Go to parameter 16-03
-enter 2303 as passcode
-press enter
-"..." Should appear for a brief moment
Go to parameter 145 (yes 145 now exists, before it only went to 99)
-go to sub-parameter 13 Titled "FAN ON-TIME"
-Press enter
-now you must hold the down arrow until you have brought the hours down to zero. This will take some time as
it only decreases in increments of 10, my counter is at 50 000+
-once back to zero press enter. Problem solved, drive should run immediately if being called on to start
Now you are done. ACT button out and let fly!
PREKOSTRUJA
Prekostruja javlja kada struja poraste od 1.65 do 2.17 puta vise od Imax
"Preprogrammed faults
Overcurrent
The overcurrent trip limit for the drive is 1.65 to 2.17 Imax depending on the drive
Type."
-Automatic resets
The drive can automatically reset itself after overcurrent, overvoltage, undervoltage
and .analogue input below a minimum. faults. The Automatic Resets must be
activated by the user.
Settings
Parameter group 31 AUTOMATIC RESET.
-Fault word 1 drugi bit(tj nulti pa prvi- koji je drugi po redu ) oznacava
prekostruju
-OVERCURRENT
(2310)
3.05 FW 1 bit 1
- If the drive tripped during flying start, check that Parameter 21.01 START
FUNCTION is set to AUTO. (Other modes do not support flying start). Check motor load.
Check motor and motor cable (including phasing). Check pulse encoder and pulse encoder
cable. Check that there are no power factor correction capacitors or surge absorbers in the
motor cable
Check acceleration time.
Check the nominal motor values from Group 99 to confirm that the motor
model is correct.
-The Overcurrent trip limit is 3.5 * Ihd (nominal motor current for heavy
duty use). There are several sources of the overcurrent trip:
Software trip (time level 100 s, level = 97 % of measurement
scale)
Hardware level trip (97 % of measurement scale for 35 s)
Hardware derivative trip (12.5 % of measurement scale for 75 s)
Hardware level trip in parallel connected units by PBU logic (94 %
of measurement scale for 75 s)
A fault OVERCURRENT is given and FW_1 (09.01) bit 1 is set to 1.
The current measurement is calibrated automatically during the start
procedure.
-Overcurrent 30.08
(Default: 230%
Type: R
OC equiv: 1=1) CONV OVCUR LEV F02
-OVERCURRENT
Par. 9.01 bit 1
Par. 9.11 bit 1
Input current is excessive. The overcurrent trip
limit is 0.98 (Par. 4.08 CONV MAX
CURRENT). The trip limit is approximately
190% of the converter nominal current I1N (Par.
4.05 CONV NOM CURRENT).
Check motor load.
Check supply voltage.
Check that there is no power factor
compensation capacitors in the supply.
Check ISU power semiconductors and current
transducers.
-The minimum ground cable recommendation assumes that the overcurrent protection for each drive
is selected to provide protection at 125% of the rated drive input current. If the overcurrent protection
(e.g. circuit breaker) is sized larger than this, then larger ground cables will need to be determined
Manuall