Вы находитесь на странице: 1из 21

Energy Management Systems (EMS)

Introduction
Abstract

This talk deals with the role of an Energy Management System (EMS) in the
overall Smart Grid. Why an EMS is needed will be discussed and its importance
to the overall reliability and efficiency of the electric grid. The NERC operating
regions
g will be explain
p as well as the NERC requirements
q placed
p on electric
operating authorities. We will look at key operating functions such as
monitoring and control, generation control, load forecasting, load balancing
and the economic factors in generation and transmission of electricity. We will
also discuss key security and reliability factors which must be maintained
during normal and dynamic system operations. How operators are trained for
all emergency events will also be discussed. Finally we will look at the future of
EMS and
EMSs d where
h the
th technology
t h l is
i going.
i

2/
GE /
April 25, 2011
Why Do We need an EMS

What happens when you turn that light switch


on?

3/
GE /
April 25, 2011
Where does an EMS fit in the network?
Transmission, Distribution, &
Generation Customers

Distribution SCADA Systems


Generation Management Systems
Energy Management Systems

Distribution Sub-transmission
Residential Load Substation
Distribution

Commercial Transmission Overhead Central


Load Substation Transmission Stations
Industrial
Load

4/
GE /
April 25, 2011
NERC Region

5/
GE /
April 25, 2011
Energy Management Overview
High performance, distributed, mission critical, control

Capability to monitor, control, and optimize the operation of


geographically dispersed transmission and generation
assets in real-time
real-time.

Real-time SCADA Applications


Generation Dispatch and Control
Energy Scheduling and Accounting
Transmission Security Management

6/
GE /
April 25, 2011
EMS Application Description
Real-time SCADA Applications Providing Supervisory Control and
Data Acquisition including alarm/events, tagging, data historians, data
links, control sequences, and load shed applications used to
monitor/operate
i / the
h network.
k
Generation Dispatch and Control - GDC provides the functions
required for dispatch and closed loop digital control of multiple generators
i an economic
in i fashion
f hi while hil adhering
dh i to t NERC operating
ti guides
id att the
th
same time considering interchange schedules, dynamic schedules (load or
generation in an out of the area), inadvertent interchange payback, time
error correction,, reserve requirements,
q , and securityy constraints of the
transmission network.
Energy Scheduling and Accounting ESA provides applications to
monitor NERC reporting
p g criteria, production
p costs, interchange
g scheduling,
g
inadvertent interchange accounting, and weather adaptive demand
forecasting.
Transmission Security Management TSM provides sophisticated
applications to analyze and optimize the use of the transmission network in
a reliable and secure manner. 7/
GE /
April 25, 2011
Energy Management Systems (EMS) XA/21TM
Need
Optimally manage transmission grid and
energy generation in a reliable and secure
manner:
manner
Increase overall transmission grid
reliability proactively minimizing
blackouts
Meet stringent security requirements

Solution Benefits
Comprehensive, Integrated, Secure Sys. Improved Operational Security
State of the Art Generation Control Improved Service Reliability
and Transmission Security Applications Fuel & O&M Cost Reduction
Platform Independent User Interface Transmission Loss Reduction
Flexible Backup Control Center Options
Regulatory Compliance
Dispatcher/Operator Training Simulator
Deferred Capital Expenditure
Long-Term Evergreen Solution
8/
GE /
April 25, 2011
EMS Vision
Optimise our customers' network performance by:
Improved G&T Operational Security / Service Reliability
Improving
p g Operating
p g Efficiencyy
Fuel & O&M Cost Reduction
Transmission Loss Reduction
Regulatory
egu ato y Compliance
Co p a ce
Optimization Growth
Opportunity
Info Mgmt
Value

& Control

IEDs and Sensors Current


Offering

T&D Assets

9/
GE /
April 25, 2011
Transmission Security Management
State-of-the-Art Analytic
y Engines
g from Nexant/PCA
/
Network Topology Analysis
Load Flow
p
Complete Studyy Capability
p y Isolated From RT
Orthogonal Transformation-based State Estimator
Status/parameter estimation, Plausibility Checks
Contingency
g y Analysis
y
Analyzes The Impact Of Possible Events
Successive LP-based Optimization
Provides both active and reactive control
movement strategies to relieve violations
Contingency & Control Action Time Constraints
Real Time and Study Mode Suites
Multi-User Support - 10 cases (configurable)

A l
Analyze and
dOOptimize
ti i Utili
Utilization
ti off T
Transmission
i i A Assets
t
10 /
GE /
April 25, 2011
Security Constrained Optimal Power Flow
Objective function Algorithm
Minimize MW and MVAr losses are
MW and MVAr losses non-separable and quite nonlinear
MVArs supplied/absorbed by generating Apply cost curves to gen MVArs,
units (i.e. maximize reactive reserves) discouraging operation near limits
MVArs through network interfaces Use Successive LP with special
Subject to efficient
ffi i t piecewiselinearization
i i li i ti
techniques, iterated with accurate
Power Flow Constraints AC power flow

Maximize
MVAR
Reserves

Minimize
Losses
11 /
GE /
April 25, 2011
SCOPF (2)
SCOPF initial state (at ISO/RTOs) typically comes
from the Day-Ahead
Day Ahead SCUC
SCUC (Security
Constrained Unit Commitment) - optimal gen.
schedules within grid thermal limits.
Inputs: SCADA measurements, load forecast,
possible use of phasor
p p data,, contingency
g y list
Control variables include:
> Regulated bus voltages
> Xfmr taps
> Switching for Cap banks
> Settings for phase-shifting devices
SCOPF is run in real-time (<10 minutes to solve) in
predictive mode - suggests schedules for
control variables to operators.
operators
It is not run in an automatic post-contingency
corrective mode - yet. Nexant doing research
in this area.

12 /
GE /
April 25, 2011
Generation Dispatch & Control
Closed Loop Monitoring & Control of Generating
Assets
Automatic Generation Control (AGC)
> ATE, TLB, CNI and CF Ace Modes
> CPS1 & CPS2 Control Criteria
> Multi-Area Support
> Jointly Owned Units
Generation Dispatch (GD)
> Economic
> Security Constrained (w/TSM)
Reserve Monitoring (RMON)
> Time Limited
> Considers Role of Quick Start Assets
> Notifies Operator of Deficiencies

Meet Frequency and Interchange Obligations, Minimize Fuel-Related


Fuel Related O&M

13 /
GE /
April 25, 2011
Energy Scheduling & Accounting
Oracle Resident, Temporal Data Store
AGC Performance Monitoring (APM)
> Meets All NERC Reporting Criteria
Production Costing (PC)
> Complete Fuel, Maintenance and
Transition Cost Accounting
All GDC displays DCR driven
> Devices automaticallyy added
External ISO interfaces
> Net Schedule interchange
> Generation
G ti Basepoints
B i t

Develop and Track Performance Against Short Term Operating Plan


14 /
GE /
April 25, 2011
Operator/Dispatcher Training Simulator
Realistic,
R li ti St
Steady
d State
St t Simulation
Si l ti off the
th Electrical
El t i l Network
N t k
from the Perspective of the Operator
Same Application Software as Online System
> Database / Display Checkout
> Software Test Bed
Detailed Models
> Generation
> Load
> Frequency
> Network
> Relays
Instructor Interface
> Model Selection & Setup
> Pre-Scheduling of Events (including conditional)
> Run Time Changes to Scenario
> Simulation Control (Speed, Start/Stop)
Much More than a Tool for Training Operators
15 /
GE /
April 25, 2011
Where does the EMS fit in the network
lifecycle?
Monitor: XA/21 SCADA and
applications monitor the entire network.
network
Operate: Along with SCADA,
transmission security management
applications
pp and closed-loop
p generation
g
dispatch and control software help
operate the network.
Maintain: Transmission switching
applications
li ti coordinate
di t maintenance
i t
activities with the control room
operations.
Plan: XA/21 applications plan
equipment outages and help determine
optimal future asset placement for
optimal network reliability.

16 /
GE /
April 25, 2011
EMS Customer Value
Improved Operational Security / Service Reliability
State of the Art Generation Control and Transmission Applications
Fuel
F l & O&M C
Costt R
Reduction
d ti
Economic and Security Constrained Dispatch
Unit Commitment / Transaction Evaluation
Transmission Loss Reduction
Voltage/Var Scheduling
Transmission Loss Penaltyy Factors
Regulatory Compliance
AGC Performance Monitoring
Energy Accounting
Deferred Capital Expenditure
Optimal Use of Existing Assets

17 /
GE /
April 25, 2011
EMSWhat Does The Future Hold

Demand Response & EMS integration


Renewables forecasting & variability
management
Integration of EMS with DMS
Growth of phasor analysis & Visualization
Small Signal Analysis
CRAS

18 /
GE /
April 25, 2011
Backup Slides

19 /
GE /
April 25, 2011
Potential Overview Block Diagram
Primary EMS Sites IS&R RDBMS
Historian
Backup Control Center Sites
Server

FEP Main Oracle Oracle Main FEP


Server Server Server Server
IBM/Sun IBM/Sun RDBMS RDBMS Client ... Client ... Client RDBMS RDBMS
Client
2GB 2GB Server BU Server Server BU Server 2GB 2GB

Archive System Printers


WAN
100BT Switch 100BT Switch
Multiple E2s
E2 s
Backup Backup Archive System
FEP Main
(CFE) Backup Backup
Printers Main FEP
Server Server Server Server
IBM/Sun IBM/Sun Router/Firewall Router/Firewall
Secure ICCP Secure ICCP
2GB 2GB HP HP 2GB 2GB
Remote Remote
DTS/OTS (1-
(1 n)) DAC
FEP (1)
...
DAC
FEP(n)

QAS/PDS
Main Main RDBMS Clients
Server
Server Server
Enterprise Main RDBMS Clients
2GB 2GB
Server Server
Communication Links 2GB DAC
FEP

Remote Client .. Remote Client


Remote Client Remote Client Remote Client Remote Client
(CFE) . (CFE) .. ..
(CFE) (CFE) (CFE) (CFE)
. .
20 /
GE /
April 25, 2011
Graphical User Interface - EnterNet Suite
E t N tO
EnterNet t
Operator
EnterNet
Oracle Application Front End Suite
Cluster Nodes Processors Agent/
Server

EnterNet EnterNet
Control Room Agents Agents

Firewall Firewall

EnterNet EnterNet
Server Server

Firewall Firewall

Extranet Internet

HTTP - VPN HTTPS - SSL

EnterNet Control EnterNet View

21 /
GE /
April 25, 2011

Вам также может понравиться