Mihan Gas Co. Document Title: Process Data Sheet for Fire Water Pumps Rev.: 03
Date:
Dept:
Signature:
Mihan Gas Co. Document Title: Process Data Sheet for Fire Water Pumps Rev.: 03
revision Index
Rev. Rev.
Sheet Sheet
01 02 03 04 05 06 07 08 01 02 03 04 05 06 07 08
1 31
2 32
3 X X X 33
4 X X X 34
5 X 35
6 36
7 37
8 38
9 39
10 40
11 41
12 42
13 43
14 44
15 45
16 46
17 47
18 48
19 49
20 50
21 51
22 52
23 53
24 54
25 55
26 56
27 57
28 58
29 59
30 60
Spherical Tanks
P.O. No.: MGC/VOL/IPS/110
Petro Sazeh Beinolmelal Aram Co
Mihan Gas Co. Document Title: Process Data Sheet for Fire Water Pumps Rev.: 03
GENERAL DATA
OTHER SPECIFICATIONS
ENCLOSURES/REMARKS
NOTE(S):
1 WATER ANALYSIS SHALL BE ATTACHED BY THE CLIENT
03 2 VOID
3 EXACT VALUE WILL BE SPECIFIED BY VENDOR
4 SHUT OFF PRESSURE SHALL NOT EXCEED 120% OF THE OPERATING PRESSURE
5 INCH CIRCULATION RELIEF VALVE ACCORDING TO NFPA 20 SHALL BE SUPPLIED BY VENDOR.
03 5 SUCTION STRAINER PROPERTIES SHALL BE SPECIFIED BY VENDOR
6
7
Spherical Tanks
P.O. No.: MGC/VOL/IPS/110
Petro Sazeh Beinolmelal Aram Co
Mihan Gas Co. Document Title: Process Data Sheet for Fire Water Pumps Rev.: 03
GENERAL DATA
OTHER SPECIFICATIONS
ENCLOSURES/REMARKS
NOTE(S):
1 WATER ANALYSIS SHALL BE ATTACHED BY THE CLIENT
2 VOID
03
3 EXACT VALUE WILL BE SPECIFIED BY VENDOR
4 SHUT OFF PRESSURE SHALL NOT EXCEED 120% OF THE OPERATING PRESSURE
5 1 INCH CIRCULATION RELIEF VALVE ACCORDING TO NFPA 20 SHALL BE SUPPLIED BY VENDOR.
6 FOR EACH DIESEL ENGINE DRIVERS FOR FIRE PUMPS A DAILY FUEL TANK SHALL BE SUPPLIED BY THE VENDOR WHICH SHALL HAVE SUFFICIENT
03 CAPACITY OF 24 HOURS OF CONTINUOUS OPERATION.
7 SUCTION STRAINER PROPERTIES SHALL BE SPECIFIED BY VENDOR
Spherical Tanks
P.O. No.: MGC/VOL/IPS/110
Petro Sazeh Beinolmelal Aram Co
Mihan Gas Co. Document Title: Process Data Sheet for Fire Water Pumps Rev.: 03
GENERAL DATA
OTHER SPECIFICATIONS
ENCLOSURES/REMARKS
NOTE(S):
1 WATER ANALYSIS SHALL BE ATTACHED BY THE CLIENT
03 2 VOID
3 EXACT VALUE WILL BE SPECIFIED BY VENDOR
03 4 SUCTION STRAINER PROPERTIES SHALL BE SPECIFIED BY VENDOR
5
6