Академический Документы
Профессиональный Документы
Культура Документы
5 5 5 5
5
ARCHITECT: fi
mOrphosis
153 W. 27th Street
Suite 1200,
12 New York, NY 10001
5 T: 212.675.1100
5
4 www.morphosis.com
OWNER:
5
CORNELLNYC TECH
111 EIGHTH AVENUE, #302
NEW YORK, NY 10011
TEL: 212.309.9020
ARUP
77 WATER STREET
NEW YORK, NY 10005
TEL: 212.896.3000
GEOTECHNICAL:
MUESER RUTLEDGE
CONSULTING ENGINEERS
225 W. 34TH STREET
NEW YORK, NY 10122
TEL: 917.339.9300
COST ESTIMATOR:
DHARAM CONSULTING
240 WEST 37TH STREET, SUITE 302
NEW YORK, NY 10018
TEL: 508.344.3820
CODE:
CODE CONSULTANTS
10 PROFESSIONAL ENGINEERS, PC
215 W. 40TH STREET, 15FL
3 NEW YORK, NY 10018
TEL: 212.216.9596
SPECIFICATIONS:
WATER PROOFING:
KITCHEN CONSULTANT:
ISSUES / REVISIONS:
01/11/2013 100% CD
08/09/2013 100% DD
01/17/2014 50% CD
12 05/16/2014 100% CD
06/30/2014 2 ADDENDUM 2
5 05/15/2015 10 BULLETIN #4
5
05/22/2015 11 BULLETIN #5
5 11/25/2015 12 BULLETIN #6
2 11
5
KEY PLAN:
5
5
N
5
P.N.
PROJECT
CORNELLNYC TECH
FIRST ACADEMIC
BUILDING
1 MAIN STREET,
ROOSEVELT ISLAND,
NEW YORK, NY 10044
5
1
5
DRAWING INDEX
5
5
PROJECT No.:
DRAWING BY:
CHK BY:
05-16-14
32401
ALARM
DWG No.
G-001.00
FILE No.:
E D C B A
ARCHITECT: fi
mOrphosis
153 W. 27th Street
Suite 1200,
New York, NY 10001
T: 212.675.1100
4 www.morphosis.com
OWNER:
CORNELLNYC TECH
111 EIGHTH AVENUE, #302
NEW YORK, NY 10011
TEL: 212.309.9020
ARUP
77 WATER STREET
NEW YORK, NY 10005
TEL: 212.896.3000
GEOTECHNICAL:
MUESER RUTLEDGE
CONSULTING ENGINEERS
225 W. 34TH STREET
NEW YORK, NY 10122
TEL: 917.339.9300
COST ESTIMATOR:
DHARAM CONSULTING
240 WEST 37TH STREET, SUITE 302
NEW YORK, NY 10018
TEL: 508.344.3820
CODE:
CODE CONSULTANTS
PROFESSIONAL ENGINEERS, PC
215 W. 40TH STREET, 15FL
3 NEW YORK, NY 10018
TEL: 212.216.9596
SPECIFICATIONS:
WATER PROOFING:
KITCHEN CONSULTANT:
ISSUES / REVISIONS:
01/11/2013 100% SD
08/09/2013 100% DD
01/17/2014 50% CD
05/16/2014 100% CD
06/30/2014 2 ADDENDUM 2
KEY PLAN:
N
P.N.
PROJECT
CORNELLNYC TECH
FIRST ACADEMIC
BUILDING
1 MAIN STREET,
ROOSEVELT ISLAND,
NEW YORK, NY 10044
DRAWING INDEX
DRAWING BY:
CHK BY:
DWG No.
G-002.00
FILE No.:
E D C B A
J
"NOTICE OF DEFECTS" AND REQUEST FOR ADDITIONAL INSPECTIONS AS REQUIRED UNTIL A NON-CONDITIONAL FTS - FIRE FIGHTERs TELEPHONE SYSTEM
APPROVAL IS RECEIVED FROM THE FIRE DEPARTMENT. FA-402.00 FIRE ALARM CELLAR FLOOR PLAN (SOUTH) 1/8" = 1'-0" New York, NY 10001
FA-403.00 FIRE ALARM CELLAR FLOOR PLAN (NORTH) 1/8" = 1'-0" T: 212.675.1100
3. THE ELECTRICAL CONTRACTOR/FIRE ALARM VENDOR SHALL RETAIN A NY STATE LICENSED PROFESSIONAL HEAT DETECTOR
ENGINEER TO SIGN AND SEAL ALL DOCUMENTS REQUIRED FOR FILING, AS BUILT SIGN OFF, INSPECTION TO OBTAIN R/F - RATE OF RISE AND FIXED TEMPERATURE FA-404.00 FIRE ALARM GROUND FLOOR PLAN (SOUTH) 1/8" = 1'-0"
FINAL LETTER OF APPROVAL. THIS SHALL INCLUDE A SIGNED AND SEALED 11X17 AS BUILT DRAWING, STATEMENT R/C - RATE COMPENSATION FA-405.00 FIRE ALARM GROUND FLOOR PLAN (NORTH) 1/8" = 1'-0"
F www.morphosis.com
4 OF OPERATION, NFPA PROGRAMMING MATRIX AND CONTRACTOR'S SIGNED AND SEALED FORM. F - FIXED TEMPERATURE
CONTRACTOR/VENDOR'S PROFESSIONAL ENGINEER SHALL SELF CERTIFY AT COMPLETION OF PROJECT. IF A R - RATE OF RISE ONLY
FA-406.00 FIRE ALARM SECOND FLOOR PLAN (SOUTH) 1/8" = 1'-0"
LETTER OF DEFECT IS ISSUED BY THE FIRE DEPARTMENT, THE CONTRACTOR SHALL CORRECT ALL ITEMS AND OWNER:
FA-407.00 FIRE ALARM SECOND FLOOR PLAN (NORTH) 1/8" = 1'-0"
SUBMIT A SIGNED AND SEALED CERTIFICATE OF CORRECTION TO THE NYC FIRE DEPARTMENT TO OBTAIN A FINAL
LETTER OF APPROVAL AT NO ADDITIONAL COST TO OWNER. SMOKE DETECTOR FA-408.00 FIRE ALARM THIRD FLOOR PLAN (SOUTH) 1/8" = 1'-0" CORNELLNYC TECH
P - PHOTOELECTRIC I - IONIZATION 111 EIGHTH AVENUE, #302
P B - BEAM TRANSMITTER ASD - AIR SAMPLING
FA-409.00 FIRE ALARM THIRD FLOOR PLAN (NORTH) 1/8" = 1'-0" NEW YORK, NY 10011
4. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR FILING DRAWINGS AND NECESSARY DOCUMENTATION FOR
PERMIT PRIOR TO THE COMMENCEMENT OF THE WORK. ALL PERMIT COSTS, INSPECTION FEES SHALL BE INCLUDED SC - SMOKE CONTROL ACTIVATION FA-410.00 FIRE ALARM FOURTH FLOOR PLAN (SOUTH) 1/8" = 1'-0" TEL: 212.309.9020
AS PART OF THIS CONTRACT. FORM SHALL BE FILED BY THE LICENSED ELECTRICAL CONTRACTOR WITH THE FA-411.00 FIRE ALARM FOURTH FLOOR PLAN (NORTH) 1/8" = 1'-0"
BUREAU OF ELECTRICAL CONTROL PRIOR TO START OF ANY WORK. R PROJECTED BEAM RECEIVER 2
FA-412.00 FIRE ALARM MECHANICAL ROOF PLAN (SOUTH) 1/8" = 1'-0" SMEP/SUSTAINABILITY/ LEED/
5. WHEN THE ENGINEERS HAVE FILED DESIGN DRAWINGS ON BEHALF OF THE OWNER FOR SCHEDULING PURPOSES,
SMOKE DETECTOR FOR DUCT
FA-413.00 FIRE ALARM MECHANICAL ROOF PLAN (NORTH) 1/8" = 1'-0" LIGHTING EXTERIOR
THE ENGINEER SHALL WITHDRAW APPLICATION UPON GC/CM CONTRACTING WITH CONTRACTOR. ENVELOPE/ AV/ IT/ SECURITY
CONTRACTOR/VENDOR'S PROFESSIONAL ENGINEER SHALL REFILE PROJECT AS ENGINEER OF RECORD. THE NYC FA-901.00 FIRE ALARM MATRIX NTS
ACOUSTICS/ SMART BUILDING
FIRE DEPARTMENT SHALL APPROVE PLANS PRIOR TO START OF ANY WORK.
R SMOKE/HEAT DETECTOR
6. FIRE ALARM RISER DIAGRAM SHOWN IS FOR GENERAL ARRANGEMENT AND SHALL BE USED FOR ESTIMATING ONLY. ARUP
ELECTRICAL CONTRACTOR SHALL VERIFY FIELD CONDITIONS AND OBTAIN POINT TO POINT WIRING DIAGRAM FROM FLAME DETECTOR 77 WATER STREET
BUILDING FIRE ALARM VENDOR PRIOR TO INSTALLATION THAT IS CONSISTENT WITH LOCAL FIRE MARSHAL OFFICE F - FLAME IR - INFRARED NEW YORK, NY 10005
REQUIREMENTS. F UV - ULTRAVIOLET TEL: 212.896.3000
UV/IR - COMBINATION ULTRAVIOLET/INFRARED
7. PRIOR TO FIRE INSPECTION, UPDATE ALL AS BUILT DOCUMENTS, FIRE ALARM SYSTEM MATRIX AND SUBMIT ALL VR - VISIBLE RADIATION
REQUIRED SIGNED AND SEALED DOCUMENTS TO FIRE DEPARTMENT FOR APPROVAL.
ADDRESSABLE MODULE
8. AT COMPLETION OF WORK, CONTRACTOR SHALL DELIVER FDNY LETTER OF APPROVAL TO CORNELL. AIM - INPUT INTERPOSING FIRE GEOTECHNICAL:
AIM AOM - OUTPUT ALARM RELAY
9. ELECTRICAL CONTRACTOR/FIRE ALARM VENDOR SHALL SUBMIT FLOOR PLAN SHOP DRAWINGS INDICATING
MUESER RUTLEDGE
LOCATION OF ALL DEVICES, WIRING OF DEVICES, BATTERY CALCULATIONS, VOLTAGE DROP CALCULATIONS FOR
WIRING RUNS DEMONSTRATING A WORST CASE SCENARIO, AND ALL CIRCUITS ON FLOOR. SHOP DRAWING SHALL FLOW DETECTOR/SWITCH
FSD 225 W. 34TH STREET
NEW YORK, NY 10122
ALSO INDICATE LOCATION OF END OF LINE RESISTORS. ELECTRICAL CONTRACTOR / FIRE ALARM VENDOR SHALL
TEL: 917.339.9300
ALSO SUBMIT ALL PRODUCT CUT SHEETS AS PART OF THEIR SUBMITTAL PACKAGE. TO LOCAL 120 VOLT PANEL
PRESSURE DETECTOR/SWITCH
10. ALL EQUIPMENT SHALL BE UL LISTED, SHALL MEET REQUIREMENTS OF NFPA 72 AND 90A, ALL APPLICABLE CODES LA W - WATER COST ESTIMATOR:
AND LOCAL LAWS, AND BE INSTALLED AND CONNECTED IN ACCORDANCE WITH THE MANUFACTURER'S LA - LOW AIR
RECOMMENDATIONS AND INSTRUCTIONS. HA - HIGH AIR DHARAM CONSULTING
240 WEST 37TH STREET, SUITE 302
TAMPER DETECTOR/SWITCH NEW YORK, NY 10018
11. FIRE ALARM CABLES SHALL COMPLY WITH THE FOLLOWING REQUIREMENTS: TO 120/24V TRANSFORMER TEL: 508.344.3820
MINIMUM TEMPERATURE RATING OF 150C.
A MINIMUM AVERAGE INSULATION THICKNESS OF 15 MILS. VALVE TAMPER DETECTOR/SWITCH
A MINIMUM AVERAGE JACKET THICKNESS OF 25 MILS. CODE:
THE COLOR OF THE CABLE SHALL BE RED. R OUTPUT RELAY
CODE CONSULTANTS
THE CABLE SHALL BE TYPE FPLP (PLENUM TYPE). PROFESSIONAL ENGINEERS, PC
THE CABLE SHALL BE VISIBLY MARKED EXTERNALLY "FIRE ALARM". TEMPERATURE SWITCH 215 WEST 40TH STREET, 15FL
THE CABLE SHALL MEET THE ABOVE REQUIREMENTS AND HAVE UL 1424 AND UL 910 LISTING. HT - HIGH TEMPERATURE TO FIRE ALARM PANEL
HT NEW YORK, NY 10018
3 CABLES SHALL BE APPROVED FOR LOCAL AHJ. LT - LOW TEMPERATURE TEL: 212.216.9596
12. CABLES SHALL BE LABELED "NYC CERTIFIED" AND INSTALLED IN ACCORDANCE WITH THE BUILDING CODE OF AUDIO DEVICE (WALL MOUNTED) SPECIFICATIONS:
NEW YORK CITY, DEPARTMENT OF BUILDINGS DIRECTIVES, NEW YORK CITY ELECTRICAL CODE (NEC), NFPA H H - HORN
STANDARDS AND ALL OTHER APPLICABLE CODES AND REGULATIONS. ALL WIRING INCLUDING THE S - SPEAKER CONSTRUCTION SPECIFICATIONS, INC
GROUNDING TO BE INSTALLED ACCORDING TO THE LATEST VERSION OF THE NEW YORK CITY ELECTRICAL 22 TENNENT ROAD P.O. BOX 488
CODE. FIRE SMOKE DAMPER WIRING DIAGRAM MORGANVILLE, NJ 07751
AUDIO DEVICE (CEILING MOUNTED) 1
H H - HORN WITH INTERPOSING RELAY TEL: 732.970.0700
13. PROVIDE A MINIMUM OF TWO (2) CIRCUITS FOR FIRE ALARM SYSTEM SPEAKERS AND, A MINIMUM OF TWO (2)
CIRCUITS FOR FIRE ALARM SYSTEM STROBES. CONNECT SPEAKERS AND STROBES ON ALTERNATING S - SPEAKER NTS
CIRCUITS SO THAT THE FAILURE OF ONE CIRCUIT WILL NOT DISABLE TOTAL ALARM AUDIBILITY THROUGHOUT WATER PROOFING:
THE FLOOR. CLASS A CIRCUITS ARE ACCEPTABLE. DEVICES SHALL BE ALTERNATELY WIRE THROUGHOUT THE STROBE (WALL MOUNTED)
FLOOR. DEVICES SHALL BE ALTERNATELY WIRED THROUGHOUT THE FLOOR SO THAT NO TWO DEVICES, NOTES: HENSHELL & BUCCELLATO
ADJACENT TO EACH OTHER IN A GIVEN FIELD OF VIEW SHALL BE ON THE SAME CIRCUIT. 1. FOR SYMBOL LIST AND GENERAL NOTES REFER TO THIS DRAWING.
166 PATTERSON AVENUE
H SHREWSBURY, NJ 07702
AUDIO/VISUAL COMBINATION (WALL MOUNTED)
14. ALL FIRE ALARM CABLE SHALL BE RUN PARALLEL AND PERPENDICULAR - NO DIAGONAL RUNS. SUPPORTS 2. PROVIDE INTERPOSING RELAYS FOR ALL DEVICES REQUIRING 120V OR TEL: 732.530.4734
SHALL BE PROVIDED EVERY 5'-0" ON CENTER. MORE TO BE CONTROLLED BY ADDRESSABLE MODULE. PROVIDE
H TRANSFORMER C120V PRI/24V SEC. KITCHEN CONSULTANT:
15. DO NOT RUN FIRE ALARM CABLE IN THE SAME RACEWAY WITH NON FIRE ALARM CABLE. PROVIDE PRIMARY AND SECONDARY PROTECTION AS REQUIRED.
AUDIO/VISUAL COMBINATION (CEILING MOUNTED)
JACOB DOLAND BEER
16. NO CONDUITS ARE TO ENTER THE TOP OF A FIRE ALARM CONTROL PANEL REGARDLESS OF SYSTEM TYPE 116 E. 27TH STREET, 2FL
OR SIZE.
DOOR HOLDER FLOOR/DOOR
NEW YORK, NY 10016
TEL: 212.206.0736
17. AVOID INSTALLING FIRE ALARM CABLES NEAR SOURCES OF ALTERNATING CURRENT. (LIGHTING, POWER,
ETC.). FACP FIRE ALARM CONTROL PANEL
18. ANY REQUIREMENTS FOR SHIELDING CERTAIN CONDUCTORS OR RUNNING THEM IN SEPARATE RACEWAYS FAAP FIRE ALARM ANNUNCIATOR PANEL
ISSUES / REVISIONS:
SHALL BE AS RECOMMENDED BY THE MANUFACTURERS DOCUMENTATION. NO. DATE DESCRIPTION
FCS FIRE COMMAND SYSTEM
19. ALL EXPOSED TEFLON WIRE SHALL BE SLEEVED AND SEALED AT ALL FIRE RATED WALL AND FLOOR 05/16/2014 100% CD
PASSAGES. SEALANT SHALL BE 3M FIRE BARRIER CP-25. 2 06/30/2014 Addendum 2
CSC COMMAND STATION CONNECTION
20. OBSERVE ALL POLARITY ON ALL FIRE ALARM CIRCUITS. NO TEE TAPPING IS PERMITTED ON ALARM
INDICATING CIRCUITS (STROBES, HORNS ETC.).
21. ALL FIRE ALARM WIRE SHALL BE CLEARLY LABELED IN JUNCTION BOXES AND CABINETS. CONDUCTORS IN
CABINETS SHALL BE FORMED SO THAT THEY DROP OFF DIRECTLY OPPOSITE TO ITS TERMINAL CONNECTION.
ALL TERMINALS SHALL BE NUMBERED AND LABELED IN EVERY CABINET.
22. ALL FIRE ALARM PANELS, JUNCTION BOX COVERS, ETC. SHALL BE PAINTED "FIRE DEPARTMENT RED".
2 25. ALL CEILING MOUNTED DEVICES MUST BE SECURELY FASTENED TO THE BUILDING STRUCTURE. ALL WALL-
MOUNTED DEVICES SHALL BE SECURELY MOUNTED IN PLACE. PLASTIC ANCHORS ARE NOT ACCEPTABLE.
26. INSTALL SMOKE DETECTORS A MINIMUM OF 3'-0" FROM ANY SUPPLY OR RETURN OPENING.
27. ALL DUCT MOUNTED DETECTORS INSTALLED CONCEALED ABOVE CEILING, ETC, SHALL BE PROVIDED WITH A
REMOTE LED TO PROVIDE RAPID VISIBLE INDICATION OF DETECTOR LOCATION AND STATUS FROM THE
OCCUPIED SPACE.
28. HORNS SHALL BE TAPPED TO PROVIDE 15DB ABOVE THE AMBIENT NOISE LEVEL. CONTRACTOR SHALL
PERFORM SOUND POWER TESTING BEFORE AND AFTER INSTALLATION IS COMPLETE AND SHALL ADJUST KEY PLAN:
TAP SETTING AS REQUIRED TO OBTAIN THE REQUIRED SOUND LEVEL.
29. HORN/STROBE DEVICES SHALL NOT HAVE ANY OTHER DEVICES OR APPARATUS WITHIN FIVE (5) FEET OF
DEVICE.
30. ALL WIRING TO BE CHECKED TO ENSURE THAT THEY ARE FREE OF ANY OPENS, SHORTS OR GROUNDS.
APPROVED
31. END OF LINE RESISTOR LOCATIONS SHALL BE PERMANENTLY LABELED ON INSTALLED DEVICE IN FIELD.
32. STROBES SHALL BE WIRED SO THAT THEY REMAIN ACTIVE AFTER SILENCE FUNCTION IS PERFORMED.
33. SHUTDOWN OF ANY MECHANICAL EQUIPMENT ON FLOOR SHALL BE PERFORMED VIA A RELAY INTERFACE
WITH THE FIRE ALARM SYSTEM.
34. AFTER ALARM INDICATION MECHANICAL EQUIPMENT SHALL BE MANUALLY RESET INDEPENDENT OF FACP
RESET
35. AFTER THE SYSTEM MODIFICATIONS ARE COMPLETE, TEST ALL COMPONENTS IN ACCORDANCE WITH
SEQUENCE OF OPERATION PRIOR TO FIRE INSPECTION.
PROJECT
36. THE OPERATION OF THE FIRE ALARM INSTALLATION DOES NOT CONSTITUTE AN ACCEPTANCE OF THE WORK
BY THE OWNER. FINAL ACCEPTANCE IS TO BE MADE AFTER THE CONTRACTOR HAS DEMONSTRATED THAT
THE WORK FULFILLS THE REQUIREMENTS OF THE PLANS AND SPECIFICATIONS AND HAD FURNISHED ALL
REQUIRED CERTIFICATES OF APPROVAL FROM THE STATE AUTHORITIES, MUNICIPAL AUTHORITIES AND
CORNELLNYC TECH
UNDERWRITERS.
FIRST ACADEMIC
37. CONTRACTOR SHALL PROVIDE STROBE POWER SUPPLIES AS NECESSARY. THE POWER SUPPLIES TO THESE
UNITS SHALL BE TAPPED AHEAD OF THE MAIN LUGS OF THE NEAREST 208/120V PANEL WITH A MAXIMUM BUILDING
LENGTH OF 5'. 1 MAIN STREET
ROOSEVELT ISLAND
NEW YORK, NY 10044
1 FIRE ALARM
LEGEND AND
GENERAL NOTES
FA-001.00
FILE No.:
E D C B A
REFER TO NOTE 3 PV CANOPY LEVEL
AHU-5 RETURN AHU-4 RETURN AHU-3 RETURN AHU-2 RETURN AHU-1 RETURN AHU-5 SUPPLY AHU-4 SUPPLY AHU-3 SUPPLY AHU-2 SUPPLY AHU-1 SUPPLY SOUTH SHAFT DAMPER TYPICAL FOR (5) NORTH SHAFT DAMPER
FOR STAIR HATCH
SMOKE FAN TYPICAL FOR (3)
AIM AIM AOM AIM AIM AOM AIM AIM AOM AIM AIM AOM AIM AIM AOM AIM AIM AOM AIM AIM AOM AIM AIM AOM AIM AIM AOM AIM AIM AOM AIM AIM AOM AIM AIM AOM
STAIRWAY #1
AOM AOM AOM AOM AOM AIM AIM
FSD FSD FSD FSD FSD FSD FSD FSD FSD FSD FSD FSD FSD FSD FSD FSD FSD FSD FSD FSD FSD FSD FSD FSD FSD FSD FSD FSD FSD FSD
CLOSED OPEN ACTIVATE CLOSED OPEN ACTIVATE CLOSED OPEN ACTIVATE CLOSED OPEN ACTIVATE CLOSED OPEN ACTIVATE CLOSED OPEN ACTIVATE CLOSED OPEN ACTIVATE CLOSED OPEN ACTIVATE CLOSED OPEN ACTIVATE CLOSED OPEN ACTIVATE
AOM AIM OFF ON NORMAL FAULT AUTO OFF ON
STATUS STATUS TYPICAL FOR (17) TOP OF ELEVATOR SHAFT AHU-5 MECH ROOM AHU-4 MECH ROOM AHU-2 MECH ROOM AHU-3 MECH ROOM AHU-1 MECH ROOM ARCHITECT:
R
mOrphosis
STATUS ACTIVATE P P P 153 W. 27th Street
AIM AOM AIM AIM AIM AIM AIM AIM AIM AIM AIM AIM SMOKE FAN DAMPER TYPICAL FOR (2)
MECH SMOKE FAN TYPICAL FOR (2) MECH ROOM Suite 1200
MECH ROOM New York, NY 10001
STAIR #1 ROOM DAMPER DAMPER AOM AOM AOM AIM AIM AIM AIM
ACTIVATE STATUS SHUTDOWN SHUTDOWN SHUTDOWN SHUTDOWN SHUTDOWN AOM AOM AOM AOM AOM AIM AIM T: 212.675.1100
ATS-1 ATS-2 ATS-3 OPEN CLOSE AUTO OPEN CLOSED FAULT NORMAL
SMOKE FAN DAMPER TYPICAL FOR (3) OFF ON NORMAL FAULT AUTO OFF ON STATUS STATUS STATUS STATUS
TYPICAL FOR (18) STATUS STATUS GENERATOR STATUS www.morphosis.com
4
AIM AIM AIM AIM AIM AIM AIM AIM
AOM AOM AOM AIM AIM AIM AIM OWNER:
MECH SHAFT TYPICAL FOR (17) AIM AIM AIM AIM
FOR SHAFT HATCH CORNELLNYC TECH
OPEN CLOSE AUTO FAULT NORMAL OPEN CLOSED SHUNT TRIP NORMAL EMERG. NORMAL EMERG. NORMAL EMERG.
STATUS STATUS STATUS STATUS 111 EIGHTH AVENUE, #302
AOM AIM GENERATOR GENERATOR GENERATOR GENERATOR
NEW YORK, NY 10011
FTS
FTS
FTS
CLOSED OPEN ACTIVATE CLOSED OPEN ACTIVATE
FTS
S CLASS A
S SC SC SC SC SC SC CIRCUIT COST ESTIMATOR:
P
TYPICAL FOR (36) DEVICES DHARAM CONSULTING
RETURN ELEC. RM ELEC. STAIR RETURN
CLASS A RETURN 40068 CLOSET #2 CORR 40050 240 WEST 37TH STREET, SUITE 302
RETURN CLASS A S
CIRCUIT CLASS A 40070
NEW YORK, NY 10018
CLASS A CIRCUIT
TEL: 508.344.3820
FTS
CIRCUIT S S S TYPICAL FOR (10) DEVICES CIRCUIT S S S S S S S S S S S LEVEL 4
ELEV. LOBBY
SC SC SC SC
CODE:
1 P TYPICAL FOR (2) REFER TO NOTE 3 1
RETURN CODE CONSULTANTS
FTS
STAIRWAY #5 TELE. RM ELEC. RM CLASS A PROFESSIONAL ENGINEERS, PC
STAIR #1 336 30065 CORR 30041 ELEV. LOBBY CIRCUIT 215 WEST 40TH STREET, 15FL
RETURN AIM AIM AOM AIM AIM AOM NEW YORK, NY 10018
FTS
CLASS A TYPICAL FOR (3) REFER TO NOTE 3 TYPICAL FOR (2) R R TEL: 212.216.9596
FTS
FTS
FTS
S S CIRCUIT FACP FACP
FSD FSD FSD FSD FSD FSD SPECIFICATIONS:
3 ELEC. RM ELEV. #1/#2 CLOSED OPEN ACTIVATE CLOSED OPEN ACTIVATE ELEC. RM
30065 AIM AIM AOM AIM AIM AOM 30068 RETURN CONSTRUCTION SPECIFICATIONS, INC
SC SC SC SC B 22 TENNENT ROAD P.O. BOX 488
RETURN P CLASS A
CLASS A FOR FCU-3.3 S S MORGANVILLE, NJ 07751
TELE. RM ELEC. STAIR CIRCUIT
FSD FSD FSD FSD FSD FSD OFFICE ELEC. RM TEL: 732.970.0700
CIRCUIT
CLOSED OPEN ACTIVATE CLOSED OPEN ACTIVATE CORR 30050 ZONE B 382 30068 CLOSET #2
S S S S S S TYPICAL FOR (31)
P P
RETURN WATER PROOFING:
SMOKE CONTROL OPERABLE WINDOW TYPICAL FOR (4) OFFICE ZONE A STAIR STAIR OFFICE ZONE B SMOKE CONTROL OPERABLE WINDOW TYPICAL FOR (4) CLASS A
RETURN #3 #6 CIRCUIT HENSHELL & BUCCELLATO
CLASS A AIM AIM AIM AIM AOM AOM AOM AOM AOM AIM AIM AIM AIM AOM AOM AOM 166 PATTERSON AVENUE
CIRCUIT SHREWSBURY, NJ 07702
TEL: 732.530.4734
OPEN CLOSED FAULT NORMAL AUTO CLOSE OPEN LOCAL SHADE LOCAL SHADE OPEN CLOSED FAULT NORMAL AUTO CLOSE OPEN
STATUS STATUS STATUS STATUS ROLLUP ROLLUP STATUS STATUS STATUS STATUS S S S S S S S S S S S LEVEL 3
TYPICAL FOR (34) DEVICES KITCHEN CONSULTANT:
TYPICAL FOR (2) REFER TO NOTE 3
JACOB DOLAND BEER
116 E. 27TH STREET, 2FL
TYPICAL FOR (3) REFER TO NOTE 3 TYPICAL FOR (2)
FTS
FTS
FTS
FTS
FTS
S ELEV. LOBBY
STAIRWAY #5
AIM AIM AOM AIM AIM AOM FSD FSD FSD FSD FSD FSD
P P ISSUES / REVISIONS:
TYPICAL FOR (37) DEVICES FOR FCU-2.3 CLOSED OPEN ACTIVATE CLOSED OPEN ACTIVATE
S CORR 20050
STAIR STAIR NO. DATE DESCRIPTION
FSD FSD FSD FSD FSD FSD STAIRWAY #7 SC SC SC SC SC
#3 #6
CLOSED OPEN ACTIVATE CLOSED OPEN ACTIVATE 08/09/2013 100% DD
S S S S S S S S P S
RETURN 01/17/2014 50% CD
R R SC SC AOM AOM AOM
P CLASS A
STAIRWAY #5 AOM AOM TELE. RM ELEC. RM ELEC. STAIR CIRCUIT 05/16/2014 100% CD
STAIR TELE. RM ELEC. RM ELEV. #1/#2 CORR S DOOR RELEASE 282 BLACKOUT/SUNSHADE 20068 CLOSET #2
#1 236 20065 STAIR #1 20041 20070 2 06/30/2014 Addendum 2
ROLLUP
RETURN SMOKE CONTROL OPERABLE WINDOW TYPICAL FOR (4) OFFICE ZONE A DOOR RELEASE OFFICE ZONE B SMOKE CONTROL OPERABLE WINDOW TYPICAL FOR (4) TYPICAL FOR (36) 9 02/13/2015 Bulletin #3
CLASS A SC SC RETURN
S S CIRCUIT CLASS A 10 05/15/2015 Bulletin #4
AIM AIM AIM AIM AOM AOM AOM AOM AOM AIM AIM AIM AIM AOM AOM AOM CIRCUIT S S S
CORR 22 XX/XX/XXXX SKETCHES DO NOT
20050 DELETE
OPEN CLOSED FAULT NORMAL AUTO CLOSE OPEN LOCAL SHADE LOCAL SHADE OPEN CLOSED FAULT NORMAL AUTO CLOSE OPEN
STATUS STATUS STATUS STATUS ROLLUP ROLLUP STATUS STATUS STATUS STATUS LEVEL 2 25 03/09/2018 fire alarm temp
FTS
FTS
P P P P P REMOTE START AT LOBBY
AIM RETURN
FTS
LECTURE CORR. CORR. ELEV. CLASS A
HALL MAIN LOUNGE 10043 10040 #3 STAIR #1 TO SMOKE CIRCUIT
2 LECTURE HALL ELEV. LOBBY
TYPICAL FOR (4) REFER TO NOTE 3 TYPICAL FOR (2) 10046 CONTROL S S S S S S S S
SOUND SYSTEM
SMOKE CONTROL OPERABLE WINDOW TYPICAL FOR (6) PANEL
SHUTDOWN RETURN
1 1 CLASS A
CIRCUIT
AIM AIM AIM AIM AOM AOM AOM AIM AIM AOM AIM AIM AOM AOM AOM AOM
FTS
FOR FCU-1.1
FTS
OPEN CLOSED FAULT NORMAL AUTO CLOSE OPEN RETURN
FTS
FTS
PURPOSE OF ISSUE:
AOM AIM AIM AOM AIM AIM AIM
Vestibule Door Power/Fire Alarm AIM AIM AIM AIM AIM AIM AIM NEW YORK, NY 10044
FTS
FTS
TELE. RM ELEC. RM
FIRE PUMP ROOM
FTS
FTS
FTS
FTS
FTS
1. REFER TO FLOOR PLANS FOR DEVICE RATINGS. 1 120V CIRCUIT DOWN TO FIRE ALARM FUSE CUTOUT
FA-301.00
PANEL IN EMERGENCY ELECTRICAL ROOM AT ROOF.
2. THIS SINGLE LINE DIAGRAM IS FOR INTENT ONLY. FILE No.:
AHU-5 RETURN AHU-4 RETURN AHU-3 RETURN AHU-2 RETURN AHU-1 RETURN AHU-5 SUPPLY AHU-4 SUPPLY AHU-3 SUPPLY AHU-2 SUPPLY AHU-1 SUPPLY SOUTH SHAFT DAMPER TYPICAL FOR (5) NORTH SHAFT DAMPER
FOR STAIR HATCH
SMOKE FAN TYPICAL FOR (3)
AIM AIM AOM AIM AIM AOM AIM AIM AOM AIM AIM AOM AIM AIM AOM AIM AIM AOM AIM AIM AOM AIM AIM AOM AIM AIM AOM AIM AIM AOM AIM AIM AOM AIM AIM AOM
STAIRWAY #1
AOM AOM AOM AOM AOM AIM AIM
FSD FSD FSD FSD FSD FSD FSD FSD FSD FSD FSD FSD FSD FSD FSD FSD FSD FSD FSD FSD FSD FSD FSD FSD FSD FSD FSD FSD FSD FSD
CLOSED OPEN ACTIVATE CLOSED OPEN ACTIVATE CLOSED OPEN ACTIVATE CLOSED OPEN ACTIVATE CLOSED OPEN ACTIVATE CLOSED OPEN ACTIVATE CLOSED OPEN ACTIVATE CLOSED OPEN ACTIVATE CLOSED OPEN ACTIVATE CLOSED OPEN ACTIVATE
AOM AIM OFF ON NORMAL FAULT AUTO OFF ON
STATUS STATUS TYPICAL FOR (17) TOP OF ELEVATOR SHAFT AHU-5 MECH ROOM AHU-4 MECH ROOM AHU-2 MECH ROOM AHU-3 MECH ROOM AHU-1 MECH ROOM ARCHITECT:
R
mOrphosis
STATUS ACTIVATE P P P 153 W. 27th Street
AIM AOM AIM AIM AIM AIM AIM AIM AIM AIM AIM AIM SMOKE FAN DAMPER TYPICAL FOR (2)
MECH SMOKE FAN TYPICAL FOR (2) MECH ROOM Suite 1200
MECH ROOM New York, NY 10001
STAIR #1 ROOM DAMPER DAMPER AOM AOM AOM AIM AIM AIM AIM
ACTIVATE STATUS SHUTDOWN SHUTDOWN SHUTDOWN SHUTDOWN SHUTDOWN AOM AOM AOM AOM AOM AIM AIM T: 212.675.1100
ATS-1 ATS-2 ATS-3 OPEN CLOSE AUTO OPEN CLOSED FAULT NORMAL
SMOKE FAN DAMPER TYPICAL FOR (3) OFF ON NORMAL FAULT AUTO OFF ON STATUS STATUS STATUS STATUS
TYPICAL FOR (18) STATUS STATUS GENERATOR STATUS www.morphosis.com
4
AIM AIM AIM AIM AIM AIM AIM AIM
AOM AOM AOM AIM AIM AIM AIM OWNER:
MECH SHAFT TYPICAL FOR (17) AIM AIM AIM AIM
FOR SHAFT HATCH CORNELLNYC TECH
OPEN CLOSE AUTO FAULT NORMAL OPEN CLOSED SHUNT TRIP NORMAL EMERG. NORMAL EMERG. NORMAL EMERG.
STATUS STATUS STATUS STATUS 111 EIGHTH AVENUE, #302
AOM AIM GENERATOR GENERATOR GENERATOR GENERATOR
NEW YORK, NY 10011
FTS
FTS
FTS
CLOSED OPEN ACTIVATE CLOSED OPEN ACTIVATE
FTS
S CLASS A
S SC SC SC SC SC SC CIRCUIT COST ESTIMATOR:
P
TYPICAL FOR (36) DEVICES DHARAM CONSULTING
RETURN ELEC. RM ELEC. STAIR RETURN
CLASS A RETURN 40068 CLOSET #2 CORR 40050 240 WEST 37TH STREET, SUITE 302
RETURN CLASS A S
CIRCUIT CLASS A 40070
NEW YORK, NY 10018
CLASS A CIRCUIT
TEL: 508.344.3820
FTS
CIRCUIT S S S TYPICAL FOR (10) DEVICES CIRCUIT S S S S S S S S S S S LEVEL 4
ELEV. LOBBY
SC SC SC SC
CODE:
1 P TYPICAL FOR (2) REFER TO NOTE 3 1
RETURN CODE CONSULTANTS
FTS
STAIRWAY #5 TELE. RM ELEC. RM CLASS A PROFESSIONAL ENGINEERS, PC
STAIR #1 336 30065 CORR 30041 ELEV. LOBBY CIRCUIT 215 WEST 40TH STREET, 15FL
RETURN AIM AIM AOM AIM AIM AOM NEW YORK, NY 10018
FTS
CLASS A TYPICAL FOR (3) REFER TO NOTE 3 TYPICAL FOR (2) R R TEL: 212.216.9596
FTS
FTS
FTS
S S CIRCUIT FACP FACP
FSD FSD FSD FSD FSD FSD SPECIFICATIONS:
3 ELEC. RM ELEV. #1/#2 CLOSED OPEN ACTIVATE CLOSED OPEN ACTIVATE ELEC. RM
30065 AIM AIM AOM AIM AIM AOM 30068 RETURN CONSTRUCTION SPECIFICATIONS, INC
SC SC SC SC B 22 TENNENT ROAD P.O. BOX 488
RETURN P CLASS A
CLASS A FOR FCU-3.3 S S MORGANVILLE, NJ 07751
TELE. RM ELEC. STAIR CIRCUIT
FSD FSD FSD FSD FSD FSD OFFICE ELEC. RM TEL: 732.970.0700
CIRCUIT
CLOSED OPEN ACTIVATE CLOSED OPEN ACTIVATE CORR 30050 ZONE B 382 30068 CLOSET #2
S S S S S S TYPICAL FOR (31)
P P
RETURN WATER PROOFING:
SMOKE CONTROL OPERABLE WINDOW TYPICAL FOR (4) OFFICE ZONE A STAIR STAIR OFFICE ZONE B SMOKE CONTROL OPERABLE WINDOW TYPICAL FOR (4) CLASS A
RETURN #3 #6 CIRCUIT HENSHELL & BUCCELLATO
CLASS A AIM AIM AIM AIM AOM AOM AOM AOM AOM AIM AIM AIM AIM AOM AOM AOM 166 PATTERSON AVENUE
CIRCUIT SHREWSBURY, NJ 07702
TEL: 732.530.4734
OPEN CLOSED FAULT NORMAL AUTO CLOSE OPEN LOCAL SHADE LOCAL SHADE OPEN CLOSED FAULT NORMAL AUTO CLOSE OPEN
STATUS STATUS STATUS STATUS ROLLUP ROLLUP STATUS STATUS STATUS STATUS S S S S S S S S S S S LEVEL 3
TYPICAL FOR (34) DEVICES KITCHEN CONSULTANT:
TYPICAL FOR (2) REFER TO NOTE 3
JACOB DOLAND BEER
116 E. 27TH STREET, 2FL
TYPICAL FOR (3) REFER TO NOTE 3 TYPICAL FOR (2)
FTS
FTS
FTS
FTS
FTS
S ELEV. LOBBY
STAIRWAY #5
AIM AIM AOM AIM AIM AOM FSD FSD FSD FSD FSD FSD
P P ISSUES / REVISIONS:
TYPICAL FOR (37) DEVICES FOR FCU-2.3 CLOSED OPEN ACTIVATE CLOSED OPEN ACTIVATE
S CORR 20050
STAIR STAIR NO. DATE DESCRIPTION
FSD FSD FSD FSD FSD FSD STAIRWAY #7 SC SC SC SC SC
#3 #6
CLOSED OPEN ACTIVATE CLOSED OPEN ACTIVATE 08/09/2013 100% DD
S S S S S S S S P S
RETURN 01/17/2014 50% CD
R R SC SC AOM AOM AOM
P CLASS A
STAIRWAY #5 AOM AOM TELE. RM ELEC. RM ELEC. STAIR CIRCUIT 05/16/2014 100% CD
STAIR TELE. RM ELEC. RM ELEV. #1/#2 CORR S DOOR RELEASE 282 BLACKOUT/SUNSHADE 20068 CLOSET #2
#1 236 20065 STAIR #1 20041 20070 2 06/30/2014 Addendum 2
ROLLUP
RETURN SMOKE CONTROL OPERABLE WINDOW TYPICAL FOR (4) OFFICE ZONE A DOOR RELEASE OFFICE ZONE B SMOKE CONTROL OPERABLE WINDOW TYPICAL FOR (4) TYPICAL FOR (36) 9 02/13/2015 Bulletin #3
CLASS A SC SC RETURN
S S CIRCUIT CLASS A 10 05/15/2015 Bulletin #4
AIM AIM AIM AIM AOM AOM AOM AOM AOM AIM AIM AIM AIM AOM AOM AOM CIRCUIT S S S
CORR 22 XX/XX/XXXX SKETCHES DO NOT
20050 DELETE
OPEN CLOSED FAULT NORMAL AUTO CLOSE OPEN LOCAL SHADE LOCAL SHADE OPEN CLOSED FAULT NORMAL AUTO CLOSE OPEN
STATUS STATUS STATUS STATUS ROLLUP ROLLUP STATUS STATUS STATUS STATUS LEVEL 2 24 Date 31 shade temp
25 Date 32 fire alarm temp
TO GENERATOR FOR FAAP
FTS
FTS
P P P P P REMOTE START AT LOBBY
AIM RETURN
FTS
LECTURE CORR. CORR. ELEV. CLASS A
HALL MAIN LOUNGE 10043 10040 #3 STAIR #1 TO SMOKE CIRCUIT
2 LECTURE HALL ELEV. LOBBY
TYPICAL FOR (4) REFER TO NOTE 3 TYPICAL FOR (2) 10046 CONTROL S S S S S S S S
SOUND SYSTEM
SMOKE CONTROL OPERABLE WINDOW TYPICAL FOR (6) PANEL
FOR FCU-1.1
FTS
OPEN CLOSED FAULT NORMAL AUTO CLOSE OPEN RETURN
FTS
ESK-CA-064.1
KS CHECKED BY: KS
UV/IR UV/IR P ELEV.
LOBBY #3
ELEV.
LOBBY STAIR #1
RETURN CORNELLNYC TECH
CLASS A
DATE: 03-07-2017 WATER SERVICES
B0067
FUEL FILL RM
B0065
LECTURE LOWER
HALL FOYER
PRIMARY
RECALL
ALTERNATE SHUNT TRIP FIREMAN HAT
RECALL
FOOD PREP CIRCUIT FIRST ACADEMIC
S S S S S SCALE: NTS
ORIGINAL PAPER SIZE:
131 B0046
BUILDING
TYPICAL FOR (3) TYPICAL FOR (13) REFER TO NOTE 3 ELEV. MACHINE RM B0066 1 MAIN STREET
R R S S S S S S S S TYPICAL FOR (15)
ROOSEVELT ISLAND
FTS
AOM AIM AIM AOM AIM AIM AIM AIM AIM AIM AIM AIM AIM AIM NEW YORK, NY 10044
FTS
ELEV. LOBBY
#1/#2
FSD FSD FSD FSD FSD FSD PRIMARY ALTERNATE SHUNT FIREMAN FIREMAN SHUNT ALTERNATE PRIMARY FIRE ALARM
1 ACTIVATE OPEN CLOSED ACTIVATE OPEN CLOSED RECALL RECALL TRIP HAT HAT TRIP RECALL RECALL
TYPICAL FOR (5) TYPICAL FOR (4) REFER TO NOTE 3 FIRE PUMP ROOM TYPICAL FOR (27) SINGLE LINE DIAGRAM
TYPICAL FOR (30) DEVICES P
AIM AIM AOM AIM AIM AOM AIM AIM AIM AIM AIM AIM AIM
FTS
TELE. RM ELEC. RM
FIRE PUMP ROOM
FTS
FTS
FTS
FTS
FTS
1. REFER TO FLOOR PLANS FOR DEVICE RATINGS. 1 120V CIRCUIT DOWN TO FIRE ALARM FUSE CUTOUT
FA-301.00
PANEL IN EMERGENCY ELECTRICAL ROOM AT ROOF.
2. THIS SINGLE LINE DIAGRAM IS FOR INTENT ONLY. FILE No.:
FTS
FTS
CLOSED OPEN ACTIVATE CLOSED OPEN ACTIVATE
FTS
S CLASS A
S SC SC SC SC SC SC CIRCUIT COST ESTIMATOR:
P
TYPICAL FOR (36) DEVICES DHARAM CONSULTING
RETURN ELEC. RM ELEC. STAIR RETURN
CLASS A RETURN 40068 CLOSET #2 CORR 40050 240 WEST 37TH STREET, SUITE 302
RETURN CLASS A S
CIRCUIT CLASS A 40070
NEW YORK, NY 10018
CLASS A CIRCUIT
TEL: 508.344.3820
FTS
CIRCUIT S S S TYPICAL FOR (10) DEVICES CIRCUIT S S S S S S S S S S S LEVEL 4
ELEV. LOBBY
SC SC SC SC
CODE:
1 P TYPICAL FOR (2) REFER TO NOTE 3 1
RETURN CODE CONSULTANTS
FTS
STAIRWAY #5 TELE. RM ELEC. RM CLASS A PROFESSIONAL ENGINEERS, PC
STAIR #1 336 30065 CORR 30041 ELEV. LOBBY CIRCUIT 215 WEST 40TH STREET, 15FL
RETURN AIM AIM AOM AIM AIM AOM NEW YORK, NY 10018
FTS
CLASS A TYPICAL FOR (3) REFER TO NOTE 3 TYPICAL FOR (2) R R TEL: 212.216.9596
FTS
FTS
FTS
S S CIRCUIT FACP FACP
FSD FSD FSD FSD FSD FSD SPECIFICATIONS:
3 ELEC. RM ELEV. #1/#2 CLOSED OPEN ACTIVATE CLOSED OPEN ACTIVATE ELEC. RM
30065 AIM AIM AOM AIM AIM AOM 30068 RETURN CONSTRUCTION SPECIFICATIONS, INC
SC SC SC SC B 22 TENNENT ROAD P.O. BOX 488
RETURN P CLASS A
CLASS A FOR FCU-3.3 S S MORGANVILLE, NJ 07751
TELE. RM ELEC. STAIR CIRCUIT
FSD FSD FSD FSD FSD FSD OFFICE ELEC. RM TEL: 732.970.0700
CIRCUIT
CLOSED OPEN ACTIVATE CLOSED OPEN ACTIVATE CORR 30050 ZONE B 382 30068 CLOSET #2
S S S S S S TYPICAL FOR (31)
P P
RETURN WATER PROOFING:
SMOKE CONTROL OPERABLE WINDOW TYPICAL FOR (4) OFFICE ZONE A STAIR STAIR OFFICE ZONE B SMOKE CONTROL OPERABLE WINDOW TYPICAL FOR (4) CLASS A
RETURN #3 #6 CIRCUIT HENSHELL & BUCCELLATO
CLASS A AIM AIM AIM AIM AOM AOM AOM AOM AOM AIM AIM AIM AIM AOM AOM AOM 166 PATTERSON AVENUE
CIRCUIT SHREWSBURY, NJ 07702
TEL: 732.530.4734
OPEN CLOSED FAULT NORMAL AUTO CLOSE OPEN LOCAL SHADE LOCAL SHADE OPEN CLOSED FAULT NORMAL AUTO CLOSE OPEN
STATUS STATUS STATUS STATUS ROLLUP ROLLUP STATUS STATUS STATUS STATUS S S S S S S S S S S S LEVEL 3
TYPICAL FOR (34) DEVICES KITCHEN CONSULTANT:
TYPICAL FOR (2) REFER TO NOTE 3
JACOB DOLAND BEER
116 E. 27TH STREET, 2FL
TYPICAL FOR (3) REFER TO NOTE 3 TYPICAL FOR (2)
FTS
FTS
FTS
FTS
FTS
S ELEV. LOBBY
STAIRWAY #5
AIM AIM AOM AIM AIM AOM FSD FSD FSD FSD FSD FSD
P P ISSUES / REVISIONS:
TYPICAL FOR (37) DEVICES FOR FCU-2.3 CLOSED OPEN ACTIVATE CLOSED OPEN ACTIVATE
S CORR 20050
STAIR STAIR NO. DATE DESCRIPTION
FSD FSD FSD FSD FSD FSD STAIRWAY #7 SC SC SC SC SC
#3 #6
CLOSED OPEN ACTIVATE CLOSED OPEN ACTIVATE 08/09/2013 100% DD
S S S S S S S S P S
RETURN 01/17/2014 50% CD
R R SC SC AOM AOM AOM
P CLASS A
STAIRWAY #5 AOM AOM TELE. RM ELEC. RM ELEC. STAIR CIRCUIT 05/16/2014 100% CD
STAIR TELE. RM ELEC. RM ELEV. #1/#2 CORR S DOOR RELEASE 282 BLACKOUT/SUNSHADE 20068 CLOSET #2
#1 236 20065 STAIR #1 20041 20070 2 06/30/2014 Addendum 2
ROLLUP
RETURN SMOKE CONTROL OPERABLE WINDOW TYPICAL FOR (4) OFFICE ZONE A DOOR RELEASE OFFICE ZONE B SMOKE CONTROL OPERABLE WINDOW TYPICAL FOR (4) TYPICAL FOR (36) 9 02/13/2015 Bulletin #3
CLASS A SC SC RETURN
S S CIRCUIT CLASS A 10 05/15/2015 Bulletin #4
AIM AIM AIM AIM AOM AOM AOM AOM AOM AIM AIM AIM AIM AOM AOM AOM CIRCUIT S S S
CORR 22 XX/XX/XXXX SKETCHES DO NOT
20050 DELETE
OPEN CLOSED FAULT NORMAL AUTO CLOSE OPEN LOCAL SHADE LOCAL SHADE OPEN CLOSED FAULT NORMAL AUTO CLOSE OPEN
STATUS STATUS STATUS STATUS ROLLUP ROLLUP STATUS STATUS STATUS STATUS LEVEL 2 24 Date 31 shade temp
FTS
FTS
P P P P P REMOTE START AT LOBBY
AIM RETURN
FTS
LECTURE CORR. CORR. ELEV. CLASS A
HALL MAIN LOUNGE 10043 10040 #3 STAIR #1 TO SMOKE CIRCUIT
2 LECTURE HALL ELEV. LOBBY
TYPICAL FOR (4) REFER TO NOTE 3 TYPICAL FOR (2) 10046 CONTROL S S S S S S S S
SOUND SYSTEM
SMOKE CONTROL OPERABLE WINDOW TYPICAL FOR (6) PANEL
SHUTDOWN RETURN
1 1 CLASS A
CIRCUIT
AIM AIM AIM AIM AOM AOM AOM AIM AIM AOM AIM AIM AOM AOM AOM AOM
FTS
FOR FCU-1.1
FTS
OPEN CLOSED FAULT NORMAL AUTO CLOSE OPEN RETURN
FTS
FTS
AOM AIM AIM AOM AIM AIM AIM AIM AIM AIM AIM AIM AIM AIM
Job # 225121
NEW YORK, NY 10044
FTS
ELEV. LOBBY
#1/#2
FSD FSD FSD FSD FSD FSD PRIMARY ALTERNATE SHUNT FIREMAN FIREMAN SHUNT ALTERNATE PRIMARY FIRE ALARM
1 ACTIVATE OPEN CLOSED ACTIVATE OPEN CLOSED RECALL RECALL TRIP HAT HAT TRIP RECALL RECALL
TYPICAL FOR (5) TYPICAL FOR (4) REFER TO NOTE 3 FIRE PUMP ROOM
REF: FA-301 TYPICAL FOR (27) SINGLE LINE DIAGRAM
TYPICAL FOR (30) DEVICES
AIM AIM AOM AIM AIM AOM AIM AIM AIM AIM AIM AIM
P
AIM
PURPOSE OF ISSUE: Fire Alarm Shade Interface
FTS
TELE. RM ELEC. RM
FIRE PUMP ROOM
PREPARED BY: KS CHECKED BY: KS
FTS
FTS
FTS
FTS
FTS
FA-301.00
1. REFER TO FLOOR PLANS FOR DEVICE RATINGS.
SCALE: NTS
1 120V CIRCUIT DOWN TO FIRE ALARM FUSE CUTOUT
PANEL IN EMERGENCY ELECTRICAL ROOM AT ROOF.
2. THIS SINGLE LINE DIAGRAM IS FOR INTENT ONLY. FILE No.:
AHU-5 RETURN AHU-4 RETURN AHU-3 RETURN AHU-2 RETURN AHU-1 RETURN AHU-5 SUPPLY AHU-4 SUPPLY AHU-3 SUPPLY AHU-2 SUPPLY AHU-1 SUPPLY SOUTH SHAFT DAMPER TYPICAL FOR (5) NORTH SHAFT DAMPER
2 2
FOR STAIR HATCH
9
SMOKE FAN TYPICAL FOR (3)
AIM AIM AOM AIM AIM AOM AIM AIM AOM AIM AIM AOM AIM AIM AOM AIM AIM AOM AIM AIM AOM AIM AIM AOM AIM AIM AOM AIM AIM AOM AIM AIM AOM AIM AIM AOM
STAIRWAY #1
AOM AOM AOM AOM AOM AIM AIM
FSD FSD FSD FSD FSD FSD FSD FSD FSD FSD FSD FSD FSD FSD FSD FSD FSD FSD FSD FSD FSD FSD FSD FSD FSD FSD FSD FSD FSD FSD
CLOSED OPEN ACTIVATE CLOSED OPEN ACTIVATE CLOSED OPEN ACTIVATE CLOSED OPEN ACTIVATE CLOSED OPEN ACTIVATE CLOSED OPEN ACTIVATE CLOSED OPEN ACTIVATE CLOSED OPEN ACTIVATE CLOSED OPEN ACTIVATE CLOSED OPEN ACTIVATE
AOM AIM OFF ON NORMAL FAULT AUTO OFF ON
STATUS STATUS TYPICAL FOR (17) TOP OF ELEVATOR SHAFT AHU-5 MECH ROOM AHU-4 MECH ROOM AHU-2 MECH ROOM AHU-3 MECH ROOM AHU-1 MECH ROOM ARCHITECT:
R
mOrphosis
STATUS ACTIVATE P P P 9
AIM AOM AIM AIM AIM AIM AIM AIM AIM AIM AIM AIM SMOKE FAN DAMPER TYPICAL FOR (2) 153 W. 27th Street
MECH SMOKE FAN TYPICAL FOR (2) MECH ROOM Suite 1200
MECH ROOM New York, NY 10001
STAIR #1 ROOM DAMPER DAMPER AOM AOM AOM AIM AIM AIM AIM
ACTIVATE STATUS SHUTDOWN SHUTDOWN SHUTDOWN SHUTDOWN SHUTDOWN AOM AOM AOM AOM AOM AIM AIM T: 212.675.1100
9 ATS-1 ATS-2 ATS-3 OPEN CLOSE AUTO OPEN CLOSED FAULT NORMAL
SMOKE FAN DAMPER TYPICAL FOR (3) OFF ON NORMAL FAULT AUTO OFF ON STATUS STATUS STATUS STATUS
TYPICAL FOR (18) STATUS STATUS GENERATOR STATUS www.morphosis.com
4
AIM AIM AIM AIM AIM AIM AIM AIM
AOM AOM AOM AIM AIM AIM AIM OWNER:
MECH SHAFT TYPICAL FOR (17) AIM AIM AIM AIM
FOR SHAFT HATCH CORNELLNYC TECH
OPEN CLOSE AUTO FAULT NORMAL OPEN CLOSED SHUNT TRIP NORMAL EMERG. NORMAL EMERG. NORMAL EMERG.
9 STATUS STATUS STATUS STATUS 111 EIGHTH AVENUE, #302
AOM AIM GENERATOR GENERATOR GENERATOR GENERATOR
NEW YORK, NY 10011
FTS
2 AIM AIM
CIRCUIT CIRCUIT AOM AIM TYPICAL FOR (33)
2 RETURN
AIM AIM AOM AIM AIM AOM
MUESER RUTLEDGE
CLASS A 225 W. 34TH STREET
TELE. RM CIRCUIT S S STATUS ACTIVATE
STATUS ACTIVATE 482 NEW YORK, NY 10122
FSD FSD FSD FSD FSD FSD TEL: 917.339.9300
RETURN
FTS
FTS
CLOSED OPEN ACTIVATE CLOSED OPEN ACTIVATE
FTS
S CLASS A
S SC SC SC SC SC SC CIRCUIT COST ESTIMATOR:
P
TYPICAL FOR (36) DEVICES DHARAM CONSULTING
RETURN ELEC. RM ELEC. STAIR RETURN
CLASS A RETURN 40068 CLOSET #2 CORR 40050 2 240 WEST 37TH STREET, SUITE 302
RETURN CLASS A S
CIRCUIT CLASS A 2 40070
NEW YORK, NY 10018
CLASS A CIRCUIT
TEL: 508.344.3820
FTS
CIRCUIT S S S TYPICAL FOR (10) DEVICES CIRCUIT S S S S S S S S S S S
2 2 LEVEL 4
ELEV. LOBBY
SC SC SC SC
CODE:
1 P TYPICAL FOR (2) REFER TO NOTE 3 1
RETURN CODE CONSULTANTS
FTS
STAIRWAY #5 TELE. RM ELEC. RM CLASS A PROFESSIONAL ENGINEERS, PC
STAIR #1 336 30065 2 CORR 30041 2 ELEV. LOBBY CIRCUIT 215 WEST 40TH STREET, 15FL
RETURN AIM AIM AOM AIM AIM AOM NEW YORK, NY 10018
FTS
9 R R TEL: 212.216.9596
CLASS A TYPICAL FOR (3) REFER TO NOTE 3 2 TYPICAL FOR (2)
FTS
FTS
FTS
S S CIRCUIT FACP FACP
FSD FSD FSD FSD FSD FSD SPECIFICATIONS:
3 ELEC. RM ELEV. #1/#2 CLOSED OPEN ACTIVATE CLOSED OPEN ACTIVATE ELEC. RM
30065 AIM AIM AOM AIM AIM AOM 30068 RETURN CONSTRUCTION SPECIFICATIONS, INC
SC SC SC SC B 22 TENNENT ROAD P.O. BOX 488
RETURN P CLASS A
CLASS A FOR FCU-3.3 S S MORGANVILLE, NJ 07751
FSD FSD FSD FSD FSD FSD TELE. RM ELEC. RM ELEC. STAIR CIRCUIT
OFFICE TEL: 732.970.0700
CIRCUIT 2 CORR 30050 #2
S S S S S S CLOSED OPEN ACTIVATE CLOSED OPEN ACTIVATE 2 ZONE B 382 30068 CLOSET
TYPICAL FOR (31)
P P 2
RETURN WATER PROOFING:
2 SMOKE CONTROL OPERABLE WINDOW TYPICAL FOR (4) 2 STAIR STAIR SMOKE CONTROL OPERABLE WINDOW TYPICAL FOR (4) 2 CLASS A
RETURN #3 #6 CIRCUIT HENSHELL & BUCCELLATO
CLASS A AIM AIM AIM AIM AOM AOM AOM AIM AIM AIM AIM AOM AOM AOM 166 PATTERSON AVENUE
CIRCUIT SHREWSBURY, NJ 07702
OFFICE ZONE A OFFICE ZONE B TEL: 732.530.4734
OPEN CLOSED FAULT NORMAL AUTO CLOSE OPEN OPEN CLOSED FAULT NORMAL AUTO CLOSE OPEN
STATUS STATUS STATUS STATUS STATUS STATUS STATUS STATUS S S S S S S S S S S S LEVEL 3
TYPICAL FOR (34) DEVICES KITCHEN CONSULTANT:
TYPICAL FOR (2) REFER TO NOTE 3
JACOB DOLAND BEER
116 E. 27TH STREET, 2FL
TYPICAL FOR (3) REFER TO NOTE 3 TYPICAL FOR (2) 2
FTS
FTS
FTS
FTS
FTS
2 S ELEV. LOBBY
2 STAIRWAY #5
9
AIM AIM AOM AIM AIM AOM FSD FSD FSD FSD FSD FSD 2
P P ISSUES / REVISIONS:
TYPICAL FOR (37) DEVICES FOR FCU-2.3 CLOSED OPEN ACTIVATE CLOSED OPEN ACTIVATE
S CORR 20050
STAIR STAIR NO. DATE DESCRIPTION
FSD FSD FSD FSD FSD FSD STAIRWAY #7 SC SC SC SC SC
#3 #6
CLOSED OPEN ACTIVATE CLOSED OPEN ACTIVATE 08/09/2013 100% DD
S S S S S S S S P S
RETURN 01/17/2014 50% CD
R R SC SC AOM AOM AOM
P CLASS A
2 STAIRWAY #5 AOM AOM TELE. RM ELEC. RM ELEC. STAIR CIRCUIT 05/16/2014 100% CD
STAIR ELEC. RM 2 CORR 282 BLACKOUT/SUNSHADE 20068 CLOSET #2
TELE. RM ELEV. #1/#2 S DOOR RELEASE
#1 236 20065 STAIR #1 20041 20070 2 06/30/2014 Addendum 2
ROLLUP
RETURN SMOKE CONTROL OPERABLE WINDOW TYPICAL FOR (4) DOOR RELEASE SMOKE CONTROL OPERABLE WINDOW TYPICAL FOR (4) TYPICAL FOR (36) 9 02/13/2015 Bulletin #3
2 2
CLASS A SC SC RETURN 2
S S CIRCUIT CLASS A 10 05/15/2015 Bulletin #4
AIM AIM AIM AIM AOM AOM AOM AIM AIM AIM AIM AOM AOM AOM CIRCUIT S S S
CORR
OFFICE ZONE A 20050 2 OFFICE ZONE B
OPEN CLOSED FAULT NORMAL AUTO CLOSE OPEN OPEN CLOSED FAULT NORMAL AUTO CLOSE OPEN
STATUS STATUS STATUS STATUS STATUS STATUS STATUS STATUS LEVEL 2
FTS
FTS
P P P P P REMOTE START AT LOBBY RETURN
AIM
CLASS A
FTS
LECTURE CORR. CORR. ELEV.
HALL MAIN LOUNGE 10043 10040 STAIR #1 TO SMOKE CIRCUIT
LECTURE HALL #3 ELEV. LOBBY
2 2 CONTROL S S S S S S S S
SOUND SYSTEM TYPICAL FOR (4) REFER TO NOTE 3 TYPICAL FOR (2) 10046
SMOKE CONTROL OPERABLE WINDOW TYPICAL FOR (6) PANEL
SHUTDOWN RETURN
1 1 CLASS A
CIRCUIT
AIM AIM AIM AIM AOM AOM AOM AIM AIM AOM AIM AIM AOM
FTS
FOR FCU-1.1
FTS
OPEN CLOSED FAULT NORMAL AUTO CLOSE OPEN 9 RETURN
FTS
FTS
AOM AIM AIM AOM AIM AIM AIM AIM AIM AIM AIM AIM AIM AIM NEW YORK, NY 10044
FTS
ELEV. LOBBY
#1/#2
FSD FSD FSD FSD FSD FSD PRIMARY ALTERNATE SHUNT FIREMAN FIREMAN SHUNT ALTERNATE PRIMARY FIRE ALARM
1 ACTIVATE OPEN CLOSED ACTIVATE OPEN CLOSED RECALL RECALL TRIP HAT HAT TRIP RECALL RECALL
TYPICAL FOR (5) TYPICAL FOR (4) REFER TO NOTE 3 9 FIRE PUMP ROOM TYPICAL FOR (27) SINGLE LINE DIAGRAM
TYPICAL FOR (30) DEVICES 2 P
AIM AIM AOM AIM AIM AOM AIM AIM AIM AIM AIM AIM AIM
FTS
TELE. RM ELEC. RM
FIRE PUMP ROOM
FTS
FTS
FTS
FTS
FTS
Superceded Reference Casey System Riser for build 1. REFER TO FLOOR PLANS FOR DEVICE RATINGS.
TYPICAL FOR EACH SEF FAN TYPICAL FOR EACH SEF FAN
ON ON
ON G OFF ON G OFF
AUTO AUTO
FAULT Y FAULT Y
SEF-1 SEF-7
OFF R OFF R
ARCHITECT:
NORMAL W NORMAL W mOrphosis
SEF-1 SEF-7 153 W. 27th Street
Suite 1200
SEF-1 SEF-2 SEF-5 SEF-3 SEF-4 New York, NY 10001
ROOF ROOF
T: 212.675.1100
ARUP
77 WATER STREET
NEW YORK, NY 10005
TEL: 212.896.3000
ON G ON
OFF
FAULT Y GEOTECHNICAL:
ON G ON
OFF MUESER RUTLEDGE
OFF R FAULT Y 225 W. 34TH STREET
NORMAL W OFF R
NEW YORK, NY 10122
TEL: 917.339.9300
AHU-3 NORMAL W
COST ESTIMATOR:
AHU-4
DHARAM CONSULTING
240 WEST 37TH STREET, SUITE 302
NEW YORK, NY 10018
TEL: 508.344.3820
PENTHOUSE PENTHOUSE
CODE:
CODE CONSULTANTS
LEVEL 4 LEVEL 4 PROFESSIONAL ENGINEERS, PC
215 WEST 40TH STREET, 15FL
NEW YORK, NY 10018
TYPICAL FOR EACH WINDOW TYPICAL FOR EACH WINDOW TEL: 212.216.9596
SPECIFICATIONS:
3
OPEN OPEN CONSTRUCTION SPECIFICATIONS, INC
OPEN G CLOSE OPEN G CLOSE 22 TENNENT ROAD P.O. BOX 488
AUTO AUTO MORGANVILLE, NJ 07751
FAULT Y FAULT Y TEL: 732.970.0700
WINDOW 3-1 WINDOW 3-8
CLOSED R WINDOW 3-1 WINDOW 3-2 WINDOW 3-3 WINDOW 3-4 WINDOW 3-5 WINDOW 3-6 WINDOW 3-7 WINDOW 3-8 WINDOW 3-9 WINDOW 3-10 WINDOW 3-11 WINDOW 3-12 WINDOW 3-13 WINDOW 3-14 WINDOW 3-15 WINDOW 3-16 CLOSED R
WATER PROOFING:
NORMAL W NORMAL W
HENSHELL & BUCCELLATO
WINDOW 3-1 WINDOW 3-8 166 PATTERSON AVENUE
SHREWSBURY, NJ 07702
TEL: 732.530.4734
LEVEL 3 LEVEL 3
KITCHEN CONSULTANT:
TYPICAL FOR EACH WINDOW TYPICAL FOR EACH WINDOW
JACOB DOLAND BEER
116 E. 27TH STREET, 2FL
NEW YORK, NY 10016
OPEN OPEN TEL: 212.206.0736
OPEN G CLOSE OPEN G CLOSE
AUTO AUTO
FAULT Y FAULT Y ISSUES / REVISIONS:
WINDOW 2-1 WINDOW 2-8
CLOSED R WINDOW 2-1 WINDOW 2-2 WINDOW 2-3 WINDOW 2-4 WINDOW 2-5 WINDOW 2-6 WINDOW 2-7 WINDOW 2-8 WINDOW 2-9 WINDOW 2-10 WINDOW 2-11 WINDOW 2-12 WINDOW 2-13 WINDOW 2-14 WINDOW 2-15 WINDOW 2-16 CLOSED R NO. DATE DESCRIPTION
NORMAL W NORMAL W 08/09/2013 100% DD
01/17/2014 50% CD
WINDOW 2-1 WINDOW 2-8 05/16/2014 100% CD
2 06/30/2014 Addendum 2
OPEN OPEN
OPEN G CLOSE OPEN G CLOSE
AUTO AUTO
LEVEL 1 LEVEL 1
KEY PLAN:
CELLAR CELLAR
REF: FA-302
CORNELL SMOKE CONTROL SEQUENCE OF OPERATION
SMOKE CONTROL OPERATION O=OPEN/ON, X=OFF/CLOSED
PURPOSE OF ISSUE:
Vestibule Door Power/Fire Alarm
OFF PREPARED BY: CHECKED BY: KS
1. ALL SMOKE EXHAUST FANS, ISOLATION SMOKE DAMPERS, OPERABLE B. RESPECTIVE ISOLUATION
KS SMOKE EXHAUST DAMPER SHALL
MAKEUP AIR OPERABLE WINDOWS
W Y G
ON WINDOWS AND OPERABLE DOORS ARE IN THE AUTOMATIC SWITCH CLOSEESK-CA-066.4
UPON FULL STOP OF SMOKE EXHAUST FAN. SMOKE
SMOKE EXHAUST FAN DAMPERS
CLOSED. ALL "NORMAL" STATUS LIGHTS ARE ACTIVE. UPON ACTIVATION 3. WHEN 2642 KEY IS MOVED TO "ON" POSITION, MANUAL CONTROL FROM
OF ANY TWO SPOT TYPE SMOKE DETECTORS IDENTIFIED FOR SMOKE CONTROL , THE SMOKE CONTROL PANEL OF OPERABLE WINDOWS AND DOORS
AIR HANDLING UNITS
ANY ATRIUM BEAM SMOKE DETECTORS OR WATER FLOW SWITCH IN SHALL BE POSSIBLE AND SHALL ILLUMINATE THE RESPECTIVE STATUS
THE BUILDING THE FOLLOWING SHALL OCCUR: LIGHTS DEPENDING ON "OPEN" OR "CLOSED" POSITION OF EACH
A. AIR HANDLING UNITS SHALL SHUT DOWN. RESPECTIVE INDIVIDUAL CONTROL SWITCH AS SMOKE CONTROL PANEL.
NOTES:
DAMPERS SHALL CLOSE.
B. ALL ISOLATION SMOKE DAMPERS AT SMOKE EXHAUST FANS 4. IF THERE IS A FAULT FOR ANY OF THE FANS, DAMPERS, OPERABLE
1. COORDINATE WITH MECHANICAL DRAWINGS FOR SHUTDOWN AND SMOKE
SHALL AUTOMATICALLY OPEN. "OPEN" LIGHT AT SMOKE WINDOWS OR DOORS, THE "FAULT" STATUS LIGHT SHALL ILLUMINATE. PROJECT
CONTROL SEQUENCES.
MANAGEMENT PANELS SHALL ILLUMINATE AFTER COMPLETING UPON CORRECTION OF THE FAULT THE STATUS LIGHT SHALL
OPENING SEQUENCE OF DAMPER. "NORMAL" LIGHT SHALL DEACTIVATE.
SEF-1
SEF-2
SEF-3
SEF-4
SEF-5
TYPICAL FOR EACH SEF FAN TYPICAL FOR EACH SEF FAN
ON ON
ON G OFF ON G OFF
AUTO AUTO
FAULT Y FAULT Y
SEF-1 SEF-7
OFF R OFF R
ARCHITECT:
NORMAL W NORMAL W mOrphosis
SEF-1 SEF-7 153 W. 27th Street
Suite 1200
SEF-1 SEF-2 SEF-5 SEF-3 SEF-4 New York, NY 10001
ROOF ROOF
T: 212.675.1100
CODE:
CODE CONSULTANTS
LEVEL 4 LEVEL 4 PROFESSIONAL ENGINEERS, PC
215 WEST 40TH STREET, 15FL
NEW YORK, NY 10018
TYPICAL FOR EACH WINDOW TYPICAL FOR EACH WINDOW TEL: 212.216.9596
SPECIFICATIONS:
3
OPEN OPEN CONSTRUCTION SPECIFICATIONS, INC
OPEN G CLOSE OPEN G CLOSE 22 TENNENT ROAD P.O. BOX 488
AUTO AUTO MORGANVILLE, NJ 07751
FAULT Y FAULT Y TEL: 732.970.0700
WINDOW 3-1 WINDOW 3-8
CLOSED R WINDOW 3-1 WINDOW 3-2 WINDOW 3-3 WINDOW 3-4 WINDOW 3-5 WINDOW 3-6 WINDOW 3-7 WINDOW 3-8 WINDOW 3-9 WINDOW 3-10 WINDOW 3-11 WINDOW 3-12 WINDOW 3-13 WINDOW 3-14 WINDOW 3-15 WINDOW 3-16 CLOSED R
WATER PROOFING:
NORMAL W NORMAL W
HENSHELL & BUCCELLATO
WINDOW 3-1 WINDOW 3-8 166 PATTERSON AVENUE
SHREWSBURY, NJ 07702
TEL: 732.530.4734
LEVEL 3 LEVEL 3
KITCHEN CONSULTANT:
TYPICAL FOR EACH WINDOW TYPICAL FOR EACH WINDOW
JACOB DOLAND BEER
116 E. 27TH STREET, 2FL
NEW YORK, NY 10016
OPEN OPEN TEL: 212.206.0736
OPEN G CLOSE OPEN G CLOSE
AUTO AUTO
FAULT Y FAULT Y ISSUES / REVISIONS:
WINDOW 2-1 WINDOW 2-8
CLOSED R WINDOW 2-1 WINDOW 2-2 WINDOW 2-3 WINDOW 2-4 WINDOW 2-5 WINDOW 2-6 WINDOW 2-7 WINDOW 2-8 WINDOW 2-9 WINDOW 2-10 WINDOW 2-11 WINDOW 2-12 WINDOW 2-13 WINDOW 2-14 WINDOW 2-15 WINDOW 2-16 CLOSED R NO. DATE DESCRIPTION
NORMAL W NORMAL W 08/09/2013 100% DD
01/17/2014 50% CD
WINDOW 2-1 WINDOW 2-8 05/16/2014 100% CD
2 06/30/2014 Addendum 2
LEVEL 2 LEVEL 2 5 08/25/2014 Post Bid Bulletin #1
OPEN OPEN
OPEN G CLOSE OPEN G CLOSE
AUTO AUTO
LEVEL 1 LEVEL 1
KEY PLAN:
CELLAR CELLAR
W Y G
ON WINDOWS AND OPERABLE DOORS ARE IN THE AUTOMATIC SWITCH CLOSE UPON FULL STOP OF SMOKE EXHAUST FAN. SMOKE
SMOKE EXHAUST FAN DAMPERS
POSITION. FIREFIGHTER'S MANUAL OPERATION KEY SWITCH IN "OFF" EXHAUST DAMPER "OFF" LIGHT SHALL ILLUMINATE AND
SYSTEM SYSTEM POWER ON FIREFIGHTER'S MANUAL POSITION. ALL SMOKE EXHAUST FANS ARE OFF, SMOKE DAMPERS ARE "ON" LIGHT SHALL DEACTIVATE.
LAMP TEST
NORMAL TROUBLE OPERATION KEY CLOSED. OPERABLE WINDOWS ARE CLOSED, AND OPERABLE DOORS ARE
CLOSED. ALL "NORMAL" STATUS LIGHTS ARE ACTIVE. UPON ACTIVATION 3. WHEN 2642 KEY IS MOVED TO "ON" POSITION, MANUAL CONTROL FROM
OF ANY TWO SPOT TYPE SMOKE DETECTORS IDENTIFIED FOR SMOKE CONTROL , THE SMOKE CONTROL PANEL OF OPERABLE WINDOWS AND DOORS
AIR HANDLING UNITS
ANY ATRIUM BEAM SMOKE DETECTORS OR WATER FLOW SWITCH IN 2 SHALL BE POSSIBLE AND SHALL ILLUMINATE THE RESPECTIVE STATUS
THE BUILDING THE FOLLOWING SHALL OCCUR: LIGHTS DEPENDING ON "OPEN" OR "CLOSED" POSITION OF EACH
A. AIR HANDLING UNITS SHALL SHUT DOWN. RESPECTIVE INDIVIDUAL CONTROL SWITCH AS SMOKE CONTROL PANEL.
NOTES:
DAMPERS SHALL CLOSE.
B. ALL ISOLATION SMOKE DAMPERS AT SMOKE EXHAUST FANS 4. IF THERE IS A FAULT FOR ANY OF THE FANS, DAMPERS, OPERABLE
1. COORDINATE WITH MECHANICAL DRAWINGS FOR SHUTDOWN AND SMOKE
SHALL AUTOMATICALLY OPEN. "OPEN" LIGHT AT SMOKE WINDOWS OR DOORS, THE "FAULT" STATUS LIGHT SHALL ILLUMINATE. PROJECT
CONTROL SEQUENCES.
MANAGEMENT PANELS SHALL ILLUMINATE AFTER COMPLETING UPON CORRECTION OF THE FAULT THE STATUS LIGHT SHALL
OPENING SEQUENCE OF DAMPER. "NORMAL" LIGHT SHALL DEACTIVATE.
SEF-1
SEF-2
SEF-3
SEF-4
SEF-5
Superceded
2. SMOKE PURGE FOR OTHER CELLAR AREAS NOT CONNECTED TO THE
Reference Casey Systems Drawings for Build 2. FIRE DEPARTMENT INSERTS 2642 KEY INTO MANUAL OPERATION KEY
SLOT AND MOVES MANUAL KEY POSITION TO "ON". SMOKE EXHAUST FANS
SWITCHES ARE MANUALLY SWITCHED TO "OFF" POSITION WHILE IN
ALARM CONDITION (SMOKE SEQUENCE HAS BEEN ACTIVATED AS NOTED
ATRIUM SUCH AS THE AUDITORIUM AND SEMINAR ROOMS SHALL OCCUR
BY INSERTING THE 2642 KEY TO THE "ON" POSITION AND PLACING THE
CONTROL SWITCH FOR AHU-3 AND AHU-4 TO "ON" POSITION. THE "ON" STATUS LIGHT
SHALL ILLUMINATE FOR AHU-4. THE SMOKE CONTROL PANEL SHALL
SEAL & SIGNATURE: DATE:
PROJECT No.:
05-16-14
225121
ABOVE IN ITEM 1): COMMUNICATE WITH THE BUILDING MANAGEMENT SYSTEM. THE
DRAWING BY:
A. RESPECTIVE SMOKE FAN SHALL STOP RUNNING. PRESSURE BUILDING MANAGEMENT SHALL START AHU-3 AND AHU-4 RESPECTIVELY AND
SWITCH DETECTS NO AIR FLOW. SMOKE EXHAUST FAN "OFF" ASSOCIATED DAMPERS SMOKE PURGE SEQUENCE. IN ADDITION: CHK BY:
LIGHT SHALL ILLUMINATE AND "ON" LIGHT SHALL DEACTIVATE. A. THE FIRE ALARM SYSTEM SHALL OPEN ALL SUPPLY FSD ASSOCIATED WITH DWG No.
AHU-3 AND AHU-4 SMOKE CLEARANCE MODE.
B. DISBALE AHU SHUTDOWN (RE-ENABLE AHU). FA-302.00
FILE No.:
E D C B A
1 2 3 3.6 4 4.6 5 6 7 8
ARCHITECT:
mOrphosis
153 W. 27th Street
Suite 1200
New York, NY 10001
T: 212.675.1100
S
B04A B04B B04C TEL: 212.309.9020
SMEP/SUSTAINABILITY/ LEED/
LIGHTING EXTERIOR
B ENVELOPE/ AV/ IT/ SECURITY
UV/IR ACOUSTICS/ SMART BUILDING
WP STORAGE FUEL OIL RM WATER SERVICES
15CD B32 B0065 B0067 ARUP
LECTURE HALL 77 WATER STREET
15CD
1 1
15CD
UV/IR
S
131 NEW YORK, NY 10005
15CD
15CD
TEL: 212.896.3000
P
FOR RISER CONTROL VALVE
9 10 8 AIM AIM AOM AIM AIM AOM
GEOTECHNICAL:
SEMINAR RM
. .
S
AIM AIM RAIM AIM UP TO MAIN FACP AIM AIM AOM
ELEV MACHINE RM 240 WEST 37TH STREET, SUITE 302
15CD
AT GROUND FLOOR
.
15CD
B0062 R 1 JANITOR NEW YORK, NY 10018
FTS
SEE FA-404
6 B0079 TEL: 508.344.3820
15CD SC
15CD 1
R R CODE:
2
ELEV #3 15CD C.8 CODE CONSULTANTS
B0075 DEDICATED STAIR RISER PROFESSIONAL ENGINEERS, PC
CIRCUIT SEPARATE FROM 215 WEST 40TH STREET, 15FL
FTS
FTS
15CD
FLOOR SPEAKER CIRCUIT NEW YORK, NY 10018
STAIR #4 D TEL: 212.216.9596
15CD
B0004
9 10 8 FOR RISER CONTROL VALVE SPECIFICATIONS:
3
AIM AIM AOM UP TO FACP AT R ELEV #1 CONSTRUCTION SPECIFICATIONS, INC
CORRIDOR GROUND FLOOR
S
.
FTS
1 B0051
15CD
15CD
D.2
.
WP WATER PROOFING:
15CD AIM AIM AOM 1 1 P
9 10 8
.
30CD
15CD
15CD
15CD KITCHEN CONSULTANT:
EF RM
15CD
AIM AIM AIM AIM
B11 FTS WP JACOB DOLAND BEER
9 2 3 4 5
R R 116 E. 27TH STREET, 2FL
1
AIM AIM AOM
6 7 NEW YORK, NY 10016
ELEV CNTR RM TEL: 212.206.0736
1
.
B0066 E
R
9 10 8 9
AIM AIM AIM AIM ISSUES / REVISIONS:
2 3 4 5 E.2 NO. DATE DESCRIPTION
30CD
08/09/2013 100% DD
CUSTODIAL/RECYCLING 01/17/2014 50% CD
MECHANICAL RM STORAGE
B0061
B0064 B21 05/16/2014 100% CD
LACTATION 2 06/30/2014 Addendum 2
B58
9 02/13/2015 Bulletin #3
SHOWER
30CD
B56
SHOWER
B54
BLDG MANAGER OFFICE SHOWER
B15 B52
2
LOCATE IN EACH BEAM POCKET (TYP.)
F
KEY PLAN:
N
P.N.
PROJECT
G
CORNELLNYC TECH
FIRST ACADEMIC
BUILDING
1 MAIN STREET
ROOSEVELT ISLAND
NEW YORK, NY 10044
1 L J FIRE ALARM
CELLAR FLOOR PLAN
A1 SCALE 1/8" = 1'-0" (SOUTH)
REFERENCE NOTES:
1 LOCATE WITHIN 5'-0" OF FIRE SMOKE DAMPER 6 LOCATE HEAT DETECTOR WITHIN 2'-0" OF SPRINKLER HEAD SEAL & SIGNATURE: DATE: 05-16-14
PROJECT No.: 225121
2 FOR ALTERNATE ELEVATOR RECALL 7 LOCATE SMOKE DETECTOR WITHIN EACH BEAM POCKET DRAWING BY:
CHK BY: Checker
3 FOR ELEVATOR SHUNT TRIP 8 ACTIVATION OF FIRE SMOKE DAMPERS. COORDINATE WITH MECHANICAL DRAWINGS.
DWG No.
9 CLOSED STATUS OF FIRE SMOKE DAMPERS. COORDINATE WITH MECHANICAL DRAWINGS.
4 FOR FIREMAN'S HAT
FA-402.00
5 FOR PRIMARY ELEVATOR RECALL 10 OPEN STATUS OF FIRE SMOKE DAMPERS. COORDINATE WITH MECHANICAL DRAWINGS.
9
FILE No.:
E D C B A
ARCHITECT:
mOrphosis
153 W. 27th Street
Suite 1200
New York, NY 10001
T: 212.675.1100
S
CORNELLNYC TECH
111 EIGHTH AVENUE, #302
NEW YORK, NY 10011
S
S
S
S
S
S
TEL: 212.309.9020
SMEP/SUSTAINABILITY/ LEED/
LIGHTING EXTERIOR
B ENVELOPE/ AV/ IT/ SECURITY
ACOUSTICS/ SMART BUILDING
K ARUP
77 WATER STREET
S
S
S
S
S
S
NEW YORK, NY 10005
TEL: 212.896.3000
FOR RISER CONTROL VALVE
GEOTECHNICAL:
SEMINAR RM SEMINAR RM SEMINAR RM SEMINAR RM
B61 B73 B81 B91 MUESER RUTLEDGE
225 W. 34TH STREET
NEW YORK, NY 10122
C TEL: 917.339.9300
S
S
9
COST ESTIMATOR:
DHARAM CONSULTING
.
30CD
15CD
15CD
15CD
15CD
15CD
VESTIBULE
C.8 CODE CONSULTANTS
15CD PROFESSIONAL ENGINEERS, PC
IT DEPOT TEL RM MAIN ELEC RM STORAGE FIRE PUMP RM B0048 215 WEST 40TH STREET, 15FL
30CD
B72 B74 B0068 B82 B0069 P
NEW YORK, NY 10018
FTS
D TEL: 212.216.9596
FTS
15CD
15CD
AIM AIM AOM
SPECIFICATIONS:
3 .
9 10 8
S
CONSTRUCTION SPECIFICATIONS, INC
9 10 8 22 TENNENT ROAD P.O. BOX 488
15CD AIM AIM AOM
WP STAIR #2 .
MORGANVILLE, NJ 07751
WOMEN LOCKER RM15CD
15CD CORRIDOR 15CD AIM AIM AIM AIM AIM AIM B0008 TEL: 732.970.0700
B0026 FOR FLOOR CONTROL
B80 ASSEMBLY
B0051
WP D.2 WATER PROOFING:
30CD 2 3 4 5 6 7
FOR FIRE PUMP (TYP. 8) HENSHELL & BUCCELLATO
15CD 166 PATTERSON AVENUE
FOR INCOMING FIRE SERVICE FOR RISER CONTROL VALVE
SHREWSBURY, NJ 07702
V R
E
TI C
U
O
S N
A
H
IS
U
LR
_ -98T
4K
N
A
M
H
S
E
R
F V R
E
TI C
U
O
S N
A
H
IS
U
LR
_ -98T
4K
N
A
M
H
S
E
R
F V R
E
TI C
U
O
S N
A
H
IS
U
LR
_ -98T
4K
N
A
M
H
S
E
R
F
TEL: 732.530.4734
15CD
DEDICATED STAIR RISER KITCHEN CONSULTANT:
MEN SPEAKER CIRCUIT SEPARATE
WP B0028 FROM FLOOR SPEAKER CIRCUIT JACOB DOLAND BEER
30CD
1 9 116 E. 27TH STREET, 2FL
NEW YORK, NY 10016
15CD TEL: 212.206.0736
1 1
R
E
15CD
UP TO FIRST FLOOR
9 ISSUES / REVISIONS:
E.2 NO. DATE DESCRIPTION
08/09/2013 100% DD
AIM AIM AOM 2
. 01/17/2014 50% CD
05/16/2014 100% CD
LACTATION 9 10 8 2 06/30/2014 Addendum 2
B58
9 02/13/2015 Bulletin #3
SHOWER
B56 CONCRETE ENCASED CONDUITS (SEE E-808/1 FOR ELEVATIONS
SHOWER
AND CONDUIT ARRANGEMENTS):
(2) 2 1/2"C FOR MAIN FIRE ALARM FEEDER FROM CUP.
B54 (2) 2"C FOR FIRE ALARM NETWORK CABLE TO CUP.
SHOWER TERMINATE CONDUITS AT GROUND FLOOR SLAB PERIMETER
B52 FOR CONNECTION INTO SITE CONDUITS. CAP CONDUITS,
INSTALL (4) DRAG LINES, AND PREPARE FOR CONNECTIONS
INTO SITE CONDUITS. COORDINATE WORK WITH SITE
F
KEY PLAN:
N
P.N.
PROJECT
G
CORNELLNYC TECH
FIRST ACADEMIC
BUILDING
1 MAIN STREET
ROOSEVELT ISLAND
NEW YORK, NY 10044
1 FIRE ALARM
CELLAR FLOOR PLAN
A1 SCALE 1/8" = 1'-0" (NORTH)
REFERENCE NOTES:
1 LOCATE WITHIN 5'-0" OF FIRE SMOKE DAMPER 6 FIRE PUMP PHASE REVERSAL 11 SECURITY SYSTEM INTERFACE TO UNLOCK DOORS. SEAL & SIGNATURE: DATE: 05-16-14
LOCATE WITHIN 3'-0'' OF SECURITY SYSTEM INTERFACE. PROJECT No.: 225121
2 FIRE PUMP LOSS OF POWER 7 FIRE PUMP DISCONNECT SWITCH OPEN DRAWING BY:
CHK BY: Checker
3 FIRE PUMP POWER AVAILABLE 8 ACTIVATION OF FIRE SMOKE DAMPERS. COORDINATE WITH MECHANICAL DRAWINGS.
DWG No.
9 CLOSED STATUS OF FIRE SMOKE DAMPERS. COORDINATE WITH MECHANICAL DRAWINGS.
4 FIRE PUMP RUNNING 9
FA-403.00
5 10 OPEN STATUS OF FIRE SMOKE DAMPERS. COORDINATE WITH MECHANICAL DRAWINGS.
CONNECTED TO ALTERNATE SOURCE
FILE No.:
E D C B A
ARCHITECT:
mOrphosis
153 W. 27th Street
Suite 1200
New York, NY 10001
T: 212.675.1100
4 www.morphosis.com
OWNER:
S
A CORNELLNYC TECH
111 EIGHTH AVENUE, #302
DOOR D1-1A / D1-1B UP NEW YORK, NY 10011
STAIR #3
TEL: 212.309.9020
10005 S
FTS
SMEP/SUSTAINABILITY/ LEED/
LIGHTING EXTERIOR
ENVELOPE/ AV/ IT/ SECURITY
B ACOUSTICS/ SMART BUILDING
P
AOM AOMAOM AIM AIM AIM AIM
.
ARUP
77 WATER STREET
2 3 4 10 11 12 13 LECTURE HALL NEW YORK, NY 10005
131 TEL: 212.896.3000
P
GEOTECHNICAL:
EXIT CORRIDOR
15CD15CD P UP MUESER RUTLEDGE
10043 GENERATOR STATUS PANEL 225 W. 34TH STREET
REMOTE GENERATOR START (BELOW GSP) STAIR #6 NEW YORK, NY 10122
10007 TEL: 917.339.9300
FTS
110CD
C
P
S S ELEVATOR STATUS PANEL RPZ RM COST ESTIMATOR:
AOM AOMAOM AIMCAFE
AIM AIM AIM OPEN 10063
SMOKE CONTROL
TOPANEL ESP GSP DHARAM CONSULTING
.
101 RP
STORAGE SERVICE CORRIDOR BELOW 240 WEST 37TH STREET, SUITE 302
SMOKE
2 3 4 10 11 12 13 104 10040 PANELS FED FROM FA FUSED CUTOUT PANEL. CORRIDOR NEW YORK, NY 10018
14
SEE POWER DRAWINGS FOR CIRCUITING 10045 TEL: 508.344.3820
15CD15CD AIM AIM
FACP
14
15CD
CODE:
FTS
1 1/2"C FOR S S S
DOOR D1-2A / D1-2B AIM AOM
ELEV #3
R NETWORK MAIN FA PANEL CODE CONSULTANTS
WIRING DOWN C.8 PROFESSIONAL ENGINEERS, PC
10075
R SC
TO CELLAR. 1 1/2"C FOR NETWORK 215 WEST 40TH STREET, 15FL
16 17
SEE FA-402. WIRING DOWN TO NEW YORK, NY 10018
1 1/2"C FOR NETWORK
CSC
3 STAIR #1 S S 30CD CENTRAL
10001 OFFICE CONSTRUCTION SPECIFICATIONS, INC
R
ELEV #1 TRANSMITTER 22 TENNENT ROAD P.O. BOX 488
LOCATE TOP OF ELEVATOR 10076 MORGANVILLE, NJ 07751
SHAFT TO ACTIVATE SHAFT TEL: 732.970.0700
LOUVER FTS
WATER PROOFING:
D.2
FTS
S S S
HENSHELL & BUCCELLATO
166 PATTERSON AVENUE
S 1 1 ELEVATOR LOBBY R ELEV #2 SHREWSBURY, NJ 07702
1
10046 10077 TEL: 732.530.4734
30CD
SERVERY KITCHEN CONSULTANT:
108 P 1
JACOB DOLAND BEER
AIM AIM AOM CONTROL RM 116 E. 27TH STREET, 2FL
.
15CD
AIM AIM AOM
6 7 5 AIM VESTIBULE
FOR FCU-1.1
.
15CD
E
V C R
M
R
H
T-984N
E
S
A
K
F LN
TIS
E A O
U
_ C
U H
S N
A
I
10044
15CD15CD ISSUES / REVISIONS:
1 NO. DATE DESCRIPTION
E.2
S
1 08/09/2013 100% DD
RECEPTION/SECURITY 16 16 01/17/2014 50% CD
152
P
F KEY PLAN:
N
P.N.
PROJECT
CORNELLNYC TECH
G FIRST ACADEMIC
BUILDING
1 MAIN STREET
ROOSEVELT ISLAND
NEW YORK, NY 10044
1 FIRE ALARM
L J
GROUND FLOOR PLAN
REFERENCE NOTES:
1 LOCATE WITHIN 5'-0" OF FIRE SMOKE DAMPER 8 FOR HOLD OPEN DOOR. LOCATE WITHIN 3'-6" OF DOOR
(SOUTH)
2 FOR "OPEN" ACTIVATION MOTORIZED OPERABLE DOOR 9 FOR HOLD OPEN DOOR
3 FOR "CLOSE" ACTIVATION MOTORIZED OPERABLE DOOR 10 FOR MOTORIZED OPERABLE DOOR "OPEN" STATUS 16 FOR ELEVATOR SHAFT LOUVER STATUS SEAL & SIGNATURE: DATE: 05-16-14
PROJECT No.: 225121
4 FOR "AUTO" ACTIVATION MOTORIZED OPERABLE DOOR 11 FOR MOTORIZED OPERABLE DOOR "CLOSED" STATUS 17 FOR ACTIVATION OF ELEVATOR SHAFT LOUVER DRAWING BY:
CHK BY: Checker
5 ACTIVATION OF FIRE SMOKE DAMPERS.. COORDINATE WITH 12 FOR MOTORIZED OPERABLE DOOR "FAULT" STATUS 18 TURNSTILE SYSTEM INTERFACE TO DROP ARMS. LOCATE WITHIN TURNSTILE
MECHANICAL DRAWINGS. DWG No.
ENCLOSURE. COORDINATE INSTALLATION WITH TURNSTILE CONTRACTOR.
CLOSED STATUS OF FIRE SMOKE DAMPERS. COORDINATE
6
WITH MECHANICAL DRAWINGS.
13 FOR MOTORIZED OPERABLE DOOR "NORMAL" STATUS
FA-404.00
7 OPEN STATUS OF FIRE SMOKE DAMPERS. COORDINATE WITH 14 FOR BMS MONITOR POINT BELOW 40F
MECHANICAL DRAWINGS. FILE No.:
8 FOR HOLD OPEN DOOR. LOCATE WITHIN 3'-6" OF DOOR 15 FOR SHUTDOWN OF LECTURE HALL SOUND SYSTEM
E D C B A
ARCHITECT:
mOrphosis
153 W. 27th Street
Suite 1200
New York, NY 10001
T: 212.675.1100
4 www.morphosis.com
OWNER:
S
A CORNELLNYC TECH
111 EIGHTH AVENUE, #302
DOOR D1-1A / D1-1B UP NEW YORK, NY 10011
STAIR #3
TEL: 212.309.9020
10005 S
FTS
SMEP/SUSTAINABILITY/ LEED/
LIGHTING EXTERIOR
ENVELOPE/ AV/ IT/ SECURITY
B ACOUSTICS/ SMART BUILDING
P
AOM AOMAOM AIM AIM AIM AIM
.
ARUP
77 WATER STREET
2 3 4 10 11 12 13 LECTURE HALL NEW YORK, NY 10005
131 TEL: 212.896.3000
P
GEOTECHNICAL:
EXIT CORRIDOR
15CD15CD P UP MUESER RUTLEDGE
10043 GENERATOR STATUS PANEL 225 W. 34TH STREET
REMOTE GENERATOR START (BELOW GSP) STAIR #6 NEW YORK, NY 10122
10007 TEL: 917.339.9300
FTS
110CD
C
P
S S ELEVATOR STATUS PANEL RPZ RM COST ESTIMATOR:
AOM AOMAOM AIMCAFE
AIM AIM AIM OPEN 10063
SMOKE CONTROL
TOPANEL ESP GSP DHARAM CONSULTING
.
101 RP
STORAGE SERVICE CORRIDOR BELOW 240 WEST 37TH STREET, SUITE 302
SMOKE
2 3 4 10 11 12 13 104 10040 PANELS FED FROM FA FUSED CUTOUT PANEL. CORRIDOR NEW YORK, NY 10018
14
SEE POWER DRAWINGS FOR CIRCUITING 10045 TEL: 508.344.3820
15CD15CD AIM AIM
FACP
14
15CD
CODE:
FTS
1 1/2"C FOR S S S
DOOR D1-2A / D1-2B AIM AOM
ELEV #3
R NETWORK MAIN FA PANEL CODE CONSULTANTS
WIRING DOWN C.8 PROFESSIONAL ENGINEERS, PC
10075
R SC
TO CELLAR. 1 1/2"C FOR NETWORK 215 WEST 40TH STREET, 15FL
16 17
SEE FA-402. WIRING DOWN TO NEW YORK, NY 10018
1 1/2"C FOR NETWORK CELLAR. SEE FA-402 S
WIRING UP TO 2ND FL.
TEL: 212.216.9596
FOR FLOOR CONTROL 110CD
D
ASSEMBLY SPECIFICATIONS:
CSC
3 STAIR #1 S S 30CD CENTRAL
10001 OFFICE CONSTRUCTION SPECIFICATIONS, INC
R
ELEV #1 TRANSMITTER 22 TENNENT ROAD P.O. BOX 488
LOCATE TOP OF ELEVATOR 10076 MORGANVILLE, NJ 07751
SHAFT TO ACTIVATE SHAFT TEL: 732.970.0700
LOUVER FTS
WATER PROOFING:
D.2
FTS
S S S
HENSHELL & BUCCELLATO
166 PATTERSON AVENUE
1 1 ELEVATOR LOBBY R ELEV #2 SHREWSBURY, NJ 07702
15CD 1
10046 10077 TEL: 732.530.4734
30CD
SERVERY KITCHEN CONSULTANT:
108 P 1
JACOB DOLAND BEER
AIM AIM AOM 30CD CONTROL RM 116 E. 27TH STREET, 2FL
.
15CD
E
V C R
M
R
H
T-984N
E
S
A
K
F LN
TIS
E A O
U
_ C
U H
S N
A
I
10044
15CD15CD ISSUES / REVISIONS:
1 NO. DATE DESCRIPTION
E.2
S
1 08/09/2013 100% DD
S RECEPTION/SECURITY 16 16 01/17/2014 50% CD
152
P
S
S
15CD 2 06/30/2014 Addendum 2
AIM AIM AOM 9 02/13/2015 Bulletin #3
15CD .
18
REF: FA-404
9 PURPOSE OF ISSUE:
STAIR #5 Lobby Speaker/strobe Mounting Type
F KEY PLAN:
N
P.N.
PROJECT
CORNELLNYC TECH
G FIRST ACADEMIC
BUILDING
1 MAIN STREET
ROOSEVELT ISLAND
NEW YORK, NY 10044
1 FIRE ALARM
L J
GROUND FLOOR PLAN
REFERENCE NOTES:
1 LOCATE WITHIN 5'-0" OF FIRE SMOKE DAMPER 8 FOR HOLD OPEN DOOR. LOCATE WITHIN 3'-6" OF DOOR
(SOUTH)
2 FOR "OPEN" ACTIVATION MOTORIZED OPERABLE DOOR 9 FOR HOLD OPEN DOOR
3 FOR "CLOSE" ACTIVATION MOTORIZED OPERABLE DOOR 10 FOR MOTORIZED OPERABLE DOOR "OPEN" STATUS 16 FOR ELEVATOR SHAFT LOUVER STATUS SEAL & SIGNATURE: DATE: 05-16-14
PROJECT No.: 225121
4 FOR "AUTO" ACTIVATION MOTORIZED OPERABLE DOOR 11 FOR MOTORIZED OPERABLE DOOR "CLOSED" STATUS 17 FOR ACTIVATION OF ELEVATOR SHAFT LOUVER DRAWING BY:
CHK BY: Checker
5 ACTIVATION OF FIRE SMOKE DAMPERS.. COORDINATE WITH 12 FOR MOTORIZED OPERABLE DOOR "FAULT" STATUS 18 TURNSTILE SYSTEM INTERFACE TO DROP ARMS. LOCATE WITHIN TURNSTILE
MECHANICAL DRAWINGS. DWG No.
ENCLOSURE. COORDINATE INSTALLATION WITH TURNSTILE CONTRACTOR.
CLOSED STATUS OF FIRE SMOKE DAMPERS. COORDINATE
6
WITH MECHANICAL DRAWINGS.
13 FOR MOTORIZED OPERABLE DOOR "NORMAL" STATUS
FA-404.00
7 OPEN STATUS OF FIRE SMOKE DAMPERS. COORDINATE WITH 14 FOR BMS MONITOR POINT BELOW 40F
MECHANICAL DRAWINGS. FILE No.:
8 FOR HOLD OPEN DOOR. LOCATE WITHIN 3'-6" OF DOOR 15 FOR SHUTDOWN OF LECTURE HALL SOUND SYSTEM
E D C B A
ARCHITECT:
mOrphosis
153 W. 27th Street
Suite 1200
New York, NY 10001
T: 212.675.1100
4 www.morphosis.com
OWNER:
S
A CORNELLNYC TECH
111 EIGHTH AVENUE, #302
DOOR D1-1A / D1-1B UP NEW YORK, NY 10011
STAIR #3
TEL: 212.309.9020
10005 S
FTS
SMEP/SUSTAINABILITY/ LEED/
LIGHTING EXTERIOR
ENVELOPE/ AV/ IT/ SECURITY
B ACOUSTICS/ SMART BUILDING
P
AOM AOMAOM AIM AIM AIM AIM
.
ARUP
77 WATER STREET
2 3 4 10 11 12 13 LECTURE HALL NEW YORK, NY 10005
131 TEL: 212.896.3000
P
GEOTECHNICAL:
EXIT CORRIDOR
15CD15CD P UP MUESER RUTLEDGE
10043 GENERATOR STATUS PANEL 225 W. 34TH STREET
REMOTE GENERATOR START (BELOW GSP) STAIR #6 NEW YORK, NY 10122
10007 TEL: 917.339.9300
FTS
110CD
C
P
S S ELEVATOR STATUS PANEL RPZ RM COST ESTIMATOR:
AOM AOMAOM AIMCAFE
AIM AIM AIM OPEN 10063
SMOKE CONTROL
TOPANEL ESP GSP DHARAM CONSULTING
.
101 RP
STORAGE SERVICE CORRIDOR BELOW 240 WEST 37TH STREET, SUITE 302
SMOKE
2 3 4 10 11 12 13 104 10040 PANELS FED FROM FA FUSED CUTOUT PANEL. CORRIDOR NEW YORK, NY 10018
14
SEE POWER DRAWINGS FOR CIRCUITING 10045 TEL: 508.344.3820
15CD15CD AIM AIM
FACP
14
15CD
CODE:
FTS
1 1/2"C FOR S S S
DOOR D1-2A / D1-2B AIM AOM
ELEV #3
R NETWORK MAIN FA PANEL CODE CONSULTANTS
WIRING DOWN C.8 PROFESSIONAL ENGINEERS, PC
10075
R SC
TO CELLAR. 1 1/2"C FOR NETWORK 215 WEST 40TH STREET, 15FL
16 17
SEE FA-402. WIRING DOWN TO NEW YORK, NY 10018
1 1/2"C FOR NETWORK CELLAR. SEE FA-402 S
WIRING UP TO 2ND FL.
TEL: 212.216.9596
FOR FLOOR CONTROL 110CD
D
ASSEMBLY SPECIFICATIONS:
CSC
3 STAIR #1 S S 30CD CENTRAL
10001 OFFICE CONSTRUCTION SPECIFICATIONS, INC
R
ELEV #1 TRANSMITTER 22 TENNENT ROAD P.O. BOX 488
LOCATE TOP OF ELEVATOR 10076 MORGANVILLE, NJ 07751
SHAFT TO ACTIVATE SHAFT TEL: 732.970.0700
LOUVER FTS
WATER PROOFING:
D.2
FTS
S S S
HENSHELL & BUCCELLATO
166 PATTERSON AVENUE
1 1 ELEVATOR LOBBY R ELEV #2 SHREWSBURY, NJ 07702
15CD 1
10046 10077 TEL: 732.530.4734
30CD
SERVERY KITCHEN CONSULTANT:
108 P 1
JACOB DOLAND BEER
AIM AIM AOM 30CD CONTROL RM 116 E. 27TH STREET, 2FL
.
15CD
E
V C R
M
R
H
T-984N
E
S
A
K
F LN
TIS
E A O
U
_ C
U H
S N
A
I
10044
15CD15CD ISSUES / REVISIONS:
1 NO. DATE DESCRIPTION
E.2
S
1
FAAP
S
S S
15CD
6 7 5 AOM
2 3 4 10 11 12 13
AOM 18
AOM 18
AOM AOMAOM AIM AIM AIM AIM
.
18
9 KEY PLAN:
2 3 4 10 11 12 13 STAIR #5
10003 8 AOM
MAIN LOUNGE K
121
MAIN LOBBY
2 WOMEN 8 10047
9
10021
AOM
MEN
DOOR D1-3C / D1-3D 10020
N
Cornell Bloomberg Center Job # 225121
CORNELLNYC TECH
H FIRST ACADEMIC
BUILDING
1 MAIN STREET
ROOSEVELT ISLAND
NEW YORK, NY 10044
1 FIRE ALARM
L J
GROUND FLOOR PLAN
REFERENCE NOTES:
1 LOCATE WITHIN 5'-0" OF FIRE SMOKE DAMPER 8 FOR HOLD OPEN DOOR. LOCATE WITHIN 3'-6" OF DOOR
(SOUTH)
2 FOR "OPEN" ACTIVATION MOTORIZED OPERABLE DOOR 9 FOR HOLD OPEN DOOR
3 FOR "CLOSE" ACTIVATION MOTORIZED OPERABLE DOOR 10 FOR MOTORIZED OPERABLE DOOR "OPEN" STATUS 16 FOR ELEVATOR SHAFT LOUVER STATUS SEAL & SIGNATURE: DATE: 07-15-14
PROJECT No.: 225121
4 FOR "AUTO" ACTIVATION MOTORIZED OPERABLE DOOR 11 FOR MOTORIZED OPERABLE DOOR "CLOSED" STATUS 17 FOR ACTIVATION OF ELEVATOR SHAFT LOUVER DRAWING BY:
CHK BY:
5 ACTIVATION OF FIRE SMOKE DAMPERS.. COORDINATE WITH 12 FOR MOTORIZED OPERABLE DOOR "FAULT" STATUS 18 TURNSTILE SYSTEM INTERFACE TO DROP ARMS.
MECHANICAL DRAWINGS. DWG No.
LOCATE WITHIN TURNSTILE ENCLOSURE.
CLOSED STATUS OF FIRE SMOKE DAMPERS. COORDINATE
6
WITH MECHANICAL DRAWINGS.
13 FOR MOTORIZED OPERABLE DOOR "NORMAL" STATUS
FA-404.00
7 OPEN STATUS OF FIRE SMOKE DAMPERS. COORDINATE WITH 14 FOR BMS MONITOR POINT BELOW 40F
MECHANICAL DRAWINGS. FILE No.:
8 FOR HOLD OPEN DOOR. LOCATE WITHIN 3'-6" OF DOOR 15 FOR SHUTDOWN OF LECTURE HALL SOUND SYSTEM
E D C B A
1 2 3 3.6 4 4.6 5 6 7 8
ARCHITECT:
mOrphosis
153 W. 27th Street
Suite 1200
New York, NY 10001
T: 212.675.1100
4 www.morphosis.com
OWNER:
S
A CORNELLNYC TECH
111 EIGHTH AVENUE, #302
DOOR D1-1A / D1-1B NEW YORK, NY 10011
STAIR #3
TEL: 212.309.9020
10005 S
FTS
SMEP/SUSTAINABILITY/ LEED/
LIGHTING EXTERIOR
ENVELOPE/ AV/ IT/ SECURITY
B ACOUSTICS/ SMART BUILDING
P
AOM AOMAOM AIM AIM AIM AIM
.
ARUP
77 WATER STREET
2 3 4 10 11 12 13 LECTURE HALL NEW YORK, NY 10005
131 TEL: 212.896.3000
P
GEOTECHNICAL:
FTS
SERVICE CORRIDOR 110CD
C
P
10040 S S ELEVATOR STATUS PANEL RPZ RM COST ESTIMATOR:
AOM AOMAOM AIMCAFE
AIM AIM AIM OPEN 10063
EXIT CORRIDOR SMOKE CONTROL
TOPANEL ESP GSP DHARAM CONSULTING
.
101 10043 RP
BELOW 2 240 WEST 37TH STREET, SUITE 302
SMOKE
2 3 4 10 11 12 13 PANELS FED FROM FA FUSED CUTOUT PANEL. CORRIDOR NEW YORK, NY 10018
14
SEE POWER DRAWINGS FOR CIRCUITING 10045 TEL: 508.344.3820
15CD15CD AIM AIM
FACP
14
15CD
CODE:
FTS
S S S
DOOR D1-2A / D1-2B AIM AOM R MAIN FA PANEL CODE CONSULTANTS
ELEV #3
10075
R C.8 PROFESSIONAL ENGINEERS, PC
SC 1 1/2"C FOR NETWORK 215 WEST 40TH STREET, 15FL
16 17 2 WIRING DOWN TO NEW YORK, NY 10018
1 1/2"C FOR NETWORK CELLAR. SEE FA-402 S 9
WIRING UP TO 2ND FL.
TEL: 212.216.9596
FOR FLOOR CONTROL 110CD
D
ASSEMBLY SPECIFICATIONS:
CSC
3 STAIR #1 S S 30CD
10001 CONSTRUCTION SPECIFICATIONS, INC
R 22 TENNENT ROAD P.O. BOX 488
ELEV #1
LOCATE TOP OF ELEVATOR 10076 MORGANVILLE, NJ 07751
FACP
SHAFT TO ACTIVATE SHAFT TEL: 732.970.0700
LOUVER FTS
WATER PROOFING:
D.2
FTS
S S S
HENSHELL & BUCCELLATO
1 1/2"C FOR NETWORK WIRING 166 PATTERSON AVENUE
1 1 DOWN TO CELLAR. SEE FA-402. ELEVATOR LOBBY R ELEV #2 1 1 SHREWSBURY, NJ 07702
15CD 1
10046 10077 TEL: 732.530.4734
9 30CD
SERVERY KITCHEN CONSULTANT:
108 P 1
JACOB DOLAND BEER
.
15CD
10044 E
15CD15CD ISSUES / REVISIONS:
1 NO. DATE DESCRIPTION
E.2
S
1 08/09/2013 100% DD
S RECEPTION/SECURITY 16 16 01/17/2014 50% CD
152 FAAP 05/16/2014 100% CD
S
S S
15CD 2 06/30/2014 Addendum 2
10
15CD
AIM AIM AOM
.
9 02/13/2015 Bulletin #3
AOM AOMAOM AIM AIM AIM AIM
10 05/15/2015 Bulletin #4
DOOR D1-3A / D1-3B
.
6 7 5
2 3 4 10 11 12 13
9
STAIR #5
F KEY PLAN:
APPROVED
N
P.N.
PROJECT
1 FIRE ALARM
L J
GROUND FLOOR PLAN
REFERENCE NOTES:
1 LOCATE WITHIN 5'-0" OF FIRE SMOKE DAMPER 8 FOR HOLD OPEN DOOR. LOCATE WITHIN 3'-6" OF DOOR
A1 SCALE 1/8" = 1'-0" (SOUTH)
2 FOR "OPEN" ACTIVATION MOTORIZED OPERABLE DOOR 9 FOR HOLD OPEN DOOR
3 FOR "CLOSE" ACTIVATION MOTORIZED OPERABLE DOOR 10 FOR MOTORIZED OPERABLE DOOR "OPEN" STATUS 16 FOR ELEVATOR SHAFT LOUVER STATUS SEAL & SIGNATURE: DATE: 05-16-14
PROJECT No.: 225121
4 FOR "AUTO" ACTIVATION MOTORIZED OPERABLE DOOR 11 FOR MOTORIZED OPERABLE DOOR "CLOSED" STATUS 17 FOR ACTIVATION OF ELEVATOR SHAFT LOUVER DRAWING BY:
CHK BY: Checker
5 ACTIVATION OF FIRE SMOKE DAMPERS.. COORDINATE WITH 12 FOR MOTORIZED OPERABLE DOOR "FAULT" STATUS
MECHANICAL DRAWINGS. DWG No.
CLOSED STATUS OF FIRE SMOKE DAMPERS. COORDINATE
9
6
WITH MECHANICAL DRAWINGS.
13 FOR MOTORIZED OPERABLE DOOR "NORMAL" STATUS
FA-404.00
7 OPEN STATUS OF FIRE SMOKE DAMPERS. COORDINATE WITH 14 FOR BMS MONITOR POINT BELOW 40F
MECHANICAL DRAWINGS. FILE No.:
8 FOR HOLD OPEN DOOR. LOCATE WITHIN 3'-6" OF DOOR 15 FOR SHUTDOWN OF LECTURE HALL SOUND SYSTEM
ASI-377 - SKA-304.1 - Relocate FA Device in Master Studio
E D C B A
4 www.morphosis.com
OWNER:
A
S CORNELLNYC TECH
15CD
111 EIGHTH AVENUE, #302
S S S S
LOCKER RM MASTERS STUDIO NEW YORK, NY 10011
185 191
TEL: 212.309.9020
SMEP/SUSTAINABILITY/ LEED/
B LIGHTING EXTERIOR
QUIET RM ENVELOPE/ AV/ IT/ SECURITY
15CD 15CD 197 ACOUSTICS/ SMART BUILDING
15CD
SEMINAR RM SEMINAR RM 15CD
161 165 K ARUP
77 WATER STREET
NEW YORK, NY 10005
TEL: 212.896.3000
GEOTECHNICAL:
15CD
15CD 15CD MUESER RUTLEDGE
225 W. 34TH STREET
C NEW YORK, NY 10122
S
S
15CD TEL: 917.339.9300
30CD
S S S S
RPZ RM
10063 15CD
COST ESTIMATOR:
15CD 15CD
DHARAM CONSULTING
STORAGE 240 WEST 37TH STREET, SUITE 302
STORAGE RPZ RM 2"C FOR FIRE
AIM 163 NEW YORK, NY 10018
167 10064 ALARM UP TO
14 TEL: 508.344.3820
15CD
PENTHOUSE
15CD
15CD
D TEL: 212.216.9596
CSC
30CD ELEC RM
TEL RM SPECIFICATIONS:
WOMEN 10068
3 164 15CD
10026
15 9 CONSTRUCTION SPECIFICATIONS, INC
AIM AIM AOM
22 TENNENT ROAD P.O. BOX 488
STAIR #2
.
MORGANVILLE, NJ 07751
AOM 10008 TEL: 732.970.0700
15CD
6 7 5
P
HUDDLE RM 15CD D.2
WATER PROOFING:
FTS
1 172
15CD
V
T-984N
K
A
H
M
S
R
E
C
F R
E
TIS
LN
U
A
_ C
U
O
S N
A
H
I V
T-984N
K
A
H
M
S
R
E
C
F R
E
TIS
LN
U
A
_ C
U
O
S N
A
H
I V
T-984N
K
A
H
M
S
R
E
C R
F E
TIS
LN
U
A
_ C
U
O
S N
A
H
I
P
166 PATTERSON AVENUE
MEN SHREWSBURY, NJ 07702
10028 15CD TEL: 732.530.4734
30CD
MAIN FIRE ALARM AIM AIM AOM HUDDLE RM 15CD
1 9 KITCHEN CONSULTANT:
DISCONNECT SWITCH .
170
15CD JACOB DOLAND BEER
6 7 5
AOM 116 E. 27TH STREET, 2FL
15CD
AIM AIM AOM 8 NEW YORK, NY 10016
.
9 02/13/2015 Bulletin #3
13 12 11 10 4 3 2 2 3 VESTIBULE
4 10 11 12 13
10048
AIM AIM AIM AIM AOM AOM AOM AOM AOMAOM AIM AIM AIM AIM
. .
MAIN DISCONNECT
10070
13 12 11 10 4 3 2 2 3 4 10 11 12 13 JANITOR
10065
15CD
F
KEY PLAN:
N
P.N.
G CORNELLNYC TECH
FIRST ACADEMIC
BUILDING
1 MAIN STREET
ROOSEVELT ISLAND
NEW YORK, NY 10044
1 FIRE ALARM
REFERENCE NOTES: GROUND FLOOR PLAN
1 LOCATE WITHIN 5'-0" OF FIRE SMOKE DAMPER 9 FOR FIBER OPTIC CABLE TO CUP BUILDING A1 SCALE 1/8" = 1'-0" (NORTH)
2 FOR "OPEN" ACTIVATION MOTORIZED OPERABLE DOOR 10 FOR MOTORIZED OPERABLE DOOR "OPEN" STATUS 16 ANNUNCIATOR PANEL FOR FIRE ALARM NOTIFICATIONS
FROM CUP. SITE CONTRACTOR TO PROVIDE 9
3 FOR "CLOSED" ACTIVATION MOTORIZED OPERABLE DOOR 11 FOR MOTORIZED OPERABLE DOOR "CLOSED" STATUS ANNUNCIATOR PANEL AND ALL NETWORK CABLING FOR
IT. FAB CONTRACTOR TO INSTALL PANEL AND PROVIDE SEAL & SIGNATURE: DATE: 05-16-14
CONDUIT FROM PANEL TO FAB PROPERTY LINE. SEE FA- PROJECT No.: 225121
4 FOR "AUTO" ACTIVATION MOTORIZED OPERABLE DOOR 12 FOR MOTORIZED OPERABLE DOOR "FAULT" STATUS
403 FOR CONDUIT SCOPE DELINIATION. PANEL
DRAWING BY:
POWERED BY FUSED CUT-OUT IN PENTHOUSE. SEE
5 ACTIVATION OF FIRE SMOKE DAMPERS. COORDINATE 13 FOR MOTORIZED OPERABLE DOOR "NORMAL" STATUS POWER DRAWINGS FOR CIRCUITING. CHK BY: Checker
WITH MECHANICAL DRAWINGS.
DWG No.
6 CLOSED STATUS OF FIRE SMOKE DAMPERS. COORDINATE
14 FOR SHUTDOWN OF FUEL OIL PUMPS
9
7
WITH MECHANICAL DRAWINGS.
OPEN STATUS OF FIRE SMOKE DAMPERS. COORDINATE
FA-405.00
15 FOR AUTOMATIC ROLLUP OF BLACKOUT/SUNSHADES.
WITH MECHANICAL DRAWINGS.
LOCATE WITHIN 3'-0" OF SHADE SYSTEM GATEWAY.
FILE No.:
8 FOR MONITORING OF FIRE ALARM DISCONNECT SWITCH
E D C B A
ARCHITECT:
mOrphosis
153 W. 27th Street
During a fire alarm condition, fire alarm system to signal all shades Suite 1200
New York, NY 10001
to roll-up as noted in sequence of operations. If a fire alarm
T: 212.675.1100
condition occurs during a power outage, these modules shall allow
for shades on generator power to maintain this roll-up operation. www.morphosis.com
4
Coordinate switch interface with shade contractor. S
OWNER:
TYPICAL FOR EACH SMOKE STAIR #6
CONTROL OPERABLE WINDOW. 20007 A
TYPICAL FOR WINDOWS: CORNELLNYC TECH
TYPICAL FOR WINDOWS:
FTS
P
-2.5 111 EIGHTH AVENUE, #302
-2.1
-2.6 AOM
NEW YORK, NY 10011
-2.2
-2.7
.
SMEP/SUSTAINABILITY/ LEED/
LIGHTING EXTERIOR
AOM AOMAOM AIM AIM AIM AIM B ENVELOPE/ AV/ IT/ SECURITY
110CD
.
2 3 4 8 9 10 11 ARUP
77 WATER STREET
CONFERENCE RM 2 3 4 8 9 10 11 NEW YORK, NY 10005
201 TEL: 212.896.3000
GEOTECHNICAL:
MUESER RUTLEDGE
S
OFFICE ZONE A
110CD
STAIR #3
FTS
225 W. 34TH STREET
231 20005 NEW YORK, NY 10122
C TEL: 917.339.9300
110CD
110CD
S P
COST ESTIMATOR:
OPEN
READING LIBRARY TO READING LIBRARY DHARAM CONSULTING
S
235 BELOW 240 WEST 37TH STREET, SUITE 302
MULTIPURPOSE RM
NEW YORK, NY 10018
TEL: 508.344.3820
205
CODE:
SC
CORRIDOR
SC SC SC SC C.8 CODE CONSULTANTS
20041
PROFESSIONAL ENGINEERS, PC
215 WEST 40TH STREET, 15FL
P S S
NEW YORK, NY 10018
D TEL: 212.216.9596
FTS
FOR FLOOR CONTROL
CONNECT TO DEDICATED
ASSEMBLY SPECIFICATIONS:
3 STAIR RISER SPEAKER CIRCUIT
STAIR #1 TEL RM ELEC RM COLLAB. AREA
20001 R CONSTRUCTION SPECIFICATIONS, INC
236 20065 240 ELEV #1
S
22 TENNENT ROAD P.O. BOX 488
15CD 20076 MORGANVILLE, NJ 07751
SWING SPACE 15CD TEL: 732.970.0700
209 30CD
FTS
1 1/2"C FOR NETWORK D.2 WATER PROOFING:
WIRING UP/DOWN
HENSHELL & BUCCELLATO
COLLAB. AREA CONFERENCE RM
R
ELEV #2 166 PATTERSON AVENUE
208 1 238 30CD 20077 SHREWSBURY, NJ 07702
1 TEL: 732.530.4734
AIM AIM AOM
OPEN
.
15CD
HUDDLE RM AIM AIM AOM
OFFICE ZONE C 240A 1 116 E. 27TH STREET, 2FL
S 212 .
15CD
HUDDLE RM
214 TEL: 212.206.0736
6 7 5
E
15CD
HUDDLE RM
216 ISSUES / REVISIONS:
15CD
S
HUDDLE RM 30CD 1 E.2 NO. DATE DESCRIPTION
218
08/09/2013 100% DD
15CD
HUDDLE RM HUDDLE RM HUDDLE RM
01/17/2014 50% CD
220 252 254
15CD
HUDDLE RM
05/16/2014 100% CD
15CD
2 06/30/2014 Addendum 2
15CD
15CD
9 02/13/2015 Bulletin #3
12 11/25/2015 Bulletin #6
S
24 Date 31 shade temp
OPEN
TO
15C
D
HUDDLE RM
2 255
WP
D
110C
HUB LOUNGE
251
13
F
13
KEY PLAN:
AOM AOM
12 12
STAIR #5
20003
FOR FCU-2.3
Cornell Bloomberg Center
H
Job # 225121
REF: FA-406
S
PURPOSE OF ISSUE: Fire Alarm Shade Interface
N
P.N.
PREPARED BY: KS CHECKED BY: KS
S
PROJECT
ESK-CA-063.9
CORNELLNYC TECH
DATE: 03-06-2017
G
FIRST ACADEMIC
SCALE: NTS BUILDING
1 MAIN STREET
ROOSEVELT ISLAND
ORIGINAL PAPER SIZE: NEW YORK, NY 10044
1 L J FIRE ALARM
SECOND FLOOR PLAN
REFERENCE NOTES: (SOUTH)
1 LOCATE WITHIN 5'-0" OF FIRE SMOKE DAMPER 8 FOR MOTORIZED OPERABLE WINDOW "OPEN" STATUS 14 FOR AUTOMATIC ROLLUP OF SHADES FED FROM LRRP
PANEL. MODULE TO INTERFACE DIRECTLY WITH
2 FOR "OPEN" ACTIVATION MOTORIZED OPERABLE WINDOW 9 FOR MOTORIZED OPERABLE WINDOW "CLOSE" STATUS SYSTEM SWITCHES FOR LOCAL CONTROL. LOCATE
WITHIN 3'-0" OF SHADE SYSTEM SWITCH. SEAL & SIGNATURE: DATE: 05-16-14
PROJECT No.: 225121
3 FOR "CLOSE" ACTIVATION MOTORIZED OPERABLE WINDOW 10 FOR MOTORIZED OPERABLE WINDOW "FAULT" STATUS
DRAWING BY:
4 FOR "AUTO" ACTIVATION MOTORIZED OPERABLE WINDOW 11 FOR MOTORIZED OPERABLE WINDOW "NORMAL" STATUS CHK BY: Checker
DWG No.
5 ACTIVATION OF FIRE SMOKE DAMPERS. COORDINATE 12 FOR HOLD OPEN DOORS.
WITH MECHANICAL DRAWINGS.
CLOSED STATUS OF FIRE SMOKE DAMPERS. COORDINATE 13 FOR HOLD OPEN DOOR. LOCATE WITHIN 3'-0'' OF DOOR
FA-406.00
6
WITH MECHANICAL DRAWINGS.
FILE No.:
7 OPEN STATUS OF FIRE SMOKE DAMPERS. COORDINATE WITH
MECHANICAL DRAWINGS.
E D C B A
TEL: 212.309.9020
2 3 4 8 9 10 11
SMEP/SUSTAINABILITY/ LEED/
LIGHTING EXTERIOR
B ENVELOPE/ AV/ IT/ SECURITY
ACOUSTICS/ SMART BUILDING
OFFICE ZONE B
283
K ARUP
77 WATER STREET
NEW YORK, NY 10005
TEL: 212.896.3000
GEOTECHNICAL:
MUESER RUTLEDGE
STAIR #3 225 W. 34TH STREET
NEW YORK, NY 10122
C TEL: 917.339.9300
15CD
15CD
AOM
14 HUDDLE RM HUDDLE RM HUDDLE RM HUDDLE RM COST ESTIMATOR:
STAIR #7 289
13 13 287 291 293
READING LIBRARY 20010
SC
DHARAM CONSULTING
AOM
281 240 WEST 37TH STREET, SUITE 302
14 NEW YORK, NY 10018
FIRE ALARM
15CD
15CD
CONDUITS UP TO TEL: 508.344.3820
PENTHOUSE SWING SPACE
295
CODE:
SC CORRIDOR SC AIM AIM AOM
SC SC C.8 CODE CONSULTANTS
1 1/2"C FOR 20050
NETWORK PROFESSIONAL ENGINEERS, PC
.
15CD
30CD
ELEC. CL.
15CD
D TEL: 212.216.9596
FTS
20070
15CD
OFFICE SPECIFICATIONS:
3 WOMEN STORAGE COLLAB. AREA 277
12 TEL RM ELEC RM
20026 276 274 CONSTRUCTION SPECIFICATIONS, INC
S
282 20068 22 TENNENT ROAD P.O. BOX 488
AIM AIM AOM
AOM .
STAIR #2 MORGANVILLE, NJ 07751
20008 TEL: 732.970.0700
15CD 1
6 7 5
HUDDLE RM D.2 WATER PROOFING:
S
V
T-984N
K
A
H
M
S
R
E
F
C R
E
TIS
LN
U
A
_ U
O
C
S N
A
H
I V
T-984N
K
A
H
M
S
R
E
F
C R
E
TIS
LN
U
A
_ U
O
C
S N
A
H
I V
T-984N
K
A
H
M
S
R
E
F
C R
E
TIS
LN
U
A
_ U
O
C
S N
A
H
I
C
V
T-984N
K
A
H
M
S
R
E
F R
E
TIS
LN
U
A
_ C
U
O
S N
A
H
I
JANITOR 270
15CD 20069 HENSHELL & BUCCELLATO
HUDDLE RM CONFERENCE RM 166 PATTERSON AVENUE
MEN 268 S 275 SHREWSBURY, NJ 07702
20028 TEL: 732.530.4734
15CD
15C
HUDDLE RM
D
15C
D
15C
TEL: 212.206.0736
15C
.
HUDDLE RM
D
262 HUDDLE RM E
15C
6 7 5 271
D
HUDDLE RM
15C
267
ISSUES / REVISIONS:
D
HUDDLE RM
15C
D
HUDDLE RM 260
D
01/17/2014 50% CD
254
HUDDLE RM 05/16/2014 100% CD
15C
HUDDLE RM
265
D
15CD
S
HUDDLE RM
263 9 02/13/2015 Bulletin #3
15C
HUDDLE RM
15C
261
D
HUDDLE RM
259
15C
D
257
D
HUDDLE RM
2 255
F
KEY PLAN:
REF: FA-407
PURPOSE OF ISSUE: Fire Alarm Shade Interface
N
P.N.
PREPARED BY: KS CHECKED BY: KS
ESK-CA-063.10 PROJECT
DATE: 03-06-2017
G
CORNELLNYC TECH
FIRST ACADEMIC
SCALE: NTS BUILDING
1 MAIN STREET
ORIGINAL PAPER SIZE: ROOSEVELT ISLAND
NEW YORK, NY 10044
1 FIRE ALARM
SECOND FLOOR PLAN
REFERENCE NOTES: (NORTH)
1 LOCATE WITHIN 5'-0" OF FIRE SMOKE DAMPER 8 FOR MOTORIZED OPERABLE WINDOW "OPEN" STATUS 15 FOR AUTOMATIC ROLLUP OF SHADES FED FROM LRRP
PANEL. MODULE TO INTERFACE DIRECTLY WITH SYSTEM
2 FOR OPEN STATUS OF MOTORIZED OPERABLE WINDOW 9 FOR MOTORIZED OPERABLE WINDOW "CLOSED" STATUS SWITCHES FOR LOCAL CONTROL. LOCATE WITHIN 3'-0" OF
SHADE SYSTEM SWITCH. SEAL & SIGNATURE: DATE: 05-16-14
3 FOR CLOSED STATUS OF MOTORIZED OPERABLE WINDOW 10 FOR MOTORIZED OPERABLE WINDOW "FAULT" STATUS PROJECT No.: 225121
DRAWING BY:
4 FOR ACTIVATION OF MOTORIZED OPERABLE WINDOW 11 FOR MOTORIZED OPERABLE WINDOW "NORMAL" STATUS
CHK BY: Checker
5 ACTIVATION OF FIRE SMOKE DAMPERS. COORDINATE 12 FOR AUTOMATIC ROLLUP OF BLACKOUT SHADES. LOCATE DWG No.
WITH MECHANICAL DRAWINGS. WITHIN 3'-3" OF SHADE SYSTEM GATEWAY
6 CLOSED STATUS OF FIRE SMOKE DAMPERS. COORDINATE FA-407.00
WITH MECHANICAL DRAWINGS. 13 FOR HOLD OPEN DOORS. LOCATE WITHIN 3'-6'' OF DOOR
7 OPEN STATUS OF FIRE SMOKE DAMPERS. COORDINATE FILE No.:
WITH MECHANICAL DRAWINGS. 14 FOR HOLD OPEN DOORS
E D C B A
ARCHITECT:
mOrphosis
During a fire alarm condition, fire alarm system to signal all shades 153 W. 27th Street
Suite 1200
to roll-up as noted in sequence of operations. If a fire alarm New York, NY 10001
condition occurs during a power outage, these modules shall allow T: 212.675.1100
for shades on generator power to maintain this roll-up operation.
4 Coordinate switch interface with shade contractor. www.morphosis.com
P
-3.1 111 EIGHTH AVENUE, #302
AOM
-3.2 .
NEW YORK, NY 10011
-3.3 TYPICAL FOR WINDOWS: TEL: 212.309.9020
-3.4 -3.5
12 -3.6
-3.7
-3.8 SMEP/SUSTAINABILITY/ LEED/
LIGHTING EXTERIOR
B ENVELOPE/ AV/ IT/ SECURITY
S
AOM AOMAOM AIM AIM AIM AIM
110CD
.
2 3 4 8 9 10 11 ARUP
CONFERENCE RM OFFICE ZONE A 2 3 4 8 9 10 11 77 WATER STREET
301 331 NEW YORK, NY 10005
TEL: 212.896.3000
GEOTECHNICAL:
MUESER RUTLEDGE
STAIR #3
110CD
FTS
225 W. 34TH STREET
30005 NEW YORK, NY 10122
C TEL: 917.339.9300
110CD
P
B
COST ESTIMATOR:
30CD OPEN
OPEN COLLAB. AREA OPEN TO DHARAM CONSULTING
TO TO 240 WEST 37TH STREET, SUITE 302
335 BELOW
BELOW BELOW NEW YORK, NY 10018
MURAL RM
OPEN TEL: 508.344.3820
305 1 1/2"C FOR NETWORK WIRING
TO
BELOW
CODE:
SC CORRIDOR C.8
SC SC SC CODE CONSULTANTS
30041 PROFESSIONAL ENGINEERS, PC
215 WEST 40TH STREET, 15FL
R P S S
NEW YORK, NY 10018
D TEL: 212.216.9596
FTS
FOR FLOOR CONTROL
ASSEMBLY
SPECIFICATIONS:
3 STAIR #1 TEL RM 15CD ELEC RM COLLAB. AREA R ELEV #1
30001 CONSTRUCTION SPECIFICATIONS, INC
336 30065 340 30076 22 TENNENT ROAD P.O. BOX 488
15CD
FED FROM FA FUSED CUTOUT PANEL MORGANVILLE, NJ 07751
SEE POWER DRAWINGS FOR CIRCUITING. TEL: 732.970.0700
DGP
SWING SPACE
309
AIM AIM AOM D.2 WATER PROOFING:
FTS
.
15CD
HUDDLE RM KITCHEN CONSULTANT:
310
PANTRY
15CD
HUDDLE RM AIM AIM AOM JACOB DOLAND BEER
OFFICE ZONE C 340A 116 E. 27TH STREET, 2FL
S 312
.
15CD
315 HUDDLE RM AIM AIM AOM
NEW YORK, NY 10016
1
314 6 7 5 .
TEL: 212.206.0736
E
15CD
HUDDLE RM
316 6 7 5
15CD
ISSUES / REVISIONS:
S HUDDLE RM E.2 NO. DATE DESCRIPTION
318 1
08/09/2013 100% DD
15CD
30CD
HUDDLE RM HUDDLE RM HUDDLE RM
01/17/2014 50% CD
320 352 354
15CD
HUDDLE RM 05/16/2014 100% CD
15CD
2 06/30/2014 Addendum 2
15CD
15CD
9 02/13/2015 Bulletin #3
24 Date 31 shade temp
15C
321 OPEN
D
TO
HUDDLE RM
BELOW
2 355
HUB LOUNGE
351
F
KEY PLAN:
STAIR #5
30003
FOR FCU-3.3
REF: FA-408
S
PURPOSE OF ISSUE: Fire Alarm Shade Interface
N
P.N.
PREPARED BY: KS CHECKED BY: KS
S
ESK-CA-063.11 PROJECT
DATE: 03-06-2017
G
CORNELLNYC TECH
FIRST ACADEMIC
SCALE: NTS BUILDING
1 MAIN STREET
ORIGINAL PAPER SIZE: ROOSEVELT ISLAND
NEW YORK, NY 10044
1 L J FIRE ALARM
THIRD FLOOR PLAN
REFERENCE NOTES:
1 LOCATE WITHIN 5'-0" OF FIRE SMOKE DAMPER
(SOUTH)
2 FOR "OPEN" ACTIVATION MOTORIZED OPERABLE WINDOW 8 FOR MOTORIZED OPERABLE WINDOW "OPEN" STATUS
3 FOR "CLOSE" ACTIVATION MOTORIZED OPERABLE WINDOW 9 SEAL & SIGNATURE: DATE: 05-16-14
FOR MOTORIZED OPERABLE WINDOW "CLOSE" STATUS
PROJECT No.: 225121
4 FOR "AUTO" ACTIVATION MOTORIZED OPERABLE WINDOW 10 FOR MOTORIZED OPERABLE WINDOW "FAULT" STATUS DRAWING BY:
CHK BY: Checker
5 ACTIVATION OF FIRE SMOKE DAMPERS. COORDINATE WITH 11 FOR MOTORIZED OPERABLE WINDOW "NORMAL" STATUS
MECHANICAL DRAWINGS. DWG No.
CLOSED STATUS OF FIRE SMOKE DAMPERS. COORDINATE
6
WITH MECHANICAL DRAWINGS.
12 FOR AUTOMATIC ROLLUP OF SHADES FED FROM LRRP
PANEL. MODULE TO INTERFACE DIRECTLY WITH SYSTEM
FA-408.00
7 OPEN STATUS OF FIRE SMOKE DAMPERS. COORDINATE WITH SWITCHES FOR LOCAL CONTROL. LOCATE WITHIN 3'-0" OF
MECHANICAL DRAWINGS. SHADE SYSTEM SWITCH. FILE No.:
E D C B A
During a fire alarm condition, fire alarm system to signal all shades
to roll-up as noted in sequence of operations. If a fire alarm ARCHITECT:
condition occurs during a power outage, these modules shall allow mOrphosis
for shades on generator power to maintain this roll-up operation. TYPICAL FOR EACH SMOKE 153 W. 27th Street
CONTROL OPERABLE WINDOW. Suite 1200
TYPICAL FOR WINDOWS: Coordinate switch interface with shade contractor. TYPICAL FOR WINDOWS: New York, NY 10001
-3.9 -3.13
-3.10 AOM -3.14 T: 212.675.1100
-3.11 -3.15
.
-3.12 -3.16
4 12 www.morphosis.com
OWNER:
FTS
AOM AOMAOM AIM AIM AIM AIM AOM AOMAOM AIM AIM AIM AIM A
.
S S S S S S
.
CORNELLNYC TECH
P 111 EIGHTH AVENUE, #302
2 3 4 8 9 10 11 2 3 4 8 9 10 11 NEW YORK, NY 10011
TEL: 212.309.9020
CONFERENCE RM
398
SMEP/SUSTAINABILITY/ LEED/
LIGHTING EXTERIOR
B ENVELOPE/ AV/ IT/ SECURITY
ACOUSTICS/ SMART BUILDING
OFFICE ZONE B
383
K ARUP
77 WATER STREET
NEW YORK, NY 10005
TEL: 212.896.3000
CONFERENCE RM
397 GEOTECHNICAL:
MUESER RUTLEDGE
110CD
225 W. 34TH STREET
NEW YORK, NY 10122
C TEL: 917.339.9300
CODE:
FED FROM FA FUSED CUTOUT
CORRIDOR SC PANEL CKT#6. SEE E-906 FOR SC SC SC C.8 CODE CONSULTANTS
30050 PANEL SCHEDULE. PROFESSIONAL ENGINEERS, PC
1 215 WEST 40TH STREET, 15FL
S S S P S
NEW YORK, NY 10018
ELEC. CL.
30CD
15CD
15CD
15CD
D TEL: 212.216.9596
FTS
30070 AIM AIM AOM
HUDDLE RM SPECIFICATIONS:
.
382 30068 PENTHOUSE COLLAB. AREA 22 TENNENT ROAD P.O. BOX 488
374 STAIR #2 MORGANVILLE, NJ 07751
15CD
30008 TEL: 732.970.0700
1
HUDDLE RM D.2 WATER PROOFING:
V
T-984N
K
A
H
M
S
R
E
F
C R
E
TIS
LN
U
A
_ U
O
C
S N
A
H
I V
T-984N
K
A
H
M
S
R
E
F
C R
E
TIS
LN
U
A
_ U
O
C
S N
A
H
I V
T-984N
K
A
H
M
S
R
E
F
C R
E
TIS
LN
U
A
_ U
O
C
S N
A
H
I
C
V
T-984N
K
A
H
M
S
R
E
F R
E
TIS
LN
U
A
_ C
U
O
S N
A
H
I
JANITOR 370 S
15C
CONFERENCE RM 166 PATTERSON AVENUE
D
368 375 SHREWSBURY, NJ 07702
MEN
30C
15CD TEL: 732.530.4734
D
30028 15CD
15C
15C
D
HUDDLE RM
15C
.
D
362 HUDDLE RM E
15C
6 7 5 371
D
HUDDLE RM
15C
367
ISSUES / REVISIONS:
D
08/09/2013 100% DD
15C
HUDDLE RM
D
D
365
D
15CD
HUDDLE RM
S
363 9 02/13/2015 Bulletin #3
15C
HUDDLE RM
15C
361
D
HUDDLE RM
359
15C
D
357
D
HUDDLE RM
2 355
F
KEY PLAN:
REF: FA-409
PURPOSE OF ISSUE: Fire Alarm Shade Interface
N
PREPARED BY: KS P.N. KS
CHECKED BY:
ESK-CA-063.12 PROJECT
1 FIRE ALARM
THIRD FLOOR PLAN
REFERENCE NOTES:
1 8
(NORTH)
LOCATE WITHIN 5'-0" OF FIRE SMOKE DAMPER FOR MOTORIZED OPERABLE WINDOW "OPEN" STATUS
2 FOR OPEN STATUS OF MOTORIZED OPERABLE WINDOW 9 FOR MOTORIZED OPERABLE WINDOW "CLOSE" STATUS
3 10 FOR MOTORIZED OPERABLE WINDOW "FAULT" STATUS SEAL & SIGNATURE: DATE: 05-16-14
FOR CLOSED STATUS OF MOTORIZED OPERABLE WINDOW
PROJECT No.: 225121
4 FOR ACTIVATION OF MOTORIZED OPERABLE WINDOW 11 FOR MOTORIZED OPERABLE WINDOW "NORMAL" STATUS DRAWING BY:
CHK BY: Checker
5 ACTIVATION OF FIRE SMOKE DAMPERS. COORDINATE WITH 12 FOR AUTOMATIC ROLLUP OF SHADES FED FROM LRRP
MECHANICAL DRAWINGS. DWG No.
PANEL. MODULE TO INTERFACE DIRECTLY WITH
6 CLOSED STATUS OF FIRE SMOKE DAMPERS. COORDINATE WITH
MECHANICAL DRAWINGS.
SYSTEM SWITCHES FOR LOCAL CONTROL. LOCATE
WITHIN 3'-0" OF SHADE SYSTEM SWITCH. FA-409.00
7 OPEN STATUS OF FIRE SMOKE DAMPERS. COORDINATE WITH
MECHANICAL DRAWINGS. FILE No.:
E D C B A
1 2 3 3.6 4 4.6 5 6 7 8
ARCHITECT:
mOrphosis
153 W. 27th Street
Suite 1200
New York, NY 10001
T: 212.675.1100
4 www.morphosis.com
S
HUDDLE RM OWNER:
467 FTS A
P
CORNELLNYC TECH
111 EIGHTH AVENUE, #302
NEW YORK, NY 10011
TEL: 212.309.9020
SMEP/SUSTAINABILITY/ LEED/
LIGHTING EXTERIOR
B ENVELOPE/ AV/ IT/ SECURITY
S
S S ACOUSTICS/ SMART BUILDING
LOCATE AT TOP OF STAIR TO
ACTIVATE SHAFT LOUVER
ARUP
77 WATER STREET
185CD NEW YORK, NY 10005
LOCATE
ABOVE METAL TEL: 212.896.3000
WP MESH CEILING AIM AOM
GEOTECHNICAL:
5 6
MUESER RUTLEDGE
OFFICE ZONE A STAIR #5
FTS 225 W. 34TH STREET
CONFERENCE RM 40003
431 NEW YORK, NY 10122
401 C TEL: 917.339.9300
110CD R P
COST ESTIMATOR:
COLLAB. AREA OPEN
30CD
OPEN OPEN TO DHARAM CONSULTING
TO 439 TO
BELOW 240 WEST 37TH STREET, SUITE 302
BELOW BELOW
NEW YORK, NY 10018
2 TEL: 508.344.3820
B
CODE:
SC SC SC 2 SC
WP CONFERENCE RM C.8 CODE CONSULTANTS
2 401 PROFESSIONAL ENGINEERS, PC
215 WEST 40TH STREET, 15FL
P S S
NEW YORK, NY 10018
D TEL: 212.216.9596
FTS
FOR FLOOR CONTROL
ASSEMBLY S
S S
STAIR #1 SPECIFICATIONS:
3 40001 15CD
TEL RM ELEC RM COLLAB. AREA R ELEV #1 CONSTRUCTION SPECIFICATIONS, INC
436 15CD 40065 440
S
40076 22 TENNENT ROAD P.O. BOX 488
MORGANVILLE, NJ 07751
COLLAB. AREA AIM AIM AOM
TEL: 732.970.0700
SWING SPACE 408
.
409
FTS
3 4 2 D.2 WATER PROOFING:
HENSHELL & BUCCELLATO
R ELEV #2 166 PATTERSON AVENUE
1 CONFERENCE RM 40077 SHREWSBURY, NJ 07702
1 438 TEL: 732.530.4734
HUDDLE RM
410 OPEN
150CD
15CD
TO KITCHEN CONSULTANT:
HUDDLE RM BELOW
412 PANTRY
15CD
1 JACOB DOLAND BEER
HUDDLE RM 440A 116 E. 27TH STREET, 2FL
S 9
15CD
414 NEW YORK, NY 10016
WP HUDDLE RM
AIM AIM AOM
TEL: 212.206.0736
.
416 E
15CD
HUDDLE RM 3 4 2
15CD
ISSUES / REVISIONS:
S 418 AIM AIM AOM 1 E.2 NO. DATE DESCRIPTION
D
110C
HUDDLE RM
.
15CD
415 420 30CD 3 4 2 HUDDLE RM HUDDLE RM HUDDLE RM
01/17/2014 50% CD
452 454 456
15CD
05/16/2014 100% CD
S
15CD
2 06/30/2014 Addendum 2
15CD
15CD
2 9 02/13/2015 Bulletin #3
15C
453 OPEN
D
TO
BELOW HUDDLE RM
2 2
455
HUB LOUNGE
451
APPROVED F
KEY PLAN:
STAIR #5
FOR FCU-4.3
40003
9
H
N
P.N.
S
PROJECT
G
CORNELLNYC TECH
FIRST ACADEMIC
BUILDING
1 MAIN STREET
ROOSEVELT ISLAND
NEW YORK, NY 10044
1 L J FIRE ALARM
FOURTH FLOOR PLAN
A1 SCALE 1/8" = 1'-0" (SOUTH)
REFERENCE NOTES:
SEAL & SIGNATURE: DATE: 05-16-14
1 LOCATE WITHIN 5'-0" OF FIRE SMOKE DAMPER
PROJECT No.: 225121
2 ACTIVATION OF FIRE SMOKE DAMPERS. COORDINATE WITH MECHANICAL DRAWINGS. 9 DRAWING BY:
CHK BY: Checker
3 CLOSED STATUS OF FIRE SMOKE DAMPERS. COORDINATE WITH MECHANICAL DRAWINGS. DWG No.
4 OPEN STATUS OF FIRE SMOKE DAMPERS. COORDINATE WITH MECHANICAL DRAWINGS. FA-410.00
5 FOR STAIR HATCH STATUS. FILE No.:
ARCHITECT:
mOrphosis
153 W. 27th Street
Suite 1200
New York, NY 10001
T: 212.675.1100
4 www.morphosis.com
OWNER:
FTS A
P
S S S S S S CORNELLNYC TECH
111 EIGHTH AVENUE, #302
NEW YORK, NY 10011
TEL: 212.309.9020
SMEP/SUSTAINABILITY/ LEED/
LIGHTING EXTERIOR
B ENVELOPE/ AV/ IT/ SECURITY
CONFERENCE RM ACOUSTICS/ SMART BUILDING
497
K ARUP
77 WATER STREET
NEW YORK, NY 10005
TEL: 212.896.3000
GEOTECHNICAL:
5 6
MUESER RUTLEDGE
225 W. 34TH STREET
NEW YORK, NY 10122
C TEL: 917.339.9300
COST ESTIMATOR:
COLLAB. AREA COLLAB. AREA
OPEN OPEN OPEN
SC DHARAM CONSULTING
30CD
30CD
TO 481 TO 487 TO COLLAB AREA 240 WEST 37TH STREET, SUITE 302
BELOW BELOW BELOW 495 NEW YORK, NY 10018
TEL: 508.344.3820
CODE:
SC SC SC SC SC
CORRIDOR C.8 CODE CONSULTANTS
40050 PROFESSIONAL ENGINEERS, PC
1 12 215 WEST 40TH STREET, 15FL
S S S P S
NEW YORK, NY 10018
ELEC. CL.
30CD
15CD
15CD
TEL: 212.216.9596
FTS
40070
STAIR #2AIM HUDDLE RM SPECIFICATIONS:
AIM AIM AOM
3 WOMEN STORAGE 5
40008 477
TEL RM ELEC RM FIRE ALARM
.
S
15CD
482 40068 CONDUITS UP TO COLLAB. AREA 22 TENNENT ROAD P.O. BOX 488
PENTHOUSE 3 4 2 474 AIM
MORGANVILLE, NJ 07751
1 6 TEL: 732.970.0700
15C
40069 CONFERENCE RM
D
MEN 30CD 468 475 SHREWSBURY, NJ 07702
30C
TEL: 732.530.4734
D
40028
15C
HUDDLE RM
15CD
D
15C
D
HUDDLE RM HUDDLE RM
15C
462 HUDDLE RM E
15C
471
D
3 4 2 HUDDLE RM
15C
467
ISSUES / REVISIONS:
D
15C
HUDDLE RM
D
460
D
01/17/2014 50% CD
454
HUDDLE RM HUDDLE RM 05/16/2014 100% CD
15C
S 465
D
15CD
HUDDLE RM
463 9 02/13/2015 Bulletin #3
15C
12 11/25/2015 Bulletin #6
D
HUDDLE RM
APPROVED
15C
461
D
HUDDLE RM
459
15C
D
457
D
HUDDLE RM
455
F
KEY PLAN:
N
P.N.
PROJECT
G
CORNELLNYC TECH
FIRST ACADEMIC
BUILDING
1 MAIN STREET
ROOSEVELT ISLAND
NEW YORK, NY 10044
1 FIRE ALARM
FOURTH FLOOR PLAN
(NORTH)
REFERENCE NOTES:
SEAL & SIGNATURE: DATE: 05-16-14
1 LOCATE WITHIN 5'-0" OF FIRE SMOKE DAMPER
PROJECT No.: 225121
2 ACTIVATION OF FIRE SMOKE DAMPERS. COORDINATE WITH MECHANICAL DRAWINGS. DRAWING BY:
CHK BY: Checker
3 CLOSED STATUS OF FIRE SMOKE DAMPERS. COORDINATE WITH MECHANICAL DRAWINGS. DWG No.
4 OPEN STATUS OF FIRE SMOKE DAMPERS. COORDINATE WITH MECHANICAL DRAWINGS. FA-411.00
5 FOR STAIR HATCH STATUS
FILE No.:
6 FOR ACTIVATION OF STAIR HATCH
E D C B A
8 8.2 8.4 9 10 11 11.3 12 13 13.2 14 15 TOTAL GROSS AREA FOURTH LEVEL: 33,868 GSF
ARCHITECT:
mOrphosis
153 W. 27th Street
Suite 1200
New York, NY 10001
T: 212.675.1100
4 www.morphosis.com
OWNER:
FTS A
P
S S S S S S CORNELLNYC TECH
111 EIGHTH AVENUE, #302
NEW YORK, NY 10011
TEL: 212.309.9020
CONFERENCE RM
497 SMEP/SUSTAINABILITY/ LEED/
LIGHTING EXTERIOR
B ENVELOPE/ AV/ IT/ SECURITY
ACOUSTICS/ SMART BUILDING
OFFICE ZONE B
483
K ARUP
77 WATER STREET
NEW YORK, NY 10005
TEL: 212.896.3000
GEOTECHNICAL:
5 6
MUESER RUTLEDGE
225 W. 34TH STREET
NEW YORK, NY 10122
C TEL: 917.339.9300
COST ESTIMATOR:
COLLAB. AREA COLLAB. AREA
OPEN OPEN OPEN
SC DHARAM CONSULTING
30CD
30CD
TO 481 TO 487 TO HUDDLE RM 240 WEST 37TH STREET, SUITE 302
BELOW BELOW BELOW 467 NEW YORK, NY 10018
TEL: 508.344.3820
CODE:
SC SC SC SC SC
OFFICE ZONE C C.8 CODE CONSULTANTS
ASI-161 - RFI-441 - ESK-CA-012 - MSK-CA-0269 - TSK-CA-004 - Huddle Room 477 MEP Relocations
415 INSTALL IN FULL HEIGHT METAL SERVICE PANEL PER
PROFESSIONAL ENGINEERS, PC
1 ARCHITECTURAL ELEVATION IN SKETCH SKA-149. 215 WEST 40TH STREET, 15FL
S S S P S
NEW YORK, NY 10018
ELEC. CL.
30CD
15CD
15CD
TEL: 212.216.9596
FTS
40070
STAIR #2AIM SPECIFICATIONS:
WOMEN AIM AIM AOM HUDDLE RM
3 STORAGE 5
40008
40026 TEL RM ELEC RM FIRE ALARM
.
477
476 CONSTRUCTION SPECIFICATIONS, INC
S
15CD
482 40068 CONDUITS UP TO COLLAB. AREA 22 TENNENT ROAD P.O. BOX 488
PENTHOUSE 3 4 2 474 AIM
MORGANVILLE, NJ 07751
1 6 TEL: 732.970.0700
CORRIDOR15CD HUDDLE RM D.2 WATER PROOFING:
40041 470 S LOCATE AT TOP OF
V
T-984N
K
A
H
M
S
R
E
F
C R
E
TIS
LN
U
A
_ U
O
C
S N
A
H
I V
T-984N
K
A
H
M
S
R
E
F
C R
E
TIS
LN
U
A
_ U
O
C
S N
A
H
I V
T-984N
K
A
H
M
S
R
E
F
C R
E
TIS
LN
U
A
_ U
O
C
S N
A
H
I V
T-984N
K
A
H
M
S
R
E
C R
F E
TIS
LN
U
A
_ C
U
O
S N
A
H
I
STAIR TO ACTIVATE Cornell Bloomberg Center Job # 225121 HENSHELL & BUCCELLATO
HUDDLE RM STAIR HATCH 166 PATTERSON AVENUE
15C
REF: FA-411
D
MEN 30CD 468 CONFERENCE RM SHREWSBURY, NJ 07702
30C
PURPOSE OF ISSUE: Huddle Room 477 Art Revision
40028 475 TEL: 732.530.4734
D
PREPARED BY: KS CHECKED BY: KS
15C
HUDDLE RM ESK-CA-012
15CD
D
15C
SCALE: NTS
D
ORIGINAL PAPER SIZE:
HUDDLE RM
15C
462 471 E
15C
D
3 4 2
15C
ISSUES / REVISIONS:
HUDDLE RM
D
1 HUDDLE RM E.2
460
NO. DATE DESCRIPTION
467
08/09/2013 100% DD
15C
15C
HUDDLE RM HUDDLE RM
D
S
D
15CD
2 06/30/2014 Addendum 2
15CD
HUDDLE RM
463
9 02/13/2015 Bulletin #3
15C
12 11/20/2015 Bulletin #6
D
HUDDLE RM
461
15C
D
HUDDLE RM
459
15C
D
HUDDLE RM
HUDDLE RM
2 455
F
KEY PLAN:
N
P.N.
PROJECT
G
CORNELLNYC TECH
FIRST ACADEMIC
BUILDING
1 MAIN STREET
ROOSEVELT ISLAND
NEW YORK, NY 10044
1 FIRE ALARM
FOURTH FLOOR PLAN
A1 SCALE 1/8" = 1'-0" (NORTH)
REFERENCE NOTES:
SEAL & SIGNATURE: DATE: 05-16-14
1 LOCATE WITHIN 5'-0" OF FIRE SMOKE DAMPER
PROJECT No.: 225121
2 ACTIVATION OF FIRE SMOKE DAMPERS. COORDINATE WITH MECHANICAL DRAWINGS. DRAWING BY:
CHK BY: Checker
3 CLOSED STATUS OF FIRE SMOKE DAMPERS. COORDINATE WITH MECHANICAL DRAWINGS. DWG No.
4 OPEN STATUS OF FIRE SMOKE DAMPERS. COORDINATE WITH MECHANICAL DRAWINGS. FA-411.00
5 FOR STAIR HATCH STATUS
FILE No.:
6 FOR ACTIVATION OF STAIR HATCH
E D C B A
1 2 3 3.6 4 4.6 5 6 7 8
ARCHITECT:
mOrphosis
153 W. 27th Street
Suite 1200
New York, NY 10001
T: 212.675.1100
4 www.morphosis.com
OWNER:
A
CORNELLNYC TECH
111 EIGHTH AVENUE, #302
NEW YORK, NY 10011
TEL: 212.309.9020
SMEP/SUSTAINABILITY/ LEED/
LIGHTING EXTERIOR
B ENVELOPE/ AV/ IT/ SECURITY
ACOUSTICS/ SMART BUILDING
ARUP
77 WATER STREET
FOR SMOKE FAN DAMPER NEW YORK, NY 10005
AOM AOMAOM AIM AIM AIM AIM
TEL: 212.896.3000
.
GEOTECHNICAL:
19 20 21 22 23 24 25
MUESER RUTLEDGE
225 W. 34TH STREET
FOR SMOKE FAN DAMPER FOR SMOKE FAN DAMPER NEW YORK, NY 10122
C TEL: 917.339.9300
AOM AOMAOM AIM AIM AIM AIM AOM AOMAOM AIM AIM AIM AIM
9 . .
9 COST ESTIMATOR:
19 20 21 22 23 24 25 19 20 21 22 23 24 25
DHARAM CONSULTING
240 WEST 37TH STREET, SUITE 302
NEW YORK, NY 10018
WP WP TEL: 508.344.3820
WP WP
185CD
185CD
185CD
185CD
AIM AIM
P 9 CODE:
30CD
FE
FTS
D TEL: 212.216.9596
AIM AOM FOR FLOOR CONTROL ASSEMBLY LOCATE TOP OF ELEVATOR SPECIFICATIONS:
3 SHAFT TO ACTIVATE
9 ELEVATOR SHAFT LOUVER CONSTRUCTION SPECIFICATIONS, INC
28 29 AIM
ELEV #1 22 TENNENT ROAD P.O. BOX 488
R 11
AIM
50076AIM MORGANVILLE, NJ 07751
AIM AIM AOM
110CD
.
.
TEL: 732.530.4734
AIM AIM AOM
.
4 5 3 KITCHEN CONSULTANT:
4 5 3 6
AIM AIM AOM 9 JACOB DOLAND BEER
LOCATE AT TOP OF 116 E. 27TH STREET, 2FL
110CD
.
110CD
110CD
110CD
P
WP WP WP WP 01/17/2014 50% CD
05/16/2014 100% CD
AOM AOMAOM AOMAOM AIM AIM
.
9 02/13/2015 Bulletin #3
TYPICAL FOR 12 13 14 15 16 17 18
EACH SMOKE FAN
F
KEY PLAN:
APPROVED
N
P.N.
PROJECT
G
CORNELLNYC TECH
FIRST ACADEMIC
Reference Casey System Floor Plans BUILDING
1 MAIN STREET
ROOSEVELT ISLAND
NEW YORK, NY 10044
1 L J FIRE ALARM
REFERENCE NOTES: MECHANICAL ROOF PLAN
A1 SCALE 1/8" = 1'-0" (SOUTH)
1 ACTIVATION OF SMOKE DAMPERS 8 FOR SHUTDOWN OF AHU-4 SUPPLY/RETURN 15 FOR SMOKE FAN "FAULT" ACTIVATION 22 FOR SMOKE FAN DAMPER "CLOSED" POSITION STATUS 29 FOR ACTIVATION OF STAIR HATCH
ARCHITECT:
mOrphosis
153 W. 27th Street
Suite 1200
New York, NY 10001
T: 212.675.1100
4 www.morphosis.com
OWNER:
A
CORNELLNYC TECH
111 EIGHTH AVENUE, #302
NEW YORK, NY 10011
TEL: 212.309.9020
SMEP/SUSTAINABILITY/ LEED/
LIGHTING EXTERIOR
B ENVELOPE/ AV/ IT/ SECURITY
ACOUSTICS/ SMART BUILDING
K ARUP
77 WATER STREET
NEW YORK, NY 10005
TEL: 212.896.3000
FOR SMOKE FAN DAMPER FOR SMOKE FAN DAMPER
AOM AOMAOM AIM AIM AIM AIM AOM AOMAOM AIM AIM AIM AIM
GEOTECHNICAL:
. .
MUESER RUTLEDGE
225 W. 34TH STREET
15 16 17 18 19 20 21 15 16 17 18 19 20 21 NEW YORK, NY 10122
C TEL: 917.339.9300
COST ESTIMATOR:
DHARAM CONSULTING
240 WEST 37TH STREET, SUITE 302
NEW YORK, NY 10018
TEL: 508.344.3820
WP
185CD
185CD
WP
TYPICAL FOR EACH CODE:
FOR SEF R-3 9 SMOKE FAN
C.8 CODE CONSULTANTS
FIRE ALARM MAIN ELEC PROFESSIONAL ENGINEERS, PC
CONDUIT DOWN 50066 215 WEST 40TH STREET, 15FL
TO FIRST FLOOR NEW YORK, NY 10018
AOM AOMAOM AOMAOM AIM AIM D TEL: 212.216.9596
.
FE
ISSUES / REVISIONS:
AIM 1 2 1 2 1 2 E.2 NO. DATE DESCRIPTION
FOR ATS-FA 08/09/2013 100% DD
110CD
110CD
N
P.N.
PROJECT
G
CORNELLNYC TECH
FIRST ACADEMIC
BUILDING
1 MAIN STREET
ROOSEVELT ISLAND
NEW YORK, NY 10044
1 FIRE ALARM
MECHANICAL ROOF PLAN
A1 SCALE 1/8" = 1'-0" (NORTH)
REFERENCE NOTES:
1 FOR NORMAL POWER ACTIVE 8 FOR SMOKE FAN "ON" ACTIVATION 15 FOR SMOKE FAN DAMPER "OPEN" 22 GENERATOR TROUBLE
2 FOR EMERGENCY POWER ACTIVE 9 FOR SMOKE FAN "OFF" ACTIVATION 16 FOR SMOKE FAN DAMPER "CLOSED" 23 GENERATOR ALARM SEAL & SIGNATURE: DATE: 05-16-14
PROJECT No.: 225121
3 ACTIVATION OF FIRE SMOKE DAMPERS. 10 FOR SMOKE FAN "AUTO" ACTIVATION 17 FOR SMOKE FAN DAMPER "AUTO" 24 GENERATOR RUN DRAWING BY:
COORDINATE WITH MECHANICAL DRAWINGS.
CLOSED STATUS OF FIRE SMOKE DAMPERS. CHK BY: Checker
4 11 FOR SMOKE FAN "FAULT" ACTIVATION 18 FOR SMOKE FAN DAMPER "CLOSED" POSITION STATUS 25 GENERATOR AUTO
COORDINATE WITH MECHANICAL DRAWINGS. DWG No.
OPEN STATUS OF FIRE SMOKE DAMPERS. 19 FOR SMOKE FAN DAMPER "OPEN" POSITION STATUS
9
5
COORDINATE WITH MECHANICAL DRAWINGS.
12 FOR SMOKE FAN "NORMAL" ACTIVATION
FA-413.00
6 LOCATE WITHIN 5'-0" OF FIRE/SMOKE DAMPER 13 FOR SMOKE FAN "ON" STATUS VIA PRESSURE SWITCH 20 FOR SMOKE FAN DAMPER "FAULT" POSITION STATUS
FILE No.:
7 FOR MONITORING SHUNT TRIP POWER 14 FOR SMOKE FAN "OFF" STATUS VIA PRESSURE SWITCH 21 FOR SMOKE FAN DAMPER "NORMAL" POSITION STATUS
E D C B A
COMMAND CENTER
SMEP/SUSTAINABILITY/ LEED/
LIGHTING EXTERIOR
ENVELOPE/ AV/ IT/ SECURITY
ACOUSTICS/ SMART BUILDING
ARUP
77 WATER STREET
NEW YORK, NY 10005
TEL: 212.896.3000
FIRE ALARM INITIATING DEVICES
MANUAL FIRE ALARM STATION X X X X X X X GEOTECHNICAL:
SMOKE DETECTOR IN ELEVATOR MACHINE ROOM X X X X X X X X X X X MUESER RUTLEDGE
HEAT DETECTOR IN ELEVATOR MACHINE ROOM 225 W. 34TH STREET
X X X X X X X X X X X NEW YORK, NY 10122
SMOKE DETECTOR IN ELEVATOR LOBBY (PRIMARY FLOOR) X X X X X X X X X TEL: 917.339.9300
SMOKE DETECTOR IN ELEVATOR LOBBY (ALTERNATE FLOOR) X X X X X X X X X X
COST ESTIMATOR:
SMOKE DETECTOR TOP OF ELEVATOR SHAFT X X X X X X X X X X X X X
AREA SMOKE DETECTOR IN MERS X X X X X X X X X DHARAM CONSULTING
240 WEST 37TH STREET, SUITE 302
SMOKE DETECTOR FOR DOOR HOLD OPEN RELEASE X X X X X X X X X X NEW YORK, NY 10018
ACTIVATION OF FIRST SPOT TYPE SMOKE DETECTOR FOR SMOKE CONTROL TEL: 508.344.3820
X X X X X X X X X
ACTIVATION OF SECOND SPOT TYPE SMOKE DETECTOR FOR SMOKE CONTROL X X X X X X X X X X X X CODE:
PROJECTED BEAM SMOKE DETECTORS IN ATRIUM FOR SMOKE CONTROL X X X X X X X X X X X X CODE CONSULTANTS
SMOKE DETECTOR TOP OF STAIR OR SHAFT X X X X X X X X X X X PROFESSIONAL ENGINEERS, PC
DUCT SMOKE DETECTOR AT UNIT RETURN 215 WEST 40TH STREET, 15FL
X X X X X X X X X X X X X NEW YORK, NY 10018
DUCT SMOKE DETECTOR FOR FIRE SMOKE DAMPER ACTUATION X X X X X X X X X X X X X TEL: 212.216.9596
DUCT SMOKE DETECTOR AT UNIT SUPPLY X X X X X X X X X X X X X SPECIFICATIONS:
3
SPRINKLER WATER FLOW SWITCH X X X X X X X X X X X X CONSTRUCTION SPECIFICATIONS, INC
FLAME DETECTOR IN FUEL OIL ROOM AND GENERATOR ROOM X X X X X X X X X X 22 TENNENT ROAD P.O. BOX 488
MORGANVILLE, NJ 07751
TEL: 732.970.0700
PROJECT
CORNELLNYC TECH
FIRST ACADEMIC
BUILDING
Cornell Bloomberg Center Job # 225121 1 MAIN STREET
ROOSEVELT ISLAND
REF: FA-901 NEW YORK, NY 10044
1 FIRE ALARM
MATRIX
FA-901.00
FILE No.:
E D C B A
COMMAND CENTER
SMEP/SUSTAINABILITY/ LEED/
LIGHTING EXTERIOR
ENVELOPE/ AV/ IT/ SECURITY
ACOUSTICS/ SMART BUILDING
ARUP
77 WATER STREET
NEW YORK, NY 10005
TEL: 212.896.3000
FIRE ALARM INITIATING DEVICES
MANUAL FIRE ALARM STATION X X X X X X X GEOTECHNICAL:
SMOKE DETECTOR IN ELEVATOR MACHINE ROOM X X X X X X X X X X X MUESER RUTLEDGE
HEAT DETECTOR IN ELEVATOR MACHINE ROOM 225 W. 34TH STREET
X X X X X X X X X X X NEW YORK, NY 10122
SMOKE DETECTOR IN ELEVATOR LOBBY (PRIMARY FLOOR) X X X X X X X X X X TEL: 917.339.9300
SMOKE DETECTOR IN ELEVATOR LOBBY (ALTERNATE FLOOR) X X X X X X X X X X
COST ESTIMATOR:
SMOKE DETECTOR TOP OF ELEVATOR SHAFT X X X X X X X X X X X X
AREA SMOKE DETECTOR IN MERS X X X X X X X X DHARAM CONSULTING
240 WEST 37TH STREET, SUITE 302
SMOKE DETECTOR FOR DOOR HOLD OPEN RELEASE X X X X X X X X X NEW YORK, NY 10018
ACTIVATION OF FIRST SPOT TYPE SMOKE DETECTOR FOR SMOKE CONTROL TEL: 508.344.3820
X X X X X X X X
ACTIVATION OF SECOND SPOT TYPE SMOKE DETECTOR FOR SMOKE CONTROL X X X X X X X X X X X 2 CODE:
2 PROJECTED BEAM SMOKE DETECTORS IN ATRIUM FOR SMOKE CONTROL X X X X X X X X X X X CODE CONSULTANTS
SMOKE DETECTOR TOP OF STAIR OR SHAFT 9 2 X X X X X X X X X X PROFESSIONAL ENGINEERS, PC
DUCT SMOKE DETECTOR AT UNIT RETURN 215 WEST 40TH STREET, 15FL
X X X X X X X X X X X X NEW YORK, NY 10018
DUCT SMOKE DETECTOR FOR FIRE SMOKE DAMPER ACTUATION X X X X X X X X X X X X TEL: 212.216.9596
DUCT SMOKE DETECTOR AT UNIT SUPPLY X X X X X X X X X X X X SPECIFICATIONS:
3
SPRINKLER WATER FLOW SWITCH X X X X X X X X X X X CONSTRUCTION SPECIFICATIONS, INC
FLAME DETECTOR IN FUEL OIL ROOM AND GENERATOR ROOM X X X X X X X X X 22 TENNENT ROAD P.O. BOX 488
MORGANVILLE, NJ 07751
TEL: 732.970.0700
KEY PLAN:
APPROVED
PROJECT
CORNELLNYC TECH
FIRST ACADEMIC
BUILDING
1 MAIN STREET
ROOSEVELT ISLAND
NEW YORK, NY 10044
1 FIRE ALARM
MATRIX
FA-901.00
FILE No.: