Cubex standard expansion vessels
Operation
PRESSURE
FLEXCON Cubex 1
Static 2
Boiler rating 3
Water A System connection
expansion height (approximate content 3/4 BSP(M)
vessel (up to) method) (accurate B except 80l which is
Before filling the installation. method) 1 BSP (M)
The diaphragm is pushed up against the
vessel wall by the pre-set initial gas charge. Type Metres Kw BTU Litres A mm B mm Weight
The gas charge supports the pressure exerted
by the static height of water above the vessel. Cubex 2/05 5 3 10,200 32 194 170 2.2 kg
Cubex 4/05 5 5 17,100 64 194 275 3.1 kg
Cubex 8/05 5 11 37,500 128 245 298 4.4 kg
TEMP
Cubex 12/05 5 16 54,600 192 286 331 5.8 kg
FLEXCON
Cubex 18/05 5 24 81,900 288 328 324 7.5 kg
Cubex 25/05 5 33 112,600 400 358 377 9.6 kg
Cubex 35/05 5 47 160,364 560 396 434 11.8 kg
PRESSURE
FLEXCON
Cubex 50/05 5 67 228,604 800 437 491 15.1 kg
Cubex 80/05 5 107 365,084 1281 519 558 22.1 kg
On filling. Cubex 12/1 10 11 37,500 134 286 331 5.8 kg
When the system is filled there will be a small Cubex 18/1 10 17 58,000 202 328 324 7.5 kg
amount of water in the Cubex expansion
vessel. Cubex 25/1 10 23 78,500 280 358 377 9.6 kg
Cubex 35/1 10 33 112,596 392 396 434 11.8 kg
Cubex 50/1 10 47 160,364 560 437 491 15.1 kg
Cubex 80/1 10 75 255,900 896 519 558 22.1 kg
TEMP
FLEXCON
Cubex 35/1.5 15 21 71,652 252 396 434 11.8 kg
Cubex 50/1.5 15 30 102,360 360 437 491 15.1 kg
Cubex 80/1.5 15 48 163,776 576 519 558 22.1 kg
PRESSURE
FLEXCON
1
Static height is the vertical distance from expansion vessel to highest point of the
At operating temperature. system above expansion vessel.
The total system water expansion is taken up 2
Sizing assumes 12 litres in the system per Kw of boiler power as suggested in
within the vessel. The pressure has risen and BS.7074:1989. Part 1.
the diaphragm is virtually static with equal 3
Use this method where possible. Calculations to BS.7074:1989. Part 1.
pressure on either side.
Flamco Cubexpaks
Cubexpaks
A complete boxed set of equipment
that fits directly on the Cubex
expansion vessel.
This provides a compact and neat
assembly of all necessary
components for a domestic sealed
system. Cubexpaks are sized in the
same way as standard expansion
vessels.
Cubexpak type A
Cubexpak type A consists of: Cubex
expansion vessel, vessel manifold,
combined safety valve and pressure
gauge, double check valve with test
point, flexible braided hose with quick
fit connections and O ring seals,
stop valve for connection to water Cubexpak Dimensions Weight
mains, MB2 vessel mounting bracket type mm Kg
with wall plugs and screws and end
A B
caps for fitting on the exposed ends
Cubexpak type A of the flexible hose when it is 4/05 A 194 383 4.3
removed. 4/05 B 194 336 4.3
1
2
3
Cubexpak type B 8/05 A 245 406 5.6
0 4
bar
FLEXCON
1 3
0
bar
4
25/1 A 358 485 10.8
FLEXCON
1. Cubex expansion vessel - locate near the inlet side of the circulating pump.
2. Boiler.
3. Circulating pump - locate in the boiler flow.
4. Prescor safety valve - locate on top of or above boiler if possible.
5. Flexcon pressure gauge - locate in site of the filling point.
6. Double check valve - locate at any convenient point but not at the bottom of the system.
7. Flamco funnel - locate on the outlet of the safety valve.
8. Flamcovent de-aerator - locate in the boiler flow, before the pump.
9. Stop valve - locate to mains supply.
10. Flexible hose - locate between the stop valve and the double check valve.
11. Flexvent automatic air vent - locate where air is naturally collected in the system.
11
4 5
8 3 Minimum requirements:
7 1. Cubex expansion vessel.
2 4. Prescor safety valve.
1
6 5. Flexcon pressure gauge.
Mains supply
9 6. Double check valve.
10