Class according to
- C # #-###A (example C 5-120A)
EN50470-3
7 FreeMASTER visualization
The FreeMASTER data visualization and calibration software is used for data exchange [5]. The
FreeMASTER software running on a PC communicates with the Kinetis-M one-phase power meter over
an optical head attached to the IR interface (IEC1107). The communication is interrupt driven and is
active when the power meter is powered from the mains. The FreeMASTER software allows remote
visualization, parameterization and calibration of the power meter. It runs visualization scripts which are
embedded into a FreeMASTER project file.
Before running a visualization script, the FreeMASTER software must be installed on your PC. After
installation, a visualization script may be started by double-clicking on the monitor.pmp file. Once
started, the following visualization script will appear on your computer screen.
Now, you should set the proper serial communication port and communication speed in the
Project/Option menu (see Figure 7-2). After communication parameters are properly set and the Stop
Now you can see the measured phase voltages, phase current, active, reactive and apparent powers, pulse
numbers and additional status information in FreeMASTER. You may also visualize some variables in a
graphical representation by selecting the respective scope or recorder item from the tree.
The visualization script allows you to monitor and parameterize the majority of the power meter features.
To eliminate inappropriate and unwanted changes, some key parameters are protected by a 5-digit system
password. These key parameters are as follows:
Set Calendar
Set Imp/kWh
Set Imp/kVARh
Recalibration
All the remaining parameters and commands can be executed anytime, without the need for entering the
system password:
LCD Screen Select
Software Reset
Clear Energy Counters
Clear Tampers
Most of all, FreeMASTER will be used for monitoring the power meter operation and analyzing the
phase voltages and phase currents waveforms in real-time. The visualization script file contains the
following visualization objects:
Recorders (833 s update rate, the number of samples optional but limited to 4096 bytes)
o Raw instantaneous phase voltage and current samples
o High-pass filtered instantaneous phase voltage and current samples
Scopes (10 ms update rate, the number of samples unlimited)
o Energy profile (kWh and kVARh counters with resolution 10-5)
o RMS voltage, RMS current, active power, reactive power, and apparent power.
o Power meters actual date and time
o Mains frequency
Variables and Enumerations (shown in text form)
Then advanced users can benefit from FreeMASTERs built-in an active-x interface that serves for
exchanging data with other signal processing and programming tools, such as Matlab, Excel, LabView,
and LabWindows.
3
The active and reactive energy LED impulse numbers were set to 50,000 pulses per kWh and kVARh respectively.
By analyzing the protocols of several Kinetis-M one-phase power meters, it can be said that this
equipment measures active and reactive energies at all power factors, a 25 C ambient temperature, and
in the current range 0.25-120 A4, more or less with an accuracy range 0.25%.
4
The current and voltage measurements were scaled to I_MAX= 152 A and U_MAX= 286 V.
Figure 8-2. Power meter inside a heat chamber temperature controlled to -40 C
Figure 8-3 shows the accuracy of the power meter evaluated at an extended temperature range. The
accuracy margins defined by EN50470-3 for Class C power meters and the extended temperature range
are denoted by gray lines. As you can see, the active energy measured by the power meter at all
temperatures fits within accuracy margins mandated by the standard.
4kV contact B A
Electrostatic
EN 61000-4-2
discharge (ESD) 8 kV air B A
Through
enclosure 15 kV indirect
B A
application
Magnetic field of No degradation of the function
network EN 61000-4-8 30 A/m A A occurred.
frequency 50 Hz
0 % -0.02 s (1 period) B A
Voltage dip
EN 61000-4-11
(DIPS) 20 % -0.2 s (10 period) C A
The records of individual tests show that the Kinetis-M one-phase power meter has a proven exceptional
EMC performance exceeding the functional criteria required by the standard. The first and last pages of
the power meters EMC test report are provided by agreement of the TV SD Czech s.r.o. in
Appendix D-EMC test report.
9 Summary
This design reference manual describes a solution for a one-phase electronic power meter based on the
MKM34Z128CLL5 microcontroller.
Freescale semiconductor offers Filter and FFT based metering algorithms for use in customer
applications. The former calculates metering quantities in the time domain, the latter in the frequency
domain. The reference manual explains the basic theory of power metering and lists all the equations to
be calculated by the power meter.
The hardware platform of the power meter is algorithm independent, so application firmware can
leverage any type of metering algorithm based on customer preference. In order to extend the power
meter uses, the hardware platform comprises a 128 KB SPI flash for firmware upgrade, 4 KB SPI
EEPROM for data storage, an MMA8491Q 3-axis multifunction digital accelerometer for enhanced
tampering, and UMI and RF MC1323x-IPB interfaces for AMR communication and monitoring.
The application software has been written in C-language and compiled using the IAR Embedded
Workbench for ARM (version 6.50.6), with full optimization for the execution speed. It is based on the
Kinetis-M bare-metal software drivers [7] and filter-based metering library [2]. The application firmware
automatically calibrates the power meter, calculates all metering quantities, controls active and reactive
energy pulse outputs, runs the HMI (LCD and button), stores and retrieves parameters from flash
memory, and allows monitoring the application, including recording selected waveforms through the
FreeMASTER. An application software of such complexity requires 29.9 KB of flash and 6.6 KB of
RAM. The system clock frequency of the MKM34Z128CLL5 device must be 12.288 MHz or higher to
calculate all metering quantities with an update rate of 1200 Hz.
The power meter is designed to transition between three operating modes. It runs in the so-called normal
mode when it is powered from the mains. In this mode, meter electronics consume 10.88 mA. The
second mode, the so-called standby mode, is entered when the power meter runs from the battery and the
user lists through the menus. In this particular mode, the 3.6V Li-SOCI2 (1.2Ah) battery is discharged by
245 A, resulting in 4,100 hours of operation (0.47 year battery lifetime). Finally, when the power meter
runs from the battery but no interaction with the user occurs, the power meter electronics automatically
transition to the power-down mode. The power-down mode is characterized by a current consumption as
low as 5.6 A, which results in 143,000 hours of operation (16.3 year battery lifetime).
VREFH
KWH_LED
VREFL
VCAP1
VDD
VLL1
VLL2
VLL3
2 DNP 1 2 SPI1_MISO
R200 0 3 4 SPI1_MOSI
2
D1 GND HDR 1X2 5 6 SPI1_SCK
C207 C209 C13 C8 C214 C213 C212 C204 C205 C203 C202 R216 C200 GND 7 8
WP7104LSRD DNP UMI_SS
KVARH_LED 390.0 C A UMI_INT 9 10 UMI_RST
0.1UF 0.1UF 0.1UF 0.1UF 0.1UF 0.1UF 0.1UF 0.1UF 0.1UF 0.1UF 0.1UF VDD J3 0.1UF
TAMPER2 R214 10K 1
VCAP2
SW1 2 HDR_2X5
TL3301AF160QG D3 GND DNP
R204
GND GND GND GND GND GND GND GND GND HSMS-C170
USER_LED 2.0K C A GND HDR 1X2 VPWR
Place close to Place close to Place close to Place close Place close Place close VDD DNP J200
VDD pins VDDA pin SAR_VDDA pin to VBAT pin to VREFH pin to VREFL pin Place close to LCD bias and charge pump pins 1 2 C201 0.1UF
Max current 700nA @3.3V when tamper inactive. GND
3 4
5 6 SCI3_TX
3
VREFH
VCAP1
VCAP2
SCI3_CTS 13 14
VLL1
VLL2
VLL3
GNDGND
15 16
I2C1_SDA
Max current 9.7uA @3.3V when button active
I2C1_SCL
RF_IO 17 18 RF_CTRL
19 20 Populate J200 on the bottom layer
100
below LCD accordingly to the size
10
62
31
99
98
97
96
24
37
61
U7 of the MC1322X-IPB board.
MMA8491 3-AXIS LOW VOLTAGE TILT SENSOR GND
1
LCD16 1 CON_2X10
VDD1
VDD2
VDDA
VLL1
VLL2
VLL3
VCAP1
VCAP2
SAR_VDDA
VBAT
VREFH
LCD15 2 PTA0/LCD23 25
LCD14 3 PTA1/LCD24 XTAL32K 26 Y1
U5 LCD13 4 PTA2/LCD25 EXTAL32K 32.768KHz SWD CONNECTOR PHASE CURRENT SENSING
12
11
PTA3/LCD26 VDD
LCD12 5 R211 4.7M
LCD11 6 PTA4/LCD27/LLWU_P15/NMI VDD J2
2
R19 22
NC_12
NC_11
1
PWR_MSR 44 PTC4/LCD43 GND
VBAT_MSR 45 PTC5/AD0/SCI0_RTS/LLWU_P12 C6 Q1 PLACE CLOSE TO MCU
C206 0.1UF SCI0_TX 46 PTC6/AD1/SCI0_CTS/QT1 OP506B
GND GND
PTC7/AD2/SCI0_TXD/PXBAR_OUT2 SCI0_RX is muxed with both 2200PF
Shutdown current: 68nA @ 2.8V
2
R209 1.6M SCI0_RX 47 41 LLWU and AWIC so wakeup
feature is supported. PHASE VOLTAGE SENSING
GND KVARH_LED 48 PTD0/CMP0P0/SCI0_RXD/PXBAR_IN2/LLWU_P11 VREF GND GND
49 PTD1/SCI1_TXD/SPI0_SS/PXBAR_OUT3/QT3 VIN
R208 4.7M SPI0_SCK D4
PTD2/CMP0P1/SCI1_RXD/SPI0_SCK/PXBAR_IN3/LLWU_P10
128kB SPI FLASH VBAT SPI0_MOSI
SPI0_MISO
50
51 PTD3/SCI1_CTS/SPI0_MOSI SCI0_TX R10 680 A C
R13 R14 R15 R12
VPWR R212 330K 52 PTD4/AD3/SCI1_RTS/SPI0_MISO/LLWU_P9
VDD
EEPROM_SS ~2.65mA @ 3.3V SDADP2 150K 150K 150K 150K
FLASH_SS 53 PTD5/AD4/LPTIM2/QT0/SCI3_CTS TSAL4400
C210 0.1UF USER_BTN 54 PTD6/AD5/LPTIM1/CMP1OUT/SCI3_RTS/LLWU_P8
GND GND
8 PTD7/CMP0P4/I2C0_SCL/PXBAR_IN4/SCI3_RXD/LLWU_P7 C14
R21
U2 KWH_LED 55 390
C12 0.1UF /RESET 56 PTE0/I2C0_SDA/PXBAR_OUT4/SCI3_TXD/CLKOUT 0.015 UF
SPI1_MOSI 5 VCC 2 SPI1_MISO GND PTE1/RESET
DI/IO0 DO/IO1
R17 4.7K
I2C1_SDA
I2C1_SCL
57
58 PTE2/EXTAL1/EWM_IN/PXBAR_IN6/I2C1_SDA ISOLATED PULSE OUTPUT
SPI1_SCK 6 63 PTE3/XTAL1/EWM_OUT/AFE_CLK/I2C1_SCL
CLK VDD RF_RST U6 GND GND
R2 10K RF_CTRL 64 PTE4/LPTIM0/SCI2_CTS/EWM_IN SFH6106-4
1 7
CS HOLD SWD_RESETR16 820 SWD_IO 65 PTE5/QT3/SCI2_RTS/EWM_OUT/LLWU_P6
SWD_CLK 66 PTE6/CMP0P2/PXBAR_IN5/SCI2_RXD/LLWU_P5/SWD_IO R11 390.02 3
3
/PULSE_OUT
PTE7/AD6/PXBAR_OUT5/SCI2_TXD/SWD_CLK SDADM2
WP
GND UMI_INT 67 J1
FLASH_SS
SCI1_TX
SPI0_MOSI 5 COM3 82
3 2
SI VCC PTG7/LCD14 LCD3
R1 10K LCD4 4 3
1 COM2 83 4
CS PTH0/LCD15 LCD5 5
COM1 84 5
PTH1/LCD16 LCD6 6
3 2 SPI0_MISO LCD22 85 6 VPWR
WP SO PTH2/LCD17 LCD7 7
LCD21 86 7
PTH3/LCD18 LCD8 8 1 4
7 LCD20 87 8
HOLD PTH4/LCD19 LCD9 9
LCD19 88 9 D201
PTH5/LCD20 LCD10 10 R3 4.7K
SPI0_SCK 6 89
11 10 A C
SCK VSS 90 PTH6/SCI1_CTS/SPI1_SS/PXBAR_IN7 LCD11
USER_LED 12 11
EEPROM_SS
LCD12
A
CAT25040VE PTH7/SCI1_RTS/SPI1_SCK/PXBAR_OUT7 MMSD4148T1G J202
C1 LCD13 13 12 R8
4 SCI1_RX 91 13 C3
0.1UF PTI0/CMP0P5/SCI1_RXD/PXBAR_IN8/SPI1_MISO/SPI1_MOSI LCD14 14 1.0K 1 2
SCI1_TX 92 14 D200
PTI1/SCI1_TXD/PXBAR_OUT8/SPI1_MOSI/SPI1_MISO LCD15 15 SFH6106-4 3 4
LCD18 93 15 2.2uF MMSD4148T1G
LCD16 16 5 6
SAR_VSSA
LCD17 94 PTI2/LCD21 U3
LCD17 17 16 7 8
C
GND GND PTI3/LCD22
Standby Current: 2uA 17 R4 470
VREFL
LCD18 18 SCI1_RX 3 2 9 10
VSSA
VSS1
VSS2
VSS3
VSS4
LCD19 19 18
LCD20 20 19
20 HDR_2X5
POWER SUPPLY TEST POINTS LCD21
LCD22
21
22 21
11
27
59
95
32
38
60
PKM34Z128CLL5 23 22
TP2 TP4 TP3 TP5 TP6 TP1 COM1 Max. 19200 Bd
COM2 24 23 D202
VREFL
COM3 25 24 4 1 C A
COM4 26 25
GND GND GND 26
VPWR VBAT GND VDD VDDA SAR_VDDA MMSD4148T1G
PLACE ALL PASSIVES CLOSE TO RESPECTIVE MCU PINS GND
LCD MODULE
2
1
3
A
VOUT VPWR
1
2
GND
L201 820uH U8
JP3
1
1 2 1 5 2
5
6
7
8
1
1
2
LNK302DN 2 L1 1uH
S10K250E2 1 2
HDR 1X1 GND
+ C220 + C221 D205 C219 C23 C24 C25 C26 10UF 10UF
2
DNP R219 3 4
4.7uF 4.7uF ES1JL C11 C10 C9
1.6K EN ADJ
JP4 JP2 100UF JP1 JP5 10UF 10UF 10UF 10UF
HDR 1X1 HDR 1X1 HDR 1X1 HDR 1X1 1uF 1uF 1uF
A
GND GND
SPX3819M5-L
GND GND
GND GND GND GND GND GND GND GND GND GND
GND
1
Home Page: Information in this document is provided solely to enable system and software
freescale.com implementers to use Freescale products. There are no express or implied copyright
licenses granted hereunder to design or fabricate any integrated circuits based on the
Web Support: information in this document.
freescale.com/support
Freescale reserves the right to make changes without further notice to any products
herein. Freescale makes no warranty, representation, or guarantee regarding the
suitability of its products for any particular purpose, nor does Freescale assume any
liability arising out of the application or use of any product or circuit, and specifically
disclaims any and all liability, including without limitation consequential or incidental
damages. Typical parameters that may be provided in Freescale data sheets and/or
specifications can and do vary in different applications, and actual performance may vary
over time. All operating parameters, including typicals, must be validated for each
customer application by customers technical experts. Freescale does not convey any
license under its patent rights nor the rights of others. Freescale sells products pursuant
to standard terms and conditions of sale, which can be found at the following address:
freescale.com/SalesTermsandConditions.
Freescale, the Freescale logo, and Kinetis are trademarks of Freescale Semiconductor,
Inc., Reg. U.S. Pat. & Tm. Off. All other product or service names are the property of their
respective owners. ARM is the registered trademarks of ARM Limited. ARM Cortex-M0+
is the trademark of ARM Limited.