Академический Документы
Профессиональный Документы
Культура Документы
Lesson 1
Functions of an Variable Frequency Drive (VFD)
Outline:
A. 3-phase AC Motor
B. Functions of an VFD
1. Start/Stop
2. Change Speed
3. Constant Speed
4. Limits
5. Ramping
6. Forward/Reverse
7. Save Energy
1
VFD 101
Lesson 1
10/2/2003
The 3-phase motor pictured above is for commercial use, but in your home, AC motors
are used as well. A vacuum cleaner uses an AC motor to clean the carpet; a blender uses
an AC motor to process food; and the clothes dryer uses an AC motor to dry clothes. In
each of these examples, how is the AC motor controlled?
When controlling motors in the home we control them by applying AC power, and
removing it, usually through a switch. Obviously when power, 120 or 240 VAC, is applied to
the motor it runs. With no power, the motor stops.
With the use of a Variable Frequency Drive (VFD) not only can the AC motor be
started and stopped as in the home, but more sophisticated controls are accomplished. A
VFD can send a modulating signal to the motor, which allows a variety of speeds to be
delivered not just an ON/OFF signal. This variety of speeds can be used to match the motor
to a particular task. There are a number of functions that the VFD accomplishes with
commercial 3-phase AC motors, which are covered in the pages that follow.
Motors in the home are almost always single-phase motors which require additional
electric parts to rotate the magnetic field. Because of these extra parts, single-phase motors
do NOT operate correctly with a VFD.
2
To understand the functions of an VFD better,
an example of cooling tower fans is used.
10/2/2003
The cooling tower in the picture above must maintain a certain temperature perhaps
30C (85F) for the condenser water temperature. Looking at this example, see if you can
identify some of the functions that must be performed by the VFD, AC motor and fans? In
other words, what must the fans be able to do? Take a couple of minutes to jot down the
functions.
_____________________ ______________________
_____________________ ______________________
A few of the basic functions of an VFD in controlling the AC motor and fans are
covered on the pages that follow.
3
Function #1 Start and Stop
STOP
In the picture above, the SPDT switch is used to stop the pump. If there are 2
separate push button switches, one to Start and one to Stop, this arrangement is known as a
3-wire Start/Stop. If only one switch, a continuous switch, is used, then it is referred to as a
2-wire Start/Stop. In the picture above, since there is one switch, so this is a 2-wire
Start/Stop.
4
Function #2 Change Speed
5
Function #3 Maintain a Constant
Speed
6
Function #4 Limits
Function #4 Limits
It is important that limits be placed on an VFD. Speed limits can be placed in the
program of the VFD so an operator can not go beyond a maximum speed or less than a
minimum speed. The maximum speed of the fans should not exceed 60Hz, due to
excessive power consumption. Because of the possibility of overheating, fans should not be
run less than 6Hz. For the same reason as the fans, pumps should not be run more than
60Hz. For lubrication purposes a pump should have a minimum speed of at least 18Hz.
If the fans gets stuck, there are torque limits that the VFD monitors stopping the motor
if they are exceeded. Current limits are also important for protection of the drive and motor.
In the picture above the maximum reference is set to 60 Hz. Notice that in the diagram there
is a minimum reference of 6Hz.
7
Function #5 Ramping
Function #5 Ramping
The VFD also ramps the fans up and ramps them down. When the fans starts,
acceleration, it is important that there is no sudden jump to the reference speed, or there can
be stress on the gear boxes. In the example above, a ramp-up slowly increases the speed
from stopped or 0Hz up to the reference, 34Hz, over a certain amount of seconds perhaps
10. If this ramp up is too short, the drive can trip on an over current alarm or torque limit. If
the VFD is tripped, the fans stop and it might require an operator to manually reset the VFD.
Many VFDs have an automatic reset setting of 1 time to infinite times. Ramping is very
important for pumps, to avoid water hammer.
8
Function #5 Ramping
A ramp is also present on the stop side. This is referred to as a ramp down or
deceleration. It is important that the fans do NOT stopped abruptly. A ramp-down of 60
seconds might be entered into the program for this application. If the ramp is too short, the
drive can trip on over voltage.
All ramp times are based on the motor speed, 60Hz in the Western Hemisphere. This
means if the the ramp time is set for 60 seconds as in the picture above, but the reference is
set to 30Hz (1/2 of 60Hz), it takes 30/60 x 60seocnds ( the time) or 30 seconds to ramp up.
In the rest of the world 50Hz is used for the motor speed. Using the same ramp up time (10)
and reference (30), the motor then takes 30/50 X 60seconds or 36 seconds to ramp up to
30Hz. Calculations for the ramp down time would be the same.
A special feature of the Danfoss VLT 6000 is automatic ramping. The VFD
automatically extends the ramp times, during ramp up and ramp down, to avoid tripping of
the drive.
9
Function #6 Forward/Reverse
Change of Direction
Forward to cool water
10/2/2003
10
Function #6 Forward/Reverse
REVERSE
In the cooling tower example the fans need to operate in Reverse in order to
complete a defrost cycle, when the outside temperature is very cool. Power going to the
motor must be changed to move the fans backwards (Reverse). If there were no VFD, 2 of
the 3 leads of the 3-phase motor would be switched in order for the motor to change its
direction and go backwards. This switching of the motor leads is done inside the VFD.
11
Function #7 Saving Energy
12
VFD 101
Lesson 2
Control Arrangements for a VFD
This training covers the major control arrangements for a VFD, starting with
the simplest arrangement then moving to the more complex.
Many of the control arrangements shown in the previous lesson (Lesson 1:
Functions of an VFD) were Closed Loop Control. There can be other
arrangements which are covered in detail in this lesson.
1) Local or Hand Control
2) Remote or Auto Control
3) Multi-motor
4) Master/Slave
5) Closed Loop
6) Cascade Control Fixed Stages
7) Cascade Control Variable Stages
8) Build Automation System (BAS) - Enable
9) BAS Enable and Reference
10) BAS Serial Communications
1) Local (Hand) Control
In the picture above there are 2 VFDs, each being controlled by its
own LCP or keypad. The one on the right uses a remote keypad kit to place
the keypad in a convenient location. The operational site on both VFDs is
considered as LOCAL or HAND.
The Hand Start key starts the VFD, assuming safeties have been
enabled. The display on the keypad changes as seen on the last page. This
allows the operator to increase (+ key) or decrease (- key) the speed of the
motor. Other start commands are ignored.
The OFF Stop key stops the drive. The display starts to flash to
indicate that this key has been pressed. Other start commands are ignored.
To remove this stop command, the Hand Start or Auto Start must be
pressed.
The Auto Start key ends Local or Hand control. This means that
remote controls, which are described in the pages that follow are in control.
The Reset key clears an alarm from the VFD, assuming that the
alarm has been corrected and is set for manual reset. Some alarms require
that power be removed (Disc.Mains) before they can be reset.
2) Remote Control
Besides stop switches, other signals can be sent into the VFD. These
could be a reference pot to change the speed, increase and decrease
buttons which would also change the speed, remote Start and Stop switches,
or other signals. All the different options for remote signals are considered
as control wiring. In the program of the drive, if the Hand keys are used,
remote signal except for safeties are ignored. On the VFD shown above, all
the control wiring terminals are shown on the black plastic cover just under
the LCP keypad.
The amount of connections for the control wiring is a means of
comparison between manufacturers of VFDs. As an example, the Danfoss
drive shown above has the ability to accept the following signals:
8 Digital Inputs
3 Analog Inputs (2 are setup for 0-10Vdc; 1 for 0-20mA)
2 Analog/Digital Outputs (0-20mA or 4-20mA signals or these can be
programmed as Digital Outputs with 24Vdc attached)
2 Relay Outputs (dry contacts)
3) Multi-Motor Operation
3. Multi-Motor Operation
The multi-motor arrangement is usually done because of strict cost
considerations. Not only must the VFD have the current capacity for all the
motors, but each individual motor must have overload protection. In the
picture above, one VFD operates 4 AC motors, which in turn operates the 4
cooling tower fans together. They operate at the same speed or close to the
same speed.
When this arrangement is used some VFD features are restricted.
First the motors and fans must all run at the same speed. Another restriction
is that the VFD can not be tuned to a individual motor. Motor Tuning is
where the VFD is tuned or matched to an individual motor for better
performance and energy savings. The last restriction given here is that the
slip compensation (calculating the difference between the field speed and
rotor speed) should be set to OFF.
3) Multi-Motor Operation
If the cooling tower fans were operating with a very light load but
motor 3 got jammed. The amp draw on motors 1,2 and 4, might be low, say
5 amps each, but the amp draw on motor 3 would need to surpass 45 amps
before the drive saw any problem. This would cause damage to motor 3. As
shown in this example, individual overload protection, such as thermal
overloads are needed to protect each motor. Motors in this arrangement
operate close to the same speed.
4) Master/Slave (Leader/Follower)
4. Master/Slave (Leader/Follower)
This arrangement allows motors to operate closer together than in the
multi-motor application. Each VFD also provides safeties for its own motor.
One VFD is selected as a Master or Leader drive. It is setup to send
a reference signal and ON/OFF commands to the Slave or Follower drive. In
the example above, 2 fans are used for Supply Air on a Variable Air Volume
(VAV) system. The VFD operating the top fan is considered the Master or
Leader. It varies its speed to match the static pressure needs in the supply
duct. The bottom fan and VFD, follows the top supply fan and is known as
the slave or follower. The slave can match the speed to within 0.3Hz of the
master, over the operating range from about 6Hz to 60Hz.
Rather than always matching the speed of the master VFD, the slave
VFD can operate at a percentage of the reference. If a positive pressure
needs to be maintained in a zone, the slave VFD on a return fan can be
slightly behind (-10% of reference) of the master VFD on the supply fan.
The supply fan always runs faster than the return fan causing a positive
pressure in the zone. In this last application using a volumetric sensor
comparing the CFM (L/s) from supply and return to control the return fan
would give a much greater accuracy than the Master/Slave arrangement.
4) Master/Slave (Leader/Follower)
In the picture above, the VFD on the first supply fan is the
Master/Leader and it generates a reference signal for one of its analog
outputs (AO). The VFD on the second supply fan is the Slave/Follower, and
it monitors this 4-20mA reference signal from the master using the slaves
analog input (AI).
It is possible with Danfoss drives to use a Digital Output (DO) as a
pulsed reference. The follower uses a Digital Input (DI) to follow this pulsed
reference signal. These 2 fans must run closely together, the greatest
variance between drives using the pulsed signal is around 0.2Hz along the
entire range of frequencies (6 to 60Hz). There is a time delay in this
arrangement. The master drive starts going to its reference before it sends
the signal to the slave drive. Usually this delay is very small, in milliseconds,
and of no consequence in this application.
5) Closed Loop/PID Control
The diagram above shows the operation of the variable pump, VFD at
the bottom of the chart and how it relates to the fixed stages, which are
shown at the top. Notice that every time the VFD reaches 100% or 60Hz, a
fixed stage on the Cascade Controller card is enabled. When the fixed pump
is running, this causes the VFD to drop its signal. With an increase in
demand the VFD goes to 100% again causing the second fixed stage to
come ON.
When the demand drops and the VFD goes to 0% or minimum speed,
20Hz, the fixed stages go OFF. With a loss of a fixed pump, the VFD then
increases its signal. Every time the VFD drops to minimum speed, a fixed
stage is turned OFF. It is possible to use 4 stages, but only 3 stages are
shown here.
7) Cascade Control Card
Variable Stages
The diagram above shows the operation of the variable pump, VFD at
the bottom of the chart and how it relates to pumps 2-4. When the 1st pump
reaches 75%, pump 2 is enabled and quickly follows the same signal that
goes to pump 1. If the demand for both pumps continues to increase to
80%, pump 3 is enabled. Pump 4 is enabled when the demand goes to
85%.
When the demand drops all the pumps start to slow down. Although
this is NOT shown above, when the demand drops to 30%, pump 4 is
disabled. When the demand drops to 20%, pump 3 is disabled; and pump 2
is disabled at 10%. Pump 1 then continues to monitor the demand.
Remember that 0% is still a minimum speed of 20Hz.
8) Building Automation Enable
VFD 101
Lesson 3
Parts of a Variable Frequency Drive (VFD)
Outline:
Parts and Operations of a Drive
1. VFD part of a Larger System
2. Rectifier
3. Soft Charge Circuit
4. Intermediate Circuit (DC Link)
5. Brake Circuit
6. Inverter
7. Pulse Width Modulation
8. Control & Regulation Section
Note: Other names are used for this device, such as Adjustable Frequency
Drive (AFD), Variable Speed Drive (ASD), Frequency Converter and
Inverter, but Variable Frequency Drive (VFD) or just Drive is used throughout
this lesson.
VFD 101
Lesson 3
Each one of these sections is reviewed in some detail in the pages that
follow.
Fuses
Disconnect
2) Rectifier Section
2. Rectifier
The 3-phase AC voltage goes into the rectifier section which is made up
of a group of gated diodes (silicon rectifiers or SCRs). In most VFDs, these
diodes are in a group of 6 as diagramed above. One VFD manufacturer has
stressed that there should be more sets of diodes, 12, 18, even 24. Reasons
for/against this are covered in lesson 5.
Diodes (D1 through D6) allow current to flow only in one direction when enabled by
the gate signal. In this diagram, the AC power on L1 goes into Diodes D1 and D2. Because
of the position of these diodes, current flow can only go up. The D1 diode conducts when the
AC is positive and D2 conducts when the AC goes negative. This drives the top line (+) more
positive and the bottom line (-) more negative. Diodes D3 and D4 convert L2 power to DC
and Diodes D5 and D6 convert L3. A volt ohmmeter or VOM can be used to measure this
DC voltage. In this type of circuit, the DC voltage is 1.35 times the AC line voltage.
If 240 Vac is coming in, 324 Vdc is generated.
If 380 Vac is coming in, 513 Vdc is generated.
If 460 Vac is the line voltage, 621 Vdc is generated.
If 575 Vac is the line voltage, 776 Vdc is generated.
Because of line (power coming in) and load (power to the motor) changes,
the DC Voltage level is constantly moving above and below this expected
value.
2) Rectifier Section
SCR
Heatsinks
Incoming Power
The picture above highlights the rectifier section of the drive. Six SCRs
are used to change the incoming power from AC to DC. This rectification
can generate a considerable amount of heat, so the SCRs are mounted onto
a gold-colored heatsink. The fins of the heatsink are facing the other way
inside a special ductwork where the air flow removes the heat. Four fans
mounted across the top of this VFD pull the air across the heatsink.
Remember that heat is the enemy both to the drive and to the motor. Any
practice which makes either run cooler makes them last longer. Because of
the high amperage (750A for this unit) there are bus bars connecting the
rectifiers to the incoming power. Even the largest wire size is too small for
this unit.
In the picture above, the soft charge circuit card is shown. This circuit
card on the 450kW (600Hp) drive is in the upper left corner, just above the
rectifier section. Notice that the soft charge fuses are just to the right of the
circuit card. The soft charge circuit card on the 315-450kW (350-600Hp)
drives uses small IGBTs instead of resistors to limit power going to the
capacitors. This is referred to as an active soft charge.
Current Resistors
Soft Charge-
Resistor Fuses
On the 160kW (200Hp) drive, shown above, the soft charge circuit is
exactly like the schematic diagram shown on the previous page. Notice the
2 large black current limiting resistors used to limit power going to the
capacitors in the DC Link section.
Cap Banks
When looking at a drive, some of the most striking components are the
2 devices that make up the DC link. The 3 banks of blue capacitors on the
450kW (600Hp) drive, shown on the left, are quite prominent. On newer
units these blue capacitors have been replaced with black ones. They are in
the center of the drive, just to the right of the rectifier section. There are 3
banks of 12 capacitors in each bank for a total of 36 capacitors. Capacitor
numbers vary with each size of drive. This 3-bank arrangement is to allow
for easier service. The plate on the right side of each capacitor bank has full
voltage.
DC Reactors
There are 2 sets of coils shown above. The DC Link coils are
always the ones with 2 terminals, shown here on the left.
In the picture above there are 2 sets of coils. The coils on the left at the
bottom center of the drive, the ones that have 2 connections (DC +, DC -)
are the DC Coils, also know as DC Reactors or DC Chokes. The other set of
coils to the right, with 3 terminal connections, are discussed in the pages that
follow.
5) Brake Circuit
When drives are ordered with dynamic braking, the drive comes
with Brake IGBTs. When the voltage gets too high on the
DC Bus, the brake IGBT activates sending power to the
brake resistor. This is NOT an option with HVAC drives.
5) Brake Circuit
This Brake Option, also known as Dynamic Braking, is used with
devices that need to stop or change directions quickly, such as conveyors,
hoists and centrifuges. On drives that have the brake option, an additional
IGBT transistor is used to remove extra power coming back into the drive
when the motor, which has a large inertia, is stopping or changing direction.
The only HVAC related application that might use dynamic braking is for
some fans for boiler combustion. This option is not required for the vast
majority of HVAC applications.
6) Inverter Section
6) Inverter
The next part of the VFD is the Inverter section. This section takes the
DC voltage from the intermediate section and, with the help of the control
section, fires each set of IGBT (Insulated Gate Bipolar Transistors) to the U,
V and W terminals of the motor. This firing of the IGBTs is known as Pulse
Width Modulation (PWM) and is described in the next couple of slides.
Notice in the diagram above that sensors monitor the current going to
each terminal of the 3-phase motor. Unlike some other manufacturers,
Danfoss monitors all 3 phases continuously. There are some manufacturers,
who in an attempt to cut costs, only have 2 sensors and guess on the output
to the 3rd. There are others that only monitor the outputs when the first run
command is given.
Another component that Danfoss insists on including are the motor coils
on any drive larger than 18.5kW (25Hp). These coils smooth the waveform
going to the motor. The smoother the waveform the less heat is generated
at the motor and the longer the motor lasts. The standard distance used by
Danfoss between its drive and the motor is 300m (1000 feet) using
unshielded cable. There are other manufacturers that are limited to shorter
distances 100m (330 feet) or less. Some end users have used distance as a
sign of quality. The longer the distance, the better the drive.
6) Inverter Section
Current Sensors
Terminals
Motor Coils
The current sensors monitor the current going to the 3-phases of the
motor. These sensors detect and alarm when a short circuit or grounded
circuit is discovered. Some manufacturers only check for short circuits or
grounding on the first run command, but Danfoss monitors for these faults all
the time. This allows Danfoss to place a motor disconnect between the drive
and the motor. If the motor is disconnected from the drive during operation,
the drive might trip, but because of this constant monitoring, it suffers no
damage.
A disconnect switch between the motor and drive is not allowed by
many other manufacturer. If a disconnect switch is used on a few drives, it
causes severe damage in other words the smoke is let out.
6) Inverter Section
The IGBTs are mounted on the heatsinks behind the capacitors in the
middle of the 450kW (600Hp) drive. The picture on the right shows two
IGBTs with the circuit card which is used to help control them, know as a
snubber card. The picture on the left shows the IGBTs without the snubber
card. The correct mounting pattern for the 6 screws (done in a rotating
manner) on each is critical, so that there is proper contact between the IGBT
and the heatsink.
Power Card
Control Card
Gate Card
In the picture above, on the 450kW (600Hp) drive, 3 circuit cards make
up the control and regulation section for the drive. These cards are mounted
onto the frame used for the capacitor banks.
The Control Card is the same card used on all drives from 0.75
450kW (1 - 600Hp). The Local Keypad (LCP) fits into this control section.
The LCP is used to program and monitor the drives operation. The next card
is known as the power card, which is specific for a particular size of drives. It
relays signals to the gate card, monitors the current from the current
sensors, coordinates the fan operation and a number of other functions. The
third is known as the gate card, whose major function is to send signals to
the IGBTs. On smaller drives these last 2 circuit cards are together on one
card.
Summary
VFD 101
Lesson 4
Application Terminology for a VFD
Note: Other names are used for this device, such as Adjustable Frequency
Drive (AFD), Variable Speed Drive (ASD), Frequency Converter and
Inverter, but Variable Frequency Drive (VFD) or just Drive is used
throughout this lesson.
1
August 04
Outline
Application Terminology
1. Application Curves CT, CP, VT
2. Starting Torque HO, Breakaway, NO
3. Open or Closed Loops
4. Closed Loop & PID Action, Setpoint,
Offset, Proportional, Integral, Derivative
5. Different Types of VFDs
2
August 04
2. Starting Torque
3. Open or Closed Loop
4. Closed Loop & PID
5. Different Types of VFDs
3
August 04
The graph above shows Torque in relationship to Speed. This graph was made when the
VFD and loaded motor, were running at Synchronous Speed, 60 Hz, 1800 rpm on a 4-pole 3-
phase AC motor. The speed of the VFD was slowly turned down to 0 Hz. Notice that the
torque drops down to its nominal rating on an AC induction motor at the lower speeds, 5Hz or
less. Please be aware that this particular CT application, reciprocating compressor, should
never run less than 30Hz.
Constant Torque applications require a constant level of torque throughout a
process regardless of different speeds. The vast majority of constant torque
applications are for industry, which involve conveyors, mixers, elevators,
feeders, hoists, and bottling machines. In HVAC reciprocating compressors,
and positive displacement pumps might be encountered which require CT.
Some VFD manufacturers attempt to apply a CT drive to fans and pumps
used in HVAC, because they do not make a specific VFD for variable torque
applications. More information is given in the pages that follow.
On most CT applications, constant torque must be maintained from 1
to 60Hz. Notice that the torque curve drops when the speed is reduce below
a minimum of 5Hz. To compensate for this drop, some VFDs can perform
Motor Tuning, which matches the VFD settings to a particular motor. This
tuning allows for more precise calculations by the VFD giving more torque
throughout the CT curve, but particularly noticeable is the torque boost at
those slow speeds from 1 to 10Hz. In HVAC, Motor tuning is only a slight
advantage for fans and pumps, saving only a small portion of energy.
Because of motor cooling, most fans and pumps have a minimum speed of
10Hz or greater.
4
August 04
VFDs attempt to generate the correct level of torque needed for its
application. Torque is directly related to current. In CT applications, voltage
going from the VFD to the motor is increased in a linear manner as the speed
increases. In the example above, on a 460Vac motor, 460 Volts is only sent to
the motor when the speed reaches 60Hz and higher.
The chart above displays the Volts/Hz relationship for a CT application.
Constant Torque is achieved because the VFD is increasing the voltage to the
motor as it increases the speed. In this chart, when the VFD sends a signal of
30Hz, it is also sending a 230V signal to the motor. When the VFD sends a
60Hz signal, the voltage is at 460V. This relationship keeps the current and in
turn the torque to the motor relatively constant. The changes seen in the motor
current are based on the load. Notice that when the speed reaches
60Hz, base speed, the voltage going to the motor from the VFD can not go
higher, it has reached its limit, 460V. If the speed is increased above base
speed, to say 90Hz, the voltage from the VFD stays at 460V, but the current and
torque drop. This Volts/Hz chart is different for motors that use different
voltages.
5
August 04
6
August 04
7
August 04
Automatic Energy
Optimization (AEO)
8
August 04
2. Starting Torque
Centrifuge
Outline:
VFD Application Terminology
1. Application Torque Curves
2. Starting Torque
a) High Overload (HO)
b) Breakaway Torque
c) Normal Overload (NO)
9
August 04
High Overload (160%) is used to apply the torque to start a load. The
inertia to start a reciprocating compressor, a positive displacement pump or
in the example above a hoist requires a great deal of starting torque. It can
be as high as 160% of the current for 1 minute. Once started the torque
drops back to 100% or less. If the load does not move and the drive
exceeds 160% or exceeds 1 minute, the drive trips, which means that the
VFD does not move the motor. This trip gives an Over-current or Torque
Limit alarm and for protection sake a reset button must be pressed to clear
the alarm and restart the VFD. Some VFDs have a High Overload limit of
150% for 1 minute. It is possible to use a High Overload or CT Start to get a
fan or pump moving, but most HVAC applications do not require High
Overload.
10
August 04
2. b) Breakaway Torque
11
August 04
12
August 04
Outline:
VFD Application Terminology
1. Application Torque Curves
2. Starting Torque
3. Open or Closed Loop
a) Open Loop
b) Closed Loop
4. Closed Loop & PID
5. Different Types of VFDs
13
August 04
3. a) Open Loop
14
August 04
4) Closed Loop
Closed Loop is where the controller inside the VFD can be used to
modulate the speed of a motor to maintain a process. It is the job of the
sensor or transmitter to measure a variable, in the example above, this is
static pressure. This sensor sends a signal (usually a 4-20mA) to the
controller over a particular range, in this example from 0 to 5wc.
The sensor is wired to the current input of the VFD, the controller.
This signal is programmed in the VFD as the feedback signal. This feedback
signal must be given engineering units, from our example, inches of water
column (wc) or Pascals. Inside the VFD the feedback signal must also be
given the range that matches the sensor. When the sensor sees 4mA it is
0wc (0 Pascals) and when the sensor sees 20mA, the reading is 5wc (1250
Pascals).
The VFD, controller, has a setpoint, action and PID settings
(explained later) to calculate the response necessary to maintain the desired
value seen at the sensor. The VFD sends a signal to the fan to speed up or
slow down to maintain a certain level.
The fan, controlled device, responds to match the signal from the
VFD, controller. It speeds up when the level of the static pressure
decreases and slows down when the level of the static pressure is too high.
15
August 04
4. a) Control Action
Normal Control (also know as Reverse Acting). In the top return fan
example, when the CFM Transmitter sends a signal that indicates it is above
the setpoint, the output from the VFD decreases. The action is correct if the
sensor is down stream from the controlled device, the return fan. As the
CFM sees an increase, the signal to the fan decreases, slowing the fan
down. As the CFM transmitter sees a drop, the speed of the fan increases.
Inverse Control (also know as Direct Acting). In the bottom return fan
example, when the signal from the CFM Transmitter increases above the
setpoint the output from the VFD increases. This action is correct if the CFM
transmitter is upstream from the return fan.
If the wrong action (Inverse) were programmed in the VFD on the top
return fan, it would speed up as the CFM in the duct rose higher. Eventually
the speed of the return fan would go to its maximum. This could put a major
stress on the ductwork. If the incorrect action is programmed in an
application the VFD ends up locked at minimum or at maximum speed.
16
August 04
17
August 04
Integral Gain is based on the history of the error. The integral function
maintains a running total of the error and creates an output based on this
total. The lower the number used for the integral gain the more frequently
the error is checked and the larger its influence. If the integral time is too low
(less than 5 seconds), the system can become unstable and starts to hunt. A
good place to start is 10 seconds, but again this can vary based on the
application. Integral gain eliminates the steady error inherent to proportional
control. As pictured above, integral gain adds overshoot every time the load
changes, but eventually settles close to setpoint. Integral is used frequently
in HVAC applications.
18
August 04
4. b) PID
19
August 04
Volts/Hz drives also known as a Basic Scalar drives, are the least expensive
drive with the least features. This drive is usually setup for CT and Open
Loop only.
Voltage Vector drives also known as Space Vector drives have more
features and may have the ability to do both CT/VT and Open/Closed Loop.
Voltage Vector Plus drives have more features than the others and
therefore have more cost than previously mentioned drives. They can
calculate motor characteristics without spinning the shaft of the motor.
These last 3 types of VFD account for 95% of all applications. There are a
few that need greater accuracy which follow.
Flux Vector drives have more calculations which makes them more
expensive and more accurate. Some Flux vector drives require special
motors.
Servo drives are DC and do not operate with AC induction motors. They are
expensive in comparison to VFDs. They are the most responsive to dynamic
changes.
These drive types are explored in greater detail in a later lesson.
20
August 04
Summary:
Type Response Accuracy Speed Range
V/Hz 500 1000ms 10% + 10:1 180rpm
Voltage Vector 200 700ms 2% - 8% 50:1 36rpm
Voltage Vector + 50 300ms 0.2%-2%
Open 100:1 18rpm
Closed 900:1 2rpm
Flux Vector 5 60ms 0.02% - 0.1% 1400:1 1.3rpm
Servo 2 8ms 0.007% - 0.08% 1800:1 1rpm
21
August 04
VFD 101
Lesson 5
Power Input Terminology for a VFD
Incoming AC Power
The first section covers the protection of the VFD from the changes in
incoming power. The first item covered is the switching of power coming into
the drive. There can also be Surges and Sags in the incoming AC power. If
these surges are too high, or the sags are too low, the VFD shuts down for
its own protection. There must also be protection against transients or
spikes in the incoming power. Another item to be covered is a Phase
Imbalance between the 3 phases of power coming into the drive. The last
item to be covered are Fuses, connectors and different voltages which might
be encountered.
Rapidly and repeatedly switching power on the input to the VFD can
have a very negative effect on the drive. The power going into the drive
requires the capacitors to be charged, which requires power to travel through
a soft charge circuit. If this is started repeatedly, the current going through
the current limiting resistors can cause the resistors to overheat and blow
fuses on the soft charge circuit, disabling the drive for its own protection.
The stress on the capacitors powering up during the ON cycle, then
discharging during the OFF cycle can also shorten the life of the capacitors
and also the life of the drive. For these reasons it is important that the drive
be limited to just 2 starts per minute. If the drive needs to start and stop its
motor repeatedly, it is best to always use the drives control circuitry.
Spikes or Transients
Metal Oxide Varistors (MOV)
d) Phase Imbalance
Single Phase into the drive is possible with some smaller size drives,
usually 3Hp and under. Notice in the picture above single phase terminals
are labeled N and L1. It is possible to use single phase input on a 3-phase
drive when properly engineered, it is NOT officially recommended or
supported by Danfoss. Performance and long term reliability problems may
result. One of the biggest concerns with single-phase input is the effect it has
on the filtering capacitors.
Fuses
No Power factor correction capacitors
2) Protecting the
Supply Line
Not only must the VFD be protected from the incoming power, it is
also important that the main power supply and all other equipment attached
to this transformer be protected from the noise generated by the VFD. All
VFDs generate noise. Noise, as voltage distortion in the supply line, can
cause sensitive equipment such as computers and PLC to malfunction.
Noise as current distortion in the transformer causes heat in the
transformer and associated wiring. This noise can be described as 2
different types:
1) Radio Frequency Interference (RFI) and
2) Harmonics.
RFI (frequencies of 450kHz and higher) can travel through the wires
and can also be radiated through the air. Many of these problems can be
corrected by using RFI filters in the drives and shielded (screened) cable.
RFI is a major concern when using drives in Europe.
Harmonics are the noise at low frequencies, less that 3kHz, which are
only generated through the wires and never radiated through the air.
Engineers in North America seem to be more concerned with harmonics.
Both of these and managing harmonics are covered in some detail on the
pages that follow.
Noise RFI
CE EN 55011
1A Filter
1B Filter
Grounded Delta
b) Harmonic Distortion
Summation of all
harmonic frequencies
Fundamental
Harmonic distortion has been a hot topic in North America with the
ever increasing use of equipment incorporating rectifiers and similar
switching devices on the input. This noise is low frequencies that appear on
wires coming from the supply transformer.
In the example above, notice that the orange fundamental sine wave,
comes from the main power supply. In a 6-pulse drive, one that has 6
diodes or SCRs rectifying the AC power to DC, the 5th harmonic (300Hz) is
quite large as seen in the blue sine wave. The 7th harmonic (420Hz) is also
quite large as seen in the pink sine wave. The summation of all of these
sine waves is shown in red, and you can see the distortion that exists on the
power supply. The harmonic distortion is related to the number of diodes
used to rectify AC to DC. As the number of harmonics increases, the lower
their amplitude, which means less problems. The 5th and 7th harmonics have
a much greater amplitude than the 11th and 13th which have a greater
amplitude than the 17th and 19th. The reduction of the 5th 7th and 11th
harmonic signals are the greatest concern.
b) Harmonic Distortion
DC Inductors
Isolation Transformers
Expensive option
12 Pulse Drive
Cancels 5th and 7th harmonics
Works with much smaller 11th and 13th harmonics
Must have 30 phase shift transformer
Works best with perfect balance between phases
One way to avoid the more expensive 12-pulse drives is to wire the
drives in a virtual or quasi 12-pulse configuration. Here a large 30 phase
shift transformer is used to power 2 sets of VFDs, one from the standard part
of the transformer and the other from the 30 phase shift part. This allows
the use of the much less expensive 6-pulse drives with the harmonic
cancellation advantages of the 12-pulse.
AHF Filters
By connecting the AHF 005 or AHF 010 in front of the VFD. The
harmonic current distortion generated back to the mains is
reduced to a minimum.
In the diagrams above the bar chart to the left shows the amounts of
current distortion on a 6-pulse drive that has DC inductors. When the AHF
filters are placed upstream from the VFD, notice in the middle chart and the
chart on the right that the harmonic levels are very small. Another
advantage that the filters have over a 12-pulse VFD is there is only a slight
increase in harmonics on the power when there is a phase imbalance.
100 200
Current/Voltage THD
80 175
Cost Index
60 150
Drive THiD
40 125
Vthd PCC2
Co s t Ind ex
20 100
0 75
Trap Filter
AccusineTM
VLT + 3% ACR.
Quasi 12 pulse
12 pulse
18 pulse filter
The Law of Diminishing Returns