Вы находитесь на странице: 1из 13

12019

LNG TRUCK LOADING FACILITY

Document Title: Logic Control Diagrams

Document Number: 12019-035-IN-DIA-2007

Revision: A

A Issued for Internal Review 11.Apr.2017


FPelaez PTrigueros DGonzales
Project
By Check Approved
Approved
Rev Revision Description Approval Date
EITL EITL COPE WPTL

Revisions Approver [PERU LNG S.R.L.]

Pages: 1 OF 13
Logic Control Diagrams

INPUTS
Document Number Title Status

PLNG-ENG-14023-702-000 Cause and Effect Diagram Charts 0

12019-035-PR-PID-1001 Piping and Instrumentation Diagram 1

12019-035-PR-PID-1002 Piping and Instrumentation Diagram 1

12019-035-IN-CAE-2001 Cause & Effect Diagram A

REVISION NOTED AND HOLDS


Revision Description of Changes & Holds

A Issued for Internal Review

Rev.A 11.Apr.2017 Page 2 of 13 12019-035-IN-DIA-2007


Logic Control Diagrams

Contents
1. SCOPE...............................................................................................4
2. DESCRIPTION.....................................................................................4
3. LOGIC CONTROL.................................................................................4
3.1 Power supply interruption (XS-135714)..............................................................................5
3.2 Loading control valve solenoid LG BAY 1 (FV-135110).....................................................6
3.3 Loading valve positioned setpoint LG BAY 1 to <5% (FV-135110)....................................6
3.4 Loading valve positioned setpoint LG BAY 1 to 0% (FV-135110)......................................7
3.5 Loading Safety on/off valve LG BAY 1 (ESDV-135006)......................................................8
3.6 Return Safety on/off valve NG BAY 1 (ESDV-135005)........................................................9
3.7 Traffic Light Green Output BAY 1 (XL-135138)...................................................................9
3.8 Traffic Light Red input BAY 1 (XL-135139).......................................................................10
3.9 Acoustic Reminder (UA-135001).......................................................................................10
3.10 Inlet Gate TLF (XZ-135002).............................................................................................10
3.11 Output Gate TLF (XZ-135003)........................................................................................11
3.12 Emergency Shutdown (XS-135010)...............................................................................11
3.13 Valve positioned setpoint Recirculation PRE-SKID to 0% (TV-135008)......................11
3.14 Depressurizing Safety on/off valve (ESDV-135004).....................................................12
3.15 Valve positioned setpoint Refrigeration PRE-SKID to 0% (HV-135009)......................12
3.16 Green Traffic Light Output Depressurization (XL-135170)..........................................12
3.17 Red Traffic Light Output Depressurization (XL-135171)..............................................13
3.18 Safety on/off valve to BOG (ESDV-135007)...................................................................13
3.19 Failure alarm valve operating system...........................................................................13

Rev.A 11.Apr.2017 Page 3 of 13 12019-035-IN-DIA-2007


Logic Control Diagrams

1 SCOPE

The main aim of this document is to describe how logic control works according to previous
requirements and restrictions were imposed by both Plant and LNG transfer, including any kind
of signal whose purpose is to activate an output.

1. DESCRIPTION

Within Cause & Effect Diagrams, all outputs were linked with every input that could activate this
concerning one.

All in all, we would need to show logic gates operation in order to summarize the whole control
according to these signals.

2 LOGIC CONTROL

Each output will be represented with its logic gate and inputs which could activate them.

Rev.A 11.Apr.2017 Page 4 of 13 12019-035-IN-DIA-2007


Logic Control Diagrams

1 Power supply interruption (XS-135714)

EA-135710
EA-135705
XS-135020
1
XS-135011
XS-135030
HS-135012
HS-135133
XZ-135178
HS-135076
XS-135135
XS-135136
ZSO-135116
ZSO-135118
ZSC-135113
ZSC-135119
ZSC-135117
XV-135110
WS-135140A
WS-135140B XS-135714
WS-135140C
FAHH-135111
FAHH-135103
FAHH-135110
PAHH-135109
PAHH-135102
PALL-135109
PALL-135102
PAHH-135017
TALL-135101
TAHH-135101
TAHH-135016
TALL-135016
HS-135007
HS-135005
HS-135006
HS-135110

Rev.A 11.Apr.2017 Page 5 of 13 12019-035-IN-DIA-2007


Logic Control Diagrams

2 Loading control valve solenoid LG BAY 1 (FV-135110)

EA-135710
EA-135705
XS-135020
1
XS-135011
XS-135030
HS-135012
HS-135013
HS-135133
XS-135040
XZ-135178
HS-135076
XS-135135
XS-135136
ZSO-135116
ZSO-135118
ZSC-135113
ZSC-135119
ZSC-135117
XV-135110 FV-135110
WS-135140A
WS-135140B
WS-135140C
FAHH-135111
FAHH-135103
FAHH-135110
PAHH-135109
PAHH-135102
PALL-135109
PALL-135102
TAHH-135108
TALL-135101
TAHH-135101
HS-135007
HS-135110

3 Loading valve positioned setpoint LG BAY 1 to <5% (FV-135110)

1
EA-135710 FV-135110

Rev.A 11.Apr.2017 Page 6 of 13 12019-035-IN-DIA-2007


Logic Control Diagrams

4 Loading valve positioned setpoint LG BAY 1 to 0% (FV-135110)

EA-135710
EA-135705
XS-135020
1
XS-135011
XS-135030
HS-135012
HS-135013
HS-135133
XS-135040
XZ-135178
HS-135076
XS-135135
XS-135136
ZSO-135116
ZSO-135118
ZSC-135113
ZSC-135119 FV-135110
ZSC-135117
XV-135110
WS-135140A
WS-135140B
WS-135140C
FAHH-135111
FAHH-135103
FAHH-135110
PAHH-135109
PAHH-135102
PALL-135109
PALL-135102
TALL-135101
TAHH-135101
HS-135110

Rev.A 11.Apr.2017 Page 7 of 13 12019-035-IN-DIA-2007


Logic Control Diagrams

5 Loading Safety on/off valve LG BAY 1 (ESDV-135006)

EA-135710
EA-135705
XS-135020
1
XS-135011
XS-135030
HS-135012
HS-135013
HS-135133
XS-135040
XZ-135178
HS-135076
XS-135135
XS-135136
ZSO-135116
ZSO-135118
ZSC-135113
ZSC-135119 ESDV-135006
ZSC-135117
XV-135110
WS-135140A
WS-135140B
WS-135140C
FAHH-135111
FAHH-135103
FAHH-135110
PAHH-135109
PAHH-135102
PALL-135109
PALL-135102
TALL-135101
TAHH-135101
HS-135106

Rev.A 11.Apr.2017 Page 8 of 13 12019-035-IN-DIA-2007


Logic Control Diagrams

6 Return Safety on/off valve NG BAY 1 (ESDV-135005)

EA-135710
EA-135705
XS-135020
1
XS-135011
XS-135030
HS-135012
HS-135013
HS-135133
XS-135040
XZ-135178
HS-135076
XS-135135
XS-135136
ZSO-135116
ZSO-135118
ZSC-135113
ZSC-135119 ESDV-135005
ZSC-135117
XV-135110
WS-135140A
WS-135140B
WS-135140C
FAHH-135111
FAHH-135103
FAHH-135110
PAHH-135109
PAHH-135102
PALL-135109
PALL-135102
TALL-135101
TAHH-135101
HS-135105

7 Traffic Light Green Output BAY 1 (XL-135138)

XS-135011
1
XS-135030
HS-135012 XL-135138
HS-135133
HS-135076

Rev.A 11.Apr.2017 Page 9 of 13 12019-035-IN-DIA-2007


Logic Control Diagrams

8 Traffic Light Red input BAY 1 (XL-135139)

XS-135011
1
XS-135030
HS-135012 XL-135139
HS-135133
HS-135076

9 Acoustic Reminder (UA-135001)

XS-135011
1
XS-135030
HS-135012
HS-135133 UA-135001
HS-135075
XZ-135179
HS-135076

10 Inlet Gate TLF (XZ-135002)

XS-135011
1
XS-135030
HS-135012
HS-135133 XZ-135002
HS-135075
XZ-135179
HS-135076

Rev.A 11.Apr.2017 Page 10 of 13 12019-035-IN-DIA-2007


Logic Control Diagrams

11 Output Gate TLF (XZ-135003)

XS-135011
1
XS-135030
HS-135012
HS-135133 XZ-135003
HS-135075
XZ-135179
HS-135076

12 Emergency Shutdown (XS-135010)

XS-135011
1
XS-135030
HS-135012 XS-135010
HS-135133
HS-135076

13 Valve positioned setpoint Recirculation PRE-SKID to 0% (TV-135008)

EA-135710
EA-135705
1
XS-135020
XS-135011 TV-135008

XS-135030
HS-135076

Rev.A 11.Apr.2017 Page 11 of 13 12019-035-IN-DIA-2007


Logic Control Diagrams

14 Depressurizing Safety on/off valve (ESDV-135004)

EA-135710
EA-135705
XS-135020
XS-135011
1
XS-135030
HS-135075
HS-135077
HS-135174
XZ-135179
HS-135076
XS-135173 ESDV-135004
XS-135180
FAHH-135156
FALL-135156
FB-135156
PAHH-135162
PALL-135162
TALL-135150
TAHH-135016
HS-135004

15 Valve positioned setpoint Refrigeration PRE-SKID to 0% (HV-135009)

EA-135710
EA-135705
1
XS-135020
XS-135011 HV-135009

XS-135030
HS-135076

16 Green Traffic Light Output Depressurization (XL-135170)

XS-135011
XS-135030
1
HS-135075 XL-135170
HS-135174
HS-135076

Rev.A 11.Apr.2017 Page 12 of 13 12019-035-IN-DIA-2007


Logic Control Diagrams

17 Red Traffic Light Output Depressurization (XL-135171)

XS-135011
XS-135030
1
HS-135075 XL-135171
HS-135174
HS-135076

18 Safety on/off valve to BOG (ESDV-135007)

1
PAHH-135017
TALL-135016 ESDV-135007
HS-135007

19 Failure alarm valve operating system

ZSO-135007 1
ZSC-135007
ZSO-135004
ZSC-135004
ZSO-135005 XA-135200
ZSC-135005
ZSO-135006
ZSC-135006
ZSO-135010
ZSC-135010

Rev.A 11.Apr.2017 Page 13 of 13 12019-035-IN-DIA-2007