Академический Документы
Профессиональный Документы
Культура Документы
AbstractThis paper presents simulation test results of the frequency of current and voltage amplitude, as it is done in
travelling wave fault location algorithm used in high voltage impedance methods. Thus the influence of many factors on
(HV) lines. The algorithm based on a wavelet transform, is tested the measurement error [2] is avoided (e.g. current distortion
for different fault types, including high impedance faults (HIF) due to saturation of current transformers). The purpose of this
and arc faults. Automatic test procedure (with use of
article is to demonstrate that the algorithm is working properly
PSCAD/EMTDC, Matlab) enabled to perform vast number of
simulations for each testing scheme. Simulation results from a for different fault types, including high impedance and arc
PSCAD/EMTDC model are compared with EMTP-RV results in faults.
order to confirm the correctness of the testing scheme. Prior to algorithm testing, the correctness of the model is
Keywords: transmission line, fault location, wavelet transform, verified by comparing the results of model simulations in two
travelling waves, arc fault, HIF, PSCAD/EMTDC programs for the simulation of electromagnetic transients
(PSCAD/EMTDC and EMTP-RV).
I. INTRODUCTION II. VERIFICATION OF THE MODEL COMPARISON BETWEEN
PSCAD/EMTDC AND EMTP-RV
Faults are events which are inevitable and occur in PSCAD/EMTDC simulation model is shown in Fig. 1 and
electrical power system. If protection devices operate as they EMTP-RV model is shown in Fig. 2. Fault locators are located
should it means - quickly and reliably, the deterioration of in substation A and B, at the opposite ends of
system status will be checked effectively, then the protection HV line (100 km long). The method based on current
of power systems is guaranteed to the maximum extent. measurements in two opposite substations is used.
Relays play a decisive role in electricity grids safe operations. The HV line is modeled as a frequency dependent model
Relay protection is just using the sudden changes of some with distributed parameters. PSCAD/EMTDC and EMTP-RV
electrical signals to distinguish whether the power system is in transmission line models are based on [3] and [4], [5],
failure or normal state. Fault types and fault locations are respectively.
detected after comparing the signals which were subject to Current transformer is modeled as a Butterworth filter with
some changes with the electrical parameters of normal system. frequency range (0 200 kHz). The chosen frequency range is
Laboratory testing of fault locators is rarely discussed, derived from the research presented in [6].
because most of protective device laboratory testing is focused HV substations are modeled as 0.1 F capacitors [7].
on functional tests of apparatus [19]-[21]. Solution time step is chosen to be 1 s in order to properly
Accurate fault location in HV line allows for efficient work analyze a travelling wave phenomenon.
of power staff and for shortening the time of failure, which
directly translates into reduced cost for power grid operators
and end-users. In HVDC transmission lines [16]-[18] location
of line faults is performed by means of calculation of
travelling-wave propagation times [15]. The main fault
location methods are impedance and travelling wave method,
of which the latter has a better accuracy. Furthermore, it
accurately locates high impedance faults [1], for which the
impedance method has higher error. Principle of operation of
travelling wave fault locators is based on determining the
exact time moment of wave arrival to a substation. There is no Fig. 1. Simulation model in PSCAD/EMTDC
requirement for precise measurement of fundamental
G1 B G2
A
+
+
+
0.1uF C1 0.1uF C2 0.1uF C3
0.1uF C4
In order to calculate detail coefficients at the second level resistance values corresponding to the actual fault resistance
of wavelet decomposition it is necessary to convolve occurring in HV lines. The algorithm is tested for following
approximation coefficients at the first level with values of fault resistance: 1, 10, 50, 100, 300, 400. The
decomposition high-pass filter coefficients and after that every model shown in Fig. 1 (with testing scheme from Fig. 4
second sample should be removed. Coefficients of such filter between substation A and B) is used for automatic testing.
for bior 3.3. are: The algorithm operation is verified for best and worst fault
cases. The best situation for the algorithm is when a fault
gD = {0, 0, -0.1768, 0.5303, -0.5303, 0.1768, 0, 0} (2)
occurs when voltage has its maximum (phase angle 90) and
the worst situation is when the fault occurs when phase angle
IV. SCHEME FOR AUTOMATIC ALGORITHM TESTING is equal to 2.5 (when the phase angle is lower than 2.5 the
In order to thoroughly test the travelling wave algorithm the algorithm does not work properly a wave amplitude is too
special testing scheme is developed. The simulation model, low to be properly located by the algorithm). Fig. 5 and Fig. 6
which is realized in PSCAD/EMTDC is shown in Fig. 4. The show three current waveforms recorded in substation A for a
purpose of testing the algorithm is to verify its proper best case. Fig. 7 and Fig. 8 present the worst case scenario.
operations for different:
x fault types (L1-E, L2-E, L3-E, L1-L2-E, L1-L3-E, L2-
L3-E, L1-L2, L1-L3, L2-L3, L1-L2-L3-E, L1-L2-L3),
x distance from fault to substation (1 km, 2 km, 5 km, 10
km, 20 km, 30 km, 40 km, 50 km, 70 km, 85 km),
x fault angle (0 - 90 in steps of 2).
In PSCAD/EMTDC there are 3960 different cases
simulated, which are characterized by different fault type (L1-
E, L2-L2 etc.), fault location and different fault angle.
Comtrade files are then loaded to Matlab where for each of
3960 files (which represent phase currents waveforms in
Fig. 5. Current waveforms in a substation A: L1-E fault (IL1-blue, IL2-red,
substations at the end of HV line) the travelling wave IL3- green), RF = 10 ; u_L1 = 90, the rectangle indicates zoomed area
algorithm (detection, classification and location) is carried out. which is shown in Fig. 6
The output excel file contains the data associated with
simulation and results of algorithm: fault type and determined
fault location.
The model of primary arc is based on the equation [13]: p time constant.
Following values are chosen:
dg p 1
G gp (5) up = 15 V/cm, average contact arc voltage gradient,
dt Wp
Rarc = 10-5 /cm, arc resistance per unit length,
where: larc = 400 cm, arc length
gp time varying arc conductance,
G stationary primary arc conductance,
DI p
W arc (6)
larc
where:
2,510-5, coefficient,
Ip 15000 A, maximum arc current.
g (k ) G (1 a1 ) g (k 1) a1 (7)
-T/p
a1 = e , T simulation time step
Initial conductance value at the fault time tF:
i
g (t F ) 0,054 (8)
up l
Fig. 11 presents time dependent resistance, which reaches
25 in its peak. Fig. 13. Results of fault location algorithm testing with and without fault arc
VII. CONCLUSION
It can be concluded that the robustness of the algorithm for
HIF and arc faults was proved by numerous simulation tests.
The algorithm based on a wavelet transform and high
frequency current signal can be used to detect and locate such
faults. The average absolute error of all simulation cases is
less than 250 m, which meets the requirement for travelling
wave fault method to be much more accurate than impedance
methods.
There is still a place for improvement of the fault location
accuracy. One of the possible way of making the algorithm
work better is to increase the sampling frequency, but this
Fig. 11. Arc fault resistance may lead to worse reliability.
Fig.12 presents the current waveform in substation A after The algorithm was already tested on hardware platform in
phase to earth fault, which occurs in the presence of primary laboratory conditions and the aim of future work is to verify
arc. Some additional high frequency oscillations can be the prototype on site. This will enable to compare the
observed in the waveform. simulations with real measurements.
All PSCAD/EMTDC models and more detailed results (list
of all 3960 test results for each case) can be found on the
website: http://www.krzysztofglik.evbox.pl
Parameter Value
Positive sequence
impedance
Z G1 _ 1 6,1 j16,7 17,8e j 70q :
Zero sequence
impedance
Z G1_ 0 2,7 j8,37 8,8e j 72 :
Fig. 12. Current waveform in substation A after arc fault in HV Line,
PSCAD/EMTDC Voltage (phase-phase, 231 kV
Fig. 13 presents the results of automatic testing of the RMS)
algorithm. There is no difference between scenario with fault Phase shift for L1: 0
arc and without it. Apparently, the arc fault value does not
cause significant decrease of wave amplitudes. It can be also
concluded that high frequency oscillation does not have any
impact on the algorithm operation. The current wave curves
have its original shape, so the wavelet transform can still
properly analyze the current waveform and accurately locate
faults.
Line Model in
Parameter
Fig. 14 presents arrangement of conductors and PSCAD/EMTDC
ground wires. Table III lists the dimensions used and R1 [/km] 0.049
REFERENCES
[1] H. Lee, "GPS travelling wave fault locator systems investigation into the
anomalous measurements related to lightning strikes", IEEE
Transactions on Power Delivery, vol. 11, p. 1214-1223,Nov. 1996.
[2] K. Glik, R. Kowalik, D. Rasolomampionona and S. Anwar, Travelling
wave fault location in power transmission systems: an overview,
Journal of Electrical Systems, vol. 7, p. 287-296, Sep. 2011.
[3] W.S. Lee and H.W. Dommel, "Numerical Modeling of Frequency-
Dependent Transmission Line Parameters in an Electromagnetic
Transient Program", IEEE Transactions on Apparatus and Systems,
vol. PAS-93, p. 1401-1409, Sept/Oct 1974.
Fig. 14. HV line, PSCAD/EMTDC [4] B. Gustavsen, G. Irwin, R. Mangelrod, D. Brandt and K. Kent,
Transmission Line Models for the Simulation of Interaction
TABLE III Phenomena Between Parallel AC and DC Overhead Lines, in Proc.
HV LINE PARAMETERS IPST '99, 1999, p. 61-67.
[5] A. Morched, B. Gustavsen and M. Tartibi, A universal model for
Parameters Values accurate calculation of electromagnetic transients on overhead lines and
Rated votlage 220 kV underground cables, IEEE Transactions on Power Delivery, vol. 14,
pp. 1032 1038, Jul. 1999.
Conductor 3 x AFL-8 [6] A. M. Elhaffar, Power transmission line fault location based on current
travelling waves, Ph. D. dissertation, Department of Electrical
Conductor cross-section 525 mm2 Engineering, Helsinki University of Technology, Helsinki, Finland,
Ground wires 2 x AFL-1,7 2008.
[7] Z.Q. Bo, A new non-communication protection technique for
70mm2 transmission lines, IEEE Transactions on Power Delivery, vol. 13,
Conductors 1 pp. 1073 1078, Oct. 1998.
[8] K. Glik, D. Rasolomampionona and R. Kowalik, Detection,
Number of sub-conductors in a bundle 2 classification and fault location in HV lines using travelling waves,
PRZEGLD ELEKTROTECHNICZNY (Electrical Review), vol. 1a, p:
Height of all conductors (measured at
23.5 m 269 275, Jan. 2012.
tower) [9] S. Mallat, A Wavelet Tour of Signal Processing, New York, Academic
Horizontal spacing between phases 7.6 m Press, 1998.
[10] Lou van der Sluis: Transients in Power Systems, West Sussex, England,
Shunt conductance 1.0E-11 S/m John Wiley & Sons Ltd, 2001.
[11] P. Maniewski, Zabezpieczenia odlegociowe dla linii przesyowych z
Conductor radius 0.01575 m szeregow kompensacj kondensatorow, Ph. D. dissertation, Institute
Conductor DC resistance 0.047 /km of Power Engineering, Wrocaw University of Technology, Wrocaw,
Poland, 2010.
Sag for all conductors 6.3 m [12] S. L. Zimath, M. A. F. Ramos, J. E.S. Filho, Comparison of impedance
and travelling wave fault location using real faults, in Proc. 2010 IEEE