Вы находитесь на странице: 1из 19

Intrinsic Safety Circuit

Design

Making instruments 3.12 of the ANSI/ISA-RP 12.6-1987


Intrinsically Safe Intrinsically Safe as any device which will neither
intrinsically safe need not Apparatus Applications(%) generate nor store more than 1.2
seem like a nightmare. Here, volts, 0.1 amps, 25 mW or 20 J.
the basics of intrinsic safety Switching 32.0% Examples are simple contacts,
mechanical switches 85.0% thermocouples, RTDs, LEDs,
circuit design are discussed. proximity switches 15.0% noninductive potentiometers, and
resistors. These simple devices do
2-wire transmitters 22.0% not need to be approved as
Paul S. Babiarz Thermocouples & RTDs 13.0% intrinsically safe. If they are
Load cells 8.5% connected to an approved
Solenoid valves 4.5% intrinsically safe associated
Potentiometers 2.5% apparatus (barrier), the circuit is
LEDs 2.0% considered intrinsically safe.
I/P transducers 2.0%
Other devices 13.5% A nonsimple device can create or
store levels of energy that exceed
Total field devices 100.0% those listed above. Typical examples
are transmitters, transducers,
Intrinsic safety prevents instruments solenoid valves, and relays. When
and other low-voltage circuits in Figure 1. Current use of intrinsically safe these devices are approved as
apparatus in hazardous areas.
hazardous areas from releasing intrinsically safe, under the entity
sufficient energy to ignite volatile device, also known as a barrier or concept, they have the following
gases. Although it is used widely in intrinsically safe associated entity parameters: Vmax (maximum
Europe to safely install and operate apparatus; and the field wiring. voltage allowed); Imax (maximum
instrumentation circuits in When designing an intrinsically safe current allowed); Ci (internal
hazardous areas, it has caused circuit, begin the analysis with the capacitance); and Li (internal
much confusion in North American field device. This will determine the inductance).
markets. Many users have heard of type of barrier that can be used so The Vmax and Imax values are
it and want to know more; however, that the circuit functions properly straightforward. Under a fault
most feel uncomfortable applying under normal operating conditions condition, excess voltage or current
intrinsically safe products. One but still is safe under fault conditions. could be transferred to the
reason is that intrinsic safety has intrinsically safe apparatus (field
been a part of Section 504 of the More than 85% of all intrinsically
safe circuits involve commonly device). If the voltage or current
National Electric Code only since exceeds the apparatus Vmax or
1990. In addition, the number of known instruments. Figure 1 shows
the approximate use of intrinsically Imax, the device can heat up or
different products on the market and spark and ignite the gases in the
seemingly endless calculations safe apparatus in hazardous areas.
hazardous area. The Ci and Li
make applying intrinsic safety seem An intrinsically safe apparatus (field values describe the devices ability
like an engineers nightmare. device) is classified either as a to store energy in the form of
This is the first of a series of short simple or nonsimple device. Simple internal capacitance and internal
articles that explain how to make apparatus is defined in paragraph inductance.
the most common field devices Safe Area Intrinsically Safe Barrier Hazardous Area
(thermocouples, RTDs, contacts,
solenoid valves, transmitters, and
Current Limiting
displays) intrinsically safe. We will Fuse Resistor
begin with an introduction to the
practical side of intrinsic safety
circuit design. Input Zener Field
Voltage Diodes Device
Start With The Field Device
All intrinsically safe circuits have
three components: the field device, Instrinsically Safe
Ground
referred to as the intrinsically safe
apparatus; the energy-limiting Figure 2. Barrier circuit
Z-131
5A

Limiting Energy To The Field


Device 2A
To protect the intrinsically safe
apparatus in a hazardous area, an
energy-limiting device must be 1A
installed. This is commonly referred
to as an intrinsically safe associated
apparatus or barrier. Under normal
Z
conditions, the device is passive

Ignition Current (A)


500 mA
and allows the intrinsically safe
apparatus to function properly.
Under fault conditions, it protects Groups C and D
the field circuit by preventing excess Methane
voltage and current from reaching 200 mA Propane
the hazardous area. The basic Ethylene
circuit diagram for an intrinsically
safe barrier is shown in Figure 2. 100 mA

There are three components to a


barrier that limit current and voltage:
a resistor, at least two zener diodes, Groups A and B
50 mA
and a fuse. The resistor limits the Hydrogen
current to a specific value known as
the short circuit current, Isc. The
zener diode limits the voltage to a
value referred to as open circuit 20 mA
voltage, Voc. The fuse will blow
when the diode conducts. This
interrupts the circuit, which prevents 10 mA
the diode from burning and allowing 10 20 30 40 50 100 200
excess voltage to reach the
hazardous area. There always are at Open Circuit Voltage (V)
least two zener diodes in parallel in
each intrinsically safe barrier. If one Figure 4. Ignition curves resistance
diode should fail, the other will
operate providing complete
protection. ground and the fuse blows, shutting Determining Safe Energy
off electrical power to the hazardous Levels
A simple analogy is a restriction in a area.
water pipe with an overpressure Voltage and current limitations are
shut-off valve. The restriction When conducting the safety ascertained by ignition curves, as
prevents too much water from analysis of the circuit, it is important seen in Figure 4. A circuit with a
flowing through the point, just like to compare the entity values of the combination of 30 V and 150 mA
the resistor in the barrier limits intrinsically safe apparatus against would fall on the ignition level of
current. If too much pressure builds the associated apparatus. These gases in Group A. This combination
up behind the restriction, the parameters usually are found on the of voltage and current could create
overpressure shutoff valve turns off product or in the control wiring a spark large enough to ignite the
all the flow in the pipe. This is similar diagram from the manufacturer (see mixture of gases and oxygen.
to what the zener diode and fuse do Figure 3). Intrinsically safe applications always
with excess voltage. If the input stay below these curves where the
voltage exceeds the allowable limit,
Will The Circuit Work? operating level of energy is about
the diode shorts the input voltage to It also is important to make sure 1 watt or less. There are also
that the intrinsically safe circuit will capacitance and inductance curves
work under normal conditions. With which must be examined in
Associated Apparatus Apparatus the current-limiting resistor, a intrinsically safe circuits.
(barrier) (field device)
voltage drop will occur between the
Open circuit voltage Voc Vmax The purpose of this series of
Short circuit current Isc Imax input and output of the barrier. This
has to be accounted for in your articles is to simplify the application
Allowed capacitance Ca Ci of intrinsic safety. Consider the
Allowed inductance La Li circuit design. In the subsequent
articles in this series, a step-by-step ignition curves to demonstrate a
Figure 3. Comparison of the entity values of explanation will be given on how to point about thermocouples.
an intrinsically safe apparatus and calculate these voltage drops and
associated apparatus
make sure that the circuit is safe.
Z-132
Intrinsic Safety Circuit Design Contd

NON-HAZARDOUS SIDE HAZARDOUS SIDE

Recorder

Maximum 0.1 volt


produced by thermocouple

Figure 5. Thermocouple installed in a hazardous area

NON-HAZARDOUS SIDE HAZARDOUS SIDE

Recorder

explosion
110 V FAULT
possible

Figure 6. Thermocouple with fault

NON-HAZARDOUS SIDE HAZARDOUS SIDE

Instrinsically
Recorder Safe
Barrier

Figure 7. Thermocouple with barrier

A thermocouple is classified as a occur on the recorder which could BEHIND THE BYLINE
simple device. It will not create or cause excess energy to reach the Paul B. Babiarz is marketing manager
store enough energy to ignite any hazardous area, as seen in Figure 6. of intrinsically safe products for Crouse-
mixture of volatile gases. If the energy To make sure that the circuit Hinds. He holds a B.S. from the
level of a typical thermocouple remains intrinsically safe, a barrier University of Rochester, an M.S. from
circuit were plotted on the ignition to limit the energy must be inserted the University of Michigan, and an
curve in Figure 4, it would not be (Figure 7). M.B.A. from Syracuse University. He
close to the ignition levels of the has more than 13 years of experience
most volatile gases in Group A. The next installment in this series in working in hazardous areas and has
will explain how the selection is specialized in intrinsic safety.
Is the thermocouple which is made for thermocouples and RTDs, Copyright Instrument Society of
installed in a hazardous area which comprise about 13% of all America. Intech, October, 1992.
(Figure 5) intrinsically safe? The intrinsically safe applications. All Rights Reserved.
answer is no, because a fault could
Z-133
Intrinsic Safety Circuit
DesignPart 2
Fault conditions in hazardous-area temperature sensors can be explosive without the proper
protection. You can safeguard all of the devices in your application with one type of intrinsic
safety barrier.
Z
Paul S. Babiarz

When thermocouples and RTDs NON-HAZARDOUS SIDE HAZARDOUS SIDE


(resistance temperature devices) CLASS I,II, III
DIVISION 1
are installed in hazardous areas, GROUPS A-G
barriers are required to make their
+
circuits intrinsically safe. These
intrinsic safety barriers prevent Control
excess energy from possible faults Room
on the safe side from reaching the
hazardous area. Without the
barriers, excessive heat or sparks GRD

produced by the fault condition Thermocouples


could ignite volatile gases or are simple devices.
Do not need approval
combustible dusts. Intrinsic Safety Barrier
Use same type of wire
Hundreds of different barriers are
available from North American
suppliers. The multitude of products Use same type of wire
can give control engineers
nightmares as they try to select the
Safety Barrier
proper barrier for common Parameters
instrumentation loops. The search
can be simplified, however. One VN: 2.5 V Ri: 71 Note: Use consistent wiring
type of barrier can be selected to
make all thermocouples and RTDs
intrinsically safe so that polarity Figure 1. Current use of intrinsically safe apparatus in hazardous areas.
problems are avoided and
calculations are not necessary.
Normally, the design of all
intrinsically safe circuits centers on
one of two approaches: the +
universal approach, which uses a
universal device that often is - V
RTD
isolated so that a ground for safety
is not required; or the engineered
approach, which uses grounded
safety barriers. V Voltmeter

Isolated temperature
converters. These universal Figure 2. Typical values of barrier in thermocouple circuit.
devices measure temperature in
hazardous areas, but at a higher
cost. (Dispensing with the need for a
ground is a convenience that may the safe side when the temperature More versatile application
cost two to three times as much as reaches a designated level. One product for all applications
grounded safety barriers.) Isolated These units must be approved as
temperature converters accept a intrinsically safe. Disadvantages include:
low-level DC signal from a Larger in size
thermocouple or 3-wire RTD and Advantages of isolated temperature Requires calibration
convert it into a proportional converters as compared to More expensive
4-20 mA signal in the safe area. grounded safety barriers include: May not work with all
They also are available with set Good signal response thermocouples and RTDs
points that trip an on-off signal to No ground required for safety
Z-134
Intrinsic Safety Barrier
R1
A A
V V
B B

C C R2
V Voltmeter V Voltmeter
Note: When R1 = R2, bridge remains balanced

Figure 3. 3-wire RTD bridge Figure 4. 3-wire RTD bridge with barrier
Grounded safety barriers. Rated voltage. Like any When barriers and thermocouples
These are passive devices that electrical device, safety barriers are being installed, the technician
prevent all excess energy from a have a rated nominal voltage, Vn, may forget which wire is positive and
fault occurring on the safe side from referred to as working voltage. The which is negative. To avoid polarity
reaching the hazardous area. barriers Vn should be greater than problems on the terminals, a double
Under normal conditions, the or equal to the supply to the barrier, AC barrier should be used. The
barriers allow the circuit to function much like the rated voltage of a wires can be connected to either
properly by allowing the signals to lamp must be equal to or greater terminal and the circuit will function
pass between the field device and than the supply to it. If the voltage properly as long as thermocouple
the control room. In a fault supply to the barrier is much greater polarity is maintained throughout.
condition, the barriers limit voltage than its Vn, the barrier will sense a
fault. The protective zener diodes Rated voltage. A thermocouple
and current to levels that are not produces a very small voltage (less
sufficient enough to ignite gases. will conduct, causing leakage
currents and inaccurate signals on than 0.1 V). It is connected to a
For a more detailed explanation, voltmeter which has a high impedance
refer to Part 1 of this series. the loop. Most barriers have a rated
working voltage that guarantees a and which requires a very small
Advantages of grounded safety minimal leakage current from 1 to current. Since the thermocouple
barriers as compared to isolated 10 micro amps if it is not exceeded. produces such a small voltage,
temperature converters include: If the supply voltage to the barrier choose a double AC barrier with a
Less expensive becomes too high, the zener diode higher rated nominal voltage (Vn). A
Precise signal response will conduct. The resulting high survey of most double AC barriers on
Very small (less than 12 in. wide) current through the fuse will cause the market shows that they are rated
Simple application the fuse to blow. Excess supply at low nominal voltages from 1 V and
One barrier for all types of voltage is the main reason why higher. Select one between 1 and 10 V.
thermocouples and RTDs grounded barriers fail. Internal resistance. Since the
Disadvantages include: mV signal has a very small current
Requires ground Internal resistance. Every safety
barrier has an internal resistance, and is going to a high-impedance
Requires some engineering Ri, that limits the current under fault voltmeter, the resistance of the
conditions. Ri also creates a voltage barrier will not influence circuit
Examine The Barrier drop across the barrier. This drop can function. A simple rule of thumb is
Parameters be calculated by applying Ohms that when a signal is going to a
Articles in this series will focus on law, V=IR. Not accounting for the high-impedance voltmeter, an
methods to select the proper grounded voltage drop produces the most internal barrier resistance of less
safety barriers. Before we analyze problems in the proper functioning than 1000 ohms will not affect the
thermocouple and RTD circuits, we of intrinsically safe systems. mV signal. It usually is good
should examine the functional practice, however, to select a barrier
parameters necessary to select the Thermocouple System with a low resistance in case the
proper barrier. These parameters Design Pointers circuit is modified later.
are: polarity of circuit; rated voltage Polarity. A thermocouple has two Barrier selection. For proper
of barrier; and resistance of barrier. wires, each with a positive and operation of thermocouples in
Polarity. The circuits polarity negative polarity. Two single-channel hazardous areas, select safety
must be known in order to choose barriers, each with the proper barriers based on the following
the correct type of barrier. DC polarity, could be used. Problems parameters:
barriers are rated either as positive would occur if the positive leg to the Barrier type: double-channel AC
or negative. AC barriers can be thermocouple were connected to barrier to avoid polarity problems
connected to circuits with either a the negative terminal of the barrier or Rated voltage: Barrier Vn > 1V
positive or negative supply. vice versa. There are two possible Internal resistance: barrier with lowest
SIGNAL & RETURN barriers are barrier choices for thermocouple resistance (less than 110 ohms)
used for transmitter and switching circuits:
Safety and installation check.
applications. All of these barriers Thermocouple circuit with one Since the thermocouple is a simple
are available in single- or positive and one negative lead
device, it does not need third-party
double-channel versions. However, 1 standard DC barrier, positive polarity
approval. Make sure that the barrier
because double-channel barriers and has the proper approvals for
save space and money by being 1 standard DC barrier, negative polarity hazardous area locations. The
connected to two legs of a loop, OR thermocouple wires will be different
they are becoming the standard. 1 double AC barrier
Z-135
from terminal connections on the effect can be minimized by using a Current loop A & B: Internal
barrier. Always use consistent wiring third wire to measure the voltage resistance. The constant current
from the thermocouple to the barrier (refer to Figure 3 for this discussion). source will have a rated maximum
and then to the control room. This If wires A and B are perfectly load or burden (resistance load it
will cancel any thermocouple effect matched and if the resistance in can drive). Assume that this
caused by the dissimilar metals on both channels of the barrier is the maximum load is 500 ohms and the
the barrier connection. same, the impedance effects will maximum resistance of the RTD at
cancel because each is in an the highest temperature is 390
RTD System Design opposite leg of the bridge. The third ohms. Knowing this information, the
Pointers wire, C, acts as a sense lead to the Ri of the barrier can be calculated:
RTDs come in 2-, 3-, and 4-wire voltmeter. control room barrier + RTD
versions. The 3-wire RTD is used in
more than 80% of all applications.
Current loop A & B: Polarity. The
resistance
500 ohms
resistance resistance
< Ri ohms + 390 ohms
Z
current loop to the RTD has a
The 2-wire version is not as positive and a negative polarity. Ri < 110 ohms
accurate and is used mostly in the Possible solutions are similar to the
heating, ventilation, and air Current loop A & B: Barrier
thermocouple: selection. Use the same barrier that
conditioning industry for set-point
temperature measurements. The 1 standard DC barrier, positive polarity was used for the thermocouple
4-wire RTD provides the most and circuit.
accurate signal, but is more 1 standard DC barrier, negative polarity Leg C to the voltmeter: Barrier
expensive and requires one more OR selection. The RTD leg going to the
extension wire to the process area. 1 double AC barrier voltmeter (C) is a millivolt signal
Understanding RTD accuracy is Select the double AC barrier to similar to the thermocouple circuit.
essential in selecting the correct avoid polarity problems. Because it The rated voltage, Vn, and internal
barrier. Many RTD measurements is smaller, it is also less expensive. resistance, Ri, of the barrier will
are in the form of a Wheatstone have the same parameters as the
bridge, whose output voltage is a Current loop A & B: Rated barriers used in the thermocouple
function of the RTD resistance. The voltage. The constant current and current loop of the RTD.
bridge requires four connection amperage sent to the RTD typically Selecting the correct barrier to
wires, an external source, and three is in the micro amp (10-6 ) level. The make all thermocouples and RTDs
resistors that have a balanced maximum resistance of the most intrinsically safe is not difficult. Use
temperature coefficient. The RTD commonly used RTD, Pt100 is a double-channel AC barrier with a
normally is separated from the 390 ohms at 1560C. The voltage rated voltage greater than 1 volt
bridge by a pair of extension wires. drop across the RTD will be in mV, with the lowest internal resistance.
so the Vn of the RTD loop is similar The double-channel barrier is the
With a 2-wire RTD, the impedance to the thermocouple. To be safe, lowest cost solution. The AC version
of the barrier in series with the RTD select a barrier with a Vn greater will avoid any polarity problems. A
will cause an imbalance on the than 1 V, similar to the Vn of the barrier with a rated voltage between
bridge and will affect the accuracy thermocouple barrier. 1 and 10 volts will provide a wide
of the temperature reading. This selection which have a low
resistance and are approved for the
HAZARDOUS SIDE
hazardous areas where the
NON-HAZARDOUS SIDE temperature sensors are located.
CLASS I,II, III
Item 1 DIVISION 1 This single barrier can then be used
GROUPS A-G to make all thermocouples and
RTDs intrinsically safe. And dont
forget, all thermocouples and RTDs
Current are simple devices, so they do not
loop RTD need third party approval to be
intrinsically safe. When they are
connected to an approved
GRD
intrinsically safe barrier, the circuits
are intrinsically safe.
Item 2 Many temperature sensors are
signal attached to 4-20 mA temperature
transmitters, which comprise 22%
of all intrinsically safe applications.
RTDs are simple devices. The next article in this series will
Do not need approval. show how to make these
transmitters intrinsically safe.
GRD This channel can
be used to serve
part of loop #2.
Safety Barrier Copyright Instrument Society of
Parameters America. Intech, December, 1992.
All Rights Reserved.
VN: 2.5 V Rj: 71

Z-136
Use The 80/20 Rule
In Intrinsic Safety
Circuit Design
Part 3 of this series on intrinsic safety circuit design describes how to select barriers for
intrinsically safe 4-20 mA transmitters. Use the 80/20 Rule to simplify this process.

Paul S. Babiarz

+ +
+24V
S
The 80/20 Rule actually is five rules 4 20 mA E
Distributed
that are based on the fact that Control 2-Wire N
certain practices prevail 80% of the Transmitter S
System O
time, and 20% of applications are R

more difficult. This article focuses on
how to choose intrinsically safe 250 4 20 mA
barriers when the transmitters are
installed in hazardous areas for both Conversion
the 80% standard category and the Figure 1. 4-20 mA 2-wire transmitter.
remaining 20% more difficult
applications.
control system over a long distance. controller reads a voltage signal, a
The most common way to process The brains of the system, the DCS, conversion resistor (most commonly
and send analog signals in the interprets the electrical signal into 250 ohms) converts the 4-20 mA
instrumentation industry is via the physical measurement. Because current range into a voltage signal
4-20 mA transmitters. Transmitters these analog signals are sent to a on the DCS input channel. Applying
can be one of the simplest devices DCS, 4-20 mA circuits are called Ohms Law of V = IR, the controller
involving barriers. However, analog inputs or A/I. Using has a 1-to-5 V signal (Table 1).
improper selection of intrinsically temperature as an example,
safe barriers in loops with 4-20 mA examine the function of the Assume the temperature span to be
transmitters can introduce too much transmitter (Fig. 1). measured is from 0C to 100C. The
impedance on the circuit and cause transmitter is calibrated so that a 4
the transmitters to function A power source in the DCS usually mA signal equals the low reading of
improperly at the high end near the supplies 24 VDC to the transmitter. 0 and a 20 mA signal equals the
20 mA reading. The transmitter converts the high reading of 100. The DCS then
physical measurement into an runs the signal through a conversion
Before selecting barriers, examine electrical current signal. Transmitter resistor which can be placed either
how 4-20 mA analog circuits current ranging from 4-20 mA is on the supply (+) or return (-) lead
function. Transmitters convert a sent back to the DCS. Current of the circuit, converting the signal
physical measurement such as signals are used to avoid potential back to a voltage reading.
temperature or pressure into an voltage drops or electrical
electrical signal that can be sent interference associated with voltage There are three types of barriers for
without signal modification to a signals. However, because the intrinsically safe transmitter
applications: ungrounded repeaters,
Temperature converted to x multiplied by = converted to grounded repeaters, or grounded
mA signal ohm resistor a voltage reading safety barriers. Each has its
in the DCS advantages and disadvantages
0C (min) 4 mA (0.004 A) x 250 = 1V
(Table 2).

100C (max) 20 mA (0.020 A) x 250 = 5V


Ungrounded repeater barriers, also
known as galvanically isolated or
transformer-isolated barriers, are
used more frequently in Europe
Table 1. Conversion of physical measurement to electrical signals.

Z-137
Imax, Ci, and Li (see Part 1 of this
Advantages Disadvantages series).

Grounded Safety Least expensive Requires ground


Selection of safety barriers. The
proper barrier must be selected by
Barrier Precise signal response Requires engineering two separate evaluations: one to
Very small size determine that the analog circuit
(<12 in. wide) functions properly at 20 mA, and
one to determine that the circuit is
Grounded One product can be used More expensive
safe under fault conditions.
Repeater Can use transmitters with Requires ground Functional parameters: Type of
higher operating voltage Larger in size safety barrier, voltage input (Vn),
Consumes more power
and internal resistance (Ri). The
type of safety barrier is largely
Z
determined by the placement of the
Ungrounded One product can be used Most expensive conversion resistor. If the resistor is
Repeater No ground required Larger in size (1 in. wide) placed on the supply leg of the
Can use transmitters with Possible radio frequency circuit, a simple DC positive barrier
higher operating voltage interference
can be used (Fig. 2).
Isolation, if good ground May not be compatible 80/20 Rule #2: Most transmitter
not available with smart transmitters circuits have the conversion
resistor on the return channel.
Use the double channel supply
Table 2. Advantages and disadvantages of grounded safety barriers, grounded and and return barrier.
ungrounded repeaters.
The supply channel is constructed
than in North America. Repeaters designates the type of vapor or dust like the positive DC barrier; it
suit most transmitter applications, in the area. Group A acetylene; prevents a fault on the safe side
but at a higher cost. Grounded or Group B hydrogen; Group C from transferring excess energy to
ungrounded repeaters supply a ethylene; Group D propane; the transmitter. The return channel
constant regulated voltage of 15 to Group E metal dust; Group F has two diodes in series which allow
17 V to the transmitter from a 24 V coal dust; Group G grain dust. the signal to pass only in one
source. The return channel is then direction back to the DCS, and
run through the barrier, which Complex devices. Because
transmitters can store energy, they prevent any excess fault energy
repeats it without any appreciable from being transferred to the
loss in signal. For example, if a are considered complex devices,
and must be approved as transmitter. These diodes and the
transmitter sends 19.6 mA through supply channel have voltage drops
the barrier, it is repeated in the intrinsically safe. If they are
third-party approved, they have which must be accounted for in the
barrier without any loss so that analog circuit (Fig. 3).
19.6 mA reaches the control room. entity parameters such as Vmax,
Repeaters act like mirrors by
retransmitting, or repeating, the Conversion
analog signals. NON-HAZARDOUS SIDE HAZARDOUS SIDE
Resistor

When budget constraints or control +


250 + + +
panel space are important +24V +
S
considerations, grounded safety Distributed Intrinsically E
barriers may be a better choice. Control Safe N
S
System Transmitter
O
80/20 Rule #1: In North America, R

most analog circuits are GRD

protected by grounded safety
barriers because of lower costs.
Define the hazardous area Figure 2. Positive DC barrier.
where the transmitter is located.
In North America, these areas are NON-HAZARDOUS SIDE HAZARDOUS SIDE
defined by the National Electric
Code as classes, divisions, and
groups. The class defines the type +24V
+ + + +
of materials that are in the S
E
Intrinsically
hazardous area. Class I Distributed
Safe N
Control
flammable gases and vapors; Class System Transmitter S
O
II combustible dusts; Class III R

fibers and flyings. Hazardous areas
250
GRD
are further broken down into two
divisions. Division 1 means normally Conversion
hazardous; Division 2 means not Resistor
normally hazardous. The group Figure 3. Supply and return barrier.

Z-138
80/20 Rule #3: The supply 24 Supply NON-HAZARDOUS SIDE HAZARDOUS SIDE
voltage normally is 24 VDC.
Select the voltage input, Vn. + + + +
One of the reasons that barriers +24V
S
fail is because the voltage supply Distributed Intrinsically
E
is too high. Use a regulated supply Control Safe
N
S
source with a high end of tolerance System Transmitter
O
that does not exceed the barrier
R
rating and a low end that is enough 250
GRD

to drive the circuit. A 24 Vdc


source 1% usually is a good
5 volt loss maximum 12 volt loss
choice. 7 volt loss
Determine the internal
resistance, Ri (also referred to VOLTAGE BALANCE:
as end-to-end resistance) of the Transmitter = 12 volts
barrier best suited for your Resistor = 5 volts
circuit. The most critical Barrier(+ line loss) = 7 volts Figure 4. Voltage balance.
component of the barrier selection Total Supply = 24 volts
is the barriers internal resistance.
If the resistance is too high, the
transmitter will not work near
20 mA. As seen in Table 1 and the NON-HAZARDOUS SIDE HAZARDOUS SIDE
following discussion, at 20 mA the
voltage drops across the barrier
and the conversion resistor will be +24V
+ + + 15 - 17V +
the highest. If the internal S
Intrinsically E
resistance is too low, the barriers Distributed
Safe N
Control Repeater
short circuit current, Isc, may System Barrier Transmitter S
O
exceed the transmitters entity R

parameter, Imax.
The easiest way to determine the 4 20 mA 4 20 mA
Conversion
barriers permitted resistance is to Resistor
calculate the total voltage drop on 750 - 1000 Repeated
the circuit. To select the proper max
transmitter barrier, determine the
following: Figure 5. Repeater barriers.
Hazardous area Groups A-G or
C-G
Placement of the conversion resistor requires 5 V at 20 mA. supply and return side. Voltage
resistor on either the supply or Simple subtraction leaves a drop on the return side diodes is
return leg of the circuit maximum allowable voltage drop of about 0.7 V. This leaves a
Size of the conversion resistor 7 V. Using Ohms Law, this maximum drop of 6.3 V on the
(250 ohms is most common) converts to an internal resistance supply side or a maximum
Minimum operating voltage of the of 350 ohms. Allow for a cable resistance of 305 ohms (allowing
transmitter (This figure, also resistance of about 10 ohms. Thus, 10 ohms for cable resistance).
referred to as lift-off voltage, is in the circuit functions properly with a Again, verify the entity
the transmitter data sheet. Most barrier having an internal parameters of the barrier and
operate at a minimum of 12 V or resistance of 340 ohms. transmitter.
lower.) Next, to make sure the circuit is 80/20 Rule #4: The two solutions
Entity parameters of approved safe, verify that the barriers entity above cover 80% of all
transmitter parameters match the transmitters transmitter applications.
Case 1. Assume that conditions entity parameters. This design
are as follows: offers the lowest cost solution But what happens if the circuit falls
Groups A-G where two transmitters can be into the 20% category? Grounded
Supply connected to one double channel safety barriers may not work in
250 ohms barrier. This circuit arrangement conditions where a loop-powered
12 V allows one common barrier to be indicator is connected, or where
Vmax = 30 V, Imax = 150 mA, used for most circuits (Fig. 4). the transmitter requires a minimum
Ci = 0 F, Li = 0 mH voltage greater than 12 V. In these
Calculate the maximum allowable Case 2. Use the same cases, the easiest solution is to
resistance of the barrier under conditions as in Case 1, except use a repeater barrier. Repeaters
worst-case conditions when the change the placement of the provide a regulated power supply
transmitter is sending a 20 mA conversion resistor to the return of 15-17 V to the transmitters and
signal. The supply is 24 Vdc; the side, and use the supply and can drive a conversion resistor
transmitter requires a minimum of return barrier. Voltage drop on load of 750 to 1000 ohms (Fig. 5)
12 V; and the 250 ohm conversion the barrier occurs on both the

Z-139
Groups Internal Resistance Voltage Drop Short Circuit Open Circuit Case 2: Resistor on the return
side. Since the resistor is on the
(Ri) at 20 mA Current, Isc Voltage, Voc return side, the barriers receive the
Barrier #1 A-G 340 ohms 6.8 V 93 mA 28 V total voltage supply. Since this
circuit is more sensitive to voltage
Barrier #2 C-G 140 ohms 2.8 V 213 mA 28 V increases, be careful about
increasing the supply above the
Table 3. Typical values of barriers rated for different groups. barrier's nominal rated voltage, Vn.
Before the zener diodes in the
If repeaters still are not the best Increasing Voltage Supply barriers reach their rated voltage,
solution, there may be other ways to If the voltage supply is increased there may be some leakage current
use grounded safety barriers. Either too much, the barrier may sense a that could affect the transmitter
the impedance in the circuit must be fault and the fuse could blow, signals. Diode leakage current Z
reduced or the voltage must be interrupting the circuit. Some values ranging from 1 to 10A are
increased. If these alternatives are allowance can be tolerated for listed by the barrier manufacturers.
used, recheck the barrier and increasing the voltage supply on In Case 1, this could mean that the
transmitter entity parameters to barriers with a nominal rated current signal could be deformed by
make sure the circuit is safe. voltage of 24 VDC. a maximum of 0.025% at 4 mA
Reducing Impedance (1 A/4 mA).
Case 1: Resistor on the supply
Case 1. Reduce the conversion side. When transmitters are first When the resistor is placed on the
resistor. As seen in Fig. 2, only two energized, they transmit 4 mA for return side, leakage current is on
fixed sources of impedance can be calibrating zero readings. There the supply side and does not affect
reduced: the conversion resistor or always is at least a 1 V drop across the transmitters 4-20 mA signal.
the barrier. One solution is to reduce the resistor before the supply
the conversion resistor to 100 or reaches the barrier. The voltage Transmitters comprise 22% of all
50 ohms to obtain maximum voltage supply could be increased to 25 to intrinsically safe circuits. The next
readings of 2.0 to 1.0 V respectively. 26 V without the barrier sensing a article will feature discrete inputs,
(Example: 20 mA (0.02 A) x fault condition. This would allow 1 to also referred to as switching. These
100 ohms = 2 V.) This may be 2 additional volts on the circuit. represent 32% or almost one-third
practical for new installations, but it of all intrinsically safe circuits.
may not be possible for cases where
additions are being made to an
existing control system. Copyright Instrument Society of
Case 2. Select a barrier with America. Intech, March, 1993.
lower resistance. All Rights Reserved.

80/20 Rule #5: Many hazardous


locations are classified as
Groups C-G.
Ignition curves in Groups C-G allow
higher rated voltages and current
before gases ignite (see Part 1 of
this series, October 1992). Barriers
designed for hydrogen and other
gases classified as Group A or B
require higher series resistance
than barriers designed for only the
more common gases in Groups C
and D. Thus, most intrinsically safe
instruments should have entity
parameters (Imax, maximum short
circuit current) that are higher for
Groups C-G. (As a practical matter,
most instrument manufacturers
have not taken advantage of this
fact.) With the Group C-G rating
high-current barriers can be used,
which have a lower internal See SIB Series of Intrinsically Safe Transmitters
resistance. These barriers have
corresponding lower voltage drops
but higher Isc (Table 3).

Z-140
Making Digital Inputs
Intrinsically Safe
Part 4 of this series describes how to make a switch intrinsically safe by using a switch
amplifier or a grounded safety barrier.

Paul S. Babiarz To make a switch intrinsically safe, location to the non-hazardous side.
the user may select a switch A closed switch on the hazardous
amplifier or a safety barrier. A switch side operates a relay or optocoupler
amplifier is an intrinsically safe relay output on the non-hazardous side.
Digital inputs constitute almost one- that solves virtually all switching The signals are electrically isolated
third of all process signals. They applications. However, if power is so that grounding is not required.
also are known as binary, on-off, not available in the control panel or
0/1, or simple switching signals if panel space is an important When proximity switches became a
where a switch is either opened or consideration, a grounded safety popular means of sensing the
closed. The most common barrier may be a better choice. There presence of objects and materials,
examples of these are mechanical is not a significant cost savings of the NAMUR-style sensor was
or reed contacts, transistors, limit, one alternative over the other. Each developed. Contrary to popular
float, on-off, and pushbutton has its own advantages and opinion, NAMUR is not an approval
switches. As defined in paragraph disadvantages, as shown in Table 1. standard. It was organized by the
3.12 of the ANSI/ISA-RP12.6-1987, German chemical industry to
switches are simple devices that Switch Amplifiers develop operating standards for
neither generate nor store more The most common application is proximity switches. A NAMUR-style
than 1.2 V, 0.1 A, 25 mW, or 20J. switching through an intrinsically proximity switch is a 2-wire DC
Since switches are simple devices, safe relay (Fig. 1). Relays, which sensor that operates at 8.2 V with
they do not have to be approved as normally are powered by 110 VAC switch points operating between 1.2
intrinsically safe. If they are or 24 VDC, have a low voltage and to 2.1 mA. This NAMUR standard
connected to an approved current which are safe at the contact later was superseded by the
intrinsically safe associated in the hazardous area. When this German Standard DIN 199234,
apparatus (barrier), the circuit is contact is closed, the relay transfers Measurement And Control:
deemed to be intrinsically safe. the signal from the hazardous
Non-Intrinsically Safe Wiring

Intrinsic Intrinsic
Safety Barrier Safety Barrier
Intrinsic Intrinsic
Safety Barrier Safety Barrier
Intrinsic Intrinsic
Safety Barrier Safety Barrier
Intrinsic Intrinsic
Safety Barrier Safety Barrier

INTRINSICALLY SAFE WIRING

To Field Circuits

Figure 1. Switch amplifier 2 channels.

Z-141
NON-HAZARDOUS SIDE HAZARDOUS SIDE NON-HAZARDOUS SIDE HAZARDOUS SIDE

Distributed
Control Intrinsic Intrinsically
Intrinsic System Safety Safe
Safety Barrier Apparatus
Barrier

ONLY THESE WIRESARE Potential of


INTRINSICALLYSAFE Ground Loops

Figure 2. Current sourcing switching. Figure 3. Current sinking switching.


Z
Electrical Sensors Used For used for transmitters (see Part 3 of than the voltage supply. Since most
Intrinsically Safe 2-Wire DC this series). switching uses 24 VDC, select a
Systems. Because these switches barrier rated at 24 V. The internal
required a remote amplifier for The current sourcing method of resistance of the barrier is not as
switching in Fig. 2 could use the critical since the current in digital
operation, most switch amplifiers same signal and return barrier that
standardized on an intrinsically safe inputs usually is very small.
was used for 4-20 mA transmitters. However, it always is good practice
voltage of 8.2 V and current of 8 mA The voltage to the switch is supplied
at the contacts in hazardous areas. to select a barrier with low
through the supply channel. The resistance. Check the approvals of
This provided enough power to second channel is used for signal
operate NAMUR-style proximity the barriers to make sure that they
return. A closed switch will close the are rated for the proper hazardous
switches safely. contact in the DCS. Most digital area group location.
The amplifiers are sensitive enough input signals operate with 24 V and
to detect closed contacts in 10 mA. If the same barrier is used Intrinsically safe relays, also referred
for switching as 4-20 mA to as switch amplifiers, can be
corrosive or abusive areas. Despite transmitters, there will be about a 3 applied universally for all digital
the fact that the intrinsically safe to 4 V drop across the barrier. inputs. However, if safety barriers
voltage and current at the contacts are used, the same barriers used to
are very low, most modern switch The barrier used for current sinking make analog inputs intrinsically safe
amplifiers will detect a closed switching can be a single-channel can be used for either current
contact when the resistance of the DC barrier as seen in Fig. 3. When sourcing or current sinking
circuit is less than 3000 ohms. the switch is open, the DCS input switching.
Intrinsically safe switches can be will sense 24 V. When the switch is
located a long distance from the closed, the DCS will recognize a The next article in this series will
switch amplifiers and still function lower voltage. This lower voltage is explain how to make digital outputs
properly. calculated as a voltage divider intrinsically safe.
circuit.
Switch amplifiers are available with
two different output contacts to the Make sure the rated voltage of the Copyright Instrument Society of America.
safe side, relays and optocouplers. barrier, Vn, is equal to or greater Intech, April, 1993. All Rights Reserved.
The more commonly used relay
versions are applied in slow speed Switch Amplifiers
switching to operate smaller pumps,
motors, or other electrical devices.
Optocouplers are transistors Advantages Disadvantages
operated by photo diodes to close Simple application Needs power supply
the output contacts. These outputs
have lower contact ratings but an No ground required Larger in size
almost infinite switching capability. No internal resistance
Optocouplers are used for switching LEDs to indicate power and
back to a DCS or for high-speed monitor operations
counting operations up to thousands
of times per second (KHz). Sensitive to detect closed
contacts in corrosive areas
Switching Through Safety
Barriers Safety Barriers
When a 110 V supply is not
available in the control panel, safety Advantages Disadvantages
barriers frequently are used for
digital inputs back to a DCS. There Smaller size Requires grounding
are two methods of switching: Does not require power supply Has internal resistance
current sourcing or current sinking.
Both of these methods can use the
same types of barriers that were Table 1. Advantages and disadvantages of switch amplifiers and safety barriers.

Z-142
Intrinsically Safe Outputs
Made Easy
Part 5 of this series explains how to make solenoid valves, LEDs, and
I/P transducers intrinsically safe.

NON-HAZARDOUS SIDE HAZARDOUS SIDE


CLASS I, II, III
DIVISION 1
GROUPS A-G

+ 24 V + + +

Digital Solenoid
Output Valve
D/O

GRD

Solenoid valves need


entity approval
Typical Safety Barrier
Parameters
VN: 24 V 350
Ri::

VN = Rated voltage
Ri = Internal resistance

Paul S. Babiarz There is good news and bad news The good news is that there are only
for making circuits (or loops) a handful of approved intrinsically
containing solenoid valves safe solenoid valves to choose from.
intrinsically safe. The bad news is For this article, manufacturers tested
that unlike transmitters which have their intrinsically safe valves with the
minimum operating voltages, valve most common barrier used in analog
manufacturers often describe their and digital input circuits the 24 Vdc
Digital outputs refer to closed valves with a nominal operating barrier with a resistance equal to or
contacts in a distributed control current or voltage. To select the less than 350 ohms (Fig. 1).
system (DCS). They transfer a proper barrier one needs to know
voltage to a process area to operate the minimum operating characteristics To determine the correct barrier, start
a field device. The two most under the most extreme conditions. with the basics. Since most digital
commonly used digital output field Without these characteristics it can output circuits operate with 24 Vdc
devices, solenoid valves and LED be quite difficult to select a barrier switched on the positive side, use a
displays, can easily be made that will allow the circuit to function positive DC barrier rated at 24 Vdc.
intrinsically safe. For solenoid properly and still meet the entity Knowing the minimum operating
valves, the same types of barriers parameters of the valves. Conditions current of the valve and the internal
are used that make analog and that may affect the operating impedance of the coil, you can
digital inputs (transmitters and characteristics are high ambient calculate the maximum allowable
switch contacts) intrinsically safe. temperatures, position of the impedance for the barrier and the
LEDs may require a different barrier. actuator, and length of cable runs. cable.
Z-143
Analog Outputs
NON-HAZARDOUS SIDE HAZARDOUS SIDE
CLASS I, II, III Analog outputs refer to I/P
DIVISION 1 transducers, also known as I/Ps
GROUPS A-G
(pronounced Ida Pease). An I/P
+24 V + + 25 mA
transducer produces a pneumatic
output proportional to the electrical
Digital current input that it receives. The
Output 12 V more current that is applied to the
D/O transducer, the more air pressure is

GRD
allowed into the system to drive a
LED Pilot Light device. As opposed to a solenoid
valve which is either in an opened or
12 volt drop across barrier
(480 x .025)
LED pilot light is a simple
device; does not need
closed position, a transducer is a Z
approval proportional valve. I/P transducers
Typical Safety Barrier are referred to as analog outputs
Parameters because a variable output, the
VN: 24 V Ri: 480 current signal, is sent from the DCS
to the transducer.
VN = Rated voltage
Ri = Internal resistance
I/P transducers need entity
approval. They act like resistors in
Figure 2. LED pilot light. the circuit, so three facts must be
known to select the correct barrier:
For example, assume a valve has a 25 mA. Since there will always be a transducer impedance; maximum
minimum operating current of 28 mA voltage drop across the barrier, the burden of the driver that sends the
and a coil impedance of 400 ohms. best application is to choose an current signal; and transducer entity
The maximum allowable impedance LED rated at less than 24 VDC. Use values. Burden, rated in ohms,
of the circuit is 857 ohms (24/.028 = a barrier rated at 24 V, then subtract measures the maximum load the
857). the rated voltage of the LED. This DCS can drive. To select the barrier,
If the internal impedance of the difference is the allowable voltage use the following characteristics:
solenoid coil is 400 ohms, the drop on the barrier at the rated Transducer impedance is 150 ohms
allowable impedance of the barrier current. Use Ohms Law (V = IR) to Burden of the drive is 1000 ohms
and cable would be 457 ohms calculate the internal impedance of The barrier must have an internal
(857-400 = 457). The resistance of the barrier. Example: resistance less than 850 ohms
one mile of #18 AWG wire at 60C LED rated at 12 V at 25 mA (1000-150 = 850). Verify the rated
is about 40 ohms (resistance of Allowable voltage drop 12 V voltage of the barrier by calculating
#18 AWG wire at 60C is 0.00737 (24-12 = 12) the voltage drop of the circuit. For
ohms/ft.). This makes the maximum Internal impedance of the barrier example, use the same barrier and
resistance of the barrier 457-40 = = 480 ohms (12/.025 = 480) cable values as in the solenoid valve
417 ohms. Choose a 24 V positive DC barrier example. The total impedance
Selecting the barrier now is simple: with an internal impedance of about (impedance of barrier + transducer
1. Select a simple DC positive barrier. 480 ohms (Fig. 2). + cable) of the circuit would be
(The rated voltage should be 24 V.)
2. Calculate the maximum allowable
resistance of the barrier as in the
example.
NON-HAZARDOUS SIDE HAZARDOUS SIDE
3.Confirm that the entity parameters CLASS I, II, III
of the solenoid valve match those DIVISION 1
GROUPS A-G
of the barrier (refer to Part 1 of this
series). + 4-20 mA + + +

Associated Apparatus Apparatus Analog


(barrier) (field device) I/P
Output
Open circuit voltage Voc Vmax Transducer
A/O
Short circuit current Isc Imax
Allowed capacitance Ca Ci GRD

Allowed inductance La Li
Single Channel DC Barrier I/P transducers need
LEDs entity approval
LEDs (light emitting diodes) are Typical Safety Barrier
simple devices since they do not Parameters
store energy (capacitance or VN 12 V Ri 150
150
inductance); therefore, they do not
need to be approved. However, they VN = Rated voltage
still must be used with safety Ri= Internal resistance
barriers to make circuits intrinsically
safe. Typical LEDs are rated at 24,
18, 12, or 6 V and operate at about Figure 3. 4-20 mA I/P transducer.

Z-144
Device Barrier Rated Internal Notes
Type Voltage Resistance (IT = INTECH)
Thermocouples AC >1 V <1000* Thermocouples are simple
devices; do not need approval.

RTDs AC >1 V <1000* RTDs are simple devices; do


not need approval.

Digital inputs switch Dry contacts are simple


amplifiers devices; do not need approval.

D/I - current supply & 24 350** Dry contacts are simple


sourcing return devices; do not need approval.

D/I - current DC 24 350** Dry contacts are simple


sinking devices; do not need approval.

A/I supply & 24 350 Transmitters need approval.


transmitters return Check entity parameters.
Conversion resistor of
250 ohms is on negative side.
Minimum lift-off voltage of
transmitter is 12 or less.

A/I transmitters DC 24 350 Same, except conversion


resistor is on + side.

D/O solenoid DC 24 350 Solenoid valves need approval.


valves Check entity parameters.

A/O transducers DC >12 >150 Transducers need approval.


Check entity parameters and
DCS burden.

* Select a barrier with a low resistance.


** Other barriers with a different resistance can be used. However, these barriers match those of the analog inputs.

Table 1. Guide to selecting grounded safety barriers.

540 ohms (350 + 150 + 40). At the storing) device that needs 5. Confirm that the entity
maximum current of 20 mA, the approval and has entity parameters of the barrier match
voltage drop would be 10.8 V parameters. those of the field device.
(540 x 0.20 = 10.8). Select a
barrier rated equal to or higher 2. Select the type of barrier Use Table 1 as a guide in selecting
than 10.8 V. A barrier rated at 12 V needed to protect the individual grounded safety barriers. There
or higher with an internal ungrounded lines of the circuit. will always be exceptions to these
resistance of 150 ohms also would Normally, temperature sensors guidelines, so verify your selection
be a good choice (Fig. 3). Confirm use an AC barrier. For analog with the manufacturer of the
that the entity parameters of the inputs and current sourcing barriers or field devices.
barrier correspond with those of switching, use the supply and
return barrier. The remainder The last installment in this series
the transducer. will discuss the general rules of
(analog and digital outputs and
This series of articles has shown some switching circuits) require grounding, installation, and
how the most common DC barriers. maintenance of intrinsically safe
applications of temperature systems.
measurements and analog or 3. Select a barrier with a rated
digital inputs/outputs can be made voltage equal to or greater than
intrinsically safe with a few intrinsic the voltage of the circuit.
safety barriers. Selection is simple: 4. Confirm that the internal
resistance of the barrier will Copyright Instrument Society of America.
1. Determine if the field device is a Intech, September, 1993. All Rights
simple or nonsimple (energy allow enough voltage for the field Reserved.
device to operate properly.
Z-145
Installing Intrinsically Safe
Systems
Part 6 of this series summarizes the major points of barrier replacement, wiring, installation,
grounding, sealing, maintenance, and troubleshooting of intrinsically safe systems.

Paul S. Babiarz To Control


Room Circuits
We have shown how an intrinsically

Non-Intrinsically Safe Wiring


safe circuit is designed for most
common applications. Now the Intrinsic Intrinsic
Safety Barrier Safety Barrier
intrinsically safe system must be
properly installed and provisions Intrinsic Intrinsic
Safety Barrier Safety Barrier
must be made to maintain and
Intrinsic Intrinsic
troubleshoot it. These procedures Safety Barrier Safety Barrier
are discussed in detail in Article 504 Intrinsic Intrinsic
of the National Electrical Code Safety Barrier Safety Barrier
(NEC) and the ANSI/ISA
RP 12.6-1987 Recommended
Practice Installation of
Intrinsically Safe Systems For INTRINSICALLY SAFE WIRING
Hazardous (Classified) Locations.
Wiring
Intrinsically safe circuits may be
wired in the same manner as To Field Circuits
comparable circuits installed for Figure 1. Suggested panel arrangement using separate wireways.
unclassified locations with two
exceptions summarized as
separation and identification. These
wiring practices are simple and NON-HAZARDOUS SIDE HAZARDOUS SIDE
clear; however, they often are
overlooked and are the source of
potential problems.
The intrinsically safe conductors
must be separated from all other
wiring by placing them in separate Intrinsic
conduits or by a separation of Safety
2 inches of air space. Within an Barrier
enclosure the conductors can be
separated by a grounded metal or
insulated partition (Fig. 1).

ONLY THESE WIRESARE


INTRINSICALLYSAFE
Figure 2. Barrier installation.

Z-146
influence the function of the system
NON-HAZARDOUS SIDE HAZARDOUS SIDE by creating noise on the circuit or
modifying the signals. Fig. 3 shows
an improperly grounded system.
The numerous grounding points
create ground loops which can
Distributed modify the signals and induce stray
Control Intrinsic Intrinsically voltages into the intrinsically safe
System Safety Safe
Barrier Apparatus circuits. The correct method of
grounding is shown in Fig. 4 where
all the grounds are tied together at
one single point in the system.
Sealing
The requirements for sealing
intrinsically safe circuits have been
Potential of discussed by a panel of experts and
published in Seals for Intrinsically
Ground Loops Safe Circuits, EC&M, September
1992, pp. 48-49. The panels
conclusion is that seals are required
Main Earth Ground to prevent the transmission of gases
Figure 3. Unacceptable grounding.
and vapors from the hazardous area
to the nonhazardous area, not to
Intrinsically safe wiring may be light The grounding conductor must be prevent passage of flames from
blue when no other conductors a minimum 12 AWG. explosions. Explosion-proof seals
colored light blue are used. The All ground path connections must are not required as long as there is
raceways, cable trays, open wiring, be secure, permanent, visible, and some other mechanical means of
and terminal boxes must be labeled accessible for routine inspection. preventing the passage of gases
Intrinsically Safe Wiring to prevent A separate isolated ground such as positive pressure in the
unintentional interference with the conductor normally is required control room and/or application of
circuits. The spacing between the since the normal protective an approved mastic at cable
labels should not exceed 25 ft. ground conductor (green or terminations and between the cable
yellow/green wire) may not be at and raceway. Many experts
Barrier Installation the same ground potential generally agree that a commercially
The barriers normally are installed because of the voltage drop from available silicon caulk is a suitable
in a dust- and moisture-free NEMA fault currents in other equipment. mastic which would minimize the
4 or 12 enclosure located in the For installations designed to passage of gases. This must,
nonhazardous area. Only the barrier Canadian standards, the however, be acceptable to the
outputs are intrinsically safe. Canadian Electrical Code authority having jurisdiction.
Conductive dust or moisture could (Appendix F) recommends
lessen the required distance of 2 in. redundant grounding conductors.
between intrinsically safe and A poor grounding system can
nonintrinsically safe conductors
(Fig. 2). The enclosure should be as NON-HAZARDOUS SIDE HAZARDOUS SIDE
close as possible to the hazardous
area to minimize cable runs and
increased capacitance of the circuit.
If they are installed in a hazardous
area, they must be in the proper Distributed
enclosure suited for that area. Control
Intrinsic Intrinsically
System
Safety Safe
Grounding Barrier Apparatus
First determine if the intrinsically
safe barriers used in the system are
grounded or isolated. The isolated
barriers normally are larger, more
expensive, and do not require a
ground for safety. The grounded Single Ground Point
safety barriers are smaller and less
expensive, but require a ground to
divert the excess energy. The main
rules of grounding intrinsically safe
systems are:
The ground path must have less
than 1 ohm of resistance from the
furthest barrier to the main Main Earth Ground
grounding electrode. Figure 4. Acceptable grounding.

Z-147
wiring diagram is defined by the
NEC as a drawing or other
NON-HAZARDOUS SIDE HAZARDOUS SIDE document provided by the
Explosion Proof
Enclosure manufacturer of the intrinsically
safe or associated apparatus that
details the allowed
interconnections between the
intrinsically safe and associated
Distributed Intrinsic Intrinsically apparatus. These diagrams are
Control Safety Safe
System Barrier Apparatus easier to obtain than in the past.
Make sure that one of the
manufacturers provides not only
diagrams which show the
interconnections between the field
Z
device and barriers, but also
Intrinsically Explosion Proof wiring diagrams which
Safe Seal Seal demonstrate that the circuit
functions properly and is safe by
Figure 5. Mounting in a hazardous area. comparing the safety parameters
of the field device and the barriers.
When barriers are installed in required. Once a year the barriers
explosion-proof enclosures, which should be checked to ensure that Make sure the circuit is powered.
are located in the hazardous area, the connections are tight, Check to see if the resistance in
the barrier is too high for the
explosion-proof seals are required the ground wiring has less than one circuit. As stated in the previous
on the enclosure (Fig. 5). Since ohm of resistance, and the barriers articles in this series, circuits are
other conduits containing are free from moisture and dirt. analyzed for the proper loop
nonintrinsically safe conductors Check the panel and conduits for resistance (barrier and cable) and
between the hazardous and separation and identification of the supply voltages. If the circuit does
nonhazardous areas require intrinsically safe wiring. Never test not operate properly, check the
explosion-proof seals, it is good the barrier with an ohmmeter or circuit against the design in the
practice to maintain consistency and other test instrument while it is control wiring diagram.
install explosion-proof seals on the connected in the circuit
conduits containing intrinsically safe (Fig. 6). This bypasses the barrier Check for a blown barrier fuse.
This is accomplished by
conductors also. The exception to and could induce voltages into the disconnecting the barrier from the
this would be where multiconductor intrinsically safe wiring. circuit and measuring the
shielded cable is used. This cable end-to-end resistance of the
may be difficult to seal in some Troubleshooting
barrier. If the ohmmeter registers
explosion-proof fittings. However, it If the intrinsic safety circuit does not an infinite resistance, the fuse in
will be necessary to seal both the operate properly once it is the barrier is blown. The fuse has
cable terminations and between the completed and energized, follow opened because of a fault in the
cable and raceway to minimize the these troubleshooting guidelines: circuit, so reevaluate the entire
passage of gases, vapors, or dust. Make sure the connections are circuit before reinstalling a new
tight. barrier.
Maintenance Check the wiring to the
No special maintenance of appropriate terminals against the Barrier Replacement
intrinsically safe systems is control wiring diagram. A control If the barriers fuse has opened, it
usually is the result of excessive
voltage being applied to the barrier.
Testmeter This causes the diode to conduct,
which results in high current in the
fuse. After determining the cause of
the excess voltage, the barrier must
be replaced. The procedure is to
disconnect the wiring from the
safety barriers in the proper order of
Intrinsic nonhazardous terminal first,
Safety hazardous terminals next, and the
Barrier ground last. Cover the bare wire
ends with tape, replace the barrier,
and then reverse the procedure to
mount the new barrier. Always install
the ground first and disconnect the
ground last.
NEVER DO THIS! Copyright Instrument Society of America.
Intech, October, 1993. All Rights Reserved.

Figure 6. The barrier should never be tested with an ohmmeter or other instrument while it is
connected in circuit.

Z-148
One Omega Drive | Stamford, CT 06907 | 1-888-TC-OMEGA (1-888-826-6342) | info@omega.com

www.omega.com
UNITED KINGDOM
www. omega.co.uk
Manchester, England
0800-488-488

UNITED STATES FRANCE


www.omega.com www.omega.fr
1-800-TC-OMEGA Guyancourt, France
Stamford, CT. 088-466-342

CANADA CZECH REPUBLIC


www.omega.ca www.omegaeng.cz
Laval(Quebec) Karvin, Czech Republic
1-800-TC-OMEGA 596-311-899

GERMANY BENELUX
www.omega.de www.omega.nl
Deckenpfronn, Germany Amstelveen, NL
0800-8266342 0800-099-33-44

More than 100,000 Products Available!


Temperature Data Acquisition
Calibrators, Connectors, General Test and Measurement Auto-Dialers and Alarm Monitoring Systems,
Instruments, Glass Bulb Thermometers, Handheld Instruments Communication Products and Converters, Data
for Temperature Measurement, Ice Point References, Acquisition and Analysis Software, Data Loggers
Indicating Labels, Crayons, Cements and Lacquers, Infrared Plug-in Cards, Signal Conditioners, USB, RS232, RS485
Temperature Measurement Instruments, Recorders Relative and Parallel Port Data Acquisition Systems, Wireless
Humidity Measurement Instruments, RTD Probes, Elements Transmitters and Receivers
and Assemblies, Temperature & Process Meters, Timers and
Counters, Temperature and Process Controllers and Power
Pressure, Strain and Force
Switching Devices, Thermistor Elements, Probes and
Displacement Transducers, Dynamic Measurement
Assemblies,Thermocouples Thermowells and Head and Well
Force Sensors, Instrumentation for Pressure and Strain
Assemblies, Transmitters, Wire
Measurements, Load Cells, Pressure Gauges, Pressure
Flow and Level Reference Section, Pressure Switches, Pressure Transducers,
Air Velocity Indicators, Doppler Flowmeters, Level Proximity Transducers, Regulators,
Measurement, Magnetic Flowmeters, Mass Flowmeters, Strain Gages, Torque Transducers, Valves
Pitot Tubes, Pumps, Rotameters, Turbine and Paddle Wheel
Flowmeters, Ultrasonic Flowmeters, Valves, Variable Area Heaters
Flowmeters, Vortex Shedding Flowmeters Band Heaters, Cartridge Heaters, Circulation Heaters,
Comfort Heaters, Controllers, Meters and Switching
pH and Conductivity Devices, Flexible Heaters, General Test and Measurement
Conductivity Instrumentation, Dissolved Oxygen Instruments, Heater Hook-up Wire, Heating Cable
Instrumentation, Environmental Instrumentation, pH Systems, Immersion Heaters, Process Air and Duct,
Electrodes and Instruments, Water and Soil Analysis Heaters, Radiant Heaters, Strip Heaters, Tubular Heaters
Instrumentation

click here to go to the omega.com home page


EPG05

Вам также может понравиться