Академический Документы
Профессиональный Документы
Культура Документы
Introduction
A circuit breaker is an electrical switch designed to
protect an electrical circuit from damage caused by
overload or short circuit. It is also used to isolate
part of a healthy circuit for regular maintenance. Its
operation can therefore be both automatic and
manual. Its basic function is to immediately
discontinue electrical flow. The circuit breaker
plays a significant role within the power system
where it;
> Minimizes losses in closed position
> Opens and closes on command Figure 1: Conventional wiring set-up for micro-ohm
> Opens or closes a circuit to connect the power measurement
to/from the transmission line
(O - break, C - make)
> Opens a circuit for planned maintenance (O -
break)
> Opens a circuit at system fault to protect the
system behind the circuit breaker (O break, O-
C reclose, O-CO, auto-reclose)
> Isolates between poles (TRV), open contacts
and earth
To ensure appropriate operation of the circuit
breaker it is important to test the performance of
key components including;
> kinematic chain
> timing of main and auxiliary contacts
> contact travel (motion) of main contacts Figure 2: Conventional wiring set-up for timing tests
> control circuits
> coil current analysis The wiring for the micro ohm certainly is not done
> minimum pick-up test all in parallel in the conventional set-up, however
> charging motor all the wires shown in the picture are needed.
> motor current analysis
> main contacts' wear and tear Classic Circuit Breaker Testing
> contact resistance of main contacts (static
and dynamic) Traditionally, reference to "circuit breaker testing"
excluded the static resistance measurement,
Conventional testing of circuit breakers does despite the fact that this is an absolutely necessary
test.
generally mean the disconnection of the circuit
breaker from the system. This involves an OMICRON defines "circuit breaker testing" as:
inevitable outage and brings about much the distribution of open and close commands of
paperwork and cost in order that safety the circuit breaker with nominal and under
requirements are met, often involving a number of voltage
staff to complete the work. It is imperative, analysis of coil currents
therefore, that testing of circuit breakers is done in the measurement on the main and auxiliary
the shortest possible time, utilising equipment contacts
which provides accurate results. static contact resistance test
The conventional set-up for circuit breaker testing and if necessary,
(Figures 1 and 2) involves rewiring between micro- a dynamic resistance measurement of the main
ohm measurement and timing tests. This involves contacts
many cables, is time-consuming and error-prone.
motion analysis or time travel diagram
Figure 3: CIBANO 500's 3-in-1 solution The motion analysis gives information on the
mechanical position of components of the circuit
The measurements possible with this combination breaker over time. The aim, if possible, is to
of equipment enable the user to draw numerous determine the position of the main contacts. As
conclusions regarding the condition of the circuit they are not directly accessible, motion sensors
breaker. are affixed to the closest possible points of the
main contacts.
Through the analysis of coil circuits from the
different open and closed coils, it can be Statements that can be made from this
determined whether an operating characteristic of measurement include whether the motion runs
any nature or manner is sluggish, and compare the within the specified boundary conditions. Also it
chronological sequence with nominal values. can show whether, for example, the damping of the
motion towards the end of the switching process
Timing analysis gives information on whether the
occurs in the desired nature and manner.
different main and auxiliary contacts are switching
within the correct time, according to the The combination of dynamic resistance
manufacturer's specified nominal behaviors. measurement and time travel analysis also allows
Synchronization of individual main contacts within the lengths of the arcing contacts to be added in
a phase is therefore particularly important, but also millimeters.
between the phases of the maximal permissible
deviations indicated by the manufacturer. Static Resistance Measurement
The dynamic resistance measurement allows the The micro ohm measurement or static contact
recording of resistance during the opening of the resistance measurement on the closed main
main contacts. The point in time the current line contacts is a further measurement that should
passed from the main to the arcing contact can be typically be undertaken.
read from the curve. This time is decreased in It leads to a larger direct current via the main
comparison to earlier measurements so that the contact and the voltage can be picked up with
arcing contact becomes shorter. In combination separate cables as close as possible to the main
with a travel analysis even the length of the arcing contact.
contact in millimeter can be determined.
This measurement is particularly easy if it is
undertaken with Kelvin clamps. A Kelvin clamp has
two separately isolated terminal jaws. The current
feeds to one side of the clamps and the voltage is
measured on the other side. The clamps are
perfectly suitable for massive lines like busbars or
conductor cables with large diameters.
CIBANO 500
The CIBANO 500 main device offers all essential
functions that are required for testing all types of
circuit breakers without the need for any peripheral
devices.