Академический Документы
Профессиональный Документы
Культура Документы
3 NOV2006 (R2012)
Installation and Maintenance of Farm Standby Electric Power
American Society of
Agricultural and Biological Engineers
ASABE is a professional and technical organization, of members worldwide, who are dedicated to advancement of
engineering applicable to agricultural, food, and biological systems. ASABE Standards are consensus documents
developed and adopted by the American Society of Agricultural and Biological Engineers to meet standardization
needs within the scope of the Society; principally agricultural field equipment, farmstead equipment, structures, soil
and water resource management, turf and landscape equipment, forest engineering, food and process engineering,
electric power applications, plant and animal environment, and waste management.
NOTE: ASABE Standards, Engineering Practices, and Data are informational and advisory only. Their use by anyone
engaged in industry or trade is entirely voluntary. The ASABE assumes no responsibility for results attributable to the
application of ASABE Standards, Engineering Practices, and Data. Conformity does not ensure compliance with
applicable ordinances, laws and regulations. Prospective users are responsible for protecting themselves against
liability for infringement of patents.
ASABE Standards, Engineering Practices, and Data initially approved prior to the society name change in July of 2005
are designated as "ASAE", regardless of the revision approval date. Newly developed Standards, Engineering
Practices and Data approved after July of 2005 are designated as "ASABE".
Standards designated as "ANSI" are American National Standards as are all ISO adoptions published by ASABE.
Adoption as an American National Standard requires verification by ANSI that the requirements for due process,
consensus, and other criteria for approval have been met by ASABE.
Consensus is established when, in the judgment of the ANSI Board of Standards Review, substantial agreement has
been reached by directly and materially affected interests. Substantial agreement means much more than a simple
majority, but not necessarily unanimity. Consensus requires that all views and objections be considered, and that a
concerted effort be made toward their resolution.
CAUTION NOTICE: ASABE and ANSI standards may be revised or withdrawn at any time. Additionally, procedures of
ASABE require that action be taken periodically to reaffirm, revise, or withdraw each standard.
Copyright American Society of Agricultural and Biological Engineers. All rights reserved.
ASABE, 2950 Niles Road, St. Joseph, Ml 49085-9659, USA, phone 269-429-0300, fax 269-429-3852, hq@asabe.org
ANSI/ASAE EP364.3 NOV2006 (R2012)
Revision approved December 2006; reaffirmed January 2012 as an American National Standard
ANSI/ASAE EP364.3 NOV2006 (R2012) Copyright American Society of Agricultural and Biological Engineers 1
4.4.2 Vibration dampening pads should be placed between the skid, or 4.9.4 Safety Requirements for Electrical Connection. The installer,
mounting base, and the floor or concrete base to minimize the transfer of maintence personnel and operators shall ensure that the electrical
vibration to other equipment. connections to the generator meet all the following requirements.
4.4.3 Tractor-driven generators are normally either stationary mounted 4.9.4.1 Compatibility of Plug and Generator. The plug and generator
or mobile mounted on a trailer or with a three-point hitch. receptacle shall be of like configurations to ensure compatibility with each
4.4.3.1 Stationary mounting should follow the manufacturers other during the mating operation. Both the plug and the generator
recommendations of mounting on concrete pads. receptacle shall have the same wiring order. The polarization shall be
4.4.3.2 In the event of mobile mounting, such as a trailer or a three-point keyed or of such design that polarization will not be defeated by improper
hitch, the mounting should be of sufficient size and stability to withstand assembly during installation.
pulling over rough terrain and to withstand torque stresses experienced 4.9.4.2 Exposed Contacts
when full loads are applied to the generator through the power take-off 4.9.4.2.1 Mating plug and connector shall not have exposed live
driveline and input connection. contacts during engagement or withdrawl (in Canada, as required in, and
4.4.3.3 Alternators should be mounted on the trailer or three-point hitch tested in accordance with, CSA Standard C22.2 No. 182.3).
such that power drive lines are in good alignment.
4.9.4.2.2 As an alternate to 4.9.4.2.1, mating connectors which have
4.5 Safety Provisions. The power take-off and power take-off drive exposed live contacts after withdrawal of the plug shall have a cover
lines for PTO tractor-driven generators should conform to safety which is:
provisions of ASAE S318 and ASAE S207. a) spring loaded for self-closing the live parts of the connector after the
4.6 Ventilation for engine-driven generators. It is imperative that the plug is removed,
engine and generator have an adequate supply of air for combustion and b) secured on the opposite end of the spring by means requiring a tool
cooling. or key to remove the cover when the connector is not in use, and,
4.6.1 Ductwork should be used when necessary from the radiator to the c) a warning sign alerting the user about the live parts under the cover
outlet to prevent hot air recirculation. and to secure the cover with the tool or key after the plug is
withdrawn.
4.6.2 There should be a flexible ductwork section at any connection to
the generator. 4.9.4.3 Weatherproof. Both connector and plug shall be of weatherproof
type (In Canada meeting the requirements of CSA Standard C22.2 No.
4.6.3 The air inlet must be larger in size than the air outlet. The air inlet 182.3), unless the generator is specifically marked for the use in
should be two times the size of the radiator frontal area or as weatherproof area only. The connector shall be located in 3R rated
recommended by the manufacturer. enclosure (In Canada, as per Table 65 of the Canadian Electrical Code,
4.7 Exhaust. When an engine-driven generator is installed inside a Part 1), if the generator is not installed in weatherproof area.
building or other enclosure, means shall be provided for exhausting the 4.9.4.4 Caution Mark. A plug, connector or receptacle marked to
gases from the engine exhaust system out of the building or enclosure. indicate that it is not suitable to interrupt current shall not be used to
4.7.1 Where the exhaust pipe passes through a wall of combustible interrupt current to the stand-by electrical power system.
material, the wall shall be shielded by a metal thimble at least 305 mm 4.9.4.5 Strain Relief. Extra-hard-usage service cord or portable power
(12 in.) larger in diameter than the exhaust pipe. cable shall be used to connect a stand-by electric power system to the
4.7.2 The end of the exhaust pipe should be equipped with a rain cap, fixed wiring. An approved method of strain relief to prevent transmission
and should be located a suitable distance away from the air inlet of the of strain to the terminal connections shall be provided for all cords and
engine so that exhaust gases cannot be drawn back through the air inlet. portable power cables.
4.7.3 Connection between the exhaust pipe and the engine shall be NOTE: In addition to requirements above, the installer shall ensure that
flexible to prevent breakage. the phases and the neutral of the generator power supply to the farm
building are mated with the corresponding phases and the neutral of the
4.7.4 Exhaust piping should be as short as possible with minimum bends
farm building. A wiring diagram or label on the power supply at the farm
and restrictions, and large enough to prevent back pressures higher than
shall be provided.
those recommended by the engine manufacturer.
4.10 Shields and guards
4.7.5 A drain cock should be installed at the lowest point in the exhaust
piping system for draining any moisture accumulations as a result of 4.10.1 Provisions shall be made to minimize the possibility of personal
condensation. contact with hot surfaces or rotating components by installing suitable
NOTE: Frequency of draining depends on time and extent of use. shields and guards.
4.8 Fuel. Engine-driven generator sets shall be provided with fuel lines 4.10.2 Guarding should conform to ANSI/ASAE S493.
and fuel equipment to comply with the following standards: In the USA,
NFPA 30, NFPA 31, NFPA 54, and NFPA 58. For Canada, comply with
CAN/CSA-B139, and CAN/CSA-B140.0. The fuel lines from the natural 5 PTO generatorsinitial start-up
gas meter to the fuel inlet of the engine shall be sized and installed in 5.1 The PTO generator owners manual should be thoroughly read and
accordance with ANSI Z83.1. followed.
NOTE: Fueling shall be carried out only after the engine is switched off. 5.2 Prior to operation the PTO speed changer shall be filled to the
4.9 Electrical specified level with oil recommended by the manufacturer.
4.9.1 Electrical wiring shall be in accordance with the recommendations 5.3 Electrical wiring should be checked for loose connections and for
of the manufacturers and comply with local regulations, (in the USA, loose or missing cap screws, bolts and nuts.
NFPA 70); (in Canada the Canadian Electrical). 5.4 Starting tractor-driven PTO generators
4.9.2 Electric generators on engine or tractor-driven units shall be 5.4.1 If not so equipped, add a breaker of appropriate size. Set the load
grounded in accordance with Article 250, NFPA 70. circuit breaker on the generator to off.
4.9.3 Automatic transfer switches or manual transfer switches shall be 5.4.2 Connect the PTO driveline, or PTO shaft, securely to the generator
approved by an independent testing agency (ie, UL 1008) and installed and the tractor. Install all safety shields. Position PTO driveline as near
so the generator and the electric utilitys power cannot be energized at to a straight line as possible, not to exceed a 10 deg angle.
the same time. Transfer switches shall be installed in accordance with
Article 702, NFPA 70. 5.4.3 Start tractor and adjust power take-off speed to 540 or 1000 rpm
ANSI/ASAE EP364.3 NOV2006 (R2012) Copyright American Society of Agricultural and Biological Engineers 2
(depending on type) by advancing the tractor throttle, so the PTO seconds without pausing for 2 minutes to allow it to cool. To do so may
generator is producing 60 Hz, as indicated on the frequency meter. If no cause overheating and damage to the motor windings.
frequency meter is available, adjust to proper voltage as indicated on the 6.6.8 Observe the oil pressure gauge, water temperature gauge, and DC
voltmeter. (battery charging) ammeter if so equipped. As soon as the engine attains
5.4.4 Place power cable coming from the manual transfer switch in the normal operating temperature, adjust the speed control, if required, to
correct power plugs or receptacle on the generator control panel. produce 60 Hz operation by viewing frequency meter or tachometer if
5.4.5 Place transfer switch in the stand-by position. supplied. Set for 1800 r/min for 4-pole generators or 3600 r/min for 2-pole
generators.
5.4.6 All load circuit breakers at the service entrance shall be in the
OFF position before putting the main load circuit breaker on the 6.6.9 Turn the voltage regulator on-off switch to the on position.
generator in the ON position. Rotate the voltage regulator adjusting rheostat clockwise (increase) to
obtain rated AC voltage indicated on the AC voltmeter.
5.4.7 Maintain frequency at 60 Hz by adjusting tractor speed. If
frequency meter is not available, the PTO speed shall be adjusted such 6.6.10 Apply the load to the generator by placing the generator circuit
that the voltmeter is maintained at the correct voltage as the individual breaker in the on position, or by closing the line switch.
load circuit breakers at the service entrance are turned on, beginning 6.6.11 Observe the monitoring meters and adjust the generator voltage
with the circuit breaker that controls the largest motor and then large to to the desired output.
small motors. 6.6.12 The generator may now be stopped and started without making
5.4.8 When normal power has been restored and after a sufficient time further adjustments.
has elapsed to assure that power restoration is not temporary, put large
motor curcuit breakers in the OFF position to minimize bump on the
utility lines and motor damage before the transfer switch is returned to 7 Automatic-start, engine-driven generator set
normal or to electric utility power. equipped with automatic switchinitial start-up
5.4.9 Place the generator circuit breaker in off position. 7.1 Perform the functions in clauses 6.1 through 6.5.
5.4.10 Slowly reduce power take-off speed to a minimum and disengage 7.2 Place the generator circuit breaker in the off position.
power take-off lever. 7.3 When so equipped, turn the ammeter and voltmeter selector
5.4.11 Remove connection power cable. switches to the desired position.
NOTE: Do not remove the connecting plug before power take-off is 7.4 When equipped with a voltage regulator, rotate the voltage regulator
disengaged. A shock hazard may result if the plug is removed sooner. adjusting rheostat counterclockwise (decrease).
7.5 Turn the voltage regulator on-off switch to the off position
(regulator will be damaged otherwise).
6 Manual-start, engine-driven generator setinitial 7.6 Place the engine start switch in the on or start position to
start-up energize the cranking motor (starter).
6.1 The engine generator set owners manual should be thoroughly read 7.7 Observe the oil pressure gauge, water temperature gauge, and DC
and followed. (battery charging) ammeter if so equipped. As soon as the engine attains
6.2 Prior to operation the engine crankcase shall be filled to the specified normal operating temperature, adjust the speed control if required to
level with oil recommended by the manufacturer. produce 60 Hz operation by viewing frequency meter or tachometer if
6.3 Fill radiator with proper mixture of water and antifreeze to specified supplied, and set for 1800 r/min for 4-pole generators or 3600 r/min for
level in accordance with manufacturers recommendations. 2-pole generators.
NOTE: Liquid cooled, engine-driven generator sets are normally shipped 7.8 Turn the voltage regulator on-off switch to the on position. Rotate
without liquid in the cooling system. the voltage regulator adjusting rheostat clockwise (increase) to obtain
6.4 Check all electrical wiring for loose connections and for loose or rated AC voltage indicated on the AC voltmeter.
missing cap screws, bolts and nuts. 7.9 Place the generator circuit breaker in the on position. Turn the
6.5 If dry charged, fill each battery cell with battery electrolyte. Do not switch on the automatic line transfer switch to auto position. Turn the
allow battery acid to contact engine or generator and control parts. main utility service breaker or switch to off (thus simulating a power
NOTE: Starting batteries may be either the standard or dry charge type. outage). The automatic line transfer switch should operate, start the
engine, and transfer the load to the generator set.
6.6 Starting manual-start, engine-driven generators
NOTE: The following may apply to old equipment and may not be 7.10 Observe AC voltmeter and adjust voltage to desired output if
relevant with new equipment. required.
6.6.1 Place the generator circuit breaker in the off position, or open the 7.11 Turn the main electric utility service breaker to on position. The
line switch to disconnect the load. automatic transfer switch should operate, transferring the load to the
normal utility source. The engine-driven generator should then shut
6.6.2 When so equipped, turn the ammeter and voltmeter selector down. The automatic generator set should start and accept load without
switches to the desired position. further adjustment upon transfer of the automatic transfer switch
6.6.3 When equipped with a voltage regulator, rotate the voltage whenever a power outage occurs.
regulator adjusting rheostat counterclockwise (decrease) to minimum
voltage.
6.6.4 Turn the voltage regulator on-off switch to the off position.
8 Portable Generator Set
NOTE: The regulator will be damaged if the switch is not turned to OFF 8.1 All above standards to apply to Portable Generator sets.
position.
6.6.5 If the engine is equipped with a speed control (throttle), set it for 9 Exercising of standby units
idle.
9.1 Tractor-driver PTO generators should be exercised at least every 90
6.6.6 Place the engine stop switch in the on position. days to blow out dust, to dry out moisture which may have entered the
6.6.7 Press the start switch button and hold in until the engine starts. generator, to remove oxidation from commutator or sliprings, and to
NOTE: Do not energize the starting motor for a period exceeding 30 familiarize the operator with the necessary steps to take during an actual
ANSI/ASAE EP364.3 NOV2006 (R2012) Copyright American Society of Agricultural and Biological Engineers 3
emergency. If possible, at least 50% of normal load should be applied to maintenance schedule record keeping process should be followed. If
the generator during the exercise period. such schedules and record keeping processes/documents are
9.2 NOTE: Some automatic engine-driven generator sets are equipped unavailable, those of Section 10.6 can be followed.
with an automatic exerciser which starts the unit automatically on a 10.2 Batteries. Batteries used for starting engine-driven generator sets
regular basis, runs the unit for a predetermined time, and then shuts the should never be allowed to stand for a long period of time in a
unit down automatically. discharged condition. It is recommended that standby engine-driven
If the engine-driven generator is not equipped with an automatic generated sets be equipped with a rectifier type battery charger. The
exerciser, the generator should be exercised at least every 7 days. level of the battery electrolyte should be checked weekly under constant
Exercising periods should be long enough to enable the engine to obtain use and monthly with intermittent use. Refill to proper level with distilled
normal operating temperature while carrying, if possible, at least 50% of water. Keep battery clean. Do not allow battery acid to contact engine or
normal load. To exercise engine-driven generator sets, proceed as generator and control parts.
follows: 10.3 Generators
a) Before starting engine, check lubricating oil and coolant levels. Make
complete visual inspection of unit to be sure it is in operating 10.3.1 Dust and dirt should be blown from the interior of the generator
condition. by means of dry, low pressure compressed air [210 kPa (30 lbf/in.2)].
b) Start and run engine 5 min with no load. NOTE: Brushless generators require little maintenance. Most generator
c) Run engine at rated speed with whatever load is available up to full bearings are of the sealed type and require no relubrication.
load for the period of time required to reach normal operating 10.3.2 Generators equipped with brushes should be checked in
temperature. Continue to operate engine for 30 min or more accordance with the manufacturers recommendations, but not to exceed
dependent upon manufacturers recommendations. Check and 500 h of initial running and every 100 h thereafter. If brush length is less
correct any coolant or oil leaks. than 13 mm (0.5 in.), the brush should be replaced.
d) Run engine with no load for 5 min to allow combustion chamber 10.3.3 On units with a commutator, an even brown film on the
temperature to decrease gradually to a minimum before stopping. commutator denotes a desirable condition, and it should not be removed.
9.3 See Table 1, Example Generator Exercising Log Sheet If the commutator becomes rough or dirty, it should be cleaned by using
a fine grade of sandpaper.
NOTE: Emery cloth should not be used since it contains metallic parts
which could short out the commutator segments.
10. Maintenance
10.4 Engine maintenance should be in accordance with the engine
10.1 Maintenance includes those functions and activities that will keep manufacturers recommendations and instructions regarding the types of
the standby generating system in peak operating condition and prevent lubricants used and the frequency of application.
unnecessary trouble from developing. The manufacturers recommended
Date Time Operators Hour Meter Test Voltage Amperage Frequency Oil Repairs/Service 4
Initials Reading Duration 240 V10 60 Hz2 Pressure Needed
(min.) 4060 psi Performed
Note: Logged details and sheets to be filed and stored for future reference and possible insurance requirements.
ANSI/ASAE EP364.3 NOV2006 (R2012) Copyright American Society of Agricultural and Biological Engineers 4
Table 2 SUGGESTED Maintenance Schedule and Record Keeping Automatic and Manual Stationary Engine Generator Set (10.6.1)
Component Change/
(as applicable) Check Clean Test Frequency
1. Fuel
(a) Main Supply Tank Level X M
(b) Day Tank Level X M
(c) Float Switch X Q
(d) Supply Pump Operation X Q
(e) Solenoid Value X Q
(f) Strainers, Filters X Q
(g) Water in system (drain check) X X Q
(h) Flexible Hose and Connections X X M
(i) Tank vents and overflow pipe X X A
(j) Piping X A
(k) Gasoline R S
2. Lubrication System
(a) Oil Level X M
(b) Oil change R 50/A
(c) Oil Filter R 50/A
(d) Crankcase breather X S
3. Cooling System
(a) Level X M
(b) Antifreeze protection level X A
(c) Antifreeze X A
(d) Clean exterior of Radiator X A
(e) Fan and Alternator Belt X R Q
(f) Water Pump X Q
(g) Flexible Hoses and connections X X M
(h) Duct work, Louvers X X A
4. Exhaust System
(a) Leakage X X M
(b) Insulation and Fire Hazard X Q
(c) Excessive Back-pressure X A
(d) Flexible exhaust section X S
5. Battery
(a) Electrolyte Level X M
(b) Terminals Clean and tight X M
(c) Remove corrosion X M
(d) Specific Gravity X M
(e) Charge rate X M
6. Electrical System
(a) General Inspection X M
(b) Tighten controls and connections X A
(c) Wire chafing X S
(d) Operation of safeties and alarms X S
(e) Circuit breakers, fuses X R 2 or A
(f) Transfer switch main contacts X X A
(g) Calibrate voltage sensors, relays X X 5 or A
(h) Wiring insulation breakdown X 3/500*
7. Generator
(a) Brush length, contact X X S
(b) Commutator, slip rings X X A
(c) Rotor and stator X X A
(d) Bearings X R A
(e) Bearing Grease X R A
(f) Exciter X X A
(g) Voltage regulator X A
(h) Resistance of windings X A
(i) General condition of unit X M
(j) Service room or housing X X M
8. Custom Maintenance Itemize below
M = Monthly, Q = Quarterly, S = Semi Annually, A = Annually, Numbers = Hours of Operation, R = Replace if necessary
*= Every 3 years or 500 hours
ANSI/ASAE EP364.3 NOV2006 (R2012) Copyright American Society of Agricultural and Biological Engineers 5
Table 3 SUGGESTED Maintenance Schedule and Record Keeping Portable Engine Generator Set (10.6.2)
Component Change/
(as applicable) Check Clean Test Frequency
1. Engine Oil
(a) Check X E
(b) Change X S
2. Air Cleaner
(a) Check X E
(b) Clean X Q/50
(c) Replace R S/100
3. Sediment Cup
(a) Clean X E
4. Spark Plug
(a) Clean/Regap X S/100
(b) Replace R A/300
5. Valve Clearance X A/300
6. Fuel Tank and Filter X A/300
7. Fuel Line X 2A
8. Custom Maintenance Itemize below
E = Every Use, M = Monthly, Q = Quarterly, S = Semi Annually, A = Annually, Numbers = Hours of Operation, R = Replace if necessary
*= Every 3 years of 500 hours
Table 4 SUGGESTED Maintenance Schedule and Record Keeping PTO-Driven Generator (10.6.3)
Component Change/
(as applicable) Check Clean Test Frequency
E = Every Use, M = Monthly, Q = Quarterly, S = Semi Annually, A = Annually, Numbers = Hours of Operation, R = Replace if necessary
ANSI/ASAE EP364.3 NOV2006 (R2012) Copyright American Society of Agricultural and Biological Engineers 6
Table 5 SUGGESTED Troubleshooting (10.7.2)
*Qualified service technicians and/or electricians should conduct most of the remedies listed.
10.5 An owners service record should be maintained showing hours of situations; hence, they should be interpreted judiciously and not
operation for scheduled tune-up and changing of lubricating oil, oil filters, necessarily reproduced verbatim in communications to users:
air cleaners, fuel filter, etc. All circuits not known to be dead must be considered live and
10.6 Suggested Maintenance Schedule and Record Keeping dangerous;
10.6.1 See Table 2, Automatic and Manual Stationary Engine Generator All exposed conductors, terminals, and components should be
Set regarded as energized and treated accordingly;
10.6.2 See Table 3, Portable Engine Generator Set Metal tools, flashlights, metallic pencils, and other exposed
10.6.3 See Table 4, PTO-Driven Generator conducting objects should not be used while working near
energized electrical equipment;
10.7 Preventive maintenance
Precautions should be taken to avoid grounding your body while
10.7.1 Troubles that occur in standby generator operation are avoided using electrical measuring apparatus or making adjustments to
when those responsible for maintenance adhere to an adequate program energized electrical equipment;
of lubrication, inspection, and maintenance.
NOTE: The time and expense involved in a good maintenance program All equipment should be de-energized before connecting or
are only a fraction of that incurred when poor maintenance practice disconnecting leads;
results in a major malfunction or breakdown at the very time that the Loose clothing should not be worn while working near rotating
standby generator is required to provide power during an emergency. equipment.
10.7.2 See Table 5, Troubleshooting 11.2 Standard Procedures
11.2.1 See Checklist 1, PTO-Driven Generator
11 Safe practice messages
11.2.2 See Checklist 2, Automatic Stationary Engine Generator Set
11.1 These safe practice messages are recognized as being effective for
enhancing safety, but may not be adequate, complete, or entirely 11.2.3 See Checklist 3, Manual Stationary Engine Generator Set
applicable for every situation. They may not cover all possible hazardous 11.2.4 See Checklist 4, Portable Engine Generator Set
ANSI/ASAE EP364.3 NOV2006 (R2012) Copyright American Society of Agricultural and Biological Engineers 7
Checklist 1 SUGGESTED CHECKLIST PTO-Driven Start Tractor and adjust PTO speed to proper RPM (either 540 or
Generators (11.2.1) 1000)
Place transfer switch in emergency position
Connecting Procedure Add loads
Check with utility on expected length of outage Adjust tractor speed to maintain 60 Hertz
Keep tractor fully fueled at all times Monitor voltage and frequency
Ensure proper alignment of PTO shaft After utility power is restored, return transfer switch to normal
Set tractor brakes before operating generator Allow 5 minutes for generator cool down
Check for downed lines Disengage PTO lever
Ensure all connections to outside power sources are disconnected Remove connector power cable
Use proper connection cable Exercising the PTO-Driven Generator
Use proper grounding cable
Use only approved connectors and receptacles Exercise the PTO generator every 90 days
For continuous operation, run at no more than 80% capacity Check all fluid levels
After shut down, store PTO shaft with generator Following start-up procedure, start and run engine for 5 min. with
no load
Start-Up Procedure Operate the generator under at least 50% load for 30 minutes
Check all fluid levels Check for any abnormalities and remedy as necessary
Connect tractor to generator Remove load and run at rated speed and no load for a 5 minute
Connect Power Cable cool down period
Record results in log
Checklist 2 SUGGESTED CHECKLIST Automatic Turn main utility breaker to off and the engine should start
Stationary Engine Generator Set (11.2.2) Adjust rheostat to obtain desired AC voltage if so equipped
Adjust engine speed to maintain 60 Hertz if so equipped
Connecting Procedure Turn main utility breaker on and the unit should automatically
Unit will power up automatically in the event of a power outage transfer the load to the utility and shut down the generator
Check for downed lines the engine generator set should operate automatically in case of
Check that unit is operating properly and all fluid levels are a power outage without further adjustment
adequate Exercising the Engine Generator Set
Monitor voltage and frequency
Keep enough fuel on hand for 72 hours operation Exercise the engine generator set every 7 days
Equip engine with Murphy Switch to automatically shut down to Check all fluid levels
prevent engine damage Following start-up procedure, start and run engine for 5 min. with
no load
Start-Up Procedure Operate the generator under at least 50% load for 30 minutes
Check all fluid levels Check for any abnormalities and remedy as necessary
For initial start up only, set generator circuit breaker to OFF Remove load and allow engine generator set to shut down
Adjust voltage rheostat to minimum if so equipped automatically
Place line transfer switch in AUTO position Record results in log
Checklist 3 SUGGESTED CHECKLIST Manual Adjust rheostat to obtain desired AC voltage if so equipped
Stationary Engine Generator Set (11.2.3) Place transfer switch in emergency position
Set circuit breaker to ON
Connecting Procedure Adjust engine speed to maintain 60 Hertz
Check with utility on expected length of outage Monitor voltage and frequency
Check for downed lines After utility power is restored, return transfer switch to normal
Ensure all connections to outside power sources are disconnected Set circuit switch to OFF
For continuous operation, run at no more than 80% capacity Allow 5 minutes for generator cool down
Monitor voltage and frequency Exercising the Engine Generator Set
Keep enough fuel on hand for 72 hours operation
Equip engine with Murphy Switch to automatically shut down to Exercise the engine generator set every 7 days
prevent engine damage Check all fluid levels
Following start-up procedure, start and run engine for 5 min, with
Start-up Procedure no load
Check all fluid levels Operate the generator under at least 50% load for 30 minutes
Set generator circuit breaker to OFF Check for any abnormalities and remedy as necessary
Adjust voltage rheostat to minimum if so equipped Remove load and run at rated speed and no load for a 5 minute
Start engine cool down period
Once engine has warmed up, adjust speed for 60 Hertz operation Record results in log
if so equipped
ANSI/ASAE EP364.3 NOV2006 (R2012) Copyright American Society of Agricultural and Biological Engineers 8
Checklist 4 SUGGESTED CHECKLIST Portable Turn on critical circuits one by one in priority sequence
Engine Generator Set (11.2.4) Adjust engine speed to maintain 60 Hertz
Monitor voltage and frequency
Connecting Procedure After utility power is restored, shut off critical circuits
Check with utility on expected length of outage Set generator breaker to OFF
Check for downed lines Shut off engine
Set hydro main breaker on essential loads panel to off Set hydro breaker to ON
Move generator into position and plug in cable Exercising the Portable Engine Generator Set
For continuous operation, run at no more than 80% capacity
Monitor voltage and frequency Portable engine generator sets may be stored for long periods of
Keep enough fuel on hand for 72 hours operation time without being exercised but it is recommended that they be
operated periodically to avoid problems during an emergency.
Start-Up Procedure To exercise a portable engine generator set, follow the normal
Check all fluid levels connect and start up procedure, running the unit for at least 1/2
Set generator circuit breaker to OFF. Set breakers for critical hour on 50% load or more.
circuits to OFF Exercise the unit once every three months
Start engine Record the results of the test on the log sheet
Once engine has warmed up, set generator breaker to ON
ANSI/ASAE EP364.3 NOV2006 (R2012) Copyright American Society of Agricultural and Biological Engineers 9