Вы находитесь на странице: 1из 10

www.ietdl.

org
Published in IET Generation, Transmission & Distribution
Received on 5th September 2013
Revised on 12th March 2014
Accepted on 21st May 2014
doi: 10.1049/iet-gtd.2013.0636

ISSN 1751-8687

Improvement of unified power quality conditioner


performance with enhanced resonant control strategy
Quoc-Nam Trinh, Hong-Hee Lee
School of Electrical Engineering, University of Ulsan, Ulsan, South Korea
E-mail: hhlee@mail.ulsan.ac.kr

Abstract: This study proposes an enhanced resonant control strategy for the unied power quality conditioner (UPQC) to
simultaneously tackle voltage sags, unbalance and distortions on the supply side as well as current harmonics on the load
side. The proposed control strategy is developed in both the series and shunt active power lters (APFs) of the UPQC. In the
series APF, a proportionalresonant controller and a resonant controller are employed to mitigate voltage sags, unbalance and
distortions, whereas a proportionalintegral (PI) controller and three vector PI controllers are used in the shunt APF to
compensate harmonic currents. The performance of the proposed UPQC control scheme is signicantly improved compared
with the conventional control strategy owing to the superiority of the resonant controllers. In addition, voltage sag/harmonic
and current harmonic detectors are not required in the proposed control scheme, which helps to simplify the control strategy
and to improve the control accuracy. The proposed control strategy is theoretically analysed and its feasibility is validated
through experiments.

1 Introduction balanced sags, whereas the majority of faults on power


systems are asymmetrical, which results in unbalanced
Voltage sags are generally considered as common and costly voltage sags on the supply side. Under such conditions, the
power quality problems affecting sensitive loads. They conventional PI controller fails to properly track the
regularly result in undesired interruptions of electronic- reference signal because of the presence of the negative
based equipment and are responsible for large productive sequence components [5]. To mitigate unbalanced voltage
losses in industrial processes [1, 2]. The series active power sags, several control strategies have been developed: two PI
lter (APF), commonly known as the dynamic voltage controllers in positive and negative dq reference frames
restorer (DVR), is an effective solution for protecting [6], a proportionalresonant (PR) controller [7] or a H
sensitive loads from voltage sags [310]. The DVR is controller in the stationary frame [8]. However, the grid
installed in series between the supply and the load side in voltage may not only be unbalanced because of voltage
order to inject a compensating voltage to maintain the load sags, but also be distorted because of non-linear loads on
voltage balanced and sinusoidal at the desired value when distribution systems. Therefore, those control strategies are
voltage sags take place on the supply side. inadequate for tackling voltage sags and distortions
The performance of a DVR in compensating the voltage simultaneously. In addition, from the view point of the
sags is determined by the voltage sag detectors and voltage power system, harmonic currents produced by non-linear
controllers. Voltage sags should be detected rapidly and loads also cause serious problems, thereby degrading the
accurately without any delay time to ensure that the DVR power quality [11]. Hence, they must be taken into account
can quickly recognise and respond to the voltage sags. and fully compensated.
Monitoring the magnitude of the supply voltage in the The unied power quality conditioner (UPQC) has been
fundamental (dq) reference frame is a common method to introduced as an advanced solution to full those goals
detect voltage sag [9]. After accurately detecting voltage [1113]. Owing to the combination of a series APF and a
sag, a voltage reference for the DVR is generated and the shunt APF, the UPQC is able to simultaneously deal with
voltage controller then executes to ensure the load voltage voltage and current-related problems to protect sensitive
is undisturbed. Hence, the voltage controller also plays a loads and to enhance the power quality. In the UPQC, the
vital role in a DVR control scheme to achieve a fast role of the shunt APF is not only to compensate the
transient response as well as good steady-state performance harmonic currents, but also to support the series APF to
of the load voltage during voltage sags. compensate long duration voltage sags by maintaining the
The conventional proportionalintegral (PI) controller common DC-link voltage of the series and the shunt APFs
combined with the supply voltage feed-forward in the dq at a constant level.
reference frame has been developed to tackle voltage sags Various UPQC control strategies have been developed
[35]. However, this method has only been evaluated under to deal with voltage distortions and current harmonics

IET Gener. Transm. Distrib., pp. 110 1


doi: 10.1049/iet-gtd.2013.0636 & The Institution of Engineering and Technology 2014
www.ietdl.org
[1123]. In [1115], in order to regulate the load voltage and
supply current to be sinusoidal, harmonic components in the
supply voltage and the load current are detected through
harmonic detectors and regulated by hysteresis controllers.
In [1620], harmonic detectors are eliminated to simplify
the control scheme, but hysteresis controllers are still used
to regulate the load voltage and supply current to be
sinusoidal. Despite the simple structure and fast response
characteristics of the hysteresis controller, this control
technique has two shortcomings: rst, the variation of
switching frequency may cause many switching noises on
the load voltage and the supply current; and second, the
control performance is limited because of the trade-off
between the hysteresis band and the switching frequency.
These drawbacks degrade the performance of the hysteresis
controller. Meanwhile, in [21, 22], articial neural network
and particle swarm optimisation-based controllers were
developed for the UPQC to deal with voltage and current Fig. 1 Block diagram of the conventional UPQC control scheme
harmonics. However, these control algorithms are obviously
complicated since a large training time is required for connected at the AC output voltage of the series APF to
optimising the controller gains. Moreover, despite the eliminate high-frequency switching ripples. The loads on
complexity of the control algorithm, the performance the system are non-linear, linear and sensitive.
presented in [21] is not so good compared with other As illustrated in Fig. 1, to tackle the voltage sags and
conventional control methods. A novel control method for distortions as well as current harmonics, the conventional
the UPQC to tackle voltage and current harmonics UPQC control strategies require a voltage sag/harmonic
problems was proposed in [23]. The control strategy in [23] detector, a current harmonic detector and hysteresis
requires fewer sensors compared with other methods and it controllers where those parts must be designed properly to
also provides a good harmonic compensation performance. achieve good performance. It makes the control scheme
However, in that study, only the voltage and current become too complex. Moreover, because of the use of
harmonic problems are considered. Other power quality hysteresis controllers, the control performance of the UPQC
issues such as voltage sags and voltage unbalance are not is generally limited.
taken into account, which restrict the compensation
capability of the UPQC.
In this paper, an enhanced resonant control strategy is 2.2 Proposed UPQC control scheme
proposed for the UPQC to simultaneously tackle various
power quality issues such as voltage sags, unbalance and To improve the control performance of the UPQC, an
distortions as well as current harmonics. To mitigate the enhanced control strategy shown in Fig. 2 is proposed in
voltage sags and distortions on the supply side, a PR this paper with the aid of resonant controllers. In the
controller tuned at the fundamental frequency (s) and a proposed control scheme, the voltage sag/harmonic and
resonant controller tuned at six multiple of the fundamental current harmonic detectors are not required. The load
frequency (6s) are employed in the series APF side. voltage and the supply current are directly sensed and
Meanwhile, to compensate the current harmonics of regulated to follow their corresponding references in the
non-linear loads, a PI controller and three vector PI (VPI) dq reference frame (vL, dq and iS, dq ) through the proposed
controllers tuned at 6ns (n = 1, 2, 3) are used in the shunt
APF side. The performance of the proposed UPQC control
scheme is signicantly improved compared with the
conventional control strategy owing to the effectiveness of
the resonant controllers. In addition, in order to simplify the
control strategy and improve the control accuracy, the
voltage sag/distortion and current harmonic detectors are
eliminated in the proposed control scheme. The feasibility
of the proposed control scheme is validated through
experiments.

2 Proposed UPQC control scheme


2.1 Conguration of an UPQC

Fig. 1 shows the block diagram of a three-phase UPQC,


which consists of two voltage source inverters connected
back-to-back through a common DC-link capacitor, where
one inverter is the shunt APF and another inverter is the
series APF. The series APF is connected in series between
the supply and the load through a series transformer.
Meanwhile, the shunt APF is connected in parallel with the
loads through an inductor Lsh. An LC (Lf, Cf ) lter is Fig. 2 Block diagram of the proposed UPQC control scheme

2 IET Gener. Transm. Distrib., pp. 110


& The Institution of Engineering and Technology 2014 doi: 10.1049/iet-gtd.2013.0636
www.ietdl.org
PR-R voltage controller and PI-VPI current controller, the supply voltage is reduced to VS or VS according to
respectively. The PWM signals for the series APF and the the voltage sag type: without or with a phase jump,
shunt APF are generated from the voltage references respectively [2]. In case of the voltage sag without a phase
vF, abc and vsh, abc , respectively, by using a sinusoidal PWM jump, the supply voltage reduces to VS and the series APF
method. Since the proposed control strategy is executed injects a compensating voltage Vf so that the load voltage
without the voltage sag/harmonic and current harmonic has maintained its nominal magnitude. Since the voltage
detectors, the control accuracy and dynamic response of the sag occurs without a phase jump, the compensating voltage
UPQC can be signicantly improved. In addition, a PI Vf is in-phase with the supply voltage VS and the load
controller is employed in the outer control loop of the shunt voltage VL. In case of the supply voltage VS, the voltage
APF for regulating the DC-link voltage of the UPQC. sag occurs with a phase jump ; the series APF generates
Moreover, since the proposed control algorithm is designed the compensating voltage Vf with the phase angle (s + )
in the dq reference frame, a phase-locked loop (PLL) is to keep the load voltage vector unchanged without any
used to detect the phase angle of the supply voltage for phase jump. In the conventional control methods, to
coordinate transformations. A second-order generalised maintain the load voltage undisturbed from the voltage sag,
integrator-PLL introduced in [24] is adopted in Fig. 2 to it is necessary to detect the voltage sag and to nd the
guarantee the precise operation of the PLL under the phase angle of the compensating voltage Vf in the control
abnormal supply voltage condition. scheme. However, in the proposed control algorithm, the
load voltage can maintain the desired voltage without the
3 Control strategy in the series APF source voltage sag detection in spite of the voltage sag with
or without a phase jump since it is directly regulated.
3.1 Voltage sags compensation To maintain the constant load voltage, despite voltage sag,
the voltage controller of the series APF plays an important
The main purpose of the series APF in an UPQC is to inject a role. The PI controller in the dq reference frame has been
compensating voltage to maintain the voltage at the load introduced and widely used for this purpose [3]. However,
terminal balanced and sinusoidal at the desired level this method has a limitation in mitigating unbalanced
irrespective of the supply voltage conditions. As illustrated voltage sags because of the presence of the negative
in Fig. 2, the load voltage is determined by the supply sequence component [5]. Therefore, a PR controller tuned
voltage and the injected voltage of the series APF as follows at the fundamental frequency in the stationary frame is used
in this paper for dealing with unbalanced voltage sags. The
vL (vt) = vS (vt) + vf (vt) (1) advantage of PR controller is that it is capable of effectively
tracking an AC signal at the selected frequency; hence, it
where vL(t), vS(t) and vf(t) are the load voltage, the supply can simultaneously regulate positive and negative sequence
voltage and the injected voltage of the series APF, components without any sequence decomposition process
respectively. [25]. The open-loop transfer function of the PR controller is
Fig. 3 shows the locus of the load voltage phasor diagram given as follows
under the voltage sag situations. In Fig. 3, it is assumed that
the supply voltage under the normal condition is sinusoidal Kr1 vc s
and balanced at the nominal magnitude with the phase GPR (s) = Kp + (2)
s2 + 2vc s + (vs )2
angle s and the load voltage vector is same as the supply
voltage vector [VL = VS(pre sag)] without any help of the
series APF. When the voltage sag occurs, the magnitude of where Kp is the proportional gain, Kr1 denotes the resonant
gain of the resonant controller, s is the selected resonant
frequency of PR controller, which means the fundamental
frequency of the grid voltage in this case and c is the
cut-off frequency which determines the control bandwidth
of the PR controller.

3.2 Voltage distortions mitigation

In practice, because of the intensive use of non-linear loads in


power systems, the voltage available at the supply bus is
usually not pure sinusoidal but distorted. This distorted
voltage condition will harmfully affect sensitive loads
connected at the load terminal if it is not taken into account
and fully compensated. The UPQC is also capable of
isolating voltage harmonics on the supply side to improve
the load voltage performance. The voltage controller, which
is used to mitigate voltage harmonics, is introduced in this
section.
Assuming that the voltage available at the supply bus (vS)
is distorted and includes the fundamental (vS1) and harmonic
components (vSh) as identied in (3)

Fig. 3 Locus of the voltage phasor diagram under the voltage sag vS (vt) = vS1 (vt) + vSh (vt) (3)
situations h=1

IET Gener. Transm. Distrib., pp. 110 3


doi: 10.1049/iet-gtd.2013.0636 & The Institution of Engineering and Technology 2014
www.ietdl.org

Fig. 4 Block diagram of the proposed PR-R voltage controller

To make the load voltage sinusoidal, the harmonic


components presented in (3) must be completely
compensated by the series APF. In three-phase systems, the
harmonic voltages have odd orders: 6n 1 (n = 1, 2, 3, )
of the fundamental frequency of the network (S). Among
them, the fth and seventh harmonics are dominant Fig. 5 Bode diagram of closed-loop PR-R controller with respect
components that need to be eliminated. A resonant to different values of Lf and Cf
controller is an effective solution to compensate those
harmonic voltages [26]. Since one resonant controller can
controller has two selected resonant frequencies: 60 and
only track a specic AC component, two resonant
360 Hz. At 60 Hz, the frequency response of the PR-R
controllers tuned at 5S and 7S are required to compensate
controller is almost the same regardless of the lter
both the fth and seventh harmonics. Fortunately, since
parameter variations. In contrast, at the vicinity of 360 Hz,
both the fth and seventh harmonics become the sixth
the frequency response of the PR-R controller shows a
harmonic in the dq reference frame, one resonant
small difference with respect to different values of Lf and
controller with a selected resonant frequency of 6S in this
Cf. However, the PR-R controller always provides unity
frame is also capable of simultaneously compensating both
gain and zero phase at selected resonant frequency 360 Hz,
the fth and seventh harmonic voltages. Accordingly, the
despite the variations of the lter parameters (Lf or Cf ).
control scheme is simplied since only one controller is
Therefore, we can say that the variations of lter parameters
needed to regulate two harmonics. The open-loop transfer
have no impact on the system stability and performance of
function of the resonant controller is given as
the proposed voltage controller.
To implement these controllers by digital signal processors
Kr6 vc s
GR (s) = (4) (DSPs), the transfer function of the PR controller in (2) and
s2 + 2vc s + (6vs )2 the resonant controller in (4) are discretised by considering
accurate resonant pole placement [28]
The block diagram of the proposed voltage controller for the
series APF is illustrated in Fig. 4. 1 cos (vs Ts )z1
GPR (z) = Kp + Kr1 vc Ts
1 (2 cos (vs Ts ) 2vc Ts )z1 + z2
3.3 Analysis and design of proposed voltage
controller (6)

Designing the gains of resonant controller is not a simple task, 1 cos (6vs Ts )z1
GR (z) = Kr6 vc Ts
especially when compensating high-order harmonics [26, 27]. 1 (2 cos (6vs Ts ) 2vc Ts )z1 + z2
In this paper, the Naslin polynomial technique is used to
(7)
determine the resonant controller gains [26]. In addition, Kp
and c values of the PR controller should be designed to be
sufciently large to make the PR controller have a wide where z is the shift operator and TS = 100 s denotes the
bandwidth, and hence provide a fast response against sampling period.
voltage sags. According to the design procedure presented For digital implementation, (6) and (7) with the same gains
in [26], the controller gains of PR and resonant controllers in continuous time domain are used because the sampling
in Fig. 4 are selected based on the system parameters given period TS is very short.
in Appendix as follows: Kp = 2, Kr1 = 2000, c = 10rad/s
and Kr6 = 500. 4 Control strategy in the shunt APF
Since these controller gains depend on the LC lter
parameters, the effect of the lter parameter variations on 4.1 Current harmonics compensation
the system stability is considered. From Fig. 4, the
closed-loop transfer function of the PR-R controller is given The main purpose of the shunt APF is to mitigate harmonic
as follows currents produced by the non-linear load. The non-linear
load under consideration is a three-phase diode rectier
GPRR (s)GLC (s) supplying a DC load. This type of load draws harmonic
GC = (5) currents into the networks that have odd orders: 6n 1 (n =
1 + GPRR (s)GLC (s)
1, 2, 3, ) of S. As a result, the load current consists of
the fundamental (iL1) and harmonic components (iLh) as
where GLC = 1/(LfCfs 2 + RfCfs + 1) is the transfer function of
the LC lter. 
Fig. 5 shows the Bode diagram of (5) with respect to iL (vt) = iL1 (vt) + iLh (vt) (8)
different values of Lf and Cf. In Fig. 5, the proposed PR-R h=6n+1

4 IET Gener. Transm. Distrib., pp. 110


& The Institution of Engineering and Technology 2014 doi: 10.1049/iet-gtd.2013.0636
www.ietdl.org

Fig. 6 Block diagram of the proposed PI-VPI current controller

To make the supply current sinusoidal, the harmonic currents


presented in (8) must be fully compensated by the shunt APF.
In other words, the shunt APF must operate as a controlled
current source to generate harmonic currents to reject those
of the load current. Since the current controller must deal
with harmonic currents which are high-frequency signals,
the PI controller is not a sufcient solution because of its Fig. 7 Bode diagram of the closed-loop transfer function of the
limitation on the control bandwidth. To overcome this proposed current controller
issue, resonant controller could be considered as an
effective solution for regulating harmonic currents. The
(6n 1) harmonic currents also become 6n harmonics in the controller provides a unity gain and zero-phase shift at
dq reference frame. Hence, one resonant controller with a selected resonant frequencies, that is, 360, 720 and 1080
resonant frequency of 6nS is capable of regulating a pair Hz, irrespective of the value of Kph. It means that the VPI
of (6n 1) harmonic currents. The number of resonant controller is able to regulate the selected harmonic currents
controllers is thereby reduced by half. In fact, the effect of with zero steady-state error. Even though any value of Kph
very high-order harmonics is usually negligible. In this can provide unity gain and zero-phase shift, Kph should
paper, only harmonic currents up to 19th order are be carefully selected to achieve a good steady-state
considered for compensation. Accordingly, three resonant performance and a fairly fast response. To full that
controllers are needed to regulate those harmonic currents. demand, it is recommended to select Kph smaller than 1
In fact, the VPI controller which is an alternative version of [29]. Finally, the controller gains of each VPI controller are
the resonant controller is used in this paper because it has tuned individually by using the system parameters shown in
some advantages over the standard resonant controllers Appendix and listed in Table 1.
when applied for the shunt APFs: it is robust in operation The controller gains of VPI controllers are tuned based on
and capable of compensating very high-order (up to 37th) the relationship of Lsh and Rsh. When these parameters
harmonic currents without requiring a time delay change, the coefcient, Krh = KphRsh/Lsh, is no longer the
compensator [29]. The open-loop transfer function of the assigned value. To investigate the robustness of the VPI
VPI controller is described as controller against the parameter variations, Bode diagram of
(10) is plotted in Fig. 8 with respect to the different values
 of Lsh. Judging from Bode diagram in Fig. 8, the inductor
Kph s2 + Krh s parameter variation has no effect on the system stability of
GVPI = (9)
h=6, 12, 18 s2 + (hvs )2 the PI-VPI current controller because a unity gain and
zero-phase shift at the selected resonant frequencies such as
where Kph and Krh are the proportional and the resonant gains 360, 720 and 1080 Hz are maintained regardless of the
at the hth-order harmonic. variation of Lsh.
In addition, the shunt APF is also responsible for regulating Similar to the PR and resonant controllers, the transfer
the DC-link voltage of the UPQC. Hence, a PI controller is function of the PI and the VPI controllers are discretised for
also needed to regulate the fundamental current to charge digital implementation
the DC-link capacitor. As a result, the current controller of
the shunt APF consists of a PI controller and three VPI 1
GPI (z) = Kp +Ki Ts
controllers as shown in Fig. 6. 1z1
 Kph +(Krh Ts 2Kph )z1 (Krh Ts Kph )z2
GVPI (z) =
4.2 Analysis of proposed current controller
h=6,12,18
12cos(hvs Ts )z1 +z2
According to Fig. 6, the closed-loop transfer function of the (11)
proposed current controller is determined as
In the discrete time domain, the same controller gains
GPIVPI (s)GL (s) designed in Table 1 can be used for the PI-VPI controller in
GC = (10) (11) because the sampling period TS is very short.
1 + GPIVPI (s)GL (s)

where GL = 1/(Lshs + Rsh) is the transfer function of the Lsh Table 1 Controller gains of PI-VPI controllers
inductor.
By selecting the resonant gains as Krh = KphRsh/Lsh, the VPI Kp = 2 Ki = 50
controller has only one gain to be tuned, that is, Kph. Fig. 7 Kp6 = 0.8 Kr6 = 20
Kp12 = 0.6 Kr12 = 15
illustrates the Bode diagram of (10) with respect to different Kp18 = 0.3 Kr18 = 7.5
values of Kph. In Fig. 7, it is obvious that the proposed

IET Gener. Transm. Distrib., pp. 110 5


doi: 10.1049/iet-gtd.2013.0636 & The Institution of Engineering and Technology 2014
www.ietdl.org
board and transferred to the driver circuit by bre optic
cables. The harmonic components and the total harmonic
distortions (THDs) are measured by a power analyser
(HIOKI 3193). When the DC-link voltage reaches the
steady-state value Vdc after the STS is closed, the control
algorithm of the UPQC is activated. To assess the
performance of the proposed UPQC experimentally, we
consider three cases: (i) voltage sag compensation;
(ii) voltage distortions and current harmonic compensation;
and (iii) voltage sag, voltage distortions and current
harmonic compensation.

5.1 Voltage sag compensation


Since the voltage sag is compensated by the series APF, the
Fig. 8 Closed-loop Bode diagrams of the VPI controllers with
shunt APF is not activated and a DC power source is
different values of the inductor parameters
supplied at the DC-link voltage of UPQC. Also, only the
three-phase resistive load is connected at the load side for
the sake of simplicity. In addition, unbalanced voltage sags
5 Experimental results are considered to investigate the compensating performance
of the UPQC since the voltage sags are generally occurred
To validate the feasibility of the proposed control algorithm, with unbalance and the performance of the UPQC under
an experimental platform is built in the laboratory as shown in unbalanced sags is more crucial.
Fig. 9. The experimental system consists of a three-phase Fig. 10 shows the experimental results of the UPQC
power supply, an UPQC, a linear load, a non-linear load compensating an unbalanced voltage sag by using the
and the system parameters are listed in Table 2. The supply conventional PI controller. In this case, a 30% unbalanced
voltage is generated by a programmable AC power source sag accompanied by a 20 phase shift (jump) is generated
(Chroma 61704), which is able to produce either voltage during 20 cycles. In Fig. 10, by using the PI controller, it is
sags or distorted supply voltage in order to investigate the obvious that the load voltage (vLabc) is unable to be
performance of the proposed control strategy. The series maintained balanced at its rated level during the voltage
APF and the shunt APF of the UPQC are developed by six sag. In fact, the PI controller cannot accurately regulate the
insulated gate bipolar transistor modules negative sequence component in the unbalanced voltage
FMG2G75US120. The non-linear load is composed of the because it behaves as second harmonic in the dq reference
three-phase diode rectier with a resistance load with frame. Therefore, the conventional PI controller is unable to
6 kVA (power)/380 V (voltage) ratings, whereas the deal with unbalanced sag conditions.
three-phase resistance load is used as the linear load. The In contrast, by using the proposed control scheme, the load
control algorithm is implemented using a 32 bit voltage can be effectively compensated to be sinusoidal as
oating-point DSP TMS320F28335 by Texas Instruments. shown in Fig. 11. According to Fig. 11, thanks to the
The control sampling and switching frequencies are set to effectiveness of the PR controller in regulating both the
be 10 and 5 kHz, respectively. Fig. 9a shows the hardware positive and negative sequence components of unbalanced
conguration to implement the proposed UPQC control voltage, the load voltage is maintained balanced at its rated
algorithm. The PWM control signals are generated by DSP value even though an unbalanced voltage sag with a phase

Fig. 9 Hardware conguration and experimental platform of the proposed UPQC


a Hardware conguration
b Experimental platform

6 IET Gener. Transm. Distrib., pp. 110


& The Institution of Engineering and Technology 2014 doi: 10.1049/iet-gtd.2013.0636
www.ietdl.org

Fig. 10 Experimental result of UPQC by using the PI controller

Fig. 11 Experimental result of UPQC using the proposed control scheme under
a Sinusoidal supply voltage
b Distorted supply voltage

IET Gener. Transm. Distrib., pp. 110 7


doi: 10.1049/iet-gtd.2013.0636 & The Institution of Engineering and Technology 2014
www.ietdl.org

Fig. 12 Experimental results of UPQC to compensate voltage distortions and current harmonics

jump occurs in Fig. 11a. The proposed control strategy voltage and the supply current sinusoidal. The THD values
provides not only good steady-state performance, but also of the load voltage and the supply current are 1.2 and
good dynamic response with the unbalanced voltage sag: 1.95%, respectively, which completely comply with the
the load voltage is always maintained undisturbed even at IEEE 519-1992 standard [30]. These results reveal that the
the transient time. Meanwhile, in Fig. 11b, we can see that proposed control strategy is capable of simultaneously
the proposed UPQC effectively compensates both dealing with the harmonic voltage and harmonic current
unbalanced voltage sag and voltage harmonics in the supply problems: both the load voltage and the supply current are
voltage to maintain the load voltage balanced and compensated to be sinusoidal without the demand of the
sinusoidal at the desired value. The THD of the load voltage harmonic or current harmonic detectors.
voltage is reduced to 1.2%, whereas the THD of the supply
voltage is 8.1%. 5.3 Voltage sag, voltage distortions and current
The experimental results verify that the proposed control harmonics compensation
strategy is able to effectively tackle both voltage sags and
voltage harmonics to improve the load voltage performance. To verify the effectiveness of the proposed control in case
voltage sag, voltage distortions and current harmonics exist
5.2 Voltage distortions and current harmonic all together, the total performance is evaluated. It can be
compensation seen in Fig. 13 that before the voltage sag occurs, the
UPQC compensates the harmonics presented in the supply
The performance of the UPQC to compensate the voltage voltage and the load current to make the load voltage and
distortions and the current harmonics is investigated in this the supply current sinusoidal. At times when the voltage
section. In the experimental test, a three-phase diode rectier sag takes place, the UPQC injects not only the harmonics,
is connected at the load side as the non-linear load and the but also the fundamental voltage to maintain the voltage
THD of the non-linear load current is 25.2%. Meanwhile, the at the load terminal sinusoidal at its rated value. In fact,
supply voltage is distorted with a THD is about 8.1%. In this to compensate the voltage sag, the UPQC requires a
case, both the series and the shunt APF are activated to certain amount of active power from the supply side
compensate harmonics in supply voltage and load current. through the shunt APF. Hence, during the voltage sag,
Fig. 12 shows that the harmonics in the supply voltage, as both the shunt APF current (isha) and the source current
well as the harmonic currents produced by the non-linear (iSa) are increased as compared with before the voltage
load, are effectively compensated to maintain both the load sag. The THD values of the load voltage and the supply

8 IET Gener. Transm. Distrib., pp. 110


& The Institution of Engineering and Technology 2014 doi: 10.1049/iet-gtd.2013.0636
www.ietdl.org

Fig. 13 Experimental results of UPQC to compensate the voltage sag, voltage distortions and current harmonics

current after compensation are about 1.22 and 1.87%, and distortion conditions. Under the distorted supply
respectively, which also comply with the IEEE-519 voltage with a non-linear load in the system, the UPQC
standard. In this test case, the THD value of the supply reduced the THD of the load voltage and the supply current
current is slightly reduced compared with Case B because to <1.22 and 1.95%, respectively, which completely
the magnitude of the supply current is increased during comply with the IEEE 519-1992 standard.
the voltage sag. The proposed control method not only improves the
Finally, we can say that the UPQC with the proposed compensation performance, but also can reduce the system
control strategy is able to simultaneously tackle various cost of the UPQC since it requires fewer sensors
power quality issues such as voltage sags, voltage compared with the conventional methods. Furthermore, the
unbalance, voltage distortions and current harmonics: the accuracy and reliability of the UPQC was improved
load voltage and the supply current are always maintained signicantly because the proposed control strategy was
sinusoidal regardless of the supply voltage and the load operated without the voltage sag/harmonic and current
current conditions. harmonic detectors. Thanks to these advantages, the
proposed control method can be applied for the UPQC as a
cost effective solution.
6 Conclusion
An enhanced resonant control strategy for the UPQC to deal 7 Acknowledgment
with various power quality issues such as voltage sags,
voltage unbalanced, voltage distortion and current This work was supported by the National Research Foundation
harmonics was proposed in this paper. The feasibility of the of Korea Grant funded by the Korean Government.
proposed control strategy was veried through various
experimental tests in which the load voltage is maintained
balanced and sinusoidal at the desired value regardless of 8 References
the voltage sag, unbalanced and distorted supply voltage
conditions. In addition, the supply current is maintained 1 Smith, J.C., Lamoree, J., Vinett, P., Duffy, T., Klein, M.: The impact of
voltage sags on industrial plant loads. Proc. Int. Conf. Power Quality:
sinusoidal irrespective of the non-linear load current. The End-Use Applications and Perspectives (PQA91), 1991, pp. 171178M
proposed control strategy exhibited a fast dynamic response 2 Bollen, M.: Understanding power quality problems, voltage sags and
as well as good steady-state performance under voltage sag interruptions (IEEE Press, Piscataway, NJ, 1999)

IET Gener. Transm. Distrib., pp. 110 9


doi: 10.1049/iet-gtd.2013.0636 & The Institution of Engineering and Technology 2014
www.ietdl.org
3 Nielsen, J.G., Blaabjerg, F.: A detailed comparison of system 21 Kinhal, V.G., Agarwal, P., Gupta, H.O.: Performance investigation of
topologies for dynamic voltage restorers, IEEE Trans. Ind. Appl., neural-network-based unied power-quality conditioner, IEEE Trans.
2005, 41, (5), pp. 12721280 Power Deliv., 2011, 26, (1), pp. 431437
4 Nielsen, J.G., Newman, M., Nielsen, H., Blaabjerg, F.: Control and 22 Karanki, S.B., Mishra, M.K., Kumar, B.K.: Particle swarm
testing of a dynamic voltage restorer (DVR) at medium voltage level, optimization-based feedback controller for unied power-quality
IEEE Trans. Power Electron., 2004, 19, (3), pp. 806813 conditioner, IEEE Trans. Power Deliv., 2010, 25, (4), pp. 28142824
5 Awad, H., Svensson, J.: Double vector control for series connected 23 Trinh, Q.N., Lee, H.H.: Improvement of power quality under distorted
voltage source converters. Proc. IEEE Power Engineering Society source and nonlinear load conditions. Proc. 2012 IEEE Seventh Int.
Winter Meeting, New York, NY, 2002, vol. 2, pp. 707712 Power Electronics and Motion Control Conf. ECCE Asia, Harbin,
6 Awad, H., Svensson, J., Bollen, M.: Mitigation of unbalanced voltage China, June 2012, pp. 546551
dips using static series compensator, IEEE Trans Power Electron., 24 Rodrguez, P., Teodorescu, R., Candela, I., et al.: New
2004, 19, (3), pp. 837846 positive-sequence voltage detector for grid synchronization of power
7 Li, Y.W., Blaabjerg, F., Vilathgamuwa, D.M., et al.: Design and converters under faulty grid conditions. Proc. 37th IEEE Power
comparison of high performance stationary-frame controllers for DVR Electronics Specialist Conf. PESC 2006, June 2006, pp. 17
implementation, IEEE Trans. Power. Electron., 2007, 22, (2), 25 Zmood, D., Holmes, D.: Stationary frame current regulation of PWM
pp. 602612 inverters with zero steady-state error, IEEE Trans. Power Electron.,
8 Li, Y.W., Vilathgamuwa, D.M., Blaabjerg, F., Loh, P.C.: A robust 2003, 18, (3), pp. 814822
control scheme for medium-voltage-level DVR implementation, IEEE 26 Phan, V.-T., Lee, H.-H.: Control strategy for harmonic elimination in
Trans. Ind. Electron., 2007, 54, (4), pp. 22492261 stand-alone DFIG applications with nonlinear loads, IEEE Trans.
9 Fitzer, C., Barnes, M., Green, P.: Voltage sag detection technique for a Power Electron., 2011, 26, (9), pp. 26622675
dynamic voltage restorer, IEEE Trans. Ind. Appl., 2004, 40, (1), 27 Liu, C., Chen, W., Blaabjerg, F., et al.: Optimized design of resonant
pp. 203212 controller for stator current harmonic compensation in DFIG wind
10 Teke, A., Bayindir, K.., Tmay, M.: Fast sag/swell detection method turbine systems. Proc. Applied Power Electronics Conf. Exposition
for fuzzy logic based dynamic voltage restorer, IET Gener. Transm. (APEC) 2012, 2012, pp. 20382044
Distrib., 2009, 4, (1), pp. 112 28 Yepes, A.G., Freijedo, F.D., Lopez, O., et al.: High-performance digital
11 Fujita, H., Akagi, H.: The unied power quality conditioner: the resonant controllers implemented with two integrators, IEEE Trans.
integration of series and shunt active lters, IEEE Trans. Power Power Electron., 2011, 26, (2), pp. 563576
Electron., 1998, 13, (2), pp. 315322 29 Lascu, C., Asiminoaei, L., Boldea, I., et al.: High performance current
12 Akagi, H., Watanabe, E.H., Aredes, M.: Instantaneous power theory controller for selective harmonic compensation in active power lters,
and applications to power conditioning (Wiley-IEEE Press, Hoboken, IEEE Trans. Power Electron., 2007, 22, (5), pp. 18261835
NJ, 2007), pp. 294326 30 IEEE Recommended Practices and Requirements for Harmonic Control
13 Khadkikar, V.: Enhancing electric power quality using UPQC: a in Electrical Power Systems, IEEE Standard 519-1992, 1992
comprehensive overview, IEEE Trans. Power Electron., 2012, 27,
(5), pp. 22842297
14 Teke, A., Saribulut, L., Tmay, M.: A novel reference signal generation 8 Appendix
method for power quality improvement of unied power quality
conditioner, IEEE Trans. Power Deliv., 2011, 26, (4), pp. 22052214
15 Teke, A., Meral, M.E., Cuma, M.U., et al.: OPEN unied power quality See Table 2.
conditioner with control based on enhanced phase locked loop, IET
Gener. Transm. Distrib., 2013, 7, (3), pp. 254264
16 Kesler, M., Ozdemir, E.: Synchronous reference frame based control Table 2 UPQC system parameters
method for UPQC under unbalanced and distorted load conditions,
IEEE Trans. Ind. Electron., 2011, 58, (9), pp. 39673975 Parameters Values
17 Khadkikar, V., Chandra, A.: A novel structure for three-phase four-wire
distribution system utilizing unied power quality conditioner (UPQC), supply line-line voltage VS 380 Vrms
IEEE Trans. Ind. Appl., 2009, 45, (5), pp. 18971902 [root mean square (RMS)]
18 Graovac, D., Katic, V., Rufer, A.: Power quality problems frequency fS 60 Hz
compensation with universal power quality conditioning system, load three-phase resistive load Rac 30
IEEE Trans. Power Deliv., 2007, 22, (2), pp. 968976 diode rectifier resistive load RL 40
19 Khadkikar, V., Chandra, A., Barry, A.O., et al.: Power quality DC-link reference voltage
Vdc 700 V
enhancement utilizing single phase unied power quality conditioner: capacitance Cdc 2.2 mF
digital signal processor-based experimental validation, IET Power shunt APF Lsh inductance Lsh 2 mH
Electron., 2011, 4, (3), pp. 323331 Lsh resistance Rsh 0.05
20 Basu, M., Das, S.P., Dubey, G.K.: Investigation on the performance series APF LC filter inductance Lf 0.7 mH
of UPQC-Q for voltage sag mitigation and power quality LC filter capacitance Cf 27 F
improvement at a critical load point, IET Gener. Transm. Distrib., damping resistance Rf 5
2008, 2, (3), pp. 414423

10 IET Gener. Transm. Distrib., pp. 110


& The Institution of Engineering and Technology 2014 doi: 10.1049/iet-gtd.2013.0636

Вам также может понравиться