Вы находитесь на странице: 1из 9

Steady-State Stability in Transmission Systems

Calculation by Means of Equivalent Circuits or Circle Diagrams


BY EDITH CLARKE 1

Associate, . I. . E.

Synopsis.The maximum load on a proposed transmission graphically. (2) By means of a circle diagram the system is tested
system must be within the steady-state power limit of the system for for stability with the maximum proposed load on the system.
stability of operation. Two methods of calculating steady state sta All formulas from published references necessary for the calcula
bility are given in detail and illustrated by examples. (1 ) The given tions are included and all calculations are given in full so that
transmission system is replaced by a simple equivalent system, then similar studies can readily be made by an engineer who has not
the steady-state power limit of this equivalent system is determined previously made a study of the subject of stability.

T HE object of this paper is to give two methods of


determining the stability of operation of a proposed
transmission system under steady-state conditions.
amount which can be transmitted at excitations which
correspond to normal voltage, any increase in synchro-
nous load will cause instability because the voltage must
The calculations will be given in detail so that drop before the voltage regulators can increase the
the engineer who has not previously made a study of excitations and at the given excitations no more power
the subject will have no difficulty in applying the tests can be transmitted. Therefore, when the voltage
for stability to his system. The first method is by starts to drop it will continue to drop, for there is no
means of an equivalent circuit and the second by means voltage at which the load can be transmitted with those
of a circle diagram. Both methods are based on excitations.
theorems which are exact, but in order to fit the trans When a generator and motor are on the same bus, at
mission system to the theorems certain assumptions no-load, neglecting no-load losses, their induced volt-
must be made. The results will therefore be approxi ages are in phase. Keeping the excitations on motor
mate to the extent to which the assumptions approxi and generator constant as the motor is gradually
mate actual conditions. loaded, the phase displacement between the excitation
Formerly when a transmission system was proposed, voltages of motor and generator increases with load
it was customary to make the line calculations for until the machines fall out of step. The load at which
voltage regulation and losses for the maximum load the machines fall out of step is the maximum load and
conditions, and to select the generators, transformers the angle is the maximum power angle. This angle and
and synchronous condensers to fit these conditions. the power corresponding to it can be calculated.
There was nothing in such calculations to indicate Power corresponding to an angle greater than the
that the system would be stable, but fortunately the maximum power angle can also be calculated although
length of line and maximum load have been such that it cannot be delivered.
cases of instability have been rare. At the present
time when the tendency is for longer lines and greater In the simple transmission system consisting of a
loads, it is necessary to consider the question of stability synchronous generator supplying power to a synchro-
both for steady state and transient conditions. Steady- nous motor over a line having resistance and reactance,
state stability only will be considered in this paper. but no appreciable capacitance or leakance, the maxi-
In steady-state stability the assumption is made that mum power that can be transmitted over the system,
the load comes on in infinitesimal amounts so that the and the angle between the generator and motor excita-
transient caused by one increment is over before the tion voltages corresponding to maximum power, are
next increment is added. The criterion of steady- not difficult to calculate. This simple system will be
state stability is this: Assuming that the system is stable under a proposed load if the phase displacement
operating satisfactorily under the assumed load con between the synchronous generator and synchronous
ditions, will it continue to operate satisfactorily if an motor excitation voltages corresponding to the proposed
increment of synchronous load is added and all ex load is less than the phase displacement which corre-
citations remain constant? When load is added there sponds to maximum power on the shaft of the motor.
is an increase in current and a drop in voltage before When a transmission system consisting of generators,
there is any change in excitation. The voltage regu lines with distributed constants, and the usual station
lators then increase the excitations and normal voltage load can be replaced by the simple transmission system,
is obtained. If the load on the system is just the the maximum power that can be transmitted over the
system is easily calculated. In studying steady-state
1. Central Station Engineering Dept., General Electric Co. stability by means of equivalent circuits an attempt
Abridgment of paper presented at the Midwinter Convention of
is made to replace the complicated transmission system
the A. I. E. ., New York, Feb. 8-11, 1926. Complete copies
available upon request.
by the equivalent simple system.
365
366 CLARKE: STEADY-STATE STABILITY IN TRANSMISSION SYSTEMS Journal . I. . E.

EQUIVALENT LINE Fig. 1 gives the real and imaginary parts of these
Dr. E . A. Kennelly has shown that a line with dis
2
correcting factors. For convenience the real and
tributed constants can be replaced by either an equiva imaginary parts of cosh / ZY are also given.
lent or line in which the constants are lumped. The Power at a Point Within the Equivalent . The
line consists of a line with a shunt at each end and 7T-line viewed from either end is an exact equivalent
the line of a line with a shunt at the center. The of the line with distributed constants but the current
nominal is formed by placing the total impedance, Z, and voltage at any point in the architrave of the do
of the actual line in the line or architrave of the and not correspond to current and voltage on the actual
one-half the admittance, Y, in each shunt or pillar. line. Let the 7r-line in Fig. 2 be the equivalent
The nominal is formed by placing one-half the total of the line A with distributed constants. Although
5 the current at d is the same as the current at B, the
current at has no counterpart in the actual line. The
power at d is the same as the power at B, but the power
0 ~" at is the power at d plus the power lost in shunt Z . 4

When the power is known at b and it can be calculated


at a and d.
j . SYNCHRONOUS IMPEDANCE
< It is understood that the synchronous impedance of a
R
/x-0. synchronous generator or motor is not constant.

\J
However, given the characteristics of the machine and
the conditions of operation, it is possible to find an

7 equivalent synchronous impedance which may be con
J ( sidered constant for the case under consideration. In
V '
/ x c . the work which follows constant synchronous impedance
refers to this equivalent synchronous impedance.
For the synchronous condenser it is necessary to
*/xA
find an equivalent excitation as well as an equivalent
synchronous impedance. This is discussed at greater
5-
5000 10,000 15,000 20,000
length in Appendix E .
FREQUENCY, CYCLES PER SECOND X LENGTH OF LINE, MILES
EQUIVALENT GENERATOR
25* 100 200 300 400 50 600 70 800
If a system consist of a synchronous generator and
60 ~ 0 50 100 150 200 250 300 350
LENGTH OF LINE - MILES synchronous motor, both of constant synchronous
FIG. 1COMPLEX HYPERBOLIC FUNCTIONS impedance, connected by a line with a shunt at the
. Z Y generator end, this system can be replaced for all
di + j a
cosh V 1 Y = 1 + 92 - + 2

points beyond the shunt by a system unchanged


sinh V
Z Y beyond the shunt, but having a new generator whose
= 1 + = 01+02
tanh V Y12
impedance is the impedance of the generator and shunt
V Y/2
71 + j 72. in parallel and whose excitation voltage

impedance of the actual line in each arm of the and


the total admittance in the shunt or staff. The nominal
and lines are not exact equivalents of the actual ,,
line, but by applying correcting factors to them the
equivalent and lines are obtained which are exact
equivalents of the actual line. FIG. 2A. LINE A WITH DISTRIBUTED CONSTANTS
Correcting Factors for Converting the Nominal or B. EQUIVALENT = LINE
Line Into the Equivalent or T. The correcting factors
which must be applied to convert the nominal or
is the

' = E l
z ^ + / Z l = E l
^ + : w h e r e

into the equivalent or are = = to be ap- 8

/ Y actual generator excitation voltage, Zi is the generator


plied to the architrave of the and the staff of the and impedance and Z is the shunt impedance. 8

This will be an exact equivalent, for the power at


tanh (V Y/2) breakdown on the two systems will be same. The
to be applied to the pillars of the
VZY/2 proof is given in Appendix ().
and the arms of the T, EQUIVALENT MOTOR
2. "Application of Hyperbolic Functions to Electric Engi If a system consist of a synchronous generator and
neering Problems.* ' synchronous motor, both of constant synchronous
Apr 1 9 2 6 CLARKE: STEADY-STATE STABILITY IN TRANSMISSION SYSTEMS 367

impedance, connected by a line with a shunt at the Zb = r + j = the impedance of the equivalent line.
motor end this system can be replaced for all points in Zi = ri + j xi = the actual generator impedance.
front of the shunt by a system unchanged up to the = ri+ j Xi = the equivalent generator impe
shunt, but having a new motor whose impedance is dance formed by taking the shunts at the generator end
the impedance of the motor and shunt in parallel of the line in parallel with the generator impedance.
Z = r + j x = the actual motor impedance.
Z $ 2 2 2

Z = r + j x = the equivalent motor impedance


2

and whose excitation voltage E = E ^, /Z 2 2 2


2

L + Z,
2
formed by taking the shunts at the motor end of the
2

line in parallel with the motor impedance.


2

z. Ei = excitation voltage of the actual generator.


= E -, 7 , where E is the actual motor excitation E = excitation voltage of the actual motor.
2 2
2

voltage, Z is the motor impedance and Z is the shunt


2 a
Ei = excitation voltage of the equivalent generator
impedance; but power on the fictitious system corre
sponding to breakdown power on the actual system
occurs when the phase displacement between the
generator and equivalent motor excitation voltages is E = excitation voltage of the equivalent motor
2

the total impedance angle of the fictitious system plus


the angle, 2 (0 '), where 0 is the impedance
2 2 2

angle of the actual motor and 0 ' is the impedance angle


2

of the equivalent motor. The proof is given in Ap E A = terminal voltage at the generator end of the
pendix (6). line.
EQUIVALENT SYSTEM AND VOLTAGE REGULATORS
If a system consists of a synchronous generator and ;
A

synchronous motor, both of constant synchronous E,HWW WWim-E't


impedance, connected by a line with a shunt at each
end, voltage being maintained at the ends of the line,
his system can be replaced for all points of the line by
a system consisting of the same line without shunts,
a generator whose impedance is the impedance of the
actual generator and shunt at the generator end in
parallel and a motor whose impedance is the impedance
of the actual motor and shunt at the motor end in
parallel; but power on the fictitious system correspond-
ing to breakdown power on the actual system occurs Fia. 3 A . EQUIVALENT TRANSMISSION SYSTEM
B . GRAPHICAL DETERMINATION OP MAXIMUM POWER
when the phase displacement between equivalent OVER THE EQUIVALENT TRANSMISSION SYSTEM
motor and generator excitation voltages is the total
impedance angle of the fictitious system plus 2 (0 ) E = terminal voltage at the receiver end of the line.
2 2

where 0 is the impedance angle of the actual motor


B
2
Zt = (r +jx + n' +jxi' +r ' + jx ') =R +jXt
and 0 ' the impedance angle of the equivalent motor. 2 2 t

The proof is given in Appendix D. = z e t


jet

When 2 (0 0 ') = 0 deg., the fictitious system


2 2 = total impedance of the equivalent system.
becomes an equivalent system, for the power at break
down on the two systems will be the same. When 0< = tan- = total impedance angle. 1

resistance is neglected in the motor and motor end shunt


2 (02 - 0 ') = 0 deg. or 360 deg.
2
0 = tan = impedance angle of the actual
-1
2
Since no limitation is placed on the shunt impedances 2
in the proofs given in the appendix, in addition to motor.
representing the capacitance in the line, they may
represent reactors, resistance load or any other dead x 2

load. 02 ' = t a n ; impedance angle of the equiva-


-1

2
EQUIVALENT CIRCUIT METHOD
lent motor.
Graphical Solution. When the actual system has Calculate a' = 0, + 2 (0 - 0 ') 2 2

been replaced by the equivalent simple system, the Since there are no shunts in the equivalent or ficti
maximum power which can be transmitted may be tious system the same current will flow in all parts of
obtained graphically. the circuit. Taking current as standard phase, lay
Let Fig. 3A represent the simple equivalent system, off
where Q = I ( ' + j x ')+I (r + j x)+I (rV + ; x ')
2 2 x

= ZI
368 CLARKE: STEADY-STATE STABILITY I N TRANSMISSION SYSTEMS Journal . I. . E.

to any convenient scale. Fig. . The value of this When X = O, which is the case for a motor and
scale will be determined when the construction has been generator on the same bus,
completed and the position of point 0 determined.
There are two conditions which determined the max =
g (3)
position of point 0.
1. a' = 6t + 2 ( 0 2 - 0 ') 2
When Xi' = X = 0, which is the case for infinite
2

2. The ratio between the magnitudes of E and E K B


busses at the ends of the line,
or between E \ and E is known. For a regulated line
2
_ _1_
E and E are given, and for a line without voltage
A B
max j (4)
regulators \ ' and E can be calculated from the known
2

values and E .
2
APPLICATION OF THE FICTITIOUS OR EQUIVALENT
Consider the case of the regulated line: To satisfy SYSTEM TO STEADY STATE STABILITY PROBLEMS
the first condition join and Q and at drawn R 1. Effect of Capacitarne in the Line. If resistance is
making an angle, (90 -a') with PQ. With R, the neglected and generator and motor of equal impedances
intersection of R with the perpendicular bisector of are assumed, equation (2) may be used to calculate
P Q, as a center and R as radius describe arc Q.
maximum power over the line with and without
If point 0 lies on this arc, the first condition will be
capacitance. Without capacitance, Xi will be the
satisfied. To satisfy the second condition, find a series
actual generator impedance. Capacitance in the line
of points whose distances from A and are in the ratio
EA/EB and draw a curve through them. will lie on
the intersection of this curve with the arc Q.
The scale of the vector diagram is determined, for
= . All voltage drops are now given in terms
of . is known, therefore all voltage drops are
known and the current can be calculated. The power
factor angle, 0, can be measured.
Maximum Power at = . / . cos .
The impedances, voltages and currents may be
expressed in ohms, volts and amperes respectively or
in per cent, as is most convenient.
Algebraic SolutionResstame Neglected. When re
sistance is neglected and equal voltages are maintained
at the ends of the line a simple formula can be derived 0 v
20 40 60 80 100 120
PER CENT IMPEDANCE OF GENERATOR
for the power delivered. AND TRANSFORMER ON 100,000
Kv-a. BASE
If
FIG. 5MAXIMUM SYNCHRONOUS LOAD DELIVERED OVER 2 2 0 -
= the equivalent generator reactance. Kv., 6 0 CYCLE, TRANSMISSION LINES OF VARIOUS LENGTHS
= the equivalent motor reactance. When resistance is neglected. Synchronous generators and motors
X = the equivalent line reactance. assumed to have equal synchronous impedances. (Transformer impedance
included in generator impedance)
VA = = magnitude of line terminal voltages,
E A and .
will reduce X, since X is multiplied by the correcting
factor which is less than unity, but it will increase X / ,
(ir for when the negative reactances of the shunts of the
equivalent -line are combined in parallel with the
( 4 ) , +
( * ' , +
4 ) ( ' , +
4 - ) positive reactances of the machines, the equivalent
reactances are greater than the actual machine react
When is in volts to neutral, and reactances are in ances. The effect of capacitance will be to increase or
ohms, power will be in watts per phase. If voltages and decrease the maximum power depending upon whether
reactances are in per cent, power will be in per cent the change in X or in X / has the greater influence.
( 2 0 % = 0.20).
When = 100 per cent and the motor and generator CURVES FOR ESTIMATING MAXIMUM POWER
have the same impedance {X = X ) equation (1) x 2 f
The curves in Fig. 5 were calculated for 60 cycles and
becomes various lengths of line, assuming reactance of 0.813
X mhos per mile and capacity susceptance of 5.22 IO -6

Xi' + -- mhos per mile, 2 2 0 kv. was maintained at each end of


max =
~ I 77 : (2) the line, resistance was neglected in the line and in
the generators and motors which were assumed of
(--) + ( * ' + 4 - ) equal synchronous impedances. These curves can be
This equation was first developed by C. A. Nickle. used as a first approximation.
April 1 9 2 6 CLARKE: STEADY-STATE STABILITY I N TRANSMISSION SYSTEMS 369

2. Reactor Across the Generator Terminals. If a When Vi and V are in volts to neutral and is in
2

reactor is placed across the generator terminals the ohms, power will be in watts per phase. If voltages and
effect is opposite to the effect produced by the capacity impedances are in per cent, power will be in per cent
shunt. The reactor reduces the equivalent generator (20 per cent = 0.20).
impedance so that more power can be transmitted over When Vi and V are bus voltages, the total impe
2

the system. It must be remembered that the excitation dance between the buses and 0 the total impedance
on the generator is increased by the use of a reactor, but angle, Pmax will be the maximum power that can be
when full field is not being used on the generator, a exchanged between the buses.
reactor increases the power that can be transmitted by
the same amount that a generator of the same rating EN
ji
WW
(34.5+j 194.6) Ohms

would do. Since reactors are cheaper than generators,
a reactor of the size that would put full excitation on the
generator can be used to advantage to increase the
stability of the system.
3.' Power Limits of a Long Line.
a. Limit of the line alone. FIG. 6EQUIVALENT * OF THE TRANSMISSION LINE ALONE
b. Limit of the line and transformers.
Z =(89.6+j232.1)Ohms
c. Limit of the line transformers and generator. ;
6

4
d. Limit of the system with various kinds of load. IG"

1. Synchronous motors.
2. Lights and synchronous motors. 2 S
I

3. Lights, induction motors, synchronous


motors and synchronous condensers.
4. Same as (3) but with a generator supplying
FIG. 9EQUIVALENT OF THE LINE AND TRANSFORMERS
local load.
A line with generator and transformers will be selected When Vi and V are excitation voltages of synchro
2

then the maximum power will be obtained for the speci nous generator and synchronous motor respectively,
fied conditions. the total impedance between them and 0 the total
Given: impedance angle, P max will be the synchronizing power
A three phase, 60 cycle, 250 mile line. between the two machines.
Line constants: r = 0.151 ohms per mile Fig. 6 gives the equivalent of the line alone. Fig. 9
= 0.813 ohms per mile gives the equivalent of the line and transformers.
y = 5.22 micro-mhos per mile The maximum power which can be transmitted over
Leakance = 0. the line alone and over the line with transformers may
Step-up transformers: 270,000 kv-a. total be obtained by subtracting the power lost in the receiver
2 per cent resistance shunt from the total power which can be exchanged
12 per cent reactance between the buses.
13,200220,000 volts. (a) The limit of the line alone = 187,000 kw.
Step-down transformers: 240,000 kv-a. total, (b) The limit of the line with transformers =
2 per cent resistance 158,500 kv.
12 per cent reactance
210,000-13,200 volts i- j 179.2 Ohms
A
Bd
Ei /
- 66 -E
V

Generators: 270,000 kv-a. total - V W W


Z(39.6+j232.1)0hms 2 Z
2

0.9 power factor, 13,200 volts


100 per cent synchronous impedance.
Voltage regulators will maintain 220 kv. and 200
kv. at the generator and receiver ends respectively on
the low sides of the transformers (assuming a one-
to-one ratio of transformation). The magnetizing FIG. 11EQUIVALENT * OF THE LINE AND TRANSFORMERS
current in the transformers will be neglected. With synchronous generator and motor. Impedances are in ohms
referred to the high side.
From equation (7) Appendix ().
Vi v2 v 2
(c) Limit of the line, transformers and generator is
= (1 ~~ cos 0), where Vi and V obtained
2
by assuming a motor of zero impedance or an
Vi infinite bus at the receiver end.
are terminal voltages at the generator and receiver ends Fig. 11 represents the line with end shunts and a
respectively, is total impedance, and 0 is total im motor and generator each of constant synchronous
pedance angle. impedance. The power at d, that is the power de-
370 CLARKE: STEADY-STATE STABILITY IN TRANSMISSION SYSTEMS Journal . I. . E.

livered to the load, will be the power at minus the Z 2 = motor impedance on 100,000 kv-a. base = 50 per
power lost in Z . Fig. 12 gives the equivalent circuit
4
cent
with the impedances in per cent on a 100,000 kv-a. Z Z4
= impedance of equivalent motor
2

base. 100 per cent voltage = 200 kv. The shunt ZJ =


Z2 + Z4
Z has been combined in parallel with the generator
3

impedance. The shunt Z has not been combined with


3
= (0.07 + ; 57.8) percent
the motor impedance. Fig. 14 gives the equivalent circuit.
Z = total impedance = (10.0 + j 166.9) per cent.
t

d 6\ = total impedance angle = 86.6 deg.


(0.04+j 51.1) % Z, (9.9+j 58.0) % Z 2
0 = impedance angle of actual motor = 90 deg.
2

Z =(9.9+j58.0)7.
6

E-WW<-WW TOWWW-E 2

Zi (0.04+J51.1)'/. A . Z ; .07+j57.8)Z
s(0

FIG. 12EQUIVALENT CIRCUIT OF LINE, TRANSFORMERS, FIG. 14EQUIVALENT CIRCUIT FOR SYNCHRONOUS MOTOR
LOAD
GENERATOR AND MOTOR
Impedances are in per cent on a lOO.OOO-kv-a. base. 100 per cent
voltage - 200 kv.
0 ' = impedance angle of equivalent motor = 89.9 deg.
2

2 (0 - 0 ') = 0.2 deg.


2 2

The voltages~and impedances in per cent from Fig. a' = e + 2 (0 - 0/) = 86.7 deg.
t 2

12 are Using the equivalent circuit given in Fig 14 and.


E A = 110 per cent, = 100 per cent, making the graphical construction as described above,
Z / = (0.04 + j 51.1) per cent, Z ' = 2 Fig. 15 is obtained.
Z = (9.9 + j 58.0) per cent,
5 Since = 100 per cent voltage, I = 112.5 per cent
Z + Z / + Zt' = (9.9 +j 109.1) percent = Z
5 t current and
a' = maximum power angle = 6\ + 2 (0 6Y) = 6\ 2 Power factor at = 0.943 lead.
109.1 Power at = 1 X 1.125 X 0.943 = 1.06
= tan- 9.94 = 84.7 deg.
1
= 106,000 kw.
Power lost in shunt Z = 180 kw. 4

Making the graphical construction as described Maximum power that can be delivered to the load
above, Fig. 13 is obtained. From Fig. 13 = 106,000 kw.
BP
Since = 100 per cent Voltage, I = > / tt

1.845
= 1.685 = 168.5 per cent current.
1.095

o:

FIG. 13GRAPHICAL DETERMINATION OF MAXIMUM POWER


WITH AN INFINITE B u s AT THE RECEIVER END FIG. 15GRAPHICAL DETERMINATION OF MAXIMUM POWER
FOR A SYNCHRONOUS MOTOR LOAD
Power factor at = 0.84 lead.
Power at = 1 X 1.685 X 0.84 = 1.415 2. Resistance load of 30,000 kw., synchronous
= 141.5 per cent on 100,000 kv-a. base motors of total capacity 170,000 kv-a. with 85 per cent
= 141,500 kw. synchronous impedance.
Power lost in shunt Z = 180 kw. 4 R = resistance of the resistance load shunt.
Limit ofthe line, transformers and generators = 141,300 kw. = 1333 ohms.
d. Limit of the system with various kinds of load. = 333.3 per cent on 100,000 kv-a. ; base,'200 kv.
1. Synchronous motor load of total capacity 170,000 ZA = impedance of Z andin parallel = (184 /165) 4

kv-a., 85 per cent synchronous impedance. per cent


Aprii 1 9 2 6 CLARKE: STEADY-STATE STABILITY IN TRANSMISSION SYSTEMS 371

2 = impedance of actual motor = 50 per cent examples of types (3) and (4), will eventually be com
2 Z pletely represented by equivalent circuits.
= ~7~, = impedance of equivalent motor CIRCLE DIAGRAM METHOD
L2 - 4
The test for stability by this method is to assume a
= (9.8 + j 56.1) per cent slight increase in load and to determine if by a drop in
Zt = total impedance of equivalent circuit = (19.74 receiver voltage this new load can be carried with the
+ j 165.2) per cent excitations corresponding to the original load.
= 83.2 deg. = total impedance angle, When a system is operating at normal voltage ana
' = + 2(02 - 0 ') = 83.2deg. + 2 ( 9 0 - 80.1deg.)
2
load is added there is an increase in current at the
= 103.0 deg. receiver end and a drop in voltage. The power given
The graphical construction is given in Fig. 16. to the additional load comes from the change in phase
Since = 100 per cent displacement between the sending and receiving end
I = 138.5 per cent and power factor at equipment. Due to the drop in voltage at the load, the
= 0.90 lead original load does not require the same power it required
Power at = 1 X 1.385 X 0.90 = 1.248 at normal voltage if it is the average station load.
= 124,800 kw. The kw. and kv-a. taken by the original load changes
Power lost in the line shunt Z = 180 kw.
A
with voltage. If voltage slightly less than normal is
Maximum power that can be delivered to the load assumed at the receiver end and the kw. and kv-a.
= 124,600 kw. corresponding to the original load at this voltage plus
a small load increment can be transmitted over the line
with the given generator excitation, the system is
stable, for the small increment is the contribution to
the additional load made by the change in phase dis
placement of the system. For the limit of stability this
increment approaches zero.
The method of obtaining the general circuit constants
of a transmission system, and the construction of the
power circle diagram from these constants has been
described by Mr. R. D. Evans and Mr. H. K. Sels in a
paper before the Institute.
4

GENERAL CIRCUIT CONSTANTS


The same line, transformers and generator used to
illustrate the equivalent circuit method will be used for
Q the circle diagram.
FIG. 1 6 -GRAPHICAL DETERMINATION OP MAXIMUM POWER The constants of the line alone are:
FOR A LOAD PARTLY RESISTANCE AND PARTLY SYNCHRONOUS A = D = cosh VY~Z = + ja = 0.8700 + ; 0.0236 2

sinh y/ZY
3. Lights, induction motors, synchronous motors = = = ( + j ) = 34.52 + j 194.6
2

and synchronous condensers. \ / Z Y

4. Same as (3) but with generator supplying local sinh y/ZY


load. = Y = Y(!+j )
As voltage drops on an induction motor load, the v 2

power required by the load remains practically con = ( - 0.0104 + j 1.248) IO" 3

stant and the power factor becomes less lagging. A (ai, a , i and obtained from Fig. 1.)
2 2

lightly loaded synchronous motor has the same charac The circuit constants of the line and the step-up and
teristics. The induction motor load therefore, may be step-down transformers, neglecting magnetizing cur
replaced by an approximately equivalent synchronous rents are calculated from Item (g) of the Evans
motor. and Sels paper. To include magnetizing current
6

A method of treating the synchronous condenser in Item (j) should be used instead of (g).
the equivalent circuit is given in Appendix E. A - A + CZ = 0.8431 + j0.0279
0 8

Examples of type (3) can be solved by the equivalent Bo = + A (Z 8 + Zr) + CZ Z


8 r = 39.6 +j 232.1
circuit method but the solution with the circle diagram Co = = ( - 0.0104 + j 1.248) 10" 3

is more satisfactory than the solution by the equivalent D = A + CZ = 0.8424 +j 0.0280


0 Z

circuit method available at present. An example of Z and Z are the transformer impedances at the
a r

type (4) is solved by the circle diagram method. See sending and receiving ends respectively.
example (3) following. It is hoped that systems more 4. Power Limitation of Transmission Systems, TRANSACTIONS
complicated than the one considered here as well as of the A . I . E . E . , Vol. 4 3 , 1 9 2 4 , page 3 3 .
372 CLARKE: STEADY-STATE STABILITY I N TRANSMISSION SYSTEMS Journal . I. . E .

It is of interest to note that these constants can beAt this point kw /kv = 3.95, and kw = 3.95 (200) r r
2
r
2

obtained from the equivalent including the line and = 158,000 kw.
transformer or the equivalent can be obtained from c. The power limit of the generator, line and trans
these constants. See Appendix F. formers is obtained from the dotted curve at the point
The circuit constants including the generator as wellwhere the tangent to the solid circle is vertical. At this
as the line and transformers are point kw /kv = 3.53, and kw = 3.54 (200) = r r
2
r
2

Aoo = A + Z i Co = 0.6193 + j 0.0260


0
141,200 kw.
Boo = Z i Do + Bo = 34.59 + j 383.1 The limit of the system with various kinds of load
Where A , Bo, C and D refer to the circuit constants
0 0 0 can not be determined directly by means of the circle
of the line and transformers and Z i is the generator diagram. A certain load must be assumed and then
impedance. the system tested for stability with this load. If the
CONSTRUCTION OF THE CIRCLE DIAGRAM
system is stable, a larger load should be assumed, but if
unstable, a test should be made with a smaller load.
(PR + l ER*)* + (QR + m ER*) = ER E* 2 2 2 2

If this process is continued until a load is obtained for


is the equation of the Receiver Power Circle Diagram in which the system is stable, but for which there is no
volt-amperes. If the question is expressed in kilovolt margin, this will be the maximum power of the system.
amperes and divided by ER* it becomes
/ PR \ 2
/ QR V / E \
t
2 To TEST FOR STABILITY ON THE CIRCLE DIAGRAMS
Calculate kw /kv for the given load at normal
r r
2

voltage and find the corresponding point on the dotted


This is a circle for receiver power in terms of the circle. The ratio of generator excitation voltage
receiver voltage and the ratio between the sending and to receiver voltage is read from the solid circle cutting
receiving voltages. The center of the circle is at the the dotted circle at this point, and the generator excita
point - I 10 , - m IO .
3 3
tion voltage calculated. Assume a receiver voltage
If slightly less than normal and calculate the active and
A = + j a
0 2 reactive power of the load corresponding to this voltage,
and assuming constants excitations. Divide the active
Bo = Ro +j Xo and reactive power in kilovolt amperes by the square of
ax Rp + 0*2 Xq the assumed receiver voltage in kilovolts and locate
the point on the diagram. Read Ei/E at this point r
' =
+ Xo
2 2

and calculate E the generator excitation voltage. If


h

d\ Xo 02 Ro this value of is equal to or less than the excitation


voltage calculated at normal voltage the system is
m =
Ro + Xo
2 2
stable. It is sometimes more satisfactory to select a
receiver voltage slightly above normal as well as one
1 below normal, then when the corresponding calculated
= ; generator excitation voltages are both higher than the
VRo 2
+ Xo 2

excitation voltage corresponding to normal receiver


Two circle diagrams will be drawn; one for the line voltage, the assumed load is the power limit.
and transformers and the other for the line, transformers
and generator. Since they are both for power at the 1. Given: 170,000 kv-a. synchronous motor, 85
receiver end in terms or receiver end voltage, they will per cent synchronous impedance.
be drawn on the same chart. The ratio of the voltage It has been shown by the equivalent circuit method
on the low side of the transformer at the generator end that 106,000 kw. is the maximum power that can be
to the voltage on the low side at the receiver end for delivered to this motor. Testing by means of the circle
normal operation has been assumed 220/200 = 1.1. diagram, Fig. 17, for a load of 106,000 kw., point A,
One circle with E /E = 1.1 will be drawn in the dia
8 r
located on the dotted circle for kw /kv = 2.65, r r
2

gram for the line and transformers. A series of circles gives the generator excitation voltage from the solid
with the ratio of the excitation voltage of the generator circle passing through A as 242 kv. at normal receiver
to the receiver voltage having various values will be voltage. Point A ' corresponds to 98 per cent receiver
drawn for the line, transformers and generator. voltage and A " to 102 per cent receiver voltage. The
The problems already solved by means of the equiva corresponding generator excitation voltage in each case
lent circuit will now be solved by the circle diagram. is just about 242 kv. which indicates that 106,000 kw.
b. The power limit of the line and transformers at is very near the limit of stability.
the specified voltages is obtained from the dotted circle 2. Given: Resistance load of 30,000 kw., and the
at the point where the tangent to the circle is vertical. synchronous motor of example 1.
*Equation ( 2 8 ) . I . E . E . TRANSACTIONS, Vol. 43, page 36. The power delivered to a resistance load varies as the
fCircle Diagrams for Transmission Systems, R. D . Evans square of the voltage. The power delivered to a shaft
and H . K. Sels, Electric Journal, December 1921. load is practically independent of voltage. Points
April 1926 CLARKE: STEADY-STATE STABILITY IN TRANSMISSION SYSTEMS 373

B, B' and B" on the circle diagram give the generator Pr = 132,600 kw. ] active and reactive power
excitation voltages corresponding to receiver voltages I of the original load at 98 per
of 100 per cent, 98 per cent and 102 per cent respectively Qr = 57,270 kv-a. J cent receiver voltage and
for a load of 120,000 kw., and points , C" and C" the constant excitations.
corresponding values for a load of 130,000 kw. The Pr+Qr
system is stable at 120,000 kw. but unstable at 130,000 =3.45+ 1.49, determines location of point D'
E 2

kw. r

3. Given: Total load of 180,000 kw. of which one- /Er = 1.41, obtained from solid circle passing
third is resistance load, one-third induction motor load through D'.
and one-third synchronous motor load, The induction Ei = 276 kv., excitation voltage of generator at
motors have an average power factor of 0.7 lag at nor thesendingend.
mal voltage. The synchronous motors have 100 per cent Since E the calculated generator excitation voltage,
u

synchronous impedance, are 75 per cent loaded and are at 98 per cent receiver-voltage is less than Ei at 100
operated at unity power factor. A 100,000 kv-a. per cent receiver voltage for the same receiver load, the
synchronous condenser is placed at the load. The system is stable. These calculations do not indicate
generators at the receiver end of the line, having total the load whih can be added with stability maintained.
capacity of 100,000 kv-a. and synchronous impedance They merely indicate that the system is stable under the
of 100 per cent, supply 45,000 kw. to the load and part assumed load conditions.
of the reactive kv-a. needed for voltage regulation. Is In the examples which have been considered a single
the system stable? generating station supplies power over one circuit to a
single receiving station. In more complicated systems
1 where it may be necessary to cut and try, the circle
\ diagram can be used to advantage for the various parts
I \ of the system.
1 0 5 ACKNOWLEDGMENT
:|orKv ,/KV;
\ LA
X * A'
The idea of combining the shunts at the ends of the

\ line with the synchronous apparatus is due to Mr.

7/
LEADII
1

1 f iD C. A . Nickle who proved that "neglecting resistance,


_
D a line with synchronous apparatus and reactance or
capacitance shunts may be replaced by a line and
12
1

2
or Kv-a

E . / E , 1.0 equivalent synchronous apparatus with no shunts."


I V 7 The writer wishes gratefully to acknowledge her

3

/ / /
/
/ indebtedness to Messrs. H. H. Dewey and R. E.
Doherty for their encouragement and suggestions which

0
4 / / 1
1 have broadened the scope of this study, and to Mr.
Nickle for his suggestions in the development of certain
FIG. 17CIRCLE DIAGRAM FOR THE TRANSMISSION SYSTEM
phases of the subject.
100 Per Cent Receiver Voltage PURER IRON PRODUCED
Er 200 kv. = 100 per cent receiver voltage. ELECTRICALLY
Pr 135,000 kw. = total power over the line.
Pig iron is now the basic form from which all types
Pr kw r
of iron and steel are made but it may become obsolete
= 3.375, determines location of and the direct manufacture of malleable iron and steel
kv 2
2
r
from ore may follow the invention of a special electric
point D on dotted circle, Fig. 17. furnace of commercial size that has been built in the
great Hagfors, Stockholm, Sweden, ironworks where
Qr_
1.28 read at point D, Fig. 17. iron ore and coal mixed and fused have been made to
E 2

produce pure iron containing only two per cent of car


Q r = 51,200 kv-a. = total reactive power over bon, and steel- that can be worked in the usual manner.
the line. The new process is continuous and fusion ceases only
temporarily when the furnace is tapped, while the ab
/Er = 1.385, obtained from solid circle passing
through D. sence of gases and slag produces a superior product.
The United States leads the world in the number of
Ex = 277 kv. = excitation voltage of generator / electric steel furnaces in use, and with the discovery of a
at sending end. process of making iron and steel directly from ore
98% Receiver Voltage. would give a tremendous impetus to the use of the
Er = 196 kv. = 98 per cent voltage electrical smelting furnace.

Вам также может понравиться