Академический Документы
Профессиональный Документы
Культура Документы
org
Published in IET Generation, Transmission & Distribution
Received on 5th September 2013
Revised on 12th March 2014
Accepted on 21st May 2014
doi: 10.1049/iet-gtd.2013.0636
ISSN 1751-8687
Abstract: This study proposes an enhanced resonant control strategy for the unied power quality conditioner (UPQC) to
simultaneously tackle voltage sags, unbalance and distortions on the supply side as well as current harmonics on the load
side. The proposed control strategy is developed in both the series and shunt active power lters (APFs) of the UPQC. In the
series APF, a proportionalresonant controller and a resonant controller are employed to mitigate voltage sags, unbalance and
distortions, whereas a proportionalintegral (PI) controller and three vector PI controllers are used in the shunt APF to
compensate harmonic currents. The performance of the proposed UPQC control scheme is signicantly improved compared
with the conventional control strategy owing to the superiority of the resonant controllers. In addition, voltage sag/harmonic
and current harmonic detectors are not required in the proposed control scheme, which helps to simplify the control strategy
and to improve the control accuracy. The proposed control strategy is theoretically analysed and its feasibility is validated
through experiments.
Designing the gains of resonant controller is not a simple task, 1 cos (6vs Ts )z1
GR (z) = Kr6 vc Ts
especially when compensating high-order harmonics [26, 27]. 1 (2 cos (6vs Ts ) 2vc Ts )z1 + z2
In this paper, the Naslin polynomial technique is used to
(7)
determine the resonant controller gains [26]. In addition, Kp
and c values of the PR controller should be designed to be
sufciently large to make the PR controller have a wide where z is the shift operator and TS = 100 s denotes the
bandwidth, and hence provide a fast response against sampling period.
voltage sags. According to the design procedure presented For digital implementation, (6) and (7) with the same gains
in [26], the controller gains of PR and resonant controllers in continuous time domain are used because the sampling
in Fig. 4 are selected based on the system parameters given period TS is very short.
in Appendix as follows: Kp = 2, Kr1 = 2000, c = 10rad/s
and Kr6 = 500. 4 Control strategy in the shunt APF
Since these controller gains depend on the LC lter
parameters, the effect of the lter parameter variations on 4.1 Current harmonics compensation
the system stability is considered. From Fig. 4, the
closed-loop transfer function of the PR-R controller is given The main purpose of the shunt APF is to mitigate harmonic
as follows currents produced by the non-linear load. The non-linear
load under consideration is a three-phase diode rectier
GPRR (s)GLC (s) supplying a DC load. This type of load draws harmonic
GC = (5) currents into the networks that have odd orders: 6n 1 (n =
1 + GPRR (s)GLC (s)
1, 2, 3, ) of S. As a result, the load current consists of
the fundamental (iL1) and harmonic components (iLh) as
where GLC = 1/(LfCfs 2 + RfCfs + 1) is the transfer function of
the LC lter.
Fig. 5 shows the Bode diagram of (5) with respect to iL (vt) = iL1 (vt) + iLh (vt) (8)
different values of Lf and Cf. In Fig. 5, the proposed PR-R h=6n+1
where GL = 1/(Lshs + Rsh) is the transfer function of the Lsh Table 1 Controller gains of PI-VPI controllers
inductor.
By selecting the resonant gains as Krh = KphRsh/Lsh, the VPI Kp = 2 Ki = 50
controller has only one gain to be tuned, that is, Kph. Fig. 7 Kp6 = 0.8 Kr6 = 20
Kp12 = 0.6 Kr12 = 15
illustrates the Bode diagram of (10) with respect to different Kp18 = 0.3 Kr18 = 7.5
values of Kph. In Fig. 7, it is obvious that the proposed
Fig. 11 Experimental result of UPQC using the proposed control scheme under
a Sinusoidal supply voltage
b Distorted supply voltage
Fig. 12 Experimental results of UPQC to compensate voltage distortions and current harmonics
jump occurs in Fig. 11a. The proposed control strategy voltage and the supply current sinusoidal. The THD values
provides not only good steady-state performance, but also of the load voltage and the supply current are 1.2 and
good dynamic response with the unbalanced voltage sag: 1.95%, respectively, which completely comply with the
the load voltage is always maintained undisturbed even at IEEE 519-1992 standard [30]. These results reveal that the
the transient time. Meanwhile, in Fig. 11b, we can see that proposed control strategy is capable of simultaneously
the proposed UPQC effectively compensates both dealing with the harmonic voltage and harmonic current
unbalanced voltage sag and voltage harmonics in the supply problems: both the load voltage and the supply current are
voltage to maintain the load voltage balanced and compensated to be sinusoidal without the demand of the
sinusoidal at the desired value. The THD of the load voltage harmonic or current harmonic detectors.
voltage is reduced to 1.2%, whereas the THD of the supply
voltage is 8.1%. 5.3 Voltage sag, voltage distortions and current
The experimental results verify that the proposed control harmonics compensation
strategy is able to effectively tackle both voltage sags and
voltage harmonics to improve the load voltage performance. To verify the effectiveness of the proposed control in case
voltage sag, voltage distortions and current harmonics exist
5.2 Voltage distortions and current harmonic all together, the total performance is evaluated. It can be
compensation seen in Fig. 13 that before the voltage sag occurs, the
UPQC compensates the harmonics presented in the supply
The performance of the UPQC to compensate the voltage voltage and the load current to make the load voltage and
distortions and the current harmonics is investigated in this the supply current sinusoidal. At times when the voltage
section. In the experimental test, a three-phase diode rectier sag takes place, the UPQC injects not only the harmonics,
is connected at the load side as the non-linear load and the but also the fundamental voltage to maintain the voltage
THD of the non-linear load current is 25.2%. Meanwhile, the at the load terminal sinusoidal at its rated value. In fact,
supply voltage is distorted with a THD is about 8.1%. In this to compensate the voltage sag, the UPQC requires a
case, both the series and the shunt APF are activated to certain amount of active power from the supply side
compensate harmonics in supply voltage and load current. through the shunt APF. Hence, during the voltage sag,
Fig. 12 shows that the harmonics in the supply voltage, as both the shunt APF current (isha) and the source current
well as the harmonic currents produced by the non-linear (iSa) are increased as compared with before the voltage
load, are effectively compensated to maintain both the load sag. The THD values of the load voltage and the supply
Fig. 13 Experimental results of UPQC to compensate the voltage sag, voltage distortions and current harmonics
current after compensation are about 1.22 and 1.87%, and distortion conditions. Under the distorted supply
respectively, which also comply with the IEEE-519 voltage with a non-linear load in the system, the UPQC
standard. In this test case, the THD value of the supply reduced the THD of the load voltage and the supply current
current is slightly reduced compared with Case B because to <1.22 and 1.95%, respectively, which completely
the magnitude of the supply current is increased during comply with the IEEE 519-1992 standard.
the voltage sag. The proposed control method not only improves the
Finally, we can say that the UPQC with the proposed compensation performance, but also can reduce the system
control strategy is able to simultaneously tackle various cost of the UPQC since it requires fewer sensors
power quality issues such as voltage sags, voltage compared with the conventional methods. Furthermore, the
unbalance, voltage distortions and current harmonics: the accuracy and reliability of the UPQC was improved
load voltage and the supply current are always maintained signicantly because the proposed control strategy was
sinusoidal regardless of the supply voltage and the load operated without the voltage sag/harmonic and current
current conditions. harmonic detectors. Thanks to these advantages, the
proposed control method can be applied for the UPQC as a
cost effective solution.
6 Conclusion
An enhanced resonant control strategy for the UPQC to deal 7 Acknowledgment
with various power quality issues such as voltage sags,
voltage unbalanced, voltage distortion and current This work was supported by the National Research Foundation
harmonics was proposed in this paper. The feasibility of the of Korea Grant funded by the Korean Government.
proposed control strategy was veried through various
experimental tests in which the load voltage is maintained
balanced and sinusoidal at the desired value regardless of 8 References
the voltage sag, unbalanced and distorted supply voltage
conditions. In addition, the supply current is maintained 1 Smith, J.C., Lamoree, J., Vinett, P., Duffy, T., Klein, M.: The impact of
voltage sags on industrial plant loads. Proc. Int. Conf. Power Quality:
sinusoidal irrespective of the non-linear load current. The End-Use Applications and Perspectives (PQA91), 1991, pp. 171178M
proposed control strategy exhibited a fast dynamic response 2 Bollen, M.: Understanding power quality problems, voltage sags and
as well as good steady-state performance under voltage sag interruptions (IEEE Press, Piscataway, NJ, 1999)